FANG BLDG 135 ANN FA 6-2019.pdf

PDF 412 KB Posted

Attached to
Inspection of Fire Alarm Panels, Main Base
Solicitation number
W50S6T24QA011
Issued by

About this file

This document contains a federal contract opportunity solicitation for fire alarm panel inspection and maintenance services at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is seeking a firm-fixed price contract to inspect Monaco Enterprises fire protection systems and devices, correct any deficiencies, and ensure compliance with all standards. Interested parties must have a CAGE code and SAM registration. Quotes are due by the date and time specified via email to the contracting office. A non-mandatory site visit will be held on January 3rd, 2023 at 9:00 AM at the base location provided; attendees must complete DBIDS pre-enrollment and be cleared through base security. The period of performance and award date are not specified.

View the file

Other files

File Type Posted
FANG BLDG 145 ANN FA 7-2019.pdf PDF
FANG BLDG 122 ANN FA 7-2019.pdf PDF
FANG BLDG 130 ANN FA 6-2019.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base (HAYW231030)-Amd2.pdf PDF
FANG BLDG 2640 ANN FA 7-2019.pdf PDF
FANG BLDG 2602 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110002 SF 30.pdf PDF
FANG BLDG 102 ANN FA 7-2019.pdf PDF
FANG BLDG 121 ANN FA 7-2019.pdf PDF
FANG BLDG 159 ANNUAL FA 6-2019.pdf PDF
FANG BLDG 124 ANN FA 6-2019.pdf PDF
Solicitation Amendment - W50S6T24QA0110002 SF1449.pdf PDF
FANG BLDG 125 ANN FA 6-2019.pdf PDF
FANG BLDG 117 ANN FA 6-2019.pdf PDF
FANG BLDG 126 ANN FA 6-2019.pdf PDF
FANG BLDG 157 ANNUAL FA 6-2019.pdf PDF
FANG Bldg 100 Annual FA 6-2019.pdf PDF
FANG BLDG 155 ANN FA 7-2019.pdf PDF
FANG BLDG 104 ANN FA 7-2019.pdf PDF
FANG BLDG 225 ANN FA 6-2019.pdf PDF
FANG BLDG 2600 2601 ANN FA 7-2019.pdf PDF
FANG BLDG 194 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110001 SF 30.pdf PDF
Base Access-144 SFS DVES FORM- 20230127 (Site Visit).pdf PDF
Wage Determinations SCA - 2015-5609 dated 3Aug2023.pdf PDF
Solicitation - W50S6T24QA011 SF1449 RFQ.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SimplexGrinnell BE SAFE

INSPECTION AND TESTING FORM

SR Number: 44909832 DATE: June 26, 2019

Task Number: TIME: 2:00PM

SERVICE ORGANIZATION PROPERTY NAME (USER)

Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 135

Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave

City, St., Zip: Fresno, CA, 93272 City, St., Zip: Fresno, CA, 93727

Representative: Jesus Salgado Owner Contact: Mike Scott

License No.: 986047 Telephone: 559-454-5137

Telephone: 559-348-0614 Occupied as: Master Chief

MONITORING ENTITY APPROVING AGENCY

Contact: In House/ Fire Department Contact: N/A

Telephone: 559-454-5145 Telephone: N/A

Monitoring Account Ref. No.: N/A

TYPE TRANSMISSION SERVICE

McCulloh Weekly

Multiplex Monthly

X Digital Quarterly

Reverse Polarity Semiannually

RF X Annually

Other (Specify) Other (Specify)

System Type: (X) Local; ( ) Auxiliary; ( ) Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm

Control Unit Manufacturer: MONACO Model No.: M-2NB

Circuit Style: CLASS B

Number of Circuits: N/A

Software Rev.: N/A

Last Date System Had Any Service Performed: October 5, 2017

Last Date That Any Software or Configuration Was Revised: N/A

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity of Devices Installed

Circuit Style

Devices Tested

19 B 19 Manual Fire Alarm Boxes (PSSA)

0 0 Ion Detectors (ISD)

94 B 94 Photo Detectors (PSD)

3 B 3 Duct Detectors (DSD)

18 B 18 Heat Detectors (HD)

1 B 1 Water Flow Switches (WF)

0 0 (Specify)

0 0 (Specify)

Alarm verification feature is disabled X Enabled .

