This is an electrical wiring schematic diagram for the RenewAire HE05 heat recovery ventilation unit with no damper configuration. The document provides detailed field wiring instructions for connecting the unit's components, including 115 VAC, 1-phase input power, two electronically commutated motors (EF ECM and SF ECM), and associated control systems.

The schematic illustrates the connections for an ON/OFF switch, doorkill switches (DOORKILL1 and DOORKILL2), external potentiometers for high-speed fan control, and board-mounted potentiometers (R9 for EF and R10 for SF) for low-speed fan adjustment. The circuit includes 24VAC power distribution, 0-10V control signals, and multiple terminal connections for bypass, exhaust air/return air (EA/RA), and outdoor air/fresh air (OA/FA) functions. The diagram specifies that the purple wire on high-speed potentiometers is positioned closest to the anti-rotation tab and provides guidance on switch positioning for fan enable and speed control (closed for high-speed, open for low-speed). The document was revised on September 3, 2024, reflecting a change to field wiring connections, with the original version dated August 5, 2024. Configuration designation is HE05-JINV-S11EE---GNT---L_001.

View the file

Other files

File Type Posted
250063_ATT 10_Submittal Register.xlsx XLSX spreadsheet
26 05 73 POWER STUDIES.pdf PDF
26 20 00.pdf PDF
09 90 00.pdf PDF
23 09 13.pdf PDF
23 36 00.00 40.pdf PDF
08 71 00.pdf PDF
05 40 00.pdf PDF
10 14 00.10.pdf PDF
08 33 23.pdf PDF
08 11 13.pdf PDF
07 92 00.pdf PDF
01 33 16.00 10.pdf PDF
01 32 16.00 20.pdf PDF
image.png PNG image
250063 React VII_Hardware schedule 25MAR26 JL.xlsx XLSX spreadsheet
JOIST SPECIAL INSPECTIONS.xlsx XLSX spreadsheet
ELECTRICAL PANEL SCHEDULE U18L.xlsx XLSX spreadsheet
esvEH_singledual_2023_V2.pdf PDF
lk406gn05t4_spec.pdf PDF
ERV Schedule_TAFB B9001_O-212477.xlsx XLSX spreadsheet
4500-CIVIL.pdf PDF
250063_ATT 10_Submittal Register.pdf PDF
250063_ATT 9_SOW.pdf PDF
250063_ATT 11_Drawings.pdf PDF
WWYK250063-04March2026.pdf PDF
2020 TAFB Facility Standard.pdf PDF
2026 TAFB Electrical Standard - Signed.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
SOW Att 02c_Controlled Area Training - Certificate.pdf PDF
22 00 00.pdf PDF
28 31 76.pdf PDF
23 09 23.02.pdf PDF
07 14 00.pdf PDF
08 51 23.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 72 00.pdf PDF
00 71 00.pdf PDF
01 78 00.pdf PDF
01 33 00.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 78 23.pdf PDF
esvperf_singledual_2023_V2.pdf PDF
lrad331965pd_spec.pdf PDF
REACT VII SA-01.pdf PDF
TAFB B9001 VAV Schedule.pdf PDF
ARCH-COMBINED.pdf PDF
4500-MUG.pdf PDF
overall plan 04.15.2021.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHANGESNAMEREV. DATE

Description

Family

Config No Damper

RenewAire

A B C D E

New0 8/5/2024 stimilsina 1 9/3/2024 stimilsina Changed field wiring connection

HE05

HE05-JINV-S11EE---GNT---L_001

DOORKILL1

DOORKILL2

24VAC

BK

RD

PU

YL

VAR

EN

24VAC

COM

Circuit Board

J1

BYPASS

YL

PU

OR

YL

PU

OR

SFGND

SFW

SF10V

EFGND

EFW

EF10V

BYPASSCOM

EA/RA

OA/FA

COM

Input Power 115 VAC, 1 Phase

NL1

OPEN FOR LOW SPEED

CLOSED FOR HIGHSPEED

CLOSE FOR FAN ENABLE

YL

PU

WH BU

RD L(L+)

N(L-)

GND

GND

0-10 V

SF ECM

BK

RD

XF

BK

BU

BK

L(L+)

N(L-)

GND

GND

0-10 V

EF ECM

SF

EF

customer supplied)

(External

(Optional)

CW

CW

Note:

1. For high speed potentiometer wiring, the purple wire is located closest to the anti-rotation tab

2. For low speed mode fan adjustment, the board mounted potentiometers are EF (R9) and SF (R10)

YL

YL

YL

PU

SF

EF

Doorkill Switch

ON/OFF Switch

GND

BK

WH

GN/YL

BK

RD