FANG BLDG 102 ANN FA 7-2019.pdf

PDF 201 KB Posted

Attached to
Inspection of Fire Alarm Panels, Main Base
Solicitation number
W50S6T24QA011
Issued by

About this file

This document contains a fire alarm system inspection report and related federal contract opportunity solicitation. The inspection report details the results of testing fire alarm panels, devices, and circuits for 19 buildings at the Fresno Air National Guard Base. It identifies deficiencies including a fire panel that did not send an alarm signal to the firehouse. The related solicitation seeks quotes to inspect and correct deficiencies in the Monaco Enterprises fire protection systems for the 19 buildings. Interested parties must register in SAM and have a CAGE code. The solicitation will award a firm fixed price contract without negotiations. Quotes are due by the specified time and date and must be submitted to the listed Contracting inbox. A site visit will be held on January 3, 2023 at 9:00 am for pre-enrolled attendees who are cleared through security screening.

View the file

Other files

File Type Posted
FANG BLDG 145 ANN FA 7-2019.pdf PDF
FANG BLDG 122 ANN FA 7-2019.pdf PDF
FANG BLDG 130 ANN FA 6-2019.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base (HAYW231030)-Amd2.pdf PDF
FANG BLDG 135 ANN FA 6-2019.pdf PDF
FANG BLDG 2640 ANN FA 7-2019.pdf PDF
FANG BLDG 2602 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110002 SF 30.pdf PDF
FANG BLDG 121 ANN FA 7-2019.pdf PDF
FANG BLDG 159 ANNUAL FA 6-2019.pdf PDF
FANG BLDG 124 ANN FA 6-2019.pdf PDF
Solicitation Amendment - W50S6T24QA0110002 SF1449.pdf PDF
FANG BLDG 125 ANN FA 6-2019.pdf PDF
FANG BLDG 117 ANN FA 6-2019.pdf PDF
FANG BLDG 126 ANN FA 6-2019.pdf PDF
FANG BLDG 157 ANNUAL FA 6-2019.pdf PDF
FANG Bldg 100 Annual FA 6-2019.pdf PDF
FANG BLDG 155 ANN FA 7-2019.pdf PDF
FANG BLDG 104 ANN FA 7-2019.pdf PDF
FANG BLDG 225 ANN FA 6-2019.pdf PDF
FANG BLDG 2600 2601 ANN FA 7-2019.pdf PDF
FANG BLDG 194 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110001 SF 30.pdf PDF
Base Access-144 SFS DVES FORM- 20230127 (Site Visit).pdf PDF
Wage Determinations SCA - 2015-5609 dated 3Aug2023.pdf PDF
Solicitation - W50S6T24QA011 SF1449 RFQ.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SimplexGrinnell BE SAFE

INSPECTION AND TESTING FORM

SR Number: 44909832 DATE: July 1, 2019

Task Number: TIME: 1:00PM

SERVICE ORGANIZATION PROPERTY NAME (USER)

Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 102

Address: 2788 N. Larkin Ave. Address: 5323 E McKinley Ave

City, St., Zip: Fresno, CA, 93727 City, St., Zip: Fresno, CA, 93727

Representative: Jesus Salgado Owner Contact: Mike Scott

License No.: 986047 Telephone: 559-454-5137

Telephone: 559-348-0614 Occupied as: Master Chief

MONITORING ENTITY APPROVING AGENCY

Contact: In House Fire Department Contact: N/A

Telephone: 559-454-5145 Telephone: N/A

Monitoring Account Ref. No.: N/A

TYPE TRANSMISSION SERVICE

McCulloh Weekly

Multiplex Monthly

X Digital Quarterly

Reverse Polarity Semiannually

RF X Annually

Other (Specify) Other (Specify)

System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm

Control Unit Manufacturer: Monaco Enterprise Model No.: BT2-7

Circuit Style: B

Number of Circuits: Unknown

Software Rev.: Unknown

Last Date System Had Any Service Performed: September 27, 2017

Last Date That Any Software or Configuration Was Revised: Unknown

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity of Devices Installed

Circuit Style

Devices Tested

7 B 7 Manual Fire Alarm Boxes (PSSA)

0 0 Ion Detectors (ISD)

2 B 2 Photo Detectors (PSD)

0 0 Duct Detectors (DSD)

4 B 4 Heat Detectors (HD)

0 0 Water Flow Switches (WF)

0 0 (Specify)

0 0 (Specify)

0 0 (Specify)

Alarm verification feature is Disabled X Enabled .

