UGM Simonka_A2.2.1 CEILING DETAILS_12.19.24.pdf
PDF 86 KB Posted
- Solicitation number
- S-C25102-00012036
- Issued by
- Marion County, Junction City, Oregon
About this file
This file contains ceiling detail architectural drawings from Merrick Lentz Architect for the Union Gospel Mission's Simonka Place project in Keizer, Oregon. The drawing sheet A2.2.1 shows detailed specifications for a suspended gypsum wallboard ceiling system, including seismic bracing requirements, compression strut assembly, and installation details. The drawings are part of an RFP set dated December 19, 2024, for an addition and interior alteration project.
The technical specifications require heavy duty main runners at 48" on center, 5/8" Type X gypsum wallboard, and 12-gauge wire hangers at maximum 4'-0" spacing. Seismic requirements specify minimum intersection strength limits of 180 lbs at main tee/cross tee connections, vertical hanger wires with maximum 1 in 6 plumb, and compression struts at 12'-0" on center in both directions. The ceiling system must comply with ASTM C 645 and CISCA 3-4 standards, with specific requirements for light fixture attachment and mechanical trim fastening to the grid. The drawings include precise measurements, assembly instructions, and notes regarding the installation of USG Drywall Suspension System or CertainTeed QuickSpan Drywall Suspension System components.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VERTICAL COMPRESSION
STRUT @ 12'-0" o.c. MAX. EA.
WAY PER SCHED; (3)#10
SCREWS EA. END
12 GA. TIE WIRE SEISMIC
BRACING ASSEMBLY PER
1B/A4.112 GA. WIRE BRACE;
PARALLEL TO MAIN RUNNER
HANGAR WIRE (12 ga) @ 4'-0" o.c. MAX.
8" MAX.
CHANNEL MOLDING
CONNECT STRUT TO
BEAM, JOIST, BLOCKING
OR UNISTRUT
WALL PER PLAN
CROSS TEE @ 24"o.c.
NOTES:
1. REFER "A" FOR CEILING SYSTEM
BRACING AND STRUT ASSEMBLY.
2. GYPSUM BOARD SUSPENDED CEILING
SYSTEMS TO COMPLY WITH ASTM C 645
AND ISCA 3-4.
3. INSTALL SEISMIC BRACING PER
MANUF'R'S ESR REPORT.
4. LATERAL BRACE AND COMPRESSION
STRUT MAY BE ELIMINATED PER ESR
REPORT IF CEILING IS IN SINGLE PLANE
AND ATTACHED TO ALL PERIMETER
WALLS, PER CISCA 3-4.
5. ALL LIGHT FIXTURES AND
MECHANICAL TRIMS SHALL BE
FASTENED TO GRID
HEAVY DUTY MAIN RUNNER
@ 48" o.c. TYP.
5/8" TYPE "X" GWB CLG
CEILING FRAMING SYSTEM: ALL MAIN
TEES, CROSS TEES, SPLICE CLIPS,
TRANSITION CLIPS, CHANNELS AND
SYSTEM COMPONENTS REQUIRED TO
COMPLETE THE CEILING SYSTEM TO BE:
"USG DRYWALL SUSPENSION SYSTEM"
OR "CERTAINTEED QUICKSPAN
DRYWALL SUSPENSION SYSTEM"
COMPRESSION STRUT MAX. HEIGHT
Per NWCB Technical Information Bulletin #401
250S137-33 SINGLE STUD 13'-6"
162S125-33 SINGLE STUD 12'-0"
CEILING ANGLE CLIP @
HANGER SUPPORT
NOTE: DO NOT CONNECT
CEILING SUPPORT OR
COMPRESSION STRUTS TO
ROOF DECKING
° T
YP
. 45° TYP.
MAIN RUNNER
CROSS TEE
COMPRESSION STRUT;
250S137-33, U.N.O. NOTCH
AS REQ'D FOR CEILING
PANEL
REFER DETAIL FOR HANGER
WIRE, STRUT AND
CONNECTION TO
STRUCTURE ABOVE
12 GA. HANGER WIRE
PARALLEL TO CROSS TEE,
ANCHORED TO MAIN
RUNNER
12 GA. MIN. HANGER WIRE @
48"O.C. MAX. & W/IN 8" OF CEILING
OR WALL DISCONTINUITY; PROVIDE
ADD'L WIRE W/IN 3" OF EA. CORNER
OF EA. FIXTURE; PROVIDE (2) ADD'L
WIRES TO OPPOSITE CORNERS OF
FIXTURE (MAY BE SLACK).
HORIZ.
NOTE: ATTACH GRID BRACING ASSEMBLY @ 12' o.c. MAX.
START FIELD 4'-0" FROM PERIMETER DEMISING WALL.
12 GA. WIRE, PARALLEL
TO MAIN RUNNER, TYP.
45° MAX.,
TYP.
A SEISMIC BRACING
CEILING SEISMIC REQUIREMENTS
· MINIMUM INTERSECTION STRENGTH
LIMITS @ MAIN TEE/CROSS TEE =
180 LBS
· VERTICAL HANGER WIRES SHALL BE
1 IN 6 MAX. PLUMB
· REQUIRED END/WALL CLEARANCE:
3/4" MIN.
· CONNECT GRID TO PERIMETER,
ATTACHED ON TWO ADJACENT
WALLS
· PERIMETER TEE ENDS SHALL BE
TIED TOGETHER
· SPLAY WIRES OR RIGID BRACING
SHALL BE LOCATED WITHIN 2" OF
INTERSECTION AND SPLAYED 90
DEGREES APART AT 45° ANGLES
· PROVIDE COMPRESSION STRUTS
12'-0" O.C. IN BOTH DIRECTIONS,
STARTING 6' MAX. FROM WALLS
· SPLAY CONNECTION STRENGTH
SHALL BE 200 LBS MIN. OR DESIGN
LOAD,, WHICHEVER IS GREATER
· PROVIDE SEISMIC SEPARATION
JOINT FOR AREAS GREATER THAN
2500 SF
2"
MAX.
2"
MAX.
45° MAX.,
TYP.
CROSS TEE
project name
12815 NE 126th Place, Kirkland, WA 98034 t.425.747.3177 www.mlarch.com
UNPUBLISHED WORK
© 2024 MERRICK LENTZ ARCHITECT
Unauthorized use or reproduction of these drawings or any part herein without the permission of
Merrick Lentz Architect is not permitted consultant stamp descriptionissued date checked by drawn by CSC drawing title
MDL
design development
11/18/24 RFP SET
Simonka Place Union Gospel Mission
5119 River Road North Keizer, OR 97303
Addition and
Interior Alteration
12/19/24 UPDATED RFP SET
SCALE: 1-1/2" = 1'-0"
A2.2.1
DETAIL - SUSPENDED GWB CEILING
A2.2.1
CEILING DETAILS