This document contains a request for quote for inspection services of fire alarm panels and devices at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is soliciting quotes for a firm fixed price contract to inspect and correct deficiencies in Monaco Enterprises Inc. fire protection systems at multiple buildings. Quotes are due by email to the 144th Fighter Wing contracting office before the specified due date and time. A site visit will be held on January 3rd, 2023 at 9:00am at the base for approved participants who complete a pre-enrollment security check. The contractor will be required to inspect and service fire alarm panels and devices at nineteen buildings to ensure compliance with applicable fire protection standards.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: June 26, 2019
Task Number: TIME: 12:00PM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 126
Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave City, St., Zip: Fresno, Ca 93272 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Master Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House/ Fire Department Contact: N/A
Telephone: 559-454-5145 Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually RF X Annually
Other (Specify) Other (Specify)
System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: Monaco Enterprise Model No.: M2 Circuit Style: B
Number of Circuits: NA
Software Rev.: NA Last Date System Had Any Service Performed: September 28, 2017
Last Date That Any Software or Configuration Was Revised: 2001
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
10 B 10 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
23 B 23 Photo Detectors (PSD)
0 0 Duct Detectors (DSD) 4 B 4 Heat Detectors (HD)
1 B 1 Water Flow Switches (WF)
0 0 (Specify) 0 0 (Specify)
0 0 (Specify)
Alarm verification feature is Disabled X Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
2 D 2 Bells
9 D 9 Horns with strobes 0 0 Chimes
2 D 2 Strobes
0 0 Speakers
0 0 (Specify)
Number of alarm notification appliance circuits: 1
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
1 B 1 Valve Position Tamper Switch (TS) 0 0 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
0 0 High / Low Pressure Switch (HLPS) 0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
0 0 Fire Pump Power 0 0 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble 0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): Mechanical Room
Disconnecting Means Location: PA Ckt#29
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah
Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system:
Location of fuel storage: None
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
NA Emergency system described in NFPA 70, Article 700
NA Legally required standby described in NFPA 70, Article 701 NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time Monitoring Entity X In House 12:00PM
Building Occupants X Staff 12:00PM Building Management X M.O.D 12:00PM
Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Good
Load Voltage X Pass-26.22VDC Discharge test X Pass-25.49VDC
Charger test X 27.71VDC
TRANSIENT SUPPRESSORS NA
REMOTE ANNUNCIATOR X X Pass-Hallway by entrance
NOTIFICATION APPLIANCES
Audible X X Pass Visible X X Pass
Speakers NA
Voice Clarity NA
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA (Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested
Elevator Recall NA
Fan Shutdown NA
Door Holders NA
Smoke Control System NA Door Release (Security Maglocks) NA
(Specify) NA
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments Building Management X M.O.D
Monitoring Agency X In House
Building Occupants X Staff Other (Specify)
The following did not operate correctly: Hallway bell did not operate during alarm testing. *See picture* NOTE: HD are on the same zone as PSD. All HD address are labeled as PSD.
System restored to normal operation: Date: June 26, 2019 Time: 2:00PM
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado Date: June 26, 2019 Time: 2:00PM
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 126 DATE: June 26, 2019
ADDRESS: 5323 E. McKinley Ave, Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Location & Serial Number Device Type VIS. FUNC. Address Pass Fail
ELECTRICAL ROOM PSSA X X Z2 X
ABOVE FACP PSD X X Z4 X
HIGH BAY PSD X X Z4 X
HIGH BAY PSSA X X Z2 X
EOD PSD X X Z4 X
EOD REC PSD X X Z4 X
FLY CHIEF OFFICE PSD X X Z4 X
EOD OFFICE PSD X X Z4 X
218 EOD OFFICE PSD X X Z4 X
217 PSD PSD X X Z4 X
WEST EXIT PSSA X X Z2 X
216 PSD X X Z4 X
216 PSD X X Z4 X
212 PSD X X Z4 X
HALLWAY BY 217 PSSA X X Z2 X
EAST EXIT PSD X X Z4 X
210 PSD X X Z4 X
EAST EXIT PSSA X X Z2 X
207 PSD X X Z4 X
201 PSD X X Z4 X
201 PSD X X Z4 X
201 PSD X X Z4 X
201 PSD X X Z4 X
201 PSD X X Z4 X
201 PSD X X Z4 X
SOUTHWEST EXIT PSSA X X Z2 X
BUTTERFLY VALVE TS X X Z3 X
208 HD X X Z4 X
FRONT OF WMN RR HD X X Z4 X
BY WMN RR PSSA X X Z2 X
215 PSD X X Z4 X
215 PSD X X Z4 X
211 HD X X Z4 X
WMN RR HD X X Z4 X
MEN RR HD X X Z4 X
ITV LOCATED IN ROOM 216 62 SECONDS WF X X Z1 X