FANG BLDG 125 ANN FA 6-2019.pdf

PDF 356 KB Posted

Attached to
Inspection of Fire Alarm Panels, Main Base
Solicitation number
W50S6T24QA011
Issued by

About this file

This document includes a request for quote for inspection services of fire alarm panels and devices at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is seeking a firm fixed price contract to inspect and correct any deficiencies in the Monaco Enterprises Inc. fire protection systems. Interested parties must have a CAGE code and SAM registration. Quotes are due by email to the specified Contracting inbox before the stated due date and time. A site visit will be held on January 3rd, 2023, with attendees requiring DBIDS pre-enrollment clearance. The requirement is being solicited through full and open competition. The Government reserves the right to amend or cancel the solicitation before or after the closing date and submitted offers will be valid for 30 days.

View the file

Other files

File Type Posted
FANG BLDG 145 ANN FA 7-2019.pdf PDF
FANG BLDG 122 ANN FA 7-2019.pdf PDF
FANG BLDG 130 ANN FA 6-2019.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base (HAYW231030)-Amd2.pdf PDF
FANG BLDG 135 ANN FA 6-2019.pdf PDF
FANG BLDG 2640 ANN FA 7-2019.pdf PDF
FANG BLDG 2602 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110002 SF 30.pdf PDF
FANG BLDG 102 ANN FA 7-2019.pdf PDF
FANG BLDG 121 ANN FA 7-2019.pdf PDF
FANG BLDG 159 ANNUAL FA 6-2019.pdf PDF
FANG BLDG 124 ANN FA 6-2019.pdf PDF
Solicitation Amendment - W50S6T24QA0110002 SF1449.pdf PDF
FANG BLDG 117 ANN FA 6-2019.pdf PDF
FANG BLDG 126 ANN FA 6-2019.pdf PDF
FANG BLDG 157 ANNUAL FA 6-2019.pdf PDF
FANG Bldg 100 Annual FA 6-2019.pdf PDF
FANG BLDG 155 ANN FA 7-2019.pdf PDF
FANG BLDG 104 ANN FA 7-2019.pdf PDF
FANG BLDG 225 ANN FA 6-2019.pdf PDF
FANG BLDG 2600 2601 ANN FA 7-2019.pdf PDF
FANG BLDG 194 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110001 SF 30.pdf PDF
Base Access-144 SFS DVES FORM- 20230127 (Site Visit).pdf PDF
Wage Determinations SCA - 2015-5609 dated 3Aug2023.pdf PDF
Solicitation - W50S6T24QA011 SF1449 RFQ.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SimplexGrinnell BE SAFE

INSPECTION AND TESTING FORM

SR Number: 44909832 DATE: June 26, 2019

Task Number: TIME: 7:00AM

SERVICE ORGANIZATION PROPERTY NAME (USER)

Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 125

Address: 2788 N. Larkin Ave. Address: 5323 E. MCKINNELY

City, St., Zip: Fresno, CA, 93272 City, St., Zip: Fresno, CA, 93727

Representative: Jesus Salgado Owner Contact: Mike Scott

License No.: 986047 Telephone: 559-454-5137

Telephone: 559-348-0614 Occupied as: 559-454-5137

MONITORING ENTITY APPROVING AGENCY

Contact: In House Contact: N/A

Telephone: N/A Telephone: N/A

Monitoring Account Ref. No.: N/A

TYPE TRANSMISSION SERVICE

McCulloh Weekly

Multiplex Monthly

X Digital Quarterly

Reverse Polarity Semiannually

RF X Annually

Other (Specify) Other (Specify)

System Type: ( X ) Local; ( ) Auxiliary; ( ) Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm

Control Unit Manufacturer: MONACO M-2 Model No.: Notifier RP-1001 Pre Action Panel

Circuit Style: B

Number of Circuits: N/A

Software Rev.: N/A

Last Date System Had Any Service Performed: October 5, 2017

Last Date That Any Software or Configuration Was Revised: N/A

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity of Devices Installed

Circuit Style

Devices Tested

10 B 10 Manual Fire Alarm Boxes (PSSA)

0 0 Ion Detectors (ISD)

30 B 30 Photo Detectors (PSD)

0 0 Duct Detectors (DSD)

65 B 65 Heat Detectors (HD)

1 B 1 Water Flow Switches (WF)

0 0 (Specify)

0 0 (Specify)

Alarm verification feature is disabled Enabled .