Rev. D

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Appliances Installed

Appliances Tested

1 B 1 Bells

3 B 3 Horns with strobes

0 0 Chimes

0 0 Strobes

1 B 1 Speakers

0 (Specify)

Number of alarm notification appliance circuits: 2

Are circuits monitored for integrity? X Yes No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Devices Installed

Devices Tested

1 0 Valve Position Tamper Switch (TS)

0 0 Outside Stem and Yoke (OSY)

0 0 Post Indicator Valve (PIV)

0 0 High / Low Pressure Switch (HLPS)

0 0 Building Temperature

0 0 Site Water Temp

0 0 Site Water Level

0 0 Fire Pump Power

0 0 Fire Pump Running

0 0 Fire Pump Auto Position

0 0 Fire Pump or Fire Controller Trouble

0 0 Fire Pump Low Fuel

0 0 Other: Switch Transfer

0 0 Other: Generator Engine Running

SIGNALING LINE CIRCUIT

Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5

Overcurrent Protection: Type Circuit Breaker Amps 20

Location (of Primary Supply Panel):

Disconnecting Means Location:

(b) Secondary (Standby):

Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 8.5Ah

Calculated capacity is 17 Amp-Hrs to operate system for 24 Hours.

Engine-driven generator dedicated to fire alarm system: N/A

Location of fuel storage: N/A

TYPE BATTERY

Dry Cell Lead-Acid

Nickel-Cadmium Other (Specify):

X Sealed Lead-Acid

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

NA Emergency system described in NFPA 70, Article 700

NA Legally required standby described in NFPA 70, Article 701

NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time

Monitoring Entity X In House/FD 1:00PM

Building Occupants X Staff 1:00PM

Building Management X Chief Mike Scott 1:00PM

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit X X Pass

Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition X Good-Batteries Installed 12-2017

Load Voltage X Pass-26.42VDC

Discharge test X Pass-25.99VDC

Charger test X Pass-27.49VDC

TRANSIENT SUPPRESSORS NA

REMOTE ANNUNCIATOR NA

NOTIFICATION APPLIANCES

Audible X X Pass

Visible X X Pass

Speakers NA

Voice Clarity NA

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Location & Serial Number Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

See attached detailed report.

Date of Last Sensitivity Test:

EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments

Phone Set NA

Phone Jacks NA

Off-Hook Indicators NA

Amplifier(s) NA

Tone Generator(s) NA

Call-in Signal NA

System Performance NA

SPECIAL HAZARD SYSTEMS

Number Installed

Number Tested Comments

Kitchen Range Hood System NA

CO2 Extinguishing System NA

(Specify) NA

CONTROL FUNCTIONS / INTERFACE

EQUIPMENT

Number Installed

Number Tested

Elevator Recall NA

Fan Shutdown NA

Door Holders NA

Smoke Control System NA

Door Release (Security Maglocks)

(Specify) NA

Special Procedures:

Comments: Fire Sprinkler Riser control valve was shut upon arrival. Did no procced with the sprinkler

Inspection.

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal X

Alarm Restoration X

Trouble Signal X

Trouble Signal Restoration X

Supervisory Signal X

Supervisory Restoration X

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments

Building Management X Chief Mike Scott

Monitoring Agency X In House

Building Occupants X Staff

Other (Specify)

The following did not operate correctly: Fire alarm panel did not send an alarm signal to the fire house

Station. Recommend placing a service call to have this checked out.

System restored to normal operation: Date: July 1, 2019 Time:

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Jesus Salgado Date: July 1, 2019 Time:

Signature:

Name of Owner or Rep.: Date: Time:

Signature:

PROPERTY NAME: Fresno Air National Guard Building 104 DATE: July 1, 2019

ADDRESS: 5323 E McKinley Ave Fresno, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Location & Serial Number Device Type VIS. FUNC. Address Pass Fail

OFFICE SUPERVISOR PSSA X X X

OFFICE PSSA X X X

SOUTH EXIT PSSA X X X

REST ROOM PSD X X X

REST ROOM PSD X X X

BAY HD X X X

BAY HD X X X

BAY HD X X X

BAY HD X X X

BAY PSSA X X X

OUTSIDE NORTH EXIT PSSA X X X

WEST EXIT PSSA X X X

WEST EXIT PSSA X X X