This document contains a fire alarm system inspection report and related federal contract opportunity solicitation. The inspection report details the results of testing fire alarm devices and systems at Fresno Air National Guard Building 225, identifying issues with various detectors, panels, and batteries that require repair or replacement. The related solicitation seeks quotes to inspect and correct deficiencies in fire alarm panels and devices at nineteen buildings on the 144th Air National Guard base. Interested parties must register in SAM and with DBIDS for a scheduled site visit. Quotes are due by the specified date and time via email. The government reserves the right to amend or cancel and will award without negotiations, so offerors should provide their most advantageous pricing initially.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: June 28, 2019
Task Number: TIME: 8:00AM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: FANG 225
Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave City, St., Zip: Fresno, CA, 93272 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Master Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House Fire Department Contact: N/A
Telephone: 559-454-5145 Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually RF X Annually
Other (Specify) Other (Specify)
System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: Harrinton Model No.: HS3030 Circuit Style: Class A
Number of Circuits: NA
Software Rev.: NA Last Date System Had Any Service Performed: October 5, 2017
Last Date That Any Software or Configuration Was Revised: 6/28/99
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
6 A 6 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
30 B 30 Photo Detectors (PSD)
3 B 3 Duct Detectors (DSD) 77 B 77 Heat Detectors (HD)
1 B 1 Water Flow Switches (WF)
0 0 (Specify) 0 0 (Specify)
0 0 (Specify)
Alarm verification feature is Disabled X Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
1 1 Bells
18 D 18 Horns with strobes 0 0 Chimes
1 D 1 Strobes
0 0 Speakers
0 0 (Specify)
Number of alarm notification appliance circuits:
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
1 A 1 Valve Position Tamper Switch (TS) 0 0 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
0 0 High / Low Pressure Switch (HLPS) 0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
0 0 Fire Pump Power 0 0 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble 0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): BOILER
Disconnecting Means Location: PANEL HS2-7 CIRCUIT #5
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 17.2Ah
Calculated capacity is 34.4 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: N/A
Location of fuel storage: N/A
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
NA Emergency system described in NFPA 70, Article 700
NA Legally required standby described in NFPA 70, Article 701 NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time Monitoring Entity X Fire Department 8:00AM
Building Occupants X Staff 8:00AM Building Management X Mike Scott 8:00AM
Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Ok
Load Voltage X Fail-19.88VDC Discharge test X Pass-25.22VDC
Charger test X Pass-27.12VDC
TRANSIENT SUPPRESSORS N/A
REMOTE ANNUNCIATOR N/A
NOTIFICATION APPLIANCES
Audible X X Fail Visible X X Fail
Speakers NA
Voice Clarity NA
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA (Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested
Elevator Recall NA
Fan Shutdown NA
Door Holders NA
Smoke Control System NA Door Release (Security Maglocks) NA
(Specify) NA
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments Building Management X Mike Scott
Monitoring Agency X Fire Department
Building Occupants X Staff Other (Specify)
The following did not operate correctly: Upon arrival FACP was showing a ground fault in zone 2.
Circuit 11 zone 2 loop 2 North offices is in trouble condition. None of the initiating devices work on zone 2.
None of the initiating devices on the fire alarm panel reported they all failed. Recommend placing a service
Call to have the system fixed. I Strongly recommend replacing this fire alarm panel.
Two 12V 17.2Ah batteries need to be replaced on the fire alarm panel. Both failed the load voltage test.
Two 12V 7.0Ah batteries need to be replaced on the Monaco panel. Both failed the load voltage test.
Fire Alarm System is basically down nothing reports or works on it.
