FANG BLDG 122 ANN FA 7-2019.pdf
PDF 222 KB Posted
- Attached to
- Inspection of Fire Alarm Panels, Main Base
- Solicitation number
- W50S6T24QA011
- Issued by
-
Department of the Army National Guard
About this file
This document contains a fire alarm system inspection report and a related federal solicitation. The inspection report details the results of testing various fire alarm components at the Fresno Air National Guard Building 122, noting deficiencies with the smoke and heat detectors. It also provides an opportunity notice for a site visit on January 3, 2023 at 9am to inspect nineteen buildings at the 144th Air National Guard Base.
The related solicitation seeks quotes for inspection and correction of deficiencies in Monaco Enterprises Inc. fire protection systems (fire panels and devices) at the nineteen buildings. It is a firm fixed price contract with award intended without negotiations. Quotes are due by email before the specified date and time. A site visit will be available on January 3, 2023 for approved attendees who complete DBIDS pre-enrollment and are cleared by security.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: July 3, 2019
Task Number: TIME: 10:00AM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 122
Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave
City, St., Zip: Fresno, CA, 93727 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott
License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Master Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House Contact: N/A
Telephone: 559-454-5145 Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly
Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually
RF X Annually
Other (Specify) Other (Specify)
System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: Monaco Enterprise Model No.: M2
Circuit Style: Class B
Number of Circuits: N/A
Software Rev.: 2002
Last Date System Had Any Service Performed: September 25, 2017
Last Date That Any Software or Configuration Was Revised: 1994
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
6 B 6 Manual Fire Alarm Boxes (PSSA)
8 B 8 Ion Detectors (ISD)
1 B 1 Photo Detectors (PSD)
0 0 Duct Detectors (DSD)
23 B 23 Heat Detectors (HD)
0 0 Water Flow Switches (WF)
0 0 (Specify)
0 0 (Specify)
Alarm verification feature is Disabled X Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
2 B 2 Bells
0 0 Horns with strobes
0 0 Chimes
0 0 Strobes
2 B 2 Speakers
Number of alarm notification appliance circuits: 2
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
0 0 Valve Position Tamper Switch (TS)
0 0 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
0 0 High / Low Pressure Switch (HLPS)
0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
0 0 Fire Pump Power
0 0 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble
0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel):
Disconnecting Means Location:
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 7Ah
Calculated capacity is 14 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: N/A
Location of fuel storage: N/A
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
NA Emergency system described in NFPA 70, Article 700
NA Legally required standby described in NFPA 70, Article 701
NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity X Fire Department 10:00AM
Building Occupants X Staff 10:00AM
Building Management X Mike Scott 10:00AM
Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass
Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Good Condition
Load Voltage X Pass-25.89VDC
Discharge test X Pass-25.48VDC
Charger test X Pass-27.41VDC
TRANSIENT SUPPRESSORS NA
REMOTE ANNUNCIATOR NA
NOTIFICATION APPLIANCES
Audible X X
Visible X X
Speakers NA
Voice Clarity NA
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA
Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA
Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA
(Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested
Elevator Recall NA
Fan Shutdown NA
Door Holders NA
Smoke Control System NA
Door Release (Security Maglocks) NA
(Specify) NA
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X
Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X
Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments
Building Management X Mike Scott
Monitoring Agency X Fire Department
Building Occupants X Staff
Other (Specify)
The following did not operate correctly: None of the smoke detectors and heat detectors worked inside the
Building. Recommend placing a service call to have the system checked out. Only the pull stations and
The audio visuals worked in the buildings. Fire alarm panels shows normal condition.
System restored to normal operation: Date: July 3, 2019 Time:
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado Date: July 3, 2019 Time:
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 122 DATE: July 3, 2019
ADDRESS: 5323 E McKinley Ave Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Location & Serial Number Device Type VIS. FUNC. Address Pass Fail
OUTSIDE ELECTRICAL ROOM PSSA X X Z1 X
COMBAT ARM MAINTANENCE PSSA X X Z1 X
ROOM 48 HD X X Z3 X
ROOM 49 HD X X Z3 X
CENTER HALL PSSA X X Z1 X
CENTER HALL ION X X Z1 X
ROOM 47 HD X X Z3 X
ROOM 41 HD X X Z3 X
HALL BETWEEN 41 AND 39 HD X X Z3 X
ROOM 43 HD X X Z3 X
EAST EXIT PSSA X X Z1 X
ROOM 37 ION X X Z3 X
ROOM 36 ION X X Z1 X
ROOM 36 RR HD X X Z3 X
ROOM 32 HD X X Z3 X
ROOM 32 HD X X Z3 X
ROOM 32 HD X X Z3 X
ROOM 39 HD X X Z3 X
OUTSIDE 39 ION X X Z3 X
ROOM 38 HD X X Z3 X
ROOM 29 ION X X Z3 X
ROOM 29 HD X X Z3 X
ROOM 26 HD X X Z3 X
ROOM 25 HD X X Z3 X
ROOM 23 HD X X Z3 X
HALLWAY/REGISTRATION AREA ION X X Z3 X
RECEPTION AREA HD X X Z3 X
LOBBY ION X X Z4 X
LOBBY/SE ENTERANCE PSSA X X Z4 X
EMERGE/BREAK HD X X Z3 X
EMERGE/BREAK HD X X Z3 X
ROOM 17 HD X X Z3 X
ROOM 17 HD X X Z3 X
ROOM 18 HD X X Z3 X
MEN RR HD X X Z3 X
MEN RR HD X X Z3 X
WOMEN RR HD X X Z3 X
WOMEN RR HD X X Z3 X
PPE ROOM HD X X Z3 X
PPE ROOM HD X X Z3 X
ROOM 17 ION X X Z4 X
HALLWAY BY ROOM 12 PSSA X X Z4 X
HALLWAY BY ROOM 47 PSD X X ZN3 X