This document provides details for a federal solicitation requesting fire alarm inspection and deficiency correction services for nineteen buildings on an Air National Guard base. The 144th Fighter Wing is seeking a firm fixed price contract for inspection of Monaco Enterprises Inc. fire protection systems including fire panels and devices. Interested parties must have a Commercial and Government Entity code and be registered in the System for Award Management. A pre-proposal site visit will be held on January 3rd, 2023, with attendees requiring base access clearance after completing Defense Biometric Identification System pre-enrollment. Quotes are due by email to the specified contracting inbox by the date and time listed in the solicitation instructions. The government reserves the right to amend or cancel the solicitation and has no obligation to reimburse offerors for any costs if cancelled. Submitted offers will be valid for 30 days.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SimplexGrinnell BE SAFE
INSPECTION AND TESTING FORM
SR Number: 44909832 DATE: July 3, 2019
Task Number: TIME: 1:30PM
SERVICE ORGANIZATION PROPERTY NAME (USER)
Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 155
Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave
City, St., Zip: Fresno, CA, 93727 City, St., Zip: Fresno, CA, 93727
Representative: Jesus Salgado Owner Contact: Mike Scott
License No.: 986047 Telephone: 559-454-5137
Telephone: 559-348-0614 Occupied as: Master Chief
MONITORING ENTITY APPROVING AGENCY
Contact: In House Fire Department Contact: N/A
Telephone: 559-454-5145 Telephone: N/A
Monitoring Account Ref. No.: N/A
TYPE TRANSMISSION SERVICE
McCulloh Weekly
Multiplex Monthly
X Digital Quarterly
Reverse Polarity Semiannually
RF X Annually
Other (Specify) Other (Specify)
System Type: ( X) Local; ( ) Auxiliary; ( ) Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm
Control Unit Manufacturer: MONICO Model No.: M-2
Circuit Style: B
Number of Circuits: 2
Software Rev.: NA
Last Date System Had Any Service Performed: NA
Last Date That Any Software or Configuration Was Revised: NA
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity of Devices Installed
Circuit Style
Devices Tested
7 B 7 Manual Fire Alarm Boxes (PSSA)
0 0 Ion Detectors (ISD)
12 B 12 Photo Detectors (PSD)
3 B 3 Duct Detectors (DSD)
0 0 Heat Detectors (HD)
1 B 1 Water Flow Switches (WF)
0 0 (Specify)
0 0 (Specify)
Alarm verification feature is disabled Enabled X .
Rev. D
ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION
Appliances Installed
Appliances Tested
3 B 3 Bells
6 B 6 Horns with strobes
0 0 Chimes
6 B 6 Strobes
0 0 Speakers
Number of alarm notification appliance circuits: 4
Are circuits monitored for integrity? X Yes No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Devices Installed
Devices Tested
1 B 1 Valve Position Tamper Switch (TS)
1 B 1 Outside Stem and Yoke (OSY)
0 0 Post Indicator Valve (PIV)
0 0 High / Low Pressure Switch (HLPS)
0 0 Building Temperature
0 0 Site Water Temp
0 0 Site Water Level
0 0 Fire Pump Power
0 0 Fire Pump Running
0 0 Fire Pump Auto Position
0 0 Fire Pump or Fire Controller Trouble
0 0 Fire Pump Low Fuel
0 0 Other: Switch Transfer
0 0 Other: Generator Engine Running
SIGNALING LINE CIRCUIT
Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):
Quantity Style(s)
SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage 120VAC Amps 2.5
Overcurrent Protection: Type Circuit Breaker Amps 20
Location (of Primary Supply Panel): Mechanical Room
Disconnecting Means Location: Electrical room LP2-20
(b) Secondary (Standby):
Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 18Ah
Calculated capacity is 36 Amp-Hrs to operate system for 24 Hours.