Rev. D

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Appliances Installed

Appliances Tested

1 1 Bells

28 B 28 Horns with strobes

0 0 Chimes

4 B 4 Strobes

0 0 Speakers

Number of alarm notification appliance circuits:

Are circuits monitored for integrity? X Yes No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Devices Installed

Devices Tested

1 B 1 Valve Position Tamper Switch (TS)

2 B 2 Outside Stem and Yoke (OSY)

1 B 1 Post Indicator Valve (PIV)

0 0 High / Low Pressure Switch (HLPS)

0 0 Building Temperature

0 0 Site Water Temp

0 0 Site Water Level

0 0 Fire Pump Power

0 0 Fire Pump Running

0 0 Fire Pump Auto Position

0 0 Fire Pump or Fire Controller Trouble

0 0 Fire Pump Low Fuel

0 0 Other: Switch Transfer

0 0 Other: Generator Engine Running

SIGNALING LINE CIRCUIT

Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5

Overcurrent Protection: Type Circuit Breaker Amps 20

Location (of Primary Supply Panel): PANEL PE

Disconnecting Means Location: BREAKER 17

(b) Secondary (Standby):

Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah

Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.

Engine-driven generator dedicated to fire alarm system: NA

Location of fuel storage: NA

TYPE BATTERY

Dry Cell Lead-Acid

Nickel-Cadmium Other (Specify):

X Sealed Lead-Acid

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701

Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time

Monitoring Entity X In House/FD 2:00PM

Building Occupants X Staff 2:00PM

Building Management X M.O.D 2:00PM

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit X X Pass

Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition X Good-Batteries Installed June 2018

Load Voltage X Pass-26.48VDC

Discharge test X Pass-25.89VDC

Charger test X Pass-27.24VDC

TRANSIENT SUPPRESSORS N/A

REMOTE ANNUNCIATOR X X Pass-Hallway By Chow Hall

NOTIFICATION APPLIANCES

Audible X X Pass

Visible X X Pass

Speakers NA

Voice Clarity NA

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Location & Serial Number Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

See attached detailed report.

Date of Last Sensitivity Test: Unknown

EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments

Phone Set NA

Phone Jacks NA

Off-Hook Indicators NA

Amplifier(s) NA

Tone Generator(s) NA

Call-in Signal NA

System Performance NA

SPECIAL HAZARD SYSTEMS

Number Installed

Number Tested Comments

Kitchen Range Hood System NA

CO2 Extinguishing System NA

(Specify) NA

CONTROL FUNCTIONS / INTERFACE

EQUIPMENT

Number Installed

Number Tested Comments

Elevator Recall NA

Fan Shutdown NA

Door Holders NA

Smoke Control System NA

Door Release (Security Maglocks) NA

(Specify) NA

Special Procedures:

Comments:

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal X

Alarm Restoration X

Trouble Signal X

Trouble Signal Restoration X

Supervisory Signal X

Supervisory Restoration X

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments

Building Management X M.O.D

Monitoring Agency X In House/FD

Building Occupants X Staff

Other (Specify)

The following did not operate correctly: Two 12V 7.0Ah batteries need to be replaced on the 4009 Simplex

NAC power extender. Both batteries failed the load voltage test.

System restored to normal operation: Date: June 26, 2019 Time:

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Jesus Salgado Date: June 26, 2019 Time:

Signature:

Name of Owner or Rep.: Date: Time:

Signature:

PROPERTY NAME: Fresno Air National Guard Building 135 DATE: June 26, 2019

ADDRESS: 5323 E. McKinley Ave, Fresno, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Type VIS. FUNC. ZONE Pass Fail

