This document contains a solicitation for inspection services of fire alarm panels and devices at nineteen buildings on an Air National Guard base. The 144th Fighter Wing is requesting quotes for a firm fixed price contract to inspect and correct any deficiencies in the Monaco Enterprises Inc. fire protection system. Interested parties must have a CAGE code and SAM registration. Quotes are due by email to the contracting inbox before the specified date and time. A non-mandatory site visit will be held on January 3, 2023 at 9:00am at the base location for pre-enrolled attendees who are cleared through security background checks. The selected contractor will be responsible for inspecting and correcting any issues found in the fire panels, devices, and related systems across nineteen buildings to ensure compliance with standards.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: June 17, 2019
Task Number: 68245545 TIME: 8:00AM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 100
Address: 2788 N. Larkin Ave. Address: 5323 E McKinley Ave
City, St., Zip: Fresno, CA, 93272 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott
License No.: 987047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House Contact: N/A
Telephone: N/A Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly
Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually
RF X Annually
Other (Specify) Other (Specify)
System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: Simplex Model No.: 4100U NODE 1 4100U NODE 2 Foam
Circuit Style: B
Number of Circuits: NA
Software Rev.: 12.07.01
Last Date System Had Any Service Performed: September 27, 2017
Last Date That Any Software or Configuration Was Revised: February 25, 2016
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
38 B 38 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
34 B 34 Photo Detectors (PSD)
12 B 12 Duct Detectors (DSD)
76 B 76 Heat Detectors (HD)
2 B 2 Water Flow Switches (WF)
1 B 1 WPS Water Pressure Switch
7 B 7 (Specify) Suppression Manual Dump
0 0 (Specify)
Alarm verification feature is Disabled X Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
1 1 Bells
36 B 36 Horns with strobes
0 0 Chimes
14 B 14 Strobes
0 0 Speakers
0 0 (Specify)
Number of alarm notification appliance circuits:
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
22 B 22 Valve Position Tamper Switch (TS)
2 B 2 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
1 B 1 High / Low Pressure Switch (HLPS)
0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
2 B 2 Fire Pump Power
2 B 2 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble
0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 10
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): Boiler Room
Disconnecting Means Location: Panel 1LBR breaker #2
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 55Ah
Calculated capacity is 110 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: NA
Location of fuel storage: NA
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
NA Emergency system described in NFPA 70, Article 700
NA Legally required standby described in NFPA 70, Article 701
NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity X In House 8:00AM
Building Occupants X Site Staff 8:00AM
Building Management X Chief Scott 8:00AM
Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass
Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Ok- Batteries Installed 12-14-15
Load Voltage X Fail-22.42VDC
Discharge test X Pass-25.24VDC
Charger test X Pass-26.46VDC
TRANSIENT SUPPRESSORS NA
REMOTE ANNUNCIATOR NA
NOTIFICATION APPLIANCES
Audible X X Pass
Visible X X Pass
Speakers NA
Voice Clarity NA
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA
Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA
Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA
(Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested
Elevator Recall NA
Fan Shutdown NA
Door Holders NA
Smoke Control System NA
Door Release (Security Maglocks) NA
(Specify) NA
Comments: Upon arrival Pre Action system on the 2nd floor room 201C was out of service. Control
Was shut we did not test anything tied to that system. The IT guy who let us in wanted to get a quote about
Comments: Having a special gas system inside that room.
Did not test any of the devices inside building 104 no access available.
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X
Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X
Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments
Building Management X M.O.D
Monitoring Agency X In House
Building Occupants X Staff
Other (Specify) X
The following did not operate correctly: 4100U Node 1 Main Panel needs two 12V 55Ah batteries replaced.
Both failed the load voltage test and have been in service since 12-14-15.
4100U Node 2 Foam Releasing Panel needs two 12V 18Ah batteries replaced both failed the load voltage test.
Also the batteries do not show dates on them.
