FANG BLDG 225 ANN FA 6-2019.pdf

PDF 357 KB Posted

Attached to
Inspection of Fire Alarm Panels, Main Base
Solicitation number
W50S6T24QA011
Issued by

About this file

This document contains a fire alarm system inspection report and related federal contract opportunity solicitation. The inspection report details the results of testing fire alarm devices and systems at Fresno Air National Guard Building 225, identifying issues with various detectors, panels, and batteries that require repair or replacement. The related solicitation seeks quotes to inspect and correct deficiencies in fire alarm panels and devices at nineteen buildings on the 144th Air National Guard base. Interested parties must register in SAM and with DBIDS for a scheduled site visit. Quotes are due by the specified date and time via email. The government reserves the right to amend or cancel and will award without negotiations, so offerors should provide their most advantageous pricing initially.

View the file

Other files

File Type Posted
FANG BLDG 145 ANN FA 7-2019.pdf PDF
FANG BLDG 122 ANN FA 7-2019.pdf PDF
FANG BLDG 130 ANN FA 6-2019.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base (HAYW231030)-Amd2.pdf PDF
FANG BLDG 135 ANN FA 6-2019.pdf PDF
FANG BLDG 2640 ANN FA 7-2019.pdf PDF
FANG BLDG 2602 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110002 SF 30.pdf PDF
FANG BLDG 102 ANN FA 7-2019.pdf PDF
FANG BLDG 121 ANN FA 7-2019.pdf PDF
FANG BLDG 159 ANNUAL FA 6-2019.pdf PDF
FANG BLDG 124 ANN FA 6-2019.pdf PDF
Solicitation Amendment - W50S6T24QA0110002 SF1449.pdf PDF
FANG BLDG 125 ANN FA 6-2019.pdf PDF
FANG BLDG 117 ANN FA 6-2019.pdf PDF
FANG BLDG 126 ANN FA 6-2019.pdf PDF
FANG BLDG 157 ANNUAL FA 6-2019.pdf PDF
FANG Bldg 100 Annual FA 6-2019.pdf PDF
FANG BLDG 155 ANN FA 7-2019.pdf PDF
FANG BLDG 104 ANN FA 7-2019.pdf PDF
FANG BLDG 2600 2601 ANN FA 7-2019.pdf PDF
FANG BLDG 194 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110001 SF 30.pdf PDF
Base Access-144 SFS DVES FORM- 20230127 (Site Visit).pdf PDF
Wage Determinations SCA - 2015-5609 dated 3Aug2023.pdf PDF
Solicitation - W50S6T24QA011 SF1449 RFQ.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SimplexGrinnell BE SAFE

INSPECTION AND TESTING FORM

SR Number: 44909832 DATE: June 28, 2019

Task Number: TIME: 8:00AM

SERVICE ORGANIZATION PROPERTY NAME (USER)

Name: SimplexGrinnell Name: FANG 225

Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave City, St., Zip: Fresno, CA, 93272 City, St., Zip: Fresno, CA, 93727

Representative: Jesus Salgado Owner Contact: Mike Scott License No.: 986047 Telephone: 559-454-5137

Telephone: 559-348-0614 Occupied as: Master Chief

MONITORING ENTITY APPROVING AGENCY

Contact: In House Fire Department Contact: N/A

Telephone: 559-454-5145 Telephone: N/A

Monitoring Account Ref. No.: N/A

TYPE TRANSMISSION SERVICE

McCulloh Weekly Multiplex Monthly

X Digital Quarterly

Reverse Polarity Semiannually RF X Annually

Other (Specify) Other (Specify)

System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm

Control Unit Manufacturer: Harrinton Model No.: HS3030 Circuit Style: Class A

Number of Circuits: NA

Software Rev.: NA Last Date System Had Any Service Performed: October 5, 2017

Last Date That Any Software or Configuration Was Revised: 6/28/99

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity of Devices Installed

Circuit Style

Devices Tested

6 A 6 Manual Fire Alarm Boxes (PSSA)

0 0 Ion Detectors (ISD)

30 B 30 Photo Detectors (PSD)

3 B 3 Duct Detectors (DSD) 77 B 77 Heat Detectors (HD)

1 B 1 Water Flow Switches (WF)

0 0 (Specify) 0 0 (Specify)

0 0 (Specify)

Alarm verification feature is Disabled X Enabled .