System restored to normal operation: Date: June 28, 2019 Time:
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado Date: June 28, 2019 Time:
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 225 DATE: June 28, 2019
ADDRESS: 5323 E McKinley Ave Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Type VIS. FUNC. Address Pass Fail
BOILER ROOM HD X X ZN2 X
BOILER ROOM HD X X ZN2 X
JANITOR CLOSET PSD X X ZN 1 X
SOUTH EXIT PSD X X ZN 1 X
SOUTH EXIT PSSA X X ZN 1 X
ROOM 57 PSD X X ZN 1 X
WOMEN RESTROOM PSD X X ZN 1 X
SOUTH HALL PSD X X ZN 1 X
ROOM 58 PSD X X ZN 1 X
ROOM 57 PSD X X ZN 1 X
ROOM 51 PSD X X ZN 1 X
CONFERENCE ROOM PSD X X ZN 1 X
CONFERENCE ROOM PSD X X ZN 1 X
SOUTH HALL PSD X X ZN 1 X
SOUTH ADMIN PSD X X ZN 1 X
WEST EXIT/ENTRY PSSA X X ZN 1 X
ROOM 63 PSD X X ZN 1 X
WEST HALL PSD X X ZN 1 X
ROOM 48 PSD X X ZN 1 X
ROOM 46 PSD X X ZN 1 X
ROOM 45 PSD X X ZN 1 X
JANITOR CLOSET PSD X X ZN 1 X
WEST HALL PSD X X ZN 1 X
WEST HALL PSD X X ZN 1 X
ROOM 41 PSD X X ZN 1 X
CENTER HALL PSD X X ZN 1 X
CENTER HALL PSD X X ZN 1 X
ROOM 34 A PSD X X ZN2 X
ROOM 34 B PSD X X ZN2 X
DISTRIBUTION AREA PSD X X ZN2 X
NORTH HALL PSD X X ZN2 X
NORTH HALL PSD X X ZN2 X
NORTH CENTRAL HALL PSD X X ZN2 X
NORTH CENTRAL HALL PSD X X ZN2 X
ROOM 38 PSD X X ZN2 X
ROOM 38 PSD X X ZN2 X
ROOM 38 PSD X X ZN2 X
ROOM 37 PSD X X ZN2 X
ROOM 30 PSD X X ZN2 X
ROOM 30 PSD X X ZN2 X
ROOM 30 PSD X X ZN2 X
ROOM 31 A PSD X X ZN2 X
ROOM 31 PSD X X ZN2 X
MEN REST ROOM PSD X X ZN2 X
NORTHEAST HALL PSD X X ZN2 X
WOMEN RESTROOM PSD X X ZN2 X
JANITORAL PSD X X ZN2 X
CLASS ROOM 19 PSD X X ZN2 X
CLASS ROOM 19 PSD X X ZN2 X
ROOM 22 PSD X X ZN2 X
Type VIS. FUNC. Address Pass Fail
ROOM 22 PSD X X ZN2 X
RECEIVING PSD X X ZN2 X
WORK SHOP HD X X ZN2 X
WORK SHOP HD X X ZN2 X
WORK SHOP HD X X ZN2 X
EAST EXIT PSSA X X ZN 3 X
EAST EXIT PSD X X ZN 3 X
WAREHOUSE SOUTH EAST HALL PSD X X ZN 3 X
WAREHOUSE ROOM 23 PSD X X ZN 3 X
WAREHOUSE OFFICE PSD X X ZN 3 X
WAREHOUSE OFFICE STORAGE PSD X X ZN 3 X
WAREHOUSE OFFICE STORAGE PSD X X ZN 3 X
WAREHOUSE OFFICE STORAGE PSD X X ZN 3 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
To add more sheets, copy this page and paste it to the end of this document. Page 7 of 8
Type VIS. FUNC.
Date Tested Pass Fail
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
WAREHOUSE HD X X ZN 4 X
SECOND FLOOR ABOVE STORAGE DD X X ZN 1 X
SCOND FLOOR ABOVE SHIPPING/REC DD X X ZN 3 X
SCOND FLOOR ABOVE SHIPPING/REC DD X X ZN 3 X