This document contains a request for quote for inspection services of fire alarm panels and devices at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is seeking a firm fixed price contract to inspect and correct any deficiencies in the fire protection systems, which were installed by Monaco Enterprises Inc. Interested parties must be registered in the System for Award Management and have a Commercial and Government Entity code. A site visit will be held on January 3rd, 2023, and attendees must complete a Department of Defense database enrollment process beforehand. Quotes are due by the date and time specified in the solicitation instructions and must be submitted to the Contracting inbox at the provided email address. The requirement is being competitively solicited and the Government reserves the right to amend or cancel the request for quote.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: June 24, 2019
Task Number: TIME: 7:00AM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 157
Address: 2788 N. Larkin Ave. Address: 5323 E McKinley Ave City, St., Zip: Fresno, CA, 93727 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House Contact: N/A
Telephone: N/A Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually RF X Annually
Other (Specify) Other (Specify)
System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: Notifier & Viking Model No.: Notifier & Viking foam releasing panel Circuit Style: B
Number of Circuits: NA
Software Rev.: NA Last Date System Had Any Service Performed: October 5, 2017
Last Date That Any Software or Configuration Was Revised: 1988
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
8 B 8 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
6 B 6 Photo Detectors (PSD)
0 0 Duct Detectors (DSD) 26 B 26 Heat Detectors (HD)
2 B 2 Water Flow Switches (WF)
4 B 4 (SMD) Suppression Manual Dump 0 0 (Specify)
0 0 (Specify)
Alarm verification feature is Disabled X Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
1 1 Bells
9 B 9 Horns with strobes 0 0 Chimes
3 B 3 Strobes
0 0 Speakers
0 0 (Specify)
Number of alarm notification appliance circuits:
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
11 B 11 Valve Position Tamper Switch (TS) 3 B 3 Outside Stem and Yoke (OSY)
1 B 1 Post Indicator Valve (PIV)
1 B 1 High / Low Pressure Switch (HLPS) 0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
1 B 1 Fire Pump Power 1 B 1 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble 0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): MECHANICAL ROOM
Disconnecting Means Location: PANEL X1 CIRCUIT 26
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah Two 12V 12Ah
Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: N/A
Location of fuel storage: N/A
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
NA Emergency system described in NFPA 70, Article 700
NA Legally required standby described in NFPA 70, Article 701 NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time Monitoring Entity X In House 7:00AM
Building Occupants X Staff 7:00AM Building Management X M.O.D 7:00AM
Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Good-Batteries Installed 12-2018
Load Voltage X Pass-26.44VDC Discharge test X Pass-25.64VDC
Charger test X Pass-27.24VDC
TRANSIENT SUPPRESSORS NA
REMOTE ANNUNCIATOR NA
NOTIFICATION APPLIANCES
Audible X X Pass Visible X X Pass
Speakers NA
Voice Clarity NA
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System N/A
CO2 Extinguishing System N/A (Specify) N/A
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested
Elevator Recall N/A
Fan Shutdown N/A Door Holders N/A Smoke Control System N/A Door Release (Security Maglocks) N/A (Specify) N/A
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments Building Management X M.O.D
Monitoring Agency X In House
Building Occupants X Staff Other (Specify)
The following did not operate correctly: No Deficiencies found during this inspection.
System restored to normal operation: Date: June 25, 2019 Time:
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado & Ryan Stone Date: June 26, 2019 Time:
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: FRESNO AIR NATIONAL GUARD BLDG 157 DATE: June 24, 2019
ADDRESS: 5323 E. MCKINLEY AVE, FRESNO, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Type VIS. FUNC. Address Pass Fail
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 8 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR HD X X ZN 9 X
HANGAR PSSA X X ZN 2 X
HANGAR OFFICE PSSA X X ZN 3 X
OFFICE PSSA X X ZN 3 X
HANGAR PSSA X X ZN 2 X
OFFICE PSSA X X ZN 3 X
OFFICE PSSA X X ZN 3 X
HANGAR PSSA X X ZN 2 X
ABOVE FACP PSD X X ZN 1 X
ABOVE FOAM TANK HD X X ZN 1 X
MECH ROOM HD X X ZN 1 X
MEN RESTROOM (2X) HD X X ZN 1 X
JANITOR CLOSET HD X X ZN 1 X
WOMEN RESTROOM (2X) HD X X ZN 1 X
SOUTHWEST HALL PSD X X ZN 1 X
SOUTH WEST OFFICE PSD X X ZN 1 X
BREAK ROOM PSD X X ZN 1 X
TANK ROOM PSD X X ZN 1 X
FUEL SHOP PSD X X ZN 1 X
STORAGE PSD X X ZN 1 X
Fire Pump Tampers TS X X 1M025 X Fire Pump Tampers TS X X 1M025 X
Fire Pump Tampers TS X X 1M025 X
Fire Pump Tampers TS X X 1M025 X Fire Pump Tampers TS X X 1M025 X
Fire Pump Tampers TS X X 1M025 X
Fire Pump Tampers TS X X 1M025 X Fire Pump Tampers TS X X 1M025 X
Fire Pump Tampers TS X X 1M025 X
OS&Y Back Flow tamper switch OS&Y X X 1M029 X OS&Y Back Flow tamper switch OS&Y X X 1M029 X
PROPERTY NAME: FRESNO AIR NATIONAL GUARD BLDG 157 DATE: June 24, 2019
ADDRESS: 5323 E. MCKINLEY AVE, FRESNO, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Type VIS. FUNC. Address Pass Fail
PIV Behind Pump Room PIV X X 1M029 X
Deluge Valve Tamper Switch TS X X ZN03 X
Wet Pipe Low Bay Riser TS X X 1M027 X Wet Pipe High Bay Riser TS X X 1M027 X
Fire Pump Water flow WF X X 1M028 X
Wet Pipe High Bay Water Flow WF X X 1M026 X
Wet Pipe Low Bay Water Flow WF X X 1M023 X
Deluge Riser Pressure Switch HLPS X X ZN04 X
Hangar suppression manual dump pull station SMD X X 1M026 X Hangar suppression manual dump pull station SMD X X 1M026 X
Hangar suppression manual dump pull station SMD X X 1M026 X
Hangar suppression manual dump pull station SMD X X 1M026 X
To add more sheets, copy this page and paste it to the end of this document. Page 6 of 6