Inspection of Fire Alarm Panels, Main Base
Solicitation number
W50S6T24QA011
Issued by

About this file

This document contains a request for quote for inspection services of fire alarm panels and devices at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is soliciting quotes for a firm fixed price contract to inspect and correct deficiencies in Monaco Enterprises Inc. fire protection systems at multiple buildings. Quotes are due by email to the 144th Fighter Wing contracting office before the specified due date and time. A site visit will be held on January 3rd, 2023 at 9:00am at the base for approved participants who complete a pre-enrollment security check. The contractor will be required to inspect and service fire alarm panels and devices at nineteen buildings to ensure compliance with applicable fire protection standards.

View the file

Other files

File Type Posted
FANG BLDG 145 ANN FA 7-2019.pdf PDF
FANG BLDG 122 ANN FA 7-2019.pdf PDF
FANG BLDG 130 ANN FA 6-2019.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base (HAYW231030)-Amd2.pdf PDF
FANG BLDG 135 ANN FA 6-2019.pdf PDF
FANG BLDG 2640 ANN FA 7-2019.pdf PDF
FANG BLDG 2602 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110002 SF 30.pdf PDF
FANG BLDG 102 ANN FA 7-2019.pdf PDF
FANG BLDG 121 ANN FA 7-2019.pdf PDF
FANG BLDG 159 ANNUAL FA 6-2019.pdf PDF
FANG BLDG 124 ANN FA 6-2019.pdf PDF
Solicitation Amendment - W50S6T24QA0110002 SF1449.pdf PDF
FANG BLDG 125 ANN FA 6-2019.pdf PDF
FANG BLDG 117 ANN FA 6-2019.pdf PDF
FANG BLDG 157 ANNUAL FA 6-2019.pdf PDF
FANG Bldg 100 Annual FA 6-2019.pdf PDF
FANG BLDG 155 ANN FA 7-2019.pdf PDF
FANG BLDG 104 ANN FA 7-2019.pdf PDF
FANG BLDG 225 ANN FA 6-2019.pdf PDF
FANG BLDG 2600 2601 ANN FA 7-2019.pdf PDF
FANG BLDG 194 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110001 SF 30.pdf PDF
Base Access-144 SFS DVES FORM- 20230127 (Site Visit).pdf PDF
Wage Determinations SCA - 2015-5609 dated 3Aug2023.pdf PDF
Solicitation - W50S6T24QA011 SF1449 RFQ.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SimplexGrinnell BE SAFE

INSPECTION AND TESTING FORM

SR Number: 44909832 DATE: June 26, 2019

Task Number: TIME: 12:00PM

SERVICE ORGANIZATION PROPERTY NAME (USER)

Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 126

Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave City, St., Zip: Fresno, Ca 93272 City, St., Zip: Fresno, CA, 93727

Representative: Jesus Salgado Owner Contact: Mike Scott License No.: 986047 Telephone: 559-454-5137

Telephone: 559-348-0614 Occupied as: Master Chief

MONITORING ENTITY APPROVING AGENCY

Contact: In House/ Fire Department Contact: N/A

Telephone: 559-454-5145 Telephone: N/A

Monitoring Account Ref. No.: N/A

TYPE TRANSMISSION SERVICE

McCulloh Weekly Multiplex Monthly

X Digital Quarterly

Reverse Polarity Semiannually RF X Annually

Other (Specify) Other (Specify)

System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm

Control Unit Manufacturer: Monaco Enterprise Model No.: M2 Circuit Style: B

Number of Circuits: NA

Software Rev.: NA Last Date System Had Any Service Performed: September 28, 2017

Last Date That Any Software or Configuration Was Revised: 2001

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity of Devices Installed

Circuit Style

Devices Tested

10 B 10 Manual Fire Alarm Boxes (PSSA)

0 0 Ion Detectors (ISD)

23 B 23 Photo Detectors (PSD)

0 0 Duct Detectors (DSD) 4 B 4 Heat Detectors (HD)

1 B 1 Water Flow Switches (WF)

0 0 (Specify) 0 0 (Specify)

0 0 (Specify)

Alarm verification feature is Disabled X Enabled .

