This is a product specification and selection guide for Titus electric heating coils designed for single and dual duct variable air volume (VAV) terminal units (PESV, AESV, DESV models). The document provides detailed capacity tables and application data for two heating configurations: staged heat and Lynergy heat systems.

The electric coils are available in multiple inlet sizes (4 through 24x16) with heating CFM ranges from 55-225 CFM up to 1800-8000 CFM. The coils support various electrical configurations including 120V single phase, 208V single phase, 240V single phase, 277V single phase, 208V three phase, and 480V three phase (4-wire wye, with 3-wire configuration available). Maximum kW capacities vary by inlet size and voltage, ranging from 2.5 kW to 36.0 kW for staged heat and up to 25.0 kW for Lynergy heat configurations. The staged heat option offers one to three heating steps, while Lynergy heat provides continuous modulation. Selection criteria require verification that desired kW capacity is available for the specified unit size, minimum airflow limits are within recommended operating ranges, and the coil satisfies the formula kW ≤ cfm × 0.0142 to limit temperature rise to 45°F. Coil discharge temperatures should not exceed 100°F for proper operation, with optimal diffuser performance achieved when discharge temperatures remain no more than 15°F above desired room temperatures. The coils feature an extended plenum section and diffuser plate to minimize stratification and heating elements designed to prevent hot spots and thermal cutout nuisance tripping.

View the file

Other files

File Type Posted
Solicitation Amendment FA813726R00260001 - CANCELLATION.pdf PDF
Solicitation Amendment FA813726R00260001 SF 30.pdf PDF
250063_ATT 10_Submittal Register.pdf PDF
250063_ATT 9_SOW.pdf PDF
250063_ATT 11_Drawings.pdf PDF
WWYK250063-04March2026.pdf PDF
2020 TAFB Facility Standard.pdf PDF
2026 TAFB Electrical Standard - Signed.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
SOW Att 02c_Controlled Area Training - Certificate.pdf PDF
22 00 00.pdf PDF
28 31 76.pdf PDF
23 09 23.02.pdf PDF
07 14 00.pdf PDF
08 51 23.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 72 00.pdf PDF
00 71 00.pdf PDF
01 78 00.pdf PDF
01 33 00.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 78 23.pdf PDF
esvperf_singledual_2023_V2.pdf PDF
lrad331965pd_spec.pdf PDF
REACT VII SA-01.pdf PDF
TAFB B9001 VAV Schedule.pdf PDF
ARCH-COMBINED.pdf PDF
4500-MUG.pdf PDF
overall plan 04.15.2021.pdf PDF
250063_ATT 4_ODS.pdf PDF
WWYK250063-04March2026 1.docx DOCX document
250063_ATT 3_RMDF.pdf PDF
23 00 00.pdf PDF
23 07 00.pdf PDF
23 31 13.00 40.pdf PDF
23 08 00.pdf PDF
03 01 00.pdf PDF
23 64 26.pdf PDF
10 14 00.20.pdf PDF
23 05 48.00 40.pdf PDF
07 84 00.pdf PDF
23 03 00.pdf PDF
01 50 00.pdf PDF
00 80 00.pdf PDF
01 42 00.pdf PDF
UMRL.pdf PDF
PILE SCHEDULE.xlsx XLSX spreadsheet
HELICAL PILES NOTES.docx DOCX document
z400i.pdf_safe.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Redefine your com fort zone. ™

| w w w .titus-hvac.com single / dual duct terminals

M23

M

ELECTRIC COILS

SELECTION AND CAPACITIES

PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)

Useful formulas: cfm x ΔT cfm ΔT kW x 3160kW x 3160 kW = or ΔT = or cfm =

Titus electric heating coils are specifically designed for use with VAV terminal units. They include an extended plenum section and diffuser plate to minimize stratification. The heating elements are designed to minimize hot spots and nuisance tripping of the thermal cutouts.

Must be within recommended ranges to ensure proper operation and long service life. For optimum diffuser performance and maximum thermal comfort, coil discharge temperatures should not be more than 15°F above desired room temperatures. For proper coil operation it is recommended that coil discharge temperatures do not to exceed 100°F.

To make a coil selection:

1. Check the desired kW is available in desired unit size and number of stages. (Required to prevent excessive watt density and current draw, while taking into account unit size limitations.)

2. Check the desired minimum airflow limit is within recommended operating range. (Ensures velocity pressure will be sufficient to close airflow sensing switch.)

3. Multiply desired minimum airflow limit by a factor of 0.0142 and check the result is equal to or greater than desired kW. (Limits temperature rise across the coil to 45°F.)

Recommended Coil Selection Data The table at the right describes the maximum recommended kW capacities and number of stages available for Titus single duct terminals.

These requirements established to prevent excessive temperature rise caused by low airflow and/or oversized coils. Minimum airflow limits kW ≤ cfm x 0.0142

Where ΔT = air temperature rise.

Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. 3-wire configuration is available.

ELECTRIC COILS

Inlet Size Heating cfm

Range

Number of Steps

Available

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 1 0.5

5.0 0.5

3.0 1.0

3.0 1.0

3.0 1.5 3.0 2.5 3.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

5 85-350 1 0.5

5.0 0.5

5.0 1.0

5.0 1.0

5.0 1.5 5.0 2.5 5.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

6 105-500 1 0.5

5.0 0.5

7.5 1.0

7.5 1.0

7.5 1.5 7.5 2.5 7.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

7 135-650 1 0.5

5.0 0.5

9.5 1.0

9.5 1.0

9.5 1.5 9.5 2.5 9.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

8 190-900 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 13.0 2.5 13.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

9 225-1050 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 16.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

10 300-1400 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 21.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

12 425-2000 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 30.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

14 575-3000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

16 750-4000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

24x16 1800-8000 1 1.0

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 4.0 36.02 2.0 2.0 2.0 3.0 2.0 3 3.0 3.0 3.0 4.5 3.0 www.

Re de fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

.c om single / dual duct terminals

M24

M

ELECTRIC COILS

PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT)

EL

EC

TR

IC

C

OI

LS

Inlet Size

Heating cfm Range

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 0.5 2.5 0.5 3.0 1.0 3.0 1.0 3.0 1.5 3.0 2.5 3.0

5 85-350 0.5 4.5 0.5 5.0 1.0 5.0 1.0 5.0 1.5 5.0 2.5 5.0

6 105-500 0.5 5.0 0.5 7.5 1.0 7.5 1.0 7.5 1.5 7.5 2.5 7.5

7 135-650 0.5 5.0 0.5 9.5 1.0 9.5 1.0 9.5 1.5 9.5 2.5 9.5

8 190-900 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 13.0

9 225-1050 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 16.0

10 300-1400 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 21.0

12 425-2000 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 25.0

14 575-3000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

16 750-4000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

24x16 1800-8000 2.0 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 4.0 25.0 www.