This document contains a fire alarm system inspection report and details of a related federal contract opportunity. The inspection report documents the results of testing fire alarm panels, devices, and circuits for 19 buildings at Fresno Air National Guard Base. It identifies replacement needs for several batteries that failed load testing. The related solicitation seeks quotes for inspection and correction of deficiencies in the fire protection system, including fire panels and devices, at the base. The firm fixed price contract will be awarded without negotiations, so offerors are encouraged to provide their most advantageous pricing initially. A pre-bid site visit will be held on January 3, 2023, with DBIDS pre-enrollment required for attendance. Quotes are due by the date and time specified and must be submitted to the contracting email address provided. The soliciting agency is the Department of the Army National Guard.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: June 20, 2019
Task Number: TIME: 7:00AM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 159
Address: 2788 N. Larkin Ave. Address: 5323 E McKinley Ave
City, St., Zip: Fresno, CA, 93727 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott
License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Master Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House Contact: N/A
Telephone: 559-454-5145 Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly
Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually
RF X Annually
Other (Specify) Other (Specify)
System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: EST Model No.: EST3 & Potter PFC Releasing Panel
Circuit Style: A
Number of Circuits: N/A
Software Rev.: N/A
Last Date System Had Any Service Performed: October 5, 2017
Last Date That Any Software or Configuration Was Revised: N/A
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
4 A 4 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
1 A 1 Photo Detectors (PSD)
0 0 Duct Smoke Detectors (DSD)
12 A 12 Heat Detectors (HD)
3 A 3 Water Flow Switches (WF)
4 A 4 (Specify) Suppression Manual Dump
0 0 (Specify)
Alarm verification feature is Disabled X Enabled .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
1 A 1 Bells
11 A 11 Horns with strobes
0 0 Chimes
0 0 Strobes
0 0 Speakers
Number of alarm notification appliance circuits:
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
6 A 6 Valve Position Tamper Switch (TS)
0 0 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
1 A 1 High / Low Pressure Switch (HLPS)
0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
1 A 1 Fire Pump Power Loss
1 A 1 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble
0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): MECH ROOM
Disconnecting Means Location: PANEL A CIRCUIT #23
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 26AH
Calculated capacity is 52 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: N/A
Location of fuel storage: N/A
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
NA Emergency system described in NFPA 70, Article 700
NA Legally required standby described in NFPA 70, Article 701
NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity X In House 7:00AM
Building Occupants X Staff 7:00AM Building Management X Mike Scott 7:00AM Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass
Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Good-No Battery Date
Load Voltage X Fail-19.48VDC
Discharge test X Pass-26.89VDC
Charger test X Pass-25.66VDC
TRANSIENT SUPPRESSORS NA
REMOTE ANNUNCIATOR NA
NOTIFICATION APPLIANCES
Audible X X Pass
Visible X X Pass
Speakers X X Pass
Voice Clarity X VOICE EVAC GOOD
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA
Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA
Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA
(Specify) NA
(Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested
Elevator Recall N/A
Fan Shutdown N/A Door Holders N/A Smoke Control System N/A Door Release (Security Maglocks) N/A (Specify) N/A
(Specify) N/A
(Specify) N/A
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X
Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X
Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments
Building Management X M.O.D
Monitoring Agency X In House
Building Occupants X Staff
Other (Specify)
The following did not operate correctly: Two 12V 7.2Ah batteries need to be replaced on the Potter PFC
Foam Releasing Panel. Both batteries failed the load voltage test and have been in service since 1-2015.
EST-3 Fire Alarm Panel needs two 12V 26Ah replaced. Both batteries failed the load voltage test
Fire Alarm Booster supply panel above the main FACP needs two 12V 7.2Ah batteries replaced. Both failed
The load voltage test.
System restored to normal operation: Date: June 21, 2019 Time:
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: Jesus Salgado & Ryan Stone Date: June 21, 2019 Time:
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 159 DATE: June 20, 2019
ADDRESS: 5323 E McKinley Ave Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Location & Serial Number Device Type VIS. FUNC. Address Pass Fail
HANGAR NE PSSA X X 129 X
HANGAR SW PSSA X X 131 X
HANGAR SE PSSA X X 126 X
PAINT BOOTH AREA PSSA X X 130 X
DELUGE CONTROL VALVE STS X X 156 X
WET PIPE HIGH BAY 65 SECONDS WF X X 134 X
WET PIPE LOW BAY 45 SECONDS WF X X X
DELUGE PRESSURE SWITCH HLPS X X X
PAINT BOOTH 32 SECONDS WF X X X
ABOVE FACP PSD X X 21 X
WET PIPE LOW BAY TAMBER SWITCH STS X X 23 X
HIGH BAY VALVE WET STS X X 136 X
MECH ROOM PSSA X X 128 X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
HANGAR HIGH CEILING HEAT HD X X X
SUPRESSION MANUAL DUMP SMD X X X
SUPRESSION MANUAL DUMP SMD X X X
SUPRESSION MANUAL DUMP SMD X X X
WET PIPE HIGH BAY TAMPER SIWTCH STS X X X
PAINT BOTH TAMER SWITCH STS X X X
HIGH BAY LOWER VALVE STS X X X
SUPRESSION MANUAL DUMP SMD X X X