Rev. D

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Appliances Installed

Appliances Tested

2 D 2 Bells

9 D 9 Horns with strobes 0 0 Chimes

2 D 2 Strobes

0 0 Speakers

0 0 (Specify)

Number of alarm notification appliance circuits: 1

Are circuits monitored for integrity? X Yes No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Devices Installed

Devices Tested

1 B 1 Valve Position Tamper Switch (TS) 0 0 Outside Stem and Yoke (OSY)

0 0 Post Indicator Valve (PIV)

0 0 High / Low Pressure Switch (HLPS) 0 0 Building Temperature

0 0 Site Water Temp

0 0 Site Water Level

0 0 Fire Pump Power 0 0 Fire Pump Running

0 0 Fire Pump Auto Position

0 0 Fire Pump or Fire Controller Trouble 0 0 Fire Pump Low Fuel

0 0 Other: Switch Transfer

0 0 Other: Generator Engine Running

SIGNALING LINE CIRCUIT

Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5

Overcurrent Protection: Type Circuit Breaker Amps 20

Location (of Primary Supply Panel): Mechanical Room

Disconnecting Means Location: PA Ckt#29

(b) Secondary (Standby):

Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah

Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.

Engine-driven generator dedicated to fire alarm system:

Location of fuel storage: None

TYPE BATTERY

Dry Cell Lead-Acid

Nickel-Cadmium Other (Specify):

X Sealed Lead-Acid

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

NA Emergency system described in NFPA 70, Article 700

NA Legally required standby described in NFPA 70, Article 701 NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time Monitoring Entity X In House 12:00PM

Building Occupants X Staff 12:00PM Building Management X M.O.D 12:00PM

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit X X Pass Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition X Good

Load Voltage X Pass-26.22VDC Discharge test X Pass-25.49VDC

Charger test X 27.71VDC

TRANSIENT SUPPRESSORS NA

REMOTE ANNUNCIATOR X X Pass-Hallway by entrance

NOTIFICATION APPLIANCES

Audible X X Pass Visible X X Pass

Speakers NA

Voice Clarity NA

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Location & Serial Number Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

See attached detailed report.

Date of Last Sensitivity Test: Unknown

EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments

Phone Set NA Phone Jacks NA

Off-Hook Indicators NA

Amplifier(s) NA

Tone Generator(s) NA Call-in Signal NA

System Performance NA

SPECIAL HAZARD SYSTEMS

Number Installed

Number Tested Comments

Kitchen Range Hood System NA

CO2 Extinguishing System NA (Specify) NA

CONTROL FUNCTIONS / INTERFACE

EQUIPMENT

Number Installed

Number Tested

Elevator Recall NA

Fan Shutdown NA

Door Holders NA

Smoke Control System NA Door Release (Security Maglocks) NA

(Specify) NA

Special Procedures:

Comments:

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal X Alarm Restoration X

Trouble Signal X

Trouble Signal Restoration X

Supervisory Signal X Supervisory Restoration X

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments Building Management X M.O.D

Monitoring Agency X In House

Building Occupants X Staff Other (Specify)

The following did not operate correctly: Hallway bell did not operate during alarm testing. *See picture* NOTE: HD are on the same zone as PSD. All HD address are labeled as PSD.

System restored to normal operation: Date: June 26, 2019 Time: 2:00PM

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Jesus Salgado Date: June 26, 2019 Time: 2:00PM

Signature:

Name of Owner or Rep.: Date: Time:

Signature:

PROPERTY NAME: Fresno Air National Guard Building 126 DATE: June 26, 2019

ADDRESS: 5323 E. McKinley Ave, Fresno, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Location & Serial Number Device Type VIS. FUNC. Address Pass Fail

ELECTRICAL ROOM PSSA X X Z2 X

ABOVE FACP PSD X X Z4 X

HIGH BAY PSD X X Z4 X

HIGH BAY PSSA X X Z2 X

EOD PSD X X Z4 X

EOD REC PSD X X Z4 X

FLY CHIEF OFFICE PSD X X Z4 X

EOD OFFICE PSD X X Z4 X

218 EOD OFFICE PSD X X Z4 X

217 PSD PSD X X Z4 X

WEST EXIT PSSA X X Z2 X

216 PSD X X Z4 X

216 PSD X X Z4 X

212 PSD X X Z4 X

HALLWAY BY 217 PSSA X X Z2 X

EAST EXIT PSD X X Z4 X

210 PSD X X Z4 X

EAST EXIT PSSA X X Z2 X

207 PSD X X Z4 X

201 PSD X X Z4 X

201 PSD X X Z4 X

201 PSD X X Z4 X

201 PSD X X Z4 X

201 PSD X X Z4 X

201 PSD X X Z4 X

SOUTHWEST EXIT PSSA X X Z2 X

BUTTERFLY VALVE TS X X Z3 X

208 HD X X Z4 X

FRONT OF WMN RR HD X X Z4 X

BY WMN RR PSSA X X Z2 X

215 PSD X X Z4 X

215 PSD X X Z4 X

211 HD X X Z4 X

WMN RR HD X X Z4 X

MEN RR HD X X Z4 X

ITV LOCATED IN ROOM 216 62 SECONDS WF X X Z1 X