System restored to normal operation: Date: June 19, 2019 Time: 1:00PM
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado Date: June 19, 2019 Time:
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 100 DATE: June 17, 2019
ADDRESS: 5323 E McKinley Ave Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Type VIS. FUNC. Address Pass Fail
1st/2nd Fl North Wing PSSA X X ZN 1 X
1st FL West Wing PSSA X X ZN 2 X
1st/2nd FL South Wing PSSA X X ZN 3 X
1st Floor Weapons & Release Shop Area PSSA X X ZN 4 X
Fire Pump Room North Door PSSA X X ZN 5 X
Building 104 Exit Doors PSSA ZN 6
1st FL North Wing East/West Exit Stairs PSD X X ZN7 X
1st FL South Wing East/West Exit Stairs PSD X X ZN 8 X
Building 104 Corridor Smokes PSD X X ZN 9 X
2nd FL North Wing Corridor Smokes PSD X X ZN 10 X
2nd FL West Wing Corridor Smokes PSD X X ZN 11 X
2nd FL South Wing Corridor Smokes PSD X X ZN 12 X
1st FL North Wing Ceiling Heats HD X X ZN 13 X
1st FL North Wing East Ceiling Heats HD X X ZN 14 X
1st FL West Wing North Ceiling Heats HD X X ZN 15 X
1st FL West Wing South Ceiling Heats HD X X ZN 16 X
1st FL South Wing West Ceiling Heats HD X X ZN 17 X
1st FL South Wing East Ceiling Heats HD X X ZN 18 X
Weapons & Release Shop Area Heats HD X X ZN 19 X
Weapons & Release Area Smokes HD X X ZN 20 X
Fire Pump Heat North Device HD X X ZN 21 X
Building 104 Ceiling Heats HD ZN 22
2nd FL North Wing West Ceiling Heats HD X X ZN 23 X
2nd FL North Wing East Ceiling Heats HD X X ZN 24 X
2nd FL West Wing North Ceiling Heats HD X X ZN 25 X
2nd FL west Wing South Ceiling Heats HD X X ZN 26 X
2nd FL South Wing West Ceiling Heats HD X X ZN 27 X
2nd FL South Wing East Ceiling Heats HD X X ZN 28 X
1st FL North Wing West Attic Heats HD X X ZN 29 X
1st FL North Wing East Attic Heats HD X X ZN 30 X
1st FL West Wing North Attic Heats HD X X ZN 31 X
1st FL West Wing South Attic Heats HD X X ZN 32 X
1st FL South Wing West Attic Heats HD X X ZN 33 X
1st FL South Wing East Attic Heats HD X X ZN 34 X
Weapons & Release Attic Heats HD X X ZN 35 X
Building 104 Attic Heats HD ZN 36
2nd FL North Wing West Attic Heats HD X X ZN 37 X
2nd FL North Wing East Attic Heats HD X X ZN 38 X
2nd FL North Wing Corridor Attic Heats HD X X ZN 39 X
2nd FL West Wing North Attic Heats HD X X ZN 40 X
2nd FL West Wing South Attic Heats HD X X ZN 41 X
2nd FL West Wing Corridor Attic Heats HD X X ZN 42 X
2nd FL South Wing West Attic Heats HD X X ZN 43 X
2nd FL South Wing East Attic Heats HD X X ZN 44 X
2nd FL South Wing Corridor Attic Heats HD X X ZN 45 X
Weapons & Release Shop Area DD X X ZN 46 X
2nd FL North Area Duct DD X X ZN 47 X
2nd FL South Wing Duct DD X X ZN 48 X
Ejection Seat Recharge RMS PSD X X ZN 49
PROPERTY NAME: Fresno Air National Guard Building 100 DATE: June 18, 2019
Type VIS. FUNC. Address Pass Fail
Fire Pump #1 Running SUPV X X ZN09 X
Fire Pump #2 Running SUPV X X ZN06 X
Fire Pump #1 Power Loss TBL X X ZN10 X
Fire Pump #2 Power Loss TBL X X ZN07 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 1 HANGAR HD X X ZN 1 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
ZN 2 HANGAR HD X X ZN 2 X
To add more sheets, copy this page and paste it to the end of this document. Page 6 Of 7
PROPERTY NAME: Fresno Air National Guard Building 100 DATE: June 17, 2019
Type VIS. FUNC. Address Pass Fail
ZN 47 DUCT 2ND FLOOR DD X X ZN 47 X
ZN 47 DUCT 2ND FLOOR DD X X ZN 47 X
ZN 47 DUCT 2ND FLOOR DD X X ZN 47 X
ZN 47 DUCT 2ND FLOOR DD X X ZN 47 X
ZN 47 DUCT 2ND FLOOR DD X X ZN 47 X
ZN 48 DUCT 2ND FLOOR DD X X ZN 48 X
ZN 48 DUCT 2ND FLOOR DD X X ZN 48 X
ZN 48 DUCT 2ND FLOOR DD X X ZN 48 X
ZN 48 DUCT 2ND FLOOR DD X X ZN 48 X
Fire Pump Room South Door PSSA X X ZN05 X
Admin Office Water Flow 52 Seconds WF X X ZN51 X
Hangar Sprinkler Water Flow 68 Seconds WF X X ZN03 X
Admin Office Tamper Switch STS X X ZN50 X
Fire Pump Heat Detector South Device HD X X ZN21 X
Fire Pump Tamper Switches Jockey Pump STS X X ZN52 X
Fire Pump Tamper Switches Jockey Pump STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
Fire Pump Tamper Switches STS X X ZN52 X
South Hangar Manual Dump Stations SMD X X ZN04 X
South Hangar Manual Dump Stations SMD X X ZN04 X
South Hangar Manual Dump Stations SMD X X ZN04 X
North Hangar Manual Dump Stations SMD X X ZN05 X
North Hangar Manual Dump Stations SMD X X ZN05 X
North Hangar Manual Dump Stations SMD X X ZN05 X
North Hangar Manual Dump Stations SMD X X ZN05 X
Office Surge Tank #19 Control Valve STS X X ZN50 X
Hangar Surge Tank #20 STS X X ZN12 X
Hangar Surge Tank #20 STS X X ZN12 X
Deluge Riser Control Valve BFV STS X X ZN12 X
Deluge Riser Over Head Valve STS X X ZN12 X
Hangar Foam Deluge Riser HLPS X X M1-08 X
To add more sheets, copy this page and paste it to the end of this document. Page 7 Of 7