FANG BLDG 157 ANNUAL FA 6-2019.pdf

PDF 279 KB Posted

Attached to
Inspection of Fire Alarm Panels, Main Base
Solicitation number
W50S6T24QA011
Issued by

About this file

This document contains a request for quote for inspection services of fire alarm panels and devices at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is seeking a firm fixed price contract to inspect and correct any deficiencies in the fire protection systems, which were installed by Monaco Enterprises Inc. Interested parties must be registered in the System for Award Management and have a Commercial and Government Entity code. A site visit will be held on January 3rd, 2023, and attendees must complete a Department of Defense database enrollment process beforehand. Quotes are due by the date and time specified in the solicitation instructions and must be submitted to the Contracting inbox at the provided email address. The requirement is being competitively solicited and the Government reserves the right to amend or cancel the request for quote.

View the file

Other files

File Type Posted
FANG BLDG 145 ANN FA 7-2019.pdf PDF
FANG BLDG 122 ANN FA 7-2019.pdf PDF
FANG BLDG 130 ANN FA 6-2019.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base (HAYW231030)-Amd2.pdf PDF
FANG BLDG 135 ANN FA 6-2019.pdf PDF
FANG BLDG 2640 ANN FA 7-2019.pdf PDF
FANG BLDG 2602 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110002 SF 30.pdf PDF
FANG BLDG 102 ANN FA 7-2019.pdf PDF
FANG BLDG 121 ANN FA 7-2019.pdf PDF
FANG BLDG 159 ANNUAL FA 6-2019.pdf PDF
FANG BLDG 124 ANN FA 6-2019.pdf PDF
Solicitation Amendment - W50S6T24QA0110002 SF1449.pdf PDF
FANG BLDG 125 ANN FA 6-2019.pdf PDF
FANG BLDG 117 ANN FA 6-2019.pdf PDF
FANG BLDG 126 ANN FA 6-2019.pdf PDF
FANG Bldg 100 Annual FA 6-2019.pdf PDF
FANG BLDG 155 ANN FA 7-2019.pdf PDF
FANG BLDG 104 ANN FA 7-2019.pdf PDF
FANG BLDG 225 ANN FA 6-2019.pdf PDF
FANG BLDG 2600 2601 ANN FA 7-2019.pdf PDF
FANG BLDG 194 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110001 SF 30.pdf PDF
Base Access-144 SFS DVES FORM- 20230127 (Site Visit).pdf PDF
Wage Determinations SCA - 2015-5609 dated 3Aug2023.pdf PDF
Solicitation - W50S6T24QA011 SF1449 RFQ.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SimplexGrinnell BE SAFE

INSPECTION AND TESTING FORM

SR Number: 44909832 DATE: June 24, 2019

Task Number: TIME: 7:00AM

SERVICE ORGANIZATION PROPERTY NAME (USER)

Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 157

Address: 2788 N. Larkin Ave. Address: 5323 E McKinley Ave City, St., Zip: Fresno, CA, 93727 City, St., Zip: Fresno, CA, 93727

Representative: Jesus Salgado Owner Contact: Mike Scott License No.: 986047 Telephone: 559-454-5137

Telephone: 559-348-0614 Occupied as: Chief

MONITORING ENTITY APPROVING AGENCY

Contact: In House Contact: N/A

Telephone: N/A Telephone: N/A

Monitoring Account Ref. No.: N/A

TYPE TRANSMISSION SERVICE

McCulloh Weekly Multiplex Monthly

X Digital Quarterly

Reverse Polarity Semiannually RF X Annually

Other (Specify) Other (Specify)

System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm

Control Unit Manufacturer: Notifier & Viking Model No.: Notifier & Viking foam releasing panel Circuit Style: B

Number of Circuits: NA

Software Rev.: NA Last Date System Had Any Service Performed: October 5, 2017

Last Date That Any Software or Configuration Was Revised: 1988

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity of Devices Installed

Circuit Style

Devices Tested

8 B 8 Manual Fire Alarm Boxes (PSSA)

0 0 Ion Detectors (ISD)

6 B 6 Photo Detectors (PSD)

0 0 Duct Detectors (DSD) 26 B 26 Heat Detectors (HD)

2 B 2 Water Flow Switches (WF)

4 B 4 (SMD) Suppression Manual Dump 0 0 (Specify)

0 0 (Specify)

Alarm verification feature is Disabled X Enabled .

Rev. D

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Appliances Installed

Appliances Tested

1 1 Bells

9 B 9 Horns with strobes 0 0 Chimes

3 B 3 Strobes

0 0 Speakers

0 0 (Specify)

Number of alarm notification appliance circuits:

Are circuits monitored for integrity? X Yes No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Devices Installed

Devices Tested

11 B 11 Valve Position Tamper Switch (TS) 3 B 3 Outside Stem and Yoke (OSY)

1 B 1 Post Indicator Valve (PIV)

1 B 1 High / Low Pressure Switch (HLPS) 0 0 Building Temperature

0 0 Site Water Temp

0 0 Site Water Level

1 B 1 Fire Pump Power 1 B 1 Fire Pump Running

0 0 Fire Pump Auto Position

0 0 Fire Pump or Fire Controller Trouble 0 0 Fire Pump Low Fuel

0 0 Other: Switch Transfer

0 0 Other: Generator Engine Running

SIGNALING LINE CIRCUIT

Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5

Overcurrent Protection: Type Circuit Breaker Amps 20

Location (of Primary Supply Panel): MECHANICAL ROOM

Disconnecting Means Location: PANEL X1 CIRCUIT 26

(b) Secondary (Standby):

Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah Two 12V 12Ah

Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.