Engine-driven generator dedicated to fire alarm system: NA
Location of fuel storage: NA
TYPE BATTERY
Dry Cell Lead-Acid
Nickel-Cadmium Other (Specify):
X Sealed Lead-Acid
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701
Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity X Fire Department 1:30PM Building Occupants X Staff 1:30PM Building Management X Mike Scott 1:30PM Other (Specify)
AHJ Notified of Any Impairments
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit X X Pass
Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass
SECONDARY POWER
TYPE Visual Functional Comments
Battery Condition X Bad Condition
Load Voltage X Fail-20.21VDC
Discharge test X Pass-24.89VDC
Charger test X Pass-27.61VDC
TRANSIENT SUPPRESSORS N/A
REMOTE ANNUNCIATOR X X N/A
NOTIFICATION APPLIANCES
Audible X X Fail
Visible X X Pass
Speakers N/A
Voice Clarity NA
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Location & Serial Number Device Type
Visual Check
Functional Test
Factory Setting
Measured Setting Pass Fail
See attached detailed report.
Date of Last Sensitivity Test: Unknown
EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments
Phone Set NA
Phone Jacks NA
Off-Hook Indicators NA
Amplifier(s) NA
Tone Generator(s) NA
Call-in Signal NA
System Performance NA
SPECIAL HAZARD SYSTEMS
Number Installed
Number Tested Comments
Kitchen Range Hood System NA
CO2 Extinguishing System NA
(Specify) NA
CONTROL FUNCTIONS / INTERFACE
EQUIPMENT
Number Installed
Number Tested Comments
Elevator Recall NA
Fan Shutdown NA
Door Holders NA
Smoke Control System NA
Door Release (Security Maglocks) NA
(Specify) NA
Special Procedures:
Comments:
SUPERVISING STATION MONITORING Yes No Time Comments
Alarm Signal X
Alarm Restoration X
Trouble Signal X
Trouble Signal Restoration X
Supervisory Signal X
Supervisory Restoration X
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments
Building Management X Mike Scott
Monitoring Agency X Fire Department
Building Occupants X Staff
Other (Specify) X
The following did not operate correctly: Two 12V 18Ah batteries need to be replaced on the fire alarm panel.
Both failed the load voltage test and have been in service since 2014.
Fire alarm booster panel needs two 12V 7Ah batteries replaced. Both failed the load voltage test and have
Been in service since 2014. Panel is locate next to the main fire alarm panel.
Five horn/strobes failed to alarm Edwards G1RF-HDVM Red. Only the strobe lights worked on those devices.
Four of the horn/strobes are located inside the gym and the other one is located inside the mechanical
Room where the fire alarm panel is at.
System restored to normal operation: Date: July 3, 2019 Time:
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: July 3, 2019 Date: July 3, 2019 Time:
Signature:
Name of Owner or Rep.: Date: Time:
Signature:
PROPERTY NAME: Fresno Air National Guard Building 155 DATE: July 3, 2019
ADDRESS: 5323 E McKinley Ave Fresno, CA, 93727 TIME:
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)
Location & Serial Number Device Type VIS. FUNC. ZONE Pass Fail
MECHANICAL ROOM TAMPER STS X X ZN 1 X
MECHANICAL ROOM PSSA X X ZN 1 X
MECHANICAL ROOM PSSA X X ZN 1 X
BY KITCHEN PSSA X X ZN 3 X
BY LOCKER ROOM PSSA X X ZN 3 X
ROOM #7 PSSA X X ZN 3 X
COMM EQUIPMENT ROOM PSSA X X ZN 3 X
EXERCISE ROOM PSSA X X ZN 3 X
BEDROOM #1 H/PSD X X ZN 1 X
BEDROOM #2 H/PSD X X ZN 1 X
BEDROOM #3 H/PSD X X ZN 1 X
BEDROOM #4 H/PSD X X ZN 1 X
BEDROOM #5 H/PSD X X ZN 1 X
BEDROOM #6 H/PSD X X ZN 1 X
BEDROOM #7 H/PSD X X ZN 2 X
BEDROOM #8 H/PSD X X ZN 2 X
BEDROOM #9 H/PSD X X ZN 2 X
BEDROOM #10 H/PSD X X ZN 2 X
BEDROOM #11 H/PSD X X ZN 2 X
BEDROOM #12 H/PSD X X ZN 2 X
MECHANICAL ROOM PSD X X ZN 1 X
MECHANICAL ROOM WF X X