Copy of 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_ADx.pdf
PDF 2 MB Posted
- Attached to
- FY27 NOAA Ship Gordon Gunter Drydock REFERENCES
- Solicitation number
- 1305M226Q0144REF
About this file
This is a User Guide for the Fire Detection System - Salwico Cargo Addressable, a state-of-the-art analogue-addressable fire detection system designed for marine, industrial, and transport applications. The guide was published in June 2021 (Document no. 5100332-01, Part no. 5100332-01) by Consilium Marine & Safety AB.
The manual provides comprehensive operational instructions for the Control Panel M 4.3 and Repeater M 4.3 components. Key system features include addressable detection zones with smoke, heat, flame, and manual call point detectors; multiple access levels (2, 2B, 3, and 4) controlling user permissions for operations and maintenance; and flexible disablement options (permanent, timer, clock, and periodic) for detectors, zones, and alarm devices. The system supports pre-alarm and fire alarm conditions with muting and reset capabilities, fault detection with detailed code references, test modes for detector verification, and alarm delay functionality. The Control Panel M 4.3 features a 4.3-inch graphical display with operational controls, system indicators, and a numerical keypad. The guide includes detailed menu navigation for accessing fire alarms, fault alarms, disablements, settings, service functions, and system history. An extensive Fault Code List (codes 128-255) provides diagnosis and remediation guidance for system malfunctions. The document also contains definitions of technical abbreviations, a quick reference guide for emergency response, and revision history noting updates through June 2021.
View the file
Other files
Show 40 more
Latest 50 of 134 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Detection System - Salwico Cargo Addressable
User Guide
Consilium Marine & Safety AB
Fire & Gas Marine Division
+46 31 710 77 00
Service: service@consilium.se Spares: spares@consilium.se www.consiliumsafety.com
The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing.
Consilium assumes no legal responsibility for any error or damage resulting from the usage of this document.
June 2021 Document no. 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD Part no. 5100332-01
© Copyright 2021, Consilium Marine & Safety AB
Table of contents
1 Introduction
1.1 About this Manual
1.2 Approvals
1.3 Symbols used in the manual
2 Fire Detection System
2.1 System Description
2.2 System Block Diagram
3 Control Panels
3.1 Control Panel M 4.3
3.1.1 General
3.1.2 Description of Keys and Indicators
3.1.3 Guide to the Menu System
3.2 Repeater M 4.3
3.2.1 General
3.2.2 Description of Keys and Indicators
4 Operations
4.1 Access Levels
4.2 Login
4.3 Pre-Alarm
4.4 Fire Alarm
4.4.1 Information Displayed when “Fire” is Flashing
4.4.2 Mute a Fire Alarm
4.4.3 Reset a Fire Alarm
4.4.4 Several Alarms
4.4.5 Type of Fire Alarms from Conventional Zones
4.5 Fault Alarm
4.5.1 Information Displayed when “Fault” is Flashing
4.5.2 Mute a Fault
4.5.3 Reset a Fault
4.5.4 Reset a Fault from the Fault List
4.5.5 Reset All Faults
4.5.6 Fault Messages
4.5.7 Warnings
4.6 Disablements
4.6.1 About Disablements
4.6.2 Available Types of Disablements
4.6.3 Acknowledgement of a New Disablement
4.6.4 Disabling Zones
4.6.5 Disabling Addressable Detectors & Manual Call Points
4.6.6 Disabling Alarm Devices
4.6.7 Old Disablements
4.6.8 Alarm Delay
4.6.9 Disabling External Control Groups
4.6.10 Disabling an Alarm Transfer Output
4.7 Reconnecting
4.7.1 Reconnecting Disabled Items
4.7.2 Reconnecting Periodic Disablements
4.7.3 Reconnecting Disabled Alarm Delays
4.7.4 Remove All Disablements
4.8 Service Menu
4.8.1 About the Service Menu
4.8.2 Save the System Log to a USB Memory Stick
4.8.3 How to report a fault
5 Testing
5.1 About Testing
5.2 Test mode overview
5.3 Testing a Fire-detecting Zone
5.4 Recommended Test Equipment
5.5 Reset Test Mode
5.6 Test the control panel display
6 Appendix - Fault Code List
6.1 Fault Code List
7 Appendix - Definitions and Abbreviations
7.1 Definitions and abbreviations
8 Quick Guide
9 Revision history
Index
User Guide 1 Introduction
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 1
1 Introduction
1.1 About this Manual
This User Guide is intended for personnel using the Fire detection system and provides basic understanding how to operate the system.
