TAFB B9001 VAV Schedule.pdf
PDF 6 KB Posted
- Solicitation number
- FA813726R0026
About this file
This document is a Single Duct Terminal Unit Schedule specification for variable air volume (VAV) units manufactured by Titus. The schedule specifies four VAV units (VAV-01 through VAV-04) with DESV models in sizes 06 and 08, configured for integration with air handling units (AHUs). The units are sized to deliver between 200 and 900 CFM at maximum capacity, with minimum airflows ranging from 200 to 250 CFM. All units operate at 480/3-phase electrical service with modulating SCR electric heat coils rated between 2.5 and 3 KW, featuring single-step heating control with heating performance validated per ASHRAE 130-2008 and AHRI 880-2011 standards.
Electrical specifications include minimum supply circuit ampacity (MCA) ratings between 3.8 and 4.5 amperes and maximum overcurrent protection (MOP) ratings of 15 amperes across all units. Units feature noise control levels of NC 55, with entering air temperatures (EAT) at 55 degrees Fahrenheit and leaving air temperatures (LAT) between 92.9 and 94.5 degrees Fahrenheit. All selections incorporate altitude corrections, and the specifications are validated against AHRI 885-2008 Appendix E for NC level determination. The document carries a standard disclaimer that results serve only as design aids and do not substitute for professional design services, with all data subject to change without notice.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Single Duct Terminal Unit Schedule
Tag AHU Room Model Size CFM Static Pressure NC Levels Electric Heat Coil Electrical Unit Information
Tag Unit Outlet Max Min Inlet Down Min Rad. Disch. CFM KW Volts/Ph. Steps EAT LAT MCA MOP Hand
VAV-01 DESV 08 12x10 500 250 1 0.25 0.02 20 27 250 3 480/3 S 55 92.9 4.5 15 RH
VAV-02 DESV 06 12x8 400 200 1 0.25 0.13 24 25 200 2.5 480/3 S 55 94.5 3.8 15 RH
VAV-03 DESV 08 12x10 900 200 1 0.25 0.07 27 28 200 2.5 480/3 S 55 94.5 3.8 15 RH
VAV-04 DESV 06 12x8 450 200 1 0.25 0.16 27 27 200 2.5 480/3 S 55 94.5 3.8 15 RH
1. Selections are based on Titus as Manufacturer.
2. All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011.
3. All NC levels determined using AHRI 885-2008 Appendix E.
4. All airflow, pressure losses and heating performance values have been corrected for altitude.
5. Units of measure: dimensions (in), airflow (cfm), water flow (gpm), air pressure (in wg), water head losses (ft) and temperatures (degF).
6. In the "Steps" column, code "S" denotes a modulating SCR heater.
7. The minimum supply circuit ampacity (MCA) and maximum overcurrent protection (MOP) ratings were calculated in accordance with UL standards based on motor and electric coil full load current ratings.
Notes:
9/24/2025 2:44 PM
The results of this program are only an aid to the designer, and are not a substitute for professional design services.
Titus accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice. 1 of 1