Rev. D

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Appliances Installed

Appliances Tested

1 1 Bells

18 D 18 Horns with strobes 0 0 Chimes

1 D 1 Strobes

0 0 Speakers

0 0 (Specify)

Number of alarm notification appliance circuits:

Are circuits monitored for integrity? X Yes No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Devices Installed

Devices Tested

1 A 1 Valve Position Tamper Switch (TS) 0 0 Outside Stem and Yoke (OSY)

0 0 Post Indicator Valve (PIV)

0 0 High / Low Pressure Switch (HLPS) 0 0 Building Temperature

0 0 Site Water Temp

0 0 Site Water Level

0 0 Fire Pump Power 0 0 Fire Pump Running

0 0 Fire Pump Auto Position

0 0 Fire Pump or Fire Controller Trouble 0 0 Fire Pump Low Fuel

0 0 Other: Switch Transfer

0 0 Other: Generator Engine Running

SIGNALING LINE CIRCUIT

Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5

Overcurrent Protection: Type Circuit Breaker Amps 20

Location (of Primary Supply Panel): BOILER

Disconnecting Means Location: PANEL HS2-7 CIRCUIT #5

(b) Secondary (Standby):

Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 17.2Ah

Calculated capacity is 34.4 Amp-Hrs to operate system for 24 Hours.

Engine-driven generator dedicated to fire alarm system: N/A

Location of fuel storage: N/A

TYPE BATTERY

Dry Cell Lead-Acid

Nickel-Cadmium Other (Specify):

X Sealed Lead-Acid

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

NA Emergency system described in NFPA 70, Article 700

NA Legally required standby described in NFPA 70, Article 701 NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time Monitoring Entity X Fire Department 8:00AM

Building Occupants X Staff 8:00AM Building Management X Mike Scott 8:00AM

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit X X Pass Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition X Ok

Load Voltage X Fail-19.88VDC Discharge test X Pass-25.22VDC

Charger test X Pass-27.12VDC

TRANSIENT SUPPRESSORS N/A

REMOTE ANNUNCIATOR N/A

NOTIFICATION APPLIANCES

Audible X X Fail Visible X X Fail

Speakers NA

Voice Clarity NA

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Location & Serial Number Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

See attached detailed report.

Date of Last Sensitivity Test: Unknown

EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments

Phone Set NA Phone Jacks NA

Off-Hook Indicators NA

Amplifier(s) NA

Tone Generator(s) NA Call-in Signal NA

System Performance NA

SPECIAL HAZARD SYSTEMS

Number Installed

Number Tested Comments

Kitchen Range Hood System NA

CO2 Extinguishing System NA (Specify) NA

CONTROL FUNCTIONS / INTERFACE

EQUIPMENT

Number Installed

Number Tested

Elevator Recall NA

Fan Shutdown NA

Door Holders NA

Smoke Control System NA Door Release (Security Maglocks) NA

(Specify) NA

Special Procedures:

Comments:

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal X Alarm Restoration X

Trouble Signal X

Trouble Signal Restoration X

Supervisory Signal X Supervisory Restoration X

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments Building Management X Mike Scott

Monitoring Agency X Fire Department

Building Occupants X Staff Other (Specify)

The following did not operate correctly: Upon arrival FACP was showing a ground fault in zone 2.

Circuit 11 zone 2 loop 2 North offices is in trouble condition. None of the initiating devices work on zone 2.

None of the initiating devices on the fire alarm panel reported they all failed. Recommend placing a service

Call to have the system fixed. I Strongly recommend replacing this fire alarm panel.

Two 12V 17.2Ah batteries need to be replaced on the fire alarm panel. Both failed the load voltage test.

Two 12V 7.0Ah batteries need to be replaced on the Monaco panel. Both failed the load voltage test.

Fire Alarm System is basically down nothing reports or works on it.