EAST WING RECEPTION AREA PSSA X X L4-1 X

EAST WING RECEPTION AREA PSD X X L3-4 X

EAST WING RECRUITING OFFICE PSD X X L3-4 X

EAST WING RECRUITING OFFICE PSD X X L3-4 X

EAST WING CUSTOMER SERVICE OFFICE PSD X X L3-4 X

EAST WING CUSTOMER SERVICE OFFICE PSD X X L3-4 X

EAST WING OPS OFFICER OFFICE PSD X X L3-4 X

E. WING CORR BY CUSTOMER SERVICE PSD X X L3-4 X

EAST WING HR OFFICE PSD X X L3-4 X

E. WING CORR BY RETENTION OFFICE PSD X X L3-4 X

E. WING RETENTION OFFICE PSD X X L3-4 X

E. WING BASE TRAINING OFFICE PSD X X L3-4 X

E. WING TESTING ROOM PSD X X L3-4 X

E. WING TESTING ROOM PSSA X X L4-1 X

E. WING FAMILY READY OFFICE PSD X X L3-4 X

E. WING COPY/STORAGE RM PSD X X L3-4 X

E. WING CORR BY COPY/STORAGE RM PSD X X L3-4 X

E. WING FSS COMMANDER OFFICE PSD X X L3-4 X

E. WING FSS SUPER. OFFICE PSD X X L3-4 X

E. WING PERSONAL SYSTEMS MANAGER PSD X X L3-4 X

E. WINGCORR BY EXITS PSSA X X L4-1 X

E. WINGCORR BY EXITS PSSA X X L4-1 X

E. WING EXITS PSD X X L3-4 X

CTR WING S READY EMPLOY OFFICE PSD X X L3-1 X

CTR WING ELECTRIC RM. PSSA X X L3-3 X

CTR WING ELECTRIC RM PSD X X L3-1 X

CTR WING CORR BY ELECTRIC RM PSD X X L3-1 X

CTR WING ORDERLY RM PSD X X L3-1 X

CTR WING DPTY COMDR OFFICE PSD X X L3-1 X

CTR WING 1ST SGTS OFFICE PSD X X L3-1 X

CTR WING CORR BY SPRT GRP COMDR PSD X X L3-1 X

CTR WING SPRT GRP COMDR OFFICE PSD X X L3-1 X

CTR WING SPRT GRP COMDR CLOSET PSD X X L3-1 X

CTR WING CORR BY BREAK RM PSD X X L3-1 X

CTR WING COMM RM PSD X X L3-1 X

CTR WING EQUAL OPP. OFFICE PSD X X L3-1 X

CTR WING EQUAL OPP. OFFICE PSD X X L3-1 X

CTR WING EQUAL OPP. OFFICE PSD X X L3-1 X

CTR WING CORR BY EQUAL OPP. OFFICE PSD X X L3-1 X

CTR WING WEIGHT STATION PSD X X L3-1 X

CTR WING ELECTRICAL RM PSD X X L3-1 X

WEST WING CORR EXIT BY STORAGE PSD X X L4-2 X

WEST WING CORR EXIT BY STORAGE PSSA X X L4-3 X

WEST WING CORR EXIT BY STORAGE PSSA X X L4-3 X

CTR WING BREAK RM. PSD X X L3-1 X

CTR WING BREAK RM CLOSET PSD X X L3-1 X

WEST WING CHAPEL PSD X X L4-2 X

WEST WING CONTRACTING OFFICE PSD X X L4-2 X

WEST WING CONTRACTING OFFICE PSD X X L4-2 X

WEST WING CONTRACTING OFFICE PSD X X L4-2 X

Type VIS. FUNC. Address Pass Fail

WEST WING CORR BY CHAPLIN SERV PSD X X L4-2 X

WEST WING CHAPLIN SERV PSD X X L4-2 X

WEST WING CHAPLIN SERV PSD X X L4-2 X

WEST WING CHAPLIN SERV PSD X X L4-2 X

WEST WING CHAPLIN SERV PSD X X L4-2 X

WEST WING JAG OFFICE PSD X X L4-2 X

WEST WING JAG OFFICE PSD X X L4-2 X

WEST WING JAG OFFICE PSD X X L4-2 X

WEST WING -WING SAFETY OFFICE PSD X X L4-2 X

WEST WING -WING SAFETY OFFICE PSD X X L4-2 X

WEST WING CORR BY BOILER RM PSD X X L4-2 X

WEST WING FINANCE OFFICE PSD X X L4-2 X

WEST WING FINANCE OFFICE PSD X X L4-2 X

WEST WING FINANCE OFFICE PSD X X L4-2 X

WEST WING FINANCE OFFICE PSD X X L4-2 X

WEST WING FINANCE OFFICE PSD X X L4-2 X

WEST WING FINANCE OFFICE PSD X X L4-2 X

WEST WING FINANCE OFFICE PSD X X L4-2 X

WEST WING FINANCE OFFICE PSSA X X L4-3 X

WEST WING CORR BY BOILER RM PSSA X X L4-3 X

