This document contains a fire alarm system inspection report and related federal contract opportunity notice. The inspection report details the results of testing fire alarm panels and devices across nineteen buildings at a National Guard base. It identifies deficiencies with several smoke detectors and strobes that failed to operate correctly. It also notes the need to replace two batteries that failed load voltage testing. The related federal contract opportunity is a request for quote to inspect and correct deficiencies in the fire protection systems across the nineteen buildings. Interested vendors must be registered in SAM and have a CAGE code. Quotes are due by the specified date and time. A pre-bid site visit will be held on January 3rd, 2023, and interested parties must complete DBIDS pre-enrollment by the listed deadline to attend. The government intends to award a firm fixed price contract without negotiations, so offerors should provide their most competitive pricing initially.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: June 27, 2019
Task Number: TIME: 10:00AM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 130
Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave
City, St., Zip: Fresno, CA, 93272 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott
License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Master Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House/ Fire Department Contact: N/A
Telephone: 559-454-5145 Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly
Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually
RF X Annually
Other (Specify) Other (Specify)
System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: Monaco Enterprise Model No.: M2
Circuit Style: Class B
Number of Circuits: N/A
Software Rev.: N/A
Last Date System Had Any Service Performed: September 29, 2017
Last Date That Any Software or Configuration Was Revised: N/A
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
7 B 7 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
13 B 13 Photo Detectors (PSD)
0 0 Duct Detectors (DSD)
47 B 47 Heat Detectors (HD)
0 0 Water Flow Switches (WF)
0 0 (Specify)
0 0 (Specify)
Alarm verification feature is Disabled X Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
0 0 Bells
5 D 5 Horns with strobes
0 0 Chimes
1 D 1 Strobes
0 0 Speakers
Number of alarm notification appliance circuits: 1
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
0 0 Valve Position Tamper Switch (TS)
0 0 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
0 0 High / Low Pressure Switch (HLPS)
0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
0 0 Fire Pump Power
0 0 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble
0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): TELCOM ROOM
Disconnecting Means Location: CIRCUIT BREAK
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 17.2Ah
Calculated capacity is 34.4 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: N/A
Location of fuel storage: N/A
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
NA Emergency system described in NFPA 70, Article 700
NA Legally required standby described in NFPA 70, Article 701
NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity X Fire Department
Building Occupants X Staff
Building Management X M.O.D
Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass
Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Ok
Load Voltage X Fail-19.89VDC
Discharge test X Pass-25.22VDC
Charger test X Pass-27.44VDC
TRANSIENT SUPPRESSORS N/A
REMOTE ANNUNCIATOR N/A
NOTIFICATION APPLIANCES
Audible X X Pass
Visible X X Pass
Speakers NA
Voice Clarity NA
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA
Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA
Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA
(Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested
Elevator Recall NA
Fan Shutdown NA
Door Holders NA
Smoke Control System NA
Door Release (Security Maglocks) NA
(Specify) NA
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X
Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X
Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments
Building Management X M.O.D
Monitoring Agency X Fire Department
Building Occupants X Staff
Other (Specify)
The following did not operate correctly:
The following devices did not report to the fire panel: Medical Lobby PSD, Medical east exit PSD, Front of
M103 PSD, & Front of M124 PSD. Hall by office 107 smoke detector failed to alarm.
Strobe did not operate by first sergeant office.
Two 12V 17.2Ah batteries need to be replaced. Both failed the load voltage test.
System Sensor Model Number 2WB is the make for the smokes failed listed above.
System restored to normal operation: Date: June 27, 2019 Time:
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado Date: June 27, 2019 Time:
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 130 DATE: June 27, 2019
ADDRESS: 5323 E. McKinley Ave, Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Type VIS. FUNC. Address Pass Fail
SOUTH ENTRY HD X X X
BREAK ROOM HD X X X
COMMANDER OFFICE HD X X X
SOUTH HALL PSD X X X
HRF PSD X X X
VAULT HD X X X
BIO HD X X X
BIO HD X X X
BIO ENGINEER HD X X X
SHOP SUPVERISOR OFFICE HD X X X
FIRE SGT OFFICE HD X X X
CORNELL OFFICE HD X X X
MID HALL PSD X X X
SGT PASILY OFFICE HD X X X
CHIEF LARRY OFFICE HD X X X
CHIEF LARRY OFFICE HD X X X
N/E EXIT PSD X X X
N/E EXIT MPS X X X
N/E EXIT MPS X X X
AUDITORIUM HD X X X
AUDITORIUM MPS X X X
WEST EXIT MPS X X X
WEST EXIT MPS X X X
MEN RESTROOM HD X X X
MEN RESTROOM HD X X X
FROM OF MEN RESTROOM HD X X X
MEN RESTROOM STORAGE HD X X X
LOBBY OF MEDICAL AREA PSD X X X
LOBBY OF MEDICAL AREA HD X X X
LOBBY OF MEDICAL AREA MPS X X X
M101 HD X X X
MEDICAL EAST EXIT PSD X X X
STATION 8 HD X X X
M102 HD X X X
M103 HD X X X
IN FRONT OF M103 PSD X X X
M105 HD X X X
M105 RESTROOM HD X X X
M106 HD X X X
M128 HD X X X
WATER HEATER HD X X X
M107 HD X X X
M132 HD X X X
M108 HD X X X
M133 HD X X X
M109 HD X X X
M134 HD X X X
M110 HD X X X
M111 HD X X X
M112 HD X X X
PROPERTY NAME: Fresno Air National Guard Building 135 DATE: June 27, 2019
ADDRESS: 5323 E. MCKINLEY AVE, FRESNO, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Type VIS. FUNC. Address Pass Fail
M112 EXTENSION HD X X X
STATION 7 PSD X X X
M136 HD X X X
M136 RESTROOM HD X X X
STATION 7 HD X X X
STATION 7 HD X X X
M116 HD X X X
M116 HD X X X
HALL BY M118 PSD X X X
HALL BY M118 PSSA X X X
S/W EXIT PSD X X X
M118 PSSA X X X
M120 HD X X X
M137 HD X X X
M137 RESTROOM HD X X X
STATION 4 HD X X X
STATION 4 HD X X X
STATION 4 REST ROOM HD X X X
HALL BY STATION 4 PSD X X X
M140 HD X X X
STATION 3 HD X X X
M123 HD X X X
M124 HD X X X
HALL BY 124 PSD X X X
M142 HD X X X
M126 HD X X X
M126 HD X X X
WOMEN LOCKER HD X X X
WOMEN RESTROOM HD X X X
WOMEN RESTROOM CLOSET HD X X X
WOMEN RESTROOM ENTRY HD X X X
To add more sheets, copy this page and paste it to the end of this document. Page 6 of 6