This document includes a request for quote for inspection services of fire alarm panels and devices at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is seeking a firm fixed price contract to inspect and correct any deficiencies in the Monaco Enterprises Inc. fire protection systems. Interested parties must have a CAGE code and SAM registration. Quotes are due by email to the specified Contracting inbox before the stated due date and time. A site visit will be held on January 3rd, 2023, with attendees requiring DBIDS pre-enrollment clearance. The requirement is being solicited through full and open competition. The Government reserves the right to amend or cancel the solicitation before or after the closing date and submitted offers will be valid for 30 days.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: June 26, 2019
Task Number: TIME: 7:00AM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 125
Address: 2788 N. Larkin Ave. Address: 5323 E. MCKINNELY
City, St., Zip: Fresno, CA, 93272 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott
License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: 559-454-5137
MONITORING ENTITY APPROVING AGENCY
Contact: In House Contact: N/A
Telephone: N/A Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly
Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually
RF X Annually
Other (Specify) Other (Specify)
System Type: ( X ) Local; ( ) Auxiliary; ( ) Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: MONACO M-2 Model No.: Notifier RP-1001 Pre Action Panel
Circuit Style: B
Number of Circuits: N/A
Software Rev.: N/A
Last Date System Had Any Service Performed: October 5, 2017
Last Date That Any Software or Configuration Was Revised: N/A
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
10 B 10 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
30 B 30 Photo Detectors (PSD)
0 0 Duct Detectors (DSD)
65 B 65 Heat Detectors (HD)
1 B 1 Water Flow Switches (WF)
0 0 (Specify)
0 0 (Specify)
Alarm verification feature is disabled Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
1 1 Bells
12 B 12 Horns with strobes
0 0 Chimes
4 B 4 Strobes
1 B 1 Horns
Number of alarm notification appliance circuits: 6
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
4 B 4 Valve Position Tamper Switch (TS)
4 B 4 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
3 B 3 High / Low Pressure Switch (HLPS)
0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
0 0 Fire Pump Power
0 0 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble
0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): Hallway
Disconnecting Means Location: Electrical Room
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah
Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: NA
Location of fuel storage: NA
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701
Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity X In House 7:30AM
Building Occupants X Staff 7:30AM
Building Management X Chief 7:30AM
Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass
Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Good Condition
Load Voltage X Pass-26.84VDC
Discharge test X Pass-25.89VDV
Charger test X Pass-27.61VDC
TRANSIENT SUPPRESSORS NA
REMOTE ANNUNCIATOR NA
NOTIFICATION APPLIANCES
Audible X X Pass
Visible X X Pass
Speakers N/A
Voice Clarity N/A
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA
Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA
Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA
(Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested Comments
Elevator Recall NA
Fan Shutdown NA
Door Holders NA
Smoke Control System NA
Door Release (Security Maglocks) NA
(Specify) NA
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X
Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X
Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments
Building Management X M.O.D
Monitoring Agency X In House
Building Occupants X Staff/FD
Other (Specify)
The following did not operate correctly: No deficiencies found during this inspection.