NOTE!
This manual has been revised based on system version 1.12.x.
The chapter Fire Detection System gives general information about the system.
The chapter Control Panels describes the function of the Control panel and the Repeater in the Fire detection system.
The chapter Operations describes how to operate the Fire detection system.
The chapter Testing provides brief instructions on how to connect and test the system (detailed information is found in the Service & Maintenance manual).
The Fault Code List in the Appendix lists the different fault codes.
Figure 1. Salwico Cargo Fire Detection System, an example.
1 Introduction User Guide
2 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
1.2 Approvals
1.3 Symbols used in the manual
DANGER!
Risk of serious or fatal injury to the user, and/or severe damage to the product, if the instructions are not followed.
WARNING!
Risk of personal injury and/or damage to the product if the instructions are not followed.
CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data, extra work, or unexpected results, if the instructions are not followed.
NOTE!
Note symbols alert you to important facts and conditions.
Hint!
Hint symbols direct you to specific instructions, such as where to find additional information and tell you how to perform a certain operation in an easier way.
User Guide 2 Fire Detection System
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 3
2 Fire Detection System
2.1 System Description
This Fire detection system is a state-of-the-art, analogue-addressable, fire-detection system designed to meet marine, industrial and transport requirements. Special care is given to ergonomics and user-friendliness with its logical and intuitive operator panel.
2.2 System Block Diagram
The following figure shows a typical system and its connected components, see Definitions and abbreviations, page 56 in the Appendix for explanation of terms and abbreviations.
Figure 2. An example of a system block diagram.
2 Fire Detection System User Guide
4 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
User Guide 3 Control Panels
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 5
3 Control Panels
3.1 Control Panel M 4.3
3.1.1 General
This menu-operated system monitors and controls all system functionality. The control panel's clear graphical display makes it easy to use.
3.1.2 Description of Keys and Indicators
Figure 3. Keys and indicators for the control panel
As shown in the figure above, the control panel is divided into three sections:
A = System Indicators B = Operational Controls C = Numerical Keypad
Part A: System Indicators
Figure 4. The system indicators section of the control panel
3 Control Panels User Guide
6 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
The System Indicators section is comprised of the following indicators:
1. Power Steady green light Power supply to the control panel is OK.
2. System fault Flashing yellow light Main process fault. A serious system fault in the system.
3. Test Steady yellow light At least one zone is manually set in test mode.
4. Warning Steady yellow light At least one warning indication exists.
5. Zone Steady yellow light At least one zone or a loop unit is disabled.
Flashing yellow light At least one zone or a loop unit is in fault condition. (Priority over disablement indication.)
6. Alarm device Steady yellow light At least one alarm device output is disabled.
Flashing yellow light At least one alarm device output is in fault condition.
7. Alarm delay off Steady yellow light The alarm delay function is disabled.
8. Custom indication 1-3 Colour and pattern of Custom LED indication is defined in the system configuration.
9. USB
USB connection for USB memory stick to load or save data.
Part B: Operational Controls
Figure 5. The operational section of the control panel
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 7
1. Main indicators Fire alarm
The Fire alarm key indicates existance of a fire alarm and gives direct access to the Fire alarm list. Indications:
Flashing red light One or more un-muted fire alarm(s) in the system.
Steady red light All fire alarms are muted.
Pre-Alarm The Pre-Alarm key indicates existance of a pre-alarm and gives direct access to the Pre-Alarm list. Indications:
Flashing orange light One or more un-muted pre-alarm(s) in the system.
Steady orange light All pre-alarms are muted.
Fault The Fault key indicates existance of a fault and gives direct access to the Fault alarm list.