System restored to normal operation: Date: June 28, 2019 Time:

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Jesus Salgado Date: June 28, 2019 Time:

Signature:

Name of Owner or Rep.: Date: Time:

Signature:

PROPERTY NAME: Fresno Air National Guard Building 225 DATE: June 28, 2019

ADDRESS: 5323 E McKinley Ave Fresno, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Type VIS. FUNC. Address Pass Fail

BOILER ROOM HD X X ZN2 X

BOILER ROOM HD X X ZN2 X

JANITOR CLOSET PSD X X ZN 1 X

SOUTH EXIT PSD X X ZN 1 X

SOUTH EXIT PSSA X X ZN 1 X

ROOM 57 PSD X X ZN 1 X

WOMEN RESTROOM PSD X X ZN 1 X

SOUTH HALL PSD X X ZN 1 X

ROOM 58 PSD X X ZN 1 X

ROOM 57 PSD X X ZN 1 X

ROOM 51 PSD X X ZN 1 X

CONFERENCE ROOM PSD X X ZN 1 X

CONFERENCE ROOM PSD X X ZN 1 X

SOUTH HALL PSD X X ZN 1 X

SOUTH ADMIN PSD X X ZN 1 X

WEST EXIT/ENTRY PSSA X X ZN 1 X

ROOM 63 PSD X X ZN 1 X

WEST HALL PSD X X ZN 1 X

ROOM 48 PSD X X ZN 1 X

ROOM 46 PSD X X ZN 1 X

ROOM 45 PSD X X ZN 1 X

JANITOR CLOSET PSD X X ZN 1 X

WEST HALL PSD X X ZN 1 X

WEST HALL PSD X X ZN 1 X

ROOM 41 PSD X X ZN 1 X

CENTER HALL PSD X X ZN 1 X

CENTER HALL PSD X X ZN 1 X

ROOM 34 A PSD X X ZN2 X

ROOM 34 B PSD X X ZN2 X

DISTRIBUTION AREA PSD X X ZN2 X

NORTH HALL PSD X X ZN2 X

NORTH HALL PSD X X ZN2 X

NORTH CENTRAL HALL PSD X X ZN2 X

NORTH CENTRAL HALL PSD X X ZN2 X

ROOM 38 PSD X X ZN2 X

ROOM 38 PSD X X ZN2 X

ROOM 38 PSD X X ZN2 X

ROOM 37 PSD X X ZN2 X

ROOM 30 PSD X X ZN2 X

ROOM 30 PSD X X ZN2 X

ROOM 30 PSD X X ZN2 X

ROOM 31 A PSD X X ZN2 X

ROOM 31 PSD X X ZN2 X

MEN REST ROOM PSD X X ZN2 X

NORTHEAST HALL PSD X X ZN2 X

WOMEN RESTROOM PSD X X ZN2 X

JANITORAL PSD X X ZN2 X

CLASS ROOM 19 PSD X X ZN2 X

CLASS ROOM 19 PSD X X ZN2 X

ROOM 22 PSD X X ZN2 X

Type VIS. FUNC. Address Pass Fail

ROOM 22 PSD X X ZN2 X

RECEIVING PSD X X ZN2 X

WORK SHOP HD X X ZN2 X

WORK SHOP HD X X ZN2 X

WORK SHOP HD X X ZN2 X

EAST EXIT PSSA X X ZN 3 X

EAST EXIT PSD X X ZN 3 X

WAREHOUSE SOUTH EAST HALL PSD X X ZN 3 X

WAREHOUSE ROOM 23 PSD X X ZN 3 X

WAREHOUSE OFFICE PSD X X ZN 3 X

WAREHOUSE OFFICE STORAGE PSD X X ZN 3 X

WAREHOUSE OFFICE STORAGE PSD X X ZN 3 X

WAREHOUSE OFFICE STORAGE PSD X X ZN 3 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

To add more sheets, copy this page and paste it to the end of this document. Page 7 of 8

Type VIS. FUNC.

Date Tested Pass Fail

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

WAREHOUSE HD X X ZN 4 X

SECOND FLOOR ABOVE STORAGE DD X X ZN 1 X

SCOND FLOOR ABOVE SHIPPING/REC DD X X ZN 3 X

SCOND FLOOR ABOVE SHIPPING/REC DD X X ZN 3 X