Engine-driven generator dedicated to fire alarm system: N/A

Location of fuel storage: N/A

TYPE BATTERY

Dry Cell Lead-Acid

Nickel-Cadmium Other (Specify):

X Sealed Lead-Acid

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

NA Emergency system described in NFPA 70, Article 700

NA Legally required standby described in NFPA 70, Article 701 NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time Monitoring Entity X In House 7:00AM

Building Occupants X Staff 7:00AM Building Management X M.O.D 7:00AM

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit X X Pass Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition X Good-Batteries Installed 12-2018

Load Voltage X Pass-26.44VDC Discharge test X Pass-25.64VDC

Charger test X Pass-27.24VDC

TRANSIENT SUPPRESSORS NA

REMOTE ANNUNCIATOR NA

NOTIFICATION APPLIANCES

Audible X X Pass Visible X X Pass

Speakers NA

Voice Clarity NA

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Location & Serial Number Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

See attached detailed report.

Date of Last Sensitivity Test: Unknown

EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments

Phone Set NA Phone Jacks NA

Off-Hook Indicators NA

Amplifier(s) NA

Tone Generator(s) NA Call-in Signal NA

System Performance NA

SPECIAL HAZARD SYSTEMS

Number Installed

Number Tested Comments

Kitchen Range Hood System N/A

CO2 Extinguishing System N/A (Specify) N/A

CONTROL FUNCTIONS / INTERFACE

EQUIPMENT

Number Installed

Number Tested

Elevator Recall N/A

Fan Shutdown N/A Door Holders N/A Smoke Control System N/A Door Release (Security Maglocks) N/A (Specify) N/A

Special Procedures:

Comments:

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal X Alarm Restoration X

Trouble Signal X

Trouble Signal Restoration X

Supervisory Signal X Supervisory Restoration X

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments Building Management X M.O.D

Monitoring Agency X In House

Building Occupants X Staff Other (Specify)

The following did not operate correctly: No Deficiencies found during this inspection.

System restored to normal operation: Date: June 25, 2019 Time:

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Jesus Salgado & Ryan Stone Date: June 26, 2019 Time:

Signature:

Name of Owner or Rep.: Date: Time:

Signature:

PROPERTY NAME: FRESNO AIR NATIONAL GUARD BLDG 157 DATE: June 24, 2019

ADDRESS: 5323 E. MCKINLEY AVE, FRESNO, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Type VIS. FUNC. Address Pass Fail

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 8 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR HD X X ZN 9 X

HANGAR PSSA X X ZN 2 X

HANGAR OFFICE PSSA X X ZN 3 X

OFFICE PSSA X X ZN 3 X

HANGAR PSSA X X ZN 2 X

OFFICE PSSA X X ZN 3 X

OFFICE PSSA X X ZN 3 X

HANGAR PSSA X X ZN 2 X

ABOVE FACP PSD X X ZN 1 X

ABOVE FOAM TANK HD X X ZN 1 X

MECH ROOM HD X X ZN 1 X

MEN RESTROOM (2X) HD X X ZN 1 X

JANITOR CLOSET HD X X ZN 1 X

WOMEN RESTROOM (2X) HD X X ZN 1 X

SOUTHWEST HALL PSD X X ZN 1 X

SOUTH WEST OFFICE PSD X X ZN 1 X

BREAK ROOM PSD X X ZN 1 X

TANK ROOM PSD X X ZN 1 X

FUEL SHOP PSD X X ZN 1 X

STORAGE PSD X X ZN 1 X

Fire Pump Tampers TS X X 1M025 X Fire Pump Tampers TS X X 1M025 X

Fire Pump Tampers TS X X 1M025 X

Fire Pump Tampers TS X X 1M025 X Fire Pump Tampers TS X X 1M025 X

Fire Pump Tampers TS X X 1M025 X

Fire Pump Tampers TS X X 1M025 X Fire Pump Tampers TS X X 1M025 X

Fire Pump Tampers TS X X 1M025 X

OS&Y Back Flow tamper switch OS&Y X X 1M029 X OS&Y Back Flow tamper switch OS&Y X X 1M029 X

PROPERTY NAME: FRESNO AIR NATIONAL GUARD BLDG 157 DATE: June 24, 2019

ADDRESS: 5323 E. MCKINLEY AVE, FRESNO, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Type VIS. FUNC. Address Pass Fail

PIV Behind Pump Room PIV X X 1M029 X

Deluge Valve Tamper Switch TS X X ZN03 X

Wet Pipe Low Bay Riser TS X X 1M027 X Wet Pipe High Bay Riser TS X X 1M027 X

Fire Pump Water flow WF X X 1M028 X

Wet Pipe High Bay Water Flow WF X X 1M026 X

Wet Pipe Low Bay Water Flow WF X X 1M023 X

Deluge Riser Pressure Switch HLPS X X ZN04 X

Hangar suppression manual dump pull station SMD X X 1M026 X Hangar suppression manual dump pull station SMD X X 1M026 X

Hangar suppression manual dump pull station SMD X X 1M026 X

Hangar suppression manual dump pull station SMD X X 1M026 X

To add more sheets, copy this page and paste it to the end of this document. Page 6 of 6