Indications:
Flashing yellow light One or more un-muted fault(s) in the system.
Steady yellow light All faults are muted.
Disablements The Disablements key indicates existance of a disablement and activates the Disablements menu. Indications:
Steady yellow light At least one disabled function in the system.
Shortcuts The Shortcut key activates the customer specific shortcut list. Indications:
Steady orange light The alternatives in the shortcut list and the corresponding indicators (Shortcut 1, Shortcut 2 and Shortcut 3) are set in the configuration program.
2. Status This key gives direct access to the System status summary list with Alarms (Fire and Pre-Alarms), Maintenance (Faults and Warnings) and Disablements (Active and Periodic).
Shortcuts are:
1. Upload the system log to USB Memory stick.
2. Go to the maintenance menu.
3. Menu This key gives direct access to the main menu and all system functions.
4. Navigation and Command Keys The arrow keys are used to navigate menus, select different menu alternatives, and show details for list items.
8 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
Go to the previous item in the list or menu.
Go to previous menu. Selects the chosen menu alternative.
Go to the next item in the list or menu.
ESC
The Escape key is used to go to the default menu.
OK
This key is used to select a menu alternative or to accept a function. The OK key is also in some cases used to show details for a selected list entry.
5. Display The control panel has a backlited 4.3" graphical, 480×272 pixels, 16-bit colour display.
6. Alarm keys Multiple alarms
Press this key to scroll through the different alarms. The list always returns to the first fire alarm after 30 seconds of inactivity.
Reset This green key is used to request for a reset of a selected alarm, fault or disablement.
Mute This red key is used to acknowledge the alarm and mute the local buzzer.
Part C: Numerical Keypad
Figure 6. The keypad on the control panel.
1. Numerical keypad
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 9
Keys 0 - 9 The numerical keypad is used to enter numerical values. Keys 1–9 are also used as shortcuts when navigating in the menus.
Erase This key is used to erase characters from the text display.
Enter This key is used to select a menu alternative or to accept a function. The Enter key is also used to show details for a selected list entry.
Day mode Increase the brightness/contrast level for the indicators and display on the panel.
Night mode Decrease the brightness/contrast level for the indicators and display on the panel.
3.1.3 Guide to the Menu System
The fire detection system is menu-operated. All system functions are available from the different menus. The fire detection system is normally displaying a greeting screen. From the greeting screen pressMenu to enter the menu system.
Default screen Installation name Project number
Menu 1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
How to navigate the menu system
• Navigate in the menu alternatives with the and arrow keys. It is also possible to choose a menu alternative by entering the menu number.
• Select a menu alternative with the arrow key or the key.
• Use the arrow key to go back to the previous menu.
In the lower part of the display the different options available for each individual menu are shown.
The numerical keypad is used to enter information, e.g. zone and detector number.
The key erases the last character.
Table 1. Top menu alternatives
Alternatives Description 1 Fault alarms The menu from which fault and warning messages are listed and handled.
10 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
Alternatives Description 2 Fire alarms Fire alarms and pre-alarms are displayed and managed from this menu. Muted alarm devices may be reactivated here.
3 Disablements Disabled parts of the fire detection system are added, removed, or listed from this menu. (For instructions, see About Disablements, page 25.)
4 Login Log in from this menu by entering a personal access code.
For further details see section Login, page 20.
5 Settings Use this menu to adjust system parameters, such as the dimmer level, date, time and alarm delay time.
It is also possible to make a lamp test for the control panel under “Test display”.
6 Service menu Use this menu to list and view information about the system and its components. It is also possible to make disablements of the listed units. The Service menu is described in more detail in the separate Service and Maintenance manual.
Access level 2B is needed for basic functions and access level 4 is needed to perform advanced service options.
7 History Use this menu to view previous events in the fire detection system.
8 Condition list Use this menu to create lists of detectors that are no longer in good condition but still fully functional. The purpose of the satisfactory and poor condition lists is to give an early indication of which detectors need to be replaced in the future.
