T2070057 ApprLtr.docx 1611110869755 1611110869755_122452230.pdf

PDF 91 KB Posted

Attached to
FY27 NOAA Ship Gordon Gunter Drydock REFERENCES
Solicitation number
1305M226Q0144REF
Issued by

About this file

This is an ABS (American Bureau of Shipping) technical review document for a Monitor & Alarm System Profinet Upgrade project dated January 19, 2021.

The document contains ABS Global Engineering's formal review of design documentation for two National Oceanic and Atmospheric Administration (NOAA) vessels: the "Oscar Elton Sette" (Class No. 8801905) and "Gordon Gunter" (Class No. 9000291), both Halter Marine Inc. vessels with hull numbers 1123 and 1128, flagged under the United States of America. The review evaluated five documents against ABS Rules for Building and Classing Marine Vessels, 2020. The submitted documentation included a Monitor & Alarm System Profinet Upgrade Overview, Monitor System Profinet Upgrade drawing, NOAA alarm inputs specification, Gunter PSTP, and an FMEA (Failure Mode Effects Analysis) for both vessels. Three open technical comments were identified requiring resolution: Comment E-001 addresses security controls for alarm set points and disabling, requiring implementation of keyswitch, keycard, password, or other approved methods per ABS Rules 4-9-3/5.1.1; Comment E-002 notes the system's Category II Computer Based System classification and mandates ABS Surveyor witnessing of on-board testing and maintenance of development procedures and software quality documentation per ABS Rules 4-9-3; and Comment E-003 requires provision of at least two computers with keyboards and monitors at the centralized control station per Marine Vessel Rules 4-9-5/9.3. Contact for clarifications is Emil Shtaygrud at 281-877-6952 or eshtaygrud@eagle.org.

View the file

Other files

File Type Posted
Copy of 1-QUADRANS-UserManual_MU-QUADRANS-AN-003-G.pdf PDF
NIX-D03066A_NETANSN1_UM_compressed.pdf PDF
Copy of 110-6233550.pdf PDF
AMC-505-1B Valve Overhaul and Test 4 pages.pdf PDF
Copy of 524-6233983.pdf PDF
AMC-631-2Dx.pdf PDF
Gauge Calibration List.xlsx XLSX spreadsheet
SCOTT AirPak_595118-01-Ex.pdf PDF
AMC-240-1 Propulsion Shafts _ Propellers.pdf PDF
150-6233566_RevJ_Sht1 THRU 6_N_A_MODULE NO. 9C STRL ASSY.pdf PDF
Copy of GU_514_TA-514-6629787_RevNO REVISION_Sht1 THRU 3_N_A_CHILLED WATER SYSTEM DIAGRAM.pdf PDF
GU_NONE_150-6233569_RevP_Sht1 THRU 9_N_A_MODULE NO. 10A STRUCTURAL ASSEMBLY.pdf PDF
Copy of GU_NONE_150-6233604_RevL_Sht1 THRU 5_N_A_MODULE NO. 15 STRUCTURAL ASSEMBLY.pdf PDF
20-KT-055A - Gordon Gunter Reefer Equipment Original.pdf PDF
Copy of 110-6233549.pdf PDF
000-1H General-Requirements-Ship-Ship-Repair-Contracts.pdf PDF
T9555-BA-MMO-010_0_0x.PDF PDF
GG Extinguisher List 5-28-25.xlsx XLSX spreadsheet
TECHNICAL MANUAL INDEX TMI.xlsx XLSX spreadsheet
Copy of 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_ADx.pdf PDF
Copy of TAGO_NONE_150-6233575_RevN_Sht1 THRU 13_N_A_MODULE NO. 10C STRUCTURAL ASSEMBLY.pdf PDF
Copy of m-202-instruction-manual-ocenco-inc.pdf PDF
Copy of 5100334-01_Salwico Cargo Addressable_Service Maintenance Manual_M_EN_2021_V.pdf PDF
Copy of GU_NONE_150-6233572_RevK_Sht1 THRU 7_N_A_MODULE NO. 10B STRUCTURAL ASSEMBLY.pdf PDF
GG SCBA Layout.pptx PPTX presentation
Copy of 512-6233801.pdf PDF
Copy of GU_342_342-6233836_RevF_Sht1 THRU 2_N_A_MAIN ENGINE SEAWATER COOLING SYSTEM ARRANGEMENT.pdf PDF
TAGO_NONE_150-6233566_RevJ_Sht1 THRU 6_N_A_MODULE NO. 9C STRL ASSY.pdf PDF
NOAA DOCKING REPORT.pdf PDF
T9568-AC-MMO-010_0_0.PDF PDF
Copy of EX-GU_524_524-6233839_RevG_Sht1 THRU 11_N_A_AUXILIARY SEA WATER COOLING SYSTEM ARRANGEMENT.pdf PDF
Copy of GU-300-102_ELEC Installations.pdf PDF
NOAA Gangway Test.docx DOCX document
T9555-BC-MMO-010_0_0.PDF PDF
s0700-3 Dry Dock Certification-1.pdf PDF
Copy of 5100195_Control-Repeater Panel M 4.3_M_EN_2018_H.pdf PDF
SE_85_085-6233567_RevH_Sht2 OF 2_N_A_GENERAL ARRANGEMENT FORECASTLE DECK AND ABOVE SHT 2.pdf PDF
8KatoGenerator.pdf PDF
TAGO_NONE_150-6233562_RevK_Sht1 THRU 9_N_A_MODULE NO. 9A STRL ASSY.pdf PDF
GU_NONE_NONE_RevNONE_Sht1THRU2_N_A_GENERALARRANGEMENTMAINDECK_BELOW.pdf PDF
TECHNICAL PUBLICATIONS INDEX - SM638027 - 2203874.pdf PDF
620-6233557.pdf PDF
E100 Rev -1 Gunter.pdf PDF
SE_NONE_NONE_RevNONE_Sht1 OF 1_N_A_OS-342-6233813-1.pdf PDF
543-6233930.pdf PDF
243-6233870 (1).pdf PDF
NOAA SETTE - NOAA GUNTER ALARM INPUTS 09November2020 Revision 0_122452722.pdf PDF
Gunter Valve List.xlsx XLSX spreadsheet
1005-01 - NOAA Ship Health Plan (public).docx DOCX document
NOAA Ships General Arrangement with camera locations (1).pdf PDF
Show 40 more