WEST WING CORR BY FINANCE OFFICE PSD X X L4-2 X

DINING CHOW HALL PSD X X L4-4 X

DINING CHOW HALL PSD X X L4-4 X

DINING CHOW HALL PSD X X L4-4 X

DINING CHOW HALL PSD X X L4-4 X

DINING CHOW HALL PSD X X L5-1 X

DINING CHOW HALL PSD X X L5-1 X

DINING CHOW HALL PSD X X L4-4 X

DINING CHOW HALL PSD X X L5-1 X

DINING CHOW HALL N/W PSSA X X L5-2 X

DINING CHOW HALL S/W PSSA X X L5-2 X

DINING CHOW HALL EAST PSSA X X L5-2 X

DINING CHOW HALL VESTIBULE PSD X X L4-4 X

DINING CHOW HALL VESTIBULE PSSA X X L5-2 X

DINING SERVICES OFFICE PSD X X L4-4 X

DINING SERVICES COM OFFICE PSD X X L4-4 X

DINING SERVICE TECH OFFICE PSD X X L4-4 X

DINING SERVICE TECH OFFICE PSSA X X L5-2 X

DINING TRAINING ROOM PSD X X L4-4 X

DINING/ WAREHSE PSD X X L4-4 X

DINING/ WAREHSE PSD X X L4-4 X

DINING/ WAREHSE PSSA X X L5-2 X

TAMPER SWITCH ON RISER IN WAREHSE TST X X L5-4 X

PIV ON GUARD ROAD TST X X L5-4 X

NW WAREHOUSE BY CHOW HALL 59 SEC WF X X L3-2 X

CTR CORR BY HOELAND RESPONSE PSD X X L3-2 X

CTR WING CORR BY HR PSD X X L3-2 X

CTR WING HR OFFICE PSD X X L3-2 X

CTR WINGINSPECTOR GENERALS OFFICE PSD X X L3-2 X

CTR WING HOMELAND OPER. OFFICE PSD X X L3-2 X

To add more sheets, copy this page and paste it to the end of this document. Page 6 of 7

Type VIS. FUNC. ZONE Pass Fail

CTR WING HOMELAND OPER. OFFICE PSD X X L3-2 X

CTR CORR BY WING 1ST SARGENT OFF. PSD X X L3-2 X

CTR CORR WING 1ST SARGENT CLOSET PSD X X L3-2 X

CTR WING 1ST SARGENT OFFICE PSD X X L3-2 X

CTR WING 1ST SARGENT OFFICE PSD X X L3-2 X

CTR WING 1ST SARGENT OFFICE PSD X X L3-2 X

CTR WING 1ST SARGENT OFFICE PSD X X L3-2 X

CTR WING -WING CONF ROOM PSD X X L3-2 X

CTR WING -WING CONF ROOM PSD X X L3-2 X

CTR WING -WING CON ROOM PSSA X X L3-3 X

CTR CORR BY WING CONF ROOM PSSA X X L3-3 X

VICE COMMAND OFFICE PSD X X L3-2 X

VICE COMMAND OFFICE PSD X X L3-2 X

COM ROOM PSD X X L3-2 X

CTR -WING COMMANDERS RESTROOM HD X X L3-2 X

CTR -HOMELAND RESP OP. CLOSET HD X X L3-2 X

WOMANS RESTROOM BY ORDERLY OFF. HD X X L3-2 X

MEN RESTROOM BY BREAK ROOM HD X X L3-2 X

WEST WING BOILER ROOM HD X X L4-2 X

DINING - CLIPPER ROOM HD X X L4-4 X

DINING -CHOW HALL STORAGE HD X X L4-4 X

DINING -KITCHEN JANITOR CLOSET HD X X L5-1 X

DINING -KITCHEN SERV CORR HD X X L5-1 X

DINING- KITCHEN SERV CORR EAST HD X X L5-1 X

DINING – KITCHEN CORR EXIT PSSA X X L5-2 X

DINING – KITCHEN ABOVE OVENS HD X X L5-1 X

DINING – KITCHEN ABOVE GRILL HD X X L5-1 X

DINING – KITCHEN STORAGE HD X X L5-1 X

DINING –KITCHEN ABOVE DISH WASH HD X X L5-1 X

DINING – KITCHEN LOCKER ROOM HD X X L5-1 X

DINING – KITCHEN RESTROOM HD X X L5-1 X

DINING – KITCHEN REC. EXIT PSSA X X L5-2 X

DINING – MENS RESTROOM KITCHEN HD X X L4-4 X

DINING – WOMENNS RESTROOM KITCHEN HD X X L4-4 X

DINING – KITCHEN DRY STORAGE PSD X X L5-1 X

DINING – KITCHEN POTS & PANS STORAG PSD X X L5-1 X

HALLWAY DD X X X

HALLWAY DD X X X

HALLWAY DD X X X

4009 SIMPLEX NAC PANEL NAC X X X

File details come from the government source that posted it. Updated .