Rev. D

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Appliances Installed

Appliances Tested

1 1 Bells

12 B 12 Horns with strobes

0 0 Chimes

4 B 4 Strobes

1 B 1 Horns

Number of alarm notification appliance circuits: 6

Are circuits monitored for integrity? X Yes No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Devices Installed

Devices Tested

4 B 4 Valve Position Tamper Switch (TS)

4 B 4 Outside Stem and Yoke (OSY)

0 0 Post Indicator Valve (PIV)

3 B 3 High / Low Pressure Switch (HLPS)

0 0 Building Temperature

0 0 Site Water Temp

0 0 Site Water Level

0 0 Fire Pump Power

0 0 Fire Pump Running

0 0 Fire Pump Auto Position

0 0 Fire Pump or Fire Controller Trouble

0 0 Fire Pump Low Fuel

0 0 Other: Switch Transfer

0 0 Other: Generator Engine Running

SIGNALING LINE CIRCUIT

Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5

Overcurrent Protection: Type Circuit Breaker Amps 20

Location (of Primary Supply Panel): Hallway

Disconnecting Means Location: Electrical Room

(b) Secondary (Standby):

Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah

Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.

Engine-driven generator dedicated to fire alarm system: NA

Location of fuel storage: NA

TYPE BATTERY

Dry Cell Lead-Acid

Nickel-Cadmium Other (Specify):

X Sealed Lead-Acid

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701

Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time

Monitoring Entity X In House 7:30AM

Building Occupants X Staff 7:30AM

Building Management X Chief 7:30AM

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit X X Pass

Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition X Good Condition

Load Voltage X Pass-26.84VDC

Discharge test X Pass-25.89VDV

Charger test X Pass-27.61VDC

TRANSIENT SUPPRESSORS NA

REMOTE ANNUNCIATOR NA

NOTIFICATION APPLIANCES

Audible X X Pass

Visible X X Pass

Speakers N/A

Voice Clarity N/A

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Location & Serial Number Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

See attached detailed report.

Date of Last Sensitivity Test: Unknown

EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments

Phone Set NA

Phone Jacks NA

Off-Hook Indicators NA

Amplifier(s) NA

Tone Generator(s) NA

Call-in Signal NA

System Performance NA

SPECIAL HAZARD SYSTEMS

Number Installed

Number Tested Comments

Kitchen Range Hood System NA

CO2 Extinguishing System NA

(Specify) NA

CONTROL FUNCTIONS / INTERFACE

EQUIPMENT

Number Installed

Number Tested Comments

Elevator Recall NA

Fan Shutdown NA

Door Holders NA

Smoke Control System NA

Door Release (Security Maglocks) NA

(Specify) NA

Special Procedures:

Comments:

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal X

Alarm Restoration X

Trouble Signal X

Trouble Signal Restoration X

Supervisory Signal X

Supervisory Restoration X

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments

Building Management X M.O.D

Monitoring Agency X In House

Building Occupants X Staff/FD

Other (Specify)

The following did not operate correctly: No deficiencies found during this inspection.

System restored to normal operation: Date: June 26, 2019 Time: 12:00PM

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Jesus Salgado & Ryan Stone Date: June 26, 2019 Time: 12:00PM

Signature:

Name of Owner or Rep.: Date: Time:

Signature:

PROPERTY NAME: Fresno Air National Guard Building 125 DATE: June 26, 2019

ADDRESS: 5323 E. McKinley Ave, Fresno, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Type VIS. FUNC. ZONE Pass Fail