System restored to normal operation: Date: June 26, 2019 Time: 12:00PM
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado & Ryan Stone Date: June 26, 2019 Time: 12:00PM
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 125 DATE: June 26, 2019
ADDRESS: 5323 E. McKinley Ave, Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Type VIS. FUNC. ZONE Pass Fail
PRE-ACTION MAIN SHOP STS X X X
PRE-ACTION DPI/COMP ROOM STS X X X
PRE-ACTION COMM VAULT STS X X X
WET RISER STS X X X
MAC CONTROL PSD X X L1-1 X
KEY ROOM PSD X X L1-1 X
BLUE PRINT ROOM PSD X X L1-1 X
ADMIN PSD X X L1-1 X
ADMIN HALL PSD X X L1-1 X
GYM PSD X X ZN 3 X
GYM PSD X X ZN 3 X
COMM BREAK ROOM PSD X X ZN 1 X
NCC HELP DESK PSD X X L2-1 X
CLASS ROOM PSD X X ZN 1 X
COMM HALLWAY PSD X X ZN 1 X
NCC ROOM PSD X X L2-2 X
NCC ROOM PSD X X L2-2 X
WAREHOUSE INFO AREA PSD X X L3-1 X
WAREHOUSE INFO AREA PSD X X L3-1 X
COMM OFFICE PSD X X L5-3 X
HALL BY COMMANDERS OFFICE PSD X X ZN 1 X
NCC SERVER ROOM PSD X X L2-1 X
NCC SERVER ROOM PSD X X L2-1 X
NCC SERRVER ROOM PSD X X L2-1 X
NCC SERVER ROOM PSD X X L2-1 X
NCC VAULT PSD X X L2-3 X
NCC VAULT PSD X X L2-3 X
COMM HALL PSD X X ZN 3 X
COMM HALL PSD X X L5-2 X
REST ROOM PSD X X L5-3 X
OUTSIDE PUBLIC AFFAIRS PSD X X L5-3 X
N.E. EXIT HALL PSD X X L5-3 X
COMM ROOM BY REST ROOM PSD X X L5-3 X
PUBLIC AFFAIRS HALL PSD X X L5-3 X
MECH SHOP HD X X L1-3 X
COMM OFFICE HD X X L5-1 X
COMM CC HD X X L5-2 X
COMM CC HD X X L5-2 X
COMM STORAGE HD X X L5-2 X
COMM HALL HD X X L5-1 X
CLASS ROOM HD X X L5-1 X
CLASS ROOM HD X X L5-1 X
CLASS ROOM HD X X L5-1 X
COMM HALL HD X X L5-1 X
COMM HALL HD X X L5-3 X
PUBLIC AFFAIRS HD X X L6-1 X
PUBLIC AFFAIRS HD X X L6-1 X
PUBLIC AFFAIRS STUDIO ROOM HD X X L6-1 X
PUBLIC AFFAIRS STUDIO ROOM HD X X L6-1 X
PUBLIC AFFAIRS END ROOM HD X X L6-1 X
Type VIS. FUNC. ZONE Pass Fail
PUBLIC AFFAIRS STORAGE HD X X L6-1 X
PUBLIC AFFAIRS COMP ROOM HD X X L6-1 X
PUBLIC AFFAIRS OFFICE HD X X L6-1 X
PUBLIC AFFAIRS OFFICE HD X X L6-1 X
OUTSIDE PUBLIC AFFAIRS HD X X L5-1 X
PUBLIC AFFAIRS HALL HD X X L5-1 X
MAIL ROOM HD X X L5-1 X
MAIL ROOM OFFICE HD X X L5-1 X
WAREHOUSE INFO AREA HD X X ZN 1 X
WAREHOUSE INFO AREA HD X X ZN 1 X
MAINTENANCE OFFICE HD X X ZN 1 X
HALL BY COMMANDERS OFFICE HD X X ZN 1 X
COMM HALL HD X X ZN 1 X
COMM HALL HD X X ZN 1 X
COMM HALL HD X X ZN 1 X
COMM HALL HD X X ZN 1 X
COMM HALL HD X X ZN 1 X
COMM HALL HD X X ZN 1 X
MAIN ENTRANCE HD X X ZN 1 X
HALL BY REST ROOMS HD X X X
HALL BY REST ROOMS HD X X X
OUTSIDE WOMENS REST ROOM HD X X X
OUTSIDE MENS REST ROOM HD X X X
VENDING AREA HD X X X
MENS REST ROOM HD X X X
MENS REST ROOM HD X X X
WOMENS REST ROOM HD X X X
CONFERENCE ROOM HALL HD X X L1-1 X
CONFERENCE ROOM HD X X L1-1 X
ADMIN AREA HD X X L1-1 X
CHIEF SCOTTS OFFICE HD X X L1-1 X
SQUADRON COMMANDER HD X X L1-1 X
REAL PROPERTY HD X X L1-1 X
BASE CIVIL ENGINEER HD X X L1-1 X
ENGINEERING HD X X L1-1 X
ASSIST BCE HD X X L1-1 X
PLANS ROOM HD X X L1-1 X
CUSTOMER SERVICE HD X X L1-1 X
SUPERINTENDANT OFFICE HD X X L1-1 X
WAREHOUSE MECH SHOP HD X X L1-1 X
WAREHOUSE MECH SHOP HD X X L1-1 X
WAREHOUSE MECH SHOP HD X X L1-1 X
WAREHOUSE MECH SHOP HD X X L1-1 X
ADMIN EXIT WORK CONTROL HD X X L1-1 X
COMM FLIGHT STORAGE HD X X L1-1 X
MECH ROOM HD X X X
ELECTRICAL SHOP HD X X X
ELECTRICAL SHOP HD X X X
WELDING SHOP HD X X X
POWER PRODUCTION HD X X X
To add more sheets, copy this page and paste it to the end of this document. Page 6 Of 7
Type VIS. FUNC. ZONE Pass Fail
COMM OFFICE PSSA X X L5-4 X
WAREHOUSE PSSA X X ZN 2 X
COMM FOCAL POINT PSSA X X L2-1 X
MAIN ENTRANCE PSSA X X ZN 4 X
COMMANDER OFFICE PSSA X X ZN 2 X
COMM HALL PSSA X X ZN4 X
PUBLIC AFFAIRS STORAGE PSSA X X L5-4 X
EXIT BY PUBLIC AFFAIRS PSSA X X L5-4 X
N.E.EXIT HALL PSSA X X L5-4 X
NE ATTIC HEATS HD X X L5-2 X
4009 Simplex NAC Panel Hall by FACP NAC X X N/A X
Pre Action Shop Room 20 Seconds HLPS X X L6-4 X
Pre Action Maintenance Shop 20 Seconds HLPS X X L3-3 X
Pre Action DP1 20 Seconds HLPS X X L3-2 X
Wet Pipe Water Flow 20 Seconds WF X X L3-4 X