1 Fault Alarms Menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
1 Fault List 2 Warning List 3 Reset All Faults
Table 2. Fault alarm menu alternatives
Alternatives Description 1 Fault List Shows all present fault alarms.
2 Warning List Shows all present warning messages.
3 Reset All Faults The system will attempt to reset all present fault alarms in the Fault List.
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 11
2 Fire Alarms Menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
1 Fire List 2 Pre-Alarm List 3 Resound (restart bells) 4 Reset All Fire Alarms
Table 3. Fire alarm menu alternatives
Alternatives Description 1 Fire List Shows all present Fire Alarms.
2 Pre-Alarm List Shows all present Pre-Alarms.
3 Resound (restart bells) If the alarm devices have been silenced by pressing Mute key , this function will restart them (if the fire alarm has not been reset).
4 Reset All Fire Alarms The system will attempt to reset all fire alarms in the Fire List.
3 Disablements menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
1 New disablement (access lvl 2B) 2 List disablements 3 List periodic disablements 4 List old disablements 5 Remove all disablements 6 Alarm Delay 7 List Alarm Delay
Table 4. Disablemens menu alternatives
Alternatives Description 1 New disablements Adds new disablements.
This requires access level 2B.
2 List disablements Shows all active disablements in the system. A periodic disablement that is not active will not be shown in this list, but in the list periodic disablements (mentioned below). The reconnection of a disabled unit is made from this list. See section Reconnecting Disabled Items, page 29 for more details.
3 List periodic disablements
Shows all periodic disablements in the system. The removal of periodic disablements is made from this list.
12 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
Alternatives Description 4 List old disablements This list displays the 150 previously removed disablements and allows these older disablements to be reactivated.
Hint!
This function is very useful if the same disablement is frequently needed during irregular time periods. Just mark the appropriate old disablement in the list and press 0 to reactivate it.
This requires access level 2B.
5 Remove all disablements Removes all active disablements shown in the Disablement list.
DANGER!
Periodic disablements are not permanently removed. Only the periodic disablement's active period is removed. Use alternative "3 List periodic disablements" to remove periodic disablements.
6 Alarm Delay Disables the alarm delay function.
Alarm delay is a programmable time delay between when a fire is detected and until the alarm device outputs are activated.
See Alarm Delay, page 27 for more information.
7 List Alarm Delay Shows all active alarm delays in the system. The reconnection of a disabled alarm delay is made from this list.
See section for more details.
New disablement sub-menu
1 New disablement (access 2B) 2 List disablements 3 List periodic disablements 4 List old disablements 5 Remove all disablements
1 Zones 2 Detectors & Manual Call Points 3 External Controls 4 Alarm Device (bells etc.)
5 Test Mode
Table 5. New disablement menu alternatives
Alternatives Description 1 Zones Disable entire zones for a specified time period or permanently.
2 Detectors & Manual Call Points
Disable individual detectors or manual call points for a specified time period or permanently.
3 External Control Deactivate 1 External Controls or 2 Alarm Transfer . See list External Control Disablements, page 12 for more information.
4 Alarm Device (Bells etc.) Disables the outputs for alarm devices, such as audible (e.g.
bells) and optical alarm devices.
5 Test Mode Set a zone into test mode.
External Control Disablements
1. External Controls
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 13
Disables outputs (all or individual groups) to external controls. This means that an alarm condition will not cause activation of the selected group.
• All groups Disable all external controls (doors, fire, fault, ventilation and indication).
• Doors Disable external door controls in the system.
• Fire Disable external fire controls in the system.
• Fault Disable external fault controls in the system.
• Ventilation Disable external ventilation controls in the system.
• Indication Disable external indication controls in the system.
2. Alarm Transfer Disables the supervised alarm transfer output, which is normally used in on-shore installations to alert the fire brigade in case of a fire alarm. Select System or Central to disable.
See also section About Disablements, page 25 for more information about the Disablements.
4 Login Menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
User 1 User 2 User 3 User 4
See Login, page 20 for more information about the Login menu alternatives.
