This is an electrical wiring schematic diagram for the RenewAire HE05 heat recovery ventilation unit with no damper configuration. The document provides detailed field wiring instructions for connecting the unit's components, including 115 VAC, 1-phase input power, two electronically commutated motors (EF ECM and SF ECM), and associated control systems.
The schematic illustrates the connections for an ON/OFF switch, doorkill switches (DOORKILL1 and DOORKILL2), external potentiometers for high-speed fan control, and board-mounted potentiometers (R9 for EF and R10 for SF) for low-speed fan adjustment. The circuit includes 24VAC power distribution, 0-10V control signals, and multiple terminal connections for bypass, exhaust air/return air (EA/RA), and outdoor air/fresh air (OA/FA) functions. The diagram specifies that the purple wire on high-speed potentiometers is positioned closest to the anti-rotation tab and provides guidance on switch positioning for fan enable and speed control (closed for high-speed, open for low-speed). The document was revised on September 3, 2024, reflecting a change to field wiring connections, with the original version dated August 5, 2024. Configuration designation is HE05-JINV-S11EE---GNT---L_001.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHANGESNAMEREV. DATE
Description
Family
Config No Damper
RenewAire
A B C D E
New0 8/5/2024 stimilsina 1 9/3/2024 stimilsina Changed field wiring connection
HE05
HE05-JINV-S11EE---GNT---L_001
DOORKILL1
DOORKILL2
24VAC
BK
RD
PU
YL
VAR
EN
24VAC
COM
Circuit Board
J1
BYPASS
YL
PU
OR
YL
PU
OR
SFGND
SFW
SF10V
EFGND
EFW
EF10V
BYPASSCOM
EA/RA
OA/FA
COM
Input Power 115 VAC, 1 Phase
NL1
OPEN FOR LOW SPEED
CLOSED FOR HIGHSPEED
CLOSE FOR FAN ENABLE
YL
PU
WH BU
RD L(L+)
N(L-)
GND
GND
0-10 V
SF ECM
BK
RD
XF
BK
BU
BK
L(L+)
N(L-)
GND
GND
0-10 V
EF ECM
SF
EF
customer supplied)
(External
(Optional)
CW
CW
Note:
1. For high speed potentiometer wiring, the purple wire is located closest to the anti-rotation tab
2. For low speed mode fan adjustment, the board mounted potentiometers are EF (R9) and SF (R10)
YL
YL
YL
PU
SF
EF
Doorkill Switch
ON/OFF Switch
GND
BK
WH
GN/YL
BK
RD