PRE-ACTION MAIN SHOP STS X X X

PRE-ACTION DPI/COMP ROOM STS X X X

PRE-ACTION COMM VAULT STS X X X

WET RISER STS X X X

MAC CONTROL PSD X X L1-1 X

KEY ROOM PSD X X L1-1 X

BLUE PRINT ROOM PSD X X L1-1 X

ADMIN PSD X X L1-1 X

ADMIN HALL PSD X X L1-1 X

GYM PSD X X ZN 3 X

GYM PSD X X ZN 3 X

COMM BREAK ROOM PSD X X ZN 1 X

NCC HELP DESK PSD X X L2-1 X

CLASS ROOM PSD X X ZN 1 X

COMM HALLWAY PSD X X ZN 1 X

NCC ROOM PSD X X L2-2 X

NCC ROOM PSD X X L2-2 X

WAREHOUSE INFO AREA PSD X X L3-1 X

WAREHOUSE INFO AREA PSD X X L3-1 X

COMM OFFICE PSD X X L5-3 X

HALL BY COMMANDERS OFFICE PSD X X ZN 1 X

NCC SERVER ROOM PSD X X L2-1 X

NCC SERVER ROOM PSD X X L2-1 X

NCC SERRVER ROOM PSD X X L2-1 X

NCC SERVER ROOM PSD X X L2-1 X

NCC VAULT PSD X X L2-3 X

NCC VAULT PSD X X L2-3 X

COMM HALL PSD X X ZN 3 X

COMM HALL PSD X X L5-2 X

REST ROOM PSD X X L5-3 X

OUTSIDE PUBLIC AFFAIRS PSD X X L5-3 X

N.E. EXIT HALL PSD X X L5-3 X

COMM ROOM BY REST ROOM PSD X X L5-3 X

PUBLIC AFFAIRS HALL PSD X X L5-3 X

MECH SHOP HD X X L1-3 X

COMM OFFICE HD X X L5-1 X

COMM CC HD X X L5-2 X

COMM CC HD X X L5-2 X

COMM STORAGE HD X X L5-2 X

COMM HALL HD X X L5-1 X

CLASS ROOM HD X X L5-1 X

CLASS ROOM HD X X L5-1 X

CLASS ROOM HD X X L5-1 X

COMM HALL HD X X L5-1 X

COMM HALL HD X X L5-3 X

PUBLIC AFFAIRS HD X X L6-1 X

PUBLIC AFFAIRS HD X X L6-1 X

PUBLIC AFFAIRS STUDIO ROOM HD X X L6-1 X

PUBLIC AFFAIRS STUDIO ROOM HD X X L6-1 X

PUBLIC AFFAIRS END ROOM HD X X L6-1 X

Type VIS. FUNC. ZONE Pass Fail

PUBLIC AFFAIRS STORAGE HD X X L6-1 X

PUBLIC AFFAIRS COMP ROOM HD X X L6-1 X

PUBLIC AFFAIRS OFFICE HD X X L6-1 X

PUBLIC AFFAIRS OFFICE HD X X L6-1 X

OUTSIDE PUBLIC AFFAIRS HD X X L5-1 X

PUBLIC AFFAIRS HALL HD X X L5-1 X

MAIL ROOM HD X X L5-1 X

MAIL ROOM OFFICE HD X X L5-1 X

WAREHOUSE INFO AREA HD X X ZN 1 X

WAREHOUSE INFO AREA HD X X ZN 1 X

MAINTENANCE OFFICE HD X X ZN 1 X

HALL BY COMMANDERS OFFICE HD X X ZN 1 X

COMM HALL HD X X ZN 1 X

COMM HALL HD X X ZN 1 X

COMM HALL HD X X ZN 1 X

COMM HALL HD X X ZN 1 X

COMM HALL HD X X ZN 1 X

COMM HALL HD X X ZN 1 X

MAIN ENTRANCE HD X X ZN 1 X

HALL BY REST ROOMS HD X X X

HALL BY REST ROOMS HD X X X

OUTSIDE WOMENS REST ROOM HD X X X

OUTSIDE MENS REST ROOM HD X X X

VENDING AREA HD X X X

MENS REST ROOM HD X X X

MENS REST ROOM HD X X X

WOMENS REST ROOM HD X X X

CONFERENCE ROOM HALL HD X X L1-1 X

CONFERENCE ROOM HD X X L1-1 X

ADMIN AREA HD X X L1-1 X

CHIEF SCOTTS OFFICE HD X X L1-1 X

SQUADRON COMMANDER HD X X L1-1 X

REAL PROPERTY HD X X L1-1 X

BASE CIVIL ENGINEER HD X X L1-1 X

ENGINEERING HD X X L1-1 X

ASSIST BCE HD X X L1-1 X

PLANS ROOM HD X X L1-1 X

CUSTOMER SERVICE HD X X L1-1 X

SUPERINTENDANT OFFICE HD X X L1-1 X

WAREHOUSE MECH SHOP HD X X L1-1 X

WAREHOUSE MECH SHOP HD X X L1-1 X

WAREHOUSE MECH SHOP HD X X L1-1 X

WAREHOUSE MECH SHOP HD X X L1-1 X

ADMIN EXIT WORK CONTROL HD X X L1-1 X

COMM FLIGHT STORAGE HD X X L1-1 X

MECH ROOM HD X X X

ELECTRICAL SHOP HD X X X

ELECTRICAL SHOP HD X X X

WELDING SHOP HD X X X

POWER PRODUCTION HD X X X

To add more sheets, copy this page and paste it to the end of this document. Page 6 Of 7

Type VIS. FUNC. ZONE Pass Fail

COMM OFFICE PSSA X X L5-4 X

WAREHOUSE PSSA X X ZN 2 X

COMM FOCAL POINT PSSA X X L2-1 X

MAIN ENTRANCE PSSA X X ZN 4 X

COMMANDER OFFICE PSSA X X ZN 2 X

COMM HALL PSSA X X ZN4 X

PUBLIC AFFAIRS STORAGE PSSA X X L5-4 X

EXIT BY PUBLIC AFFAIRS PSSA X X L5-4 X

N.E.EXIT HALL PSSA X X L5-4 X

NE ATTIC HEATS HD X X L5-2 X

4009 Simplex NAC Panel Hall by FACP NAC X X N/A X

Pre Action Shop Room 20 Seconds HLPS X X L6-4 X

Pre Action Maintenance Shop 20 Seconds HLPS X X L3-3 X

Pre Action DP1 20 Seconds HLPS X X L3-2 X

Wet Pipe Water Flow 20 Seconds WF X X L3-4 X