TAFB B9001 VAV Schedule.pdf

PDF 6 KB Posted

Attached to
WWYK250063 - INSTALL REACT VII FACILITY, B9001, POST V19
Solicitation number
FA813726R0026
Issued by

About this file

This document is a Single Duct Terminal Unit Schedule specification for variable air volume (VAV) units manufactured by Titus. The schedule specifies four VAV units (VAV-01 through VAV-04) with DESV models in sizes 06 and 08, configured for integration with air handling units (AHUs). The units are sized to deliver between 200 and 900 CFM at maximum capacity, with minimum airflows ranging from 200 to 250 CFM. All units operate at 480/3-phase electrical service with modulating SCR electric heat coils rated between 2.5 and 3 KW, featuring single-step heating control with heating performance validated per ASHRAE 130-2008 and AHRI 880-2011 standards.

Electrical specifications include minimum supply circuit ampacity (MCA) ratings between 3.8 and 4.5 amperes and maximum overcurrent protection (MOP) ratings of 15 amperes across all units. Units feature noise control levels of NC 55, with entering air temperatures (EAT) at 55 degrees Fahrenheit and leaving air temperatures (LAT) between 92.9 and 94.5 degrees Fahrenheit. All selections incorporate altitude corrections, and the specifications are validated against AHRI 885-2008 Appendix E for NC level determination. The document carries a standard disclaimer that results serve only as design aids and do not substitute for professional design services, with all data subject to change without notice.

View the file

Other files

File Type Posted
Solicitation Amendment FA813726R00260001 - CANCELLATION.pdf PDF
Solicitation Amendment FA813726R00260001 SF 30.pdf PDF
250063_ATT 10_Submittal Register.pdf PDF
250063_ATT 9_SOW.pdf PDF
250063_ATT 11_Drawings.pdf PDF
WWYK250063-04March2026.pdf PDF
2020 TAFB Facility Standard.pdf PDF
2026 TAFB Electrical Standard - Signed.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
SOW Att 02c_Controlled Area Training - Certificate.pdf PDF
22 00 00.pdf PDF
28 31 76.pdf PDF
23 09 23.02.pdf PDF
07 14 00.pdf PDF
08 51 23.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 72 00.pdf PDF
00 71 00.pdf PDF
01 78 00.pdf PDF
01 33 00.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 78 23.pdf PDF
esvperf_singledual_2023_V2.pdf PDF
lrad331965pd_spec.pdf PDF
REACT VII SA-01.pdf PDF
ARCH-COMBINED.pdf PDF
4500-MUG.pdf PDF
overall plan 04.15.2021.pdf PDF
250063_ATT 10_Submittal Register.xlsx XLSX spreadsheet
26 05 73 POWER STUDIES.pdf PDF
26 20 00.pdf PDF
09 90 00.pdf PDF
23 09 13.pdf PDF
23 36 00.00 40.pdf PDF
08 71 00.pdf PDF
05 40 00.pdf PDF
10 14 00.10.pdf PDF
08 33 23.pdf PDF
08 11 13.pdf PDF
07 92 00.pdf PDF
01 33 16.00 10.pdf PDF
01 32 16.00 20.pdf PDF
image.png PNG image
250063 React VII_Hardware schedule 25MAR26 JL.xlsx XLSX spreadsheet
JOIST SPECIAL INSPECTIONS.xlsx XLSX spreadsheet
ELECTRICAL PANEL SCHEDULE U18L.xlsx XLSX spreadsheet
esvEH_singledual_2023_V2.pdf PDF
lk406gn05t4_spec.pdf PDF
2_-_HE05-JINV-S11EE---GNT---L_001.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Single Duct Terminal Unit Schedule

Tag AHU Room Model Size CFM Static Pressure NC Levels Electric Heat Coil Electrical Unit Information

Tag Unit Outlet Max Min Inlet Down Min Rad. Disch. CFM KW Volts/Ph. Steps EAT LAT MCA MOP Hand

VAV-01 DESV 08 12x10 500 250 1 0.25 0.02 20 27 250 3 480/3 S 55 92.9 4.5 15 RH

VAV-02 DESV 06 12x8 400 200 1 0.25 0.13 24 25 200 2.5 480/3 S 55 94.5 3.8 15 RH

VAV-03 DESV 08 12x10 900 200 1 0.25 0.07 27 28 200 2.5 480/3 S 55 94.5 3.8 15 RH

VAV-04 DESV 06 12x8 450 200 1 0.25 0.16 27 27 200 2.5 480/3 S 55 94.5 3.8 15 RH

1. Selections are based on Titus as Manufacturer.

2. All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011.

3. All NC levels determined using AHRI 885-2008 Appendix E.

4. All airflow, pressure losses and heating performance values have been corrected for altitude.

5. Units of measure: dimensions (in), airflow (cfm), water flow (gpm), air pressure (in wg), water head losses (ft) and temperatures (degF).

6. In the "Steps" column, code "S" denotes a modulating SCR heater.

7. The minimum supply circuit ampacity (MCA) and maximum overcurrent protection (MOP) ratings were calculated in accordance with UL standards based on motor and electric coil full load current ratings.

Notes:

9/24/2025 2:44 PM

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

All data subject to change without notice. 1 of 1

File details come from the government source that posted it. Updated .