5 Settings Menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
1 Set Dimmer 2 Set Time 3 Set Date 4 Test Display 5 Alarm Delay Times 6 Keyboard Beep 7 Cause Effect in Test Mode
8 Use English / Use configured language
14 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
Table 6. Settings menu alternatives
Alternatives Description 1 Set Dimmer Use this menu to adjust the contrast level (1–9) for the display and indications on the control panel.
2 Set Time Use this menu to set the system time.
It is possible to synchronize the system clock with a central time.
3 Set Date Use this menu to set the system date.
NOTE!
Dates before year 2000 are not accepted by the fire detection system.
4 Test Display Use this menu to activate a lamp test in order to visually verify the function of the display and all indications on the control panel.
5 Alarm Delay Times (access level 3)
Use this menu to adjust the programmable alarm delay times if no time is set in the configuration program.
Time 1 is adjustable between 1 or 2 minutes. Time 2 (reset) is only used for on-shore installations.
See section Alarm Delay, page 27 for more information.
6 Keyboard Beep Use this menu to turn the keyboard beep ON or OFF.
7 Cause Effect in Test Mode (access level 2)
Use this menu to turn the Cause Effect programming ON or OFF during test mode. If set to ON, the outputs are activated as normal during test mode.
8 Use English / Use configured language
Use this menu to switch between English and the language chosen in the configuration file (using the CCP configuration program).
6 Service Menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
1 System Details 2 Centrals 3 Modules 4 Zones 5 Loops 6 Configuration 7 Firmware 8 System Log 9 I/O lists
Access level 2B is needed for basic functions and access level 4 is needed to perform advanced service options.
Hint!
The Service menu is described in more detail in the separate Service and Maintenance manual.
Table 7. Service menu alternatives
Alternatives Description 1 System Details This menu lists the installed system's information, such as name and reference number (if defined). It also lists when the system was last configured and by which program.
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 15
Alternatives Description 2 Centrals Use this menu to list information about the installed centrals and the modules in each central.
3 Modules Use this menu to list information about the installed system modules. It is possible to display all details about the modules, such as installed detector loops, installed program versions, input/output status. It is also possible to print information.
4 Zones This menu shows a list of all zones configured in the system.
It is possible to list all loop units in a zone if the zone consists of addressable loop units, disable zones or loop units, and set a single fire detector in alarm condition.
Installation Mode can be activated for loops and zones containing addressable loop units. Loop units affected by Installation Mode will stop reporting faults of type ‘present not configured’, ‘configured not present’ and ‘no answer’.
5 Loops This menu shows a list of all physical loops installed in an analogue addressable system. A loop can consist of conventional or addressable fire detectors and other loop units. It is possible to add and to disable entire loops. Use Scan Loop to force a scan of the loop for new loop units.
Installation Mode can be activated. Loop units affected by Installation Mode will stop reporting faults of type ‘present not configured’, ‘configured not present’ and ‘no answer’.
6 Configuration This menu is used to configure the system as further explained in Configuration sub-menu, page 15.
7 Firmware Use this menu to download firmware to modules, load or backup service pack, and to start or stop an automatic update.
8 System log The System log menu contains sub-menus to save a syslog or to reset service interval.
Once the System Log is copied to a USB memory stick, it can be sent to an authorised service organisation for further technical assistance. See section About the Service Menu, page 29 for further information and instructions.
9 I/O lists I/O lists with sub-menus Input list and Output list. Use these menus to inspect or disable active inputs and outputs in the system and on loops.
Configuration sub-menu
1 System Details 2 Centrals 3 Modules 4 Zones 5 Loops 6 Configuration 7 Firmware 8 System Log 9 I/O lists
1 Reload configuration/reboot this module 2 Load configuration from USB memory 3 Save configuration to USB memory 4 Save changes to configuration 5 Remove configuration 6 Synchronise system configuration 7 Reboot system (this module excluded)
16 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
Hint!
The Configuration menu is described in more detail in the Installation & Commissioning manual and the Service & Maintenance manual.
Table 8. Configuration sub-menu alternatives
Alternatives Description 1 Reload configuration/reboot this module
Reload the configuration when a new updated configuration file has been downloaded to the system. The operation will reboot this control module only.