Latest 50 of 134 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WARNING – This document may contain technical data whose export is restricted by the Arms Export Control Act (Title 22, U.S.C., Sec. 2751, et seq.) or the Export Administration Act of 1979 (Title 50, U.S.C., App. 2401, et seq.), as amended. Violations of these export laws are subject to severe criminal or civil penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.

ABS Global Engineering 1701 City Plaza Drive | Spring, TX 77389 USA

Task No. T2070057

“OSCAR ELTON SETTE”, Class No. 8801905

“GORDON GUNTER”, Class No. 9000291

Halter Marine Inc. Hull nos. 1123 and 1128

Flag: United States of America

Monitor & Alarm System Profinet Upgrade

Attention: Mr. Tim Langdon National Oceanic & Atmospheric Administration (WCN: 615875)

The documents shown in the attached list were reviewed in accordance with the applicable requirements of the following:

• ABS Rules for Building and Classing Marine Vessel, 2020

Please note our review is based on the following conditions:

1. The work is to be completed to the satisfaction of the attending ABS Surveyor.

2. The submitted documentation reviewed only for ABS Class requirements. Please submit the documentation to the USCG as soon as possible so that their comments can be incorporated in the vessels design.

Please see attached comments list for the comments generated as a result of this review.

For any clarifications, Mr. Emil Shtaygrud at 281-877-6952 (eshtaygrud@eagle.org).

Very truly yours, Roy H. Bleiberg

Vice President of Engineering

Electronically Signed by: Anju Valookkaran

Electronically published by ABS Houston.

Reference T2070057, dated 19-JAN-2021.

mailto:eshtaygrud@eagle.org

WARNING – This document may contain technical data whose export is restricted by the Arms Export Control Act (Title 22, U.S.C., Sec. 2751, et seq.) or the Export Administration Act of 1979 (Title 50, U.S.C., App. 2401, et seq.), as amended. Violations of these export laws are subject to severe criminal or civil penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.

ABS Global Engineering 1701 City Plaza Drive | Spring, TX 77389 USA

Documents List

Drawing No. Rev. No. Title Status

Gunter/Sette Overview 1 Monitor & Alarm System Profinet

Upgrade Overview

Reviewed with

Comments

Drawing 1 Monitor System Profinet Upgrade Reviewed with

Comment

ALARM INPUTS 1 NOAA SETTE - NOAA GUNTER ALARM

INPUTS

Reviewed

Gunter PSTP 1 Gunter PSTP Filed by ABS for

Reference only

Gunter FMEA 1 FMEA GUNTER & SETTE Reviewed

Electronic copies of the documents, appropriately stamped, are available in the ABS Client Portal.

Comments List

Comment No Comment Text Facilities Action

E-001 Gunter/Sette Overview - Monitor & Alarm System

Profinet Upgrade Overview

1128[Open] Technical

We note that an operator may adjust alarm set points and disable any alarm and advise that this is not acceptable in accordance with 4-9-3/5.1.1 of the Rules, which require keyswitch, keycard, password or other approved methods. Please resolve.

E-002 Gunter/Sette Overview - Monitor & Alarm System

Profinet Upgrade Overview

1128[Open] Surveyor

The subject system is classified as a Category II Computer Based System as per 4-9-

3/Table 1 of the Rules. The on Board Complete System Test and On-Board Integration

Test are required to be witnessed by the ABS Surveyors as per 4-9-3/Table 2 and 4-9-

3/9.3.4 (a) of the Rules. Further, the development procedures, software quality plan, evidence of software testing, and software version record are to be maintained and be made available to the Surveyor upon request as per 4-9-3/7.1 and 4-9-3/Table 2 of the Rules.

E-003 Drawing - Monitor System Profinet Upgrade 1128[Open], 1123[Open]

Technical

As per MVR 4-9-5/9.3, where a computer is used as the operator interface to display monitoring information, the centralized control station is to be provided with at least two computers, including keyboards and monitors, unless other means of display are provided capable of displaying the same information. Please resolve.

Electronically published by ABS Houston.

Reference T2070057, dated 19-JAN-2021.