2 Load configuration from USB Memory
Download a new configuration file from a suitable USB memory stick.
3 Save configuration to USB Memory
Copy the existing configuration file to a suitable USB memory stick.
4 Save changes to configuration
CAUTION!
It is highly recommended to backup the configuration file before continuing.
Use this command to save all changes made from the control panel to the system configuration.
NOTE!
The changes are not permanently saved in the configuration file until this command is performed.
5 Remove configuration Select and remove files from a list of configuration files in the system.
6 Synchronise system configuration
CAUTION!
It is highly recommended to backup the configuration file before continuing.
Use this command to synchronise the configuration files in the system.
7 Reboot system (this module excluded)
The operation will reboot the system with this control module excluded.
There will be a 15 seconds delay before the system restarts.
8 Synchronise the CS-modules
Use this menu to change the active configuration of the CS modules.
7 History Menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
1 Fire History List 2 Fault History List 3 Disable History List 4 Common History List
Table 9. History menu alternatives
Alternatives Description 1 Fire History List Shows a chronological list of the last 1000 fire alarms.
2 Fault History List Shows a chronological list of the last 1000 fault alarms.
3 Disable History List Shows a chronological list of the last 1000 disablements.
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 17
Alternatives Description 4 Common History List Shows a common chronological list of the last 1000 pre-alarms, fire alarms, fault alarms, disablements, warnings, and I/Os.
8 Condition List Menu
1 Fault Alarms 2 Fire Alarms 3 Disablements 4 Login 5 Settings 6 Service Menu 7 History 8 Condition List
1 Satisfactory 2 Poor Detectors not listed in these two choices are in Good condition.
The Condition list menu provides the means to perform a status check of the detectors in the system. Detectors that are no longer in good condition but still fully functional will be present in either of these lists, and detectors in good condition will not be present at all.
Table 10. Condition list menu alternatives
Alternatives Description 1 Satisfactory (Lightly contaminated detectors)
This list shows detectors that still are in satisfactory condition (50-80% dirty) and fully functional. However, the environment has started to degenerate the detectors and they are no longer in good condition. Please consider to replace the detectors during the next planned maintenance work.
2 Poor (Heavily contaminated detectors)
This list shows detectors that have gone beyond satisfactory condition and entered poor condition (81-100% dirty), but are still fully functional.
When the detector has gone beyond poor condition it is also shown in the fault or warning list (depending on the configuration), with the description "130 DIRTY SENSOR". (See also Note below).
When a detector has reached poor condition it shall be replaced. It will be removed from the condition list after replacement.
NOTE!
In systems with CCP version 1.9.10 or older, dirty detectors are instead removed from the poor condition list and are only present in the warning or fault list with the description "130 DIRTY SENSOR".
3.2 Repeater M 4.3
3.2.1 General
The repeater panel is used to monitor functions in the fire detection system. It is possible to view and list:
• Fire alarms
• Fault alarms
• Disablements
18 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
3.2.2 Description of Keys and Indicators
Figure 7. Keys and indicators for the repeater panel.
Repeater panel
• Power
Green steady light indicates that the power supply to the repeater panel is OK.
• Local Mute Silence the local buzzer alarm.
• Fire - Fault - Dis.
Press the key to select the lists: Fire Alarm, Fault Alarm and Disablements.
• Navigation key – previous Scroll to previous item in the selected list.
• Navigation key – next Scroll to next item in the selected list.
• Night mode Decrease the brightness/contrast level for the indicators and display on the panel.
• Day mode Increase the brightness/contrast level for the indicators and display on the panel.
• Lamp test When you press the keys for Day and Night mode at the same time, all the repeater panel indicators as well as the display are lit and the buzzer is sounding – if not, they are not working correctly.
User Guide 4 Operations
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 19
4 Operations
4.1 Access Levels
CAUTION!
To prevent un-authorised operation of the system access levels protect the different functions of the fire detection system.
Some functions in the menus will require a higher access level than the default level due to safety restrictions.
Access level 2 is the default level. After the access level has been changed to a higher level, it automatically returns to access level 2 when the control panel has not been used for 30 minutes. For special applications access level 1 can be applied. This will allow the user to only mute the local buzzer and scroll though the fire and fault lists.
Description of Access levels There are different access levels as shown in the following table:
Table 11. Access levels
Access level
Procedure to enter level User Permissions
2 Operator access level None
Personnel trained and authorised to operate the system in case of fire or maintenance.
For viewing of fire or fault alarms:
• Fire alarms have priority over fault alarms.
• Possibility to mute local buzzer.
• Access to the menu system
• List status
• Reset and muting of alarms
2B Operator access level Enter access code for level 2B via menu/login.
Personnel trained and authorised to operate the system in case of fire or maintenance.
Same permissions as level 2, plus this additional permission:
• Make disablements
3 Power User access level Enter access code for level 3 via menu/login.
Personnel trained and authorised to make changes to the configured system.
Same permissions as level 2B, plus these additional permissions:
• Possibility to make changes to the configured system
4 Service access level Enter access code for level 4 via menu/login.
Only authorised service personnel trained by an authorised service organisation.
All functions available, including advanced service options.
Custom Specific Restrictions
NOTE!
Permissions on the different access levels can in some cases vary depending on programmed custom specific restrictions.
4 Operations User Guide
20 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
A Control Panel M 4.3 could be programmed to view events in the system with restricted rights to operate functions. For example a fire alarm is shown, but mute and reset are not allowed.
4.2 Login
WARNING!
To secure the functionality of the fire detection system only authorised users should be given access to disablement or test mode privileges in the system.
Each user shall be assigned to a specific access level.
To log in to the system:
1 Go to Menu » 4 Login and select user.
2 Enter the four-digit access code for the user. The system will acknowledge if the correct code is entered.
4.3 Pre-Alarm
The pre-alarm function gives an early alarm to fire conditions (e.g., a smouldering fire). The indication “Pre-Alarm” begins flashing on the control panel.
Fire alarms have priority over pre-alarms, pre-alarms have priority over faults.
The pre-alarm is also added to the Pre-Alarm List found under: Menu » 2 Fire Alarms » 2 Pre-Alarm List.
An active pre-alarm can be muted, this silences the internal buzzer and causes the pre-alarm indicator to stop flashing. The indicator remains lit until the pre-alarm is reset. A pre-alarm will remain in the Pre-Alarm List until it has been muted and reset.
The pre-alarm usually does not activate any alarm devices or external outputs.
4.4 Fire Alarm
4.4.1 Information Displayed when “Fire” is Flashing
DANGER!
In case of a fire alarm use the information viewed on the display to verify the alarm and take the appropriate actions based on local safety procedures.
The following sections describes the information displayed during a fire alarm, how to mute and reset an alarm, and the different types of alarms.
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 21
Figure 8. A fire alarm is detected in the system.
The following information is displayed in the Control Panel:
• Number of alarm(s)
• First, last and current list entry
• Zone in alarm
• Type of unit in alarm
• Address number of unit in alarm (only for addressable loop)
• Supplementary text (defined in system configuration)
Press for more details:
• Time of alarm
• Date of alarm
• Supplementary text about location of the detector (defined in system configuration)
4.4.2 Mute a Fire Alarm
The Mute key has different functions depending on the current access level.
1 Press Silences the internal buzzer and all external alarm devices*, and mutes the fire alarm indication. The fire indicator stops flashing, but remains lit until the Fire Alarm is reset.
2 Press for more details.
* Programmable function of external devices, set in the Configuration program (programmed by system Cause/Effect).
22 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
4.4.3 Reset a Fire Alarm
1 Press to reset the current Fire Alarm. NOTE!
Alarms cannot be reset as long as the device remains in alarm condition.
When reset is not possible a dialog box appears to explain why.
4.4.4 Several Alarms
If more than one fire alarm is active in the system, the indication is activated.
The first and last fire alarms are always displayed in the control panel.
1 Scroll through the different fire alarms with the key or the / arrow keys.
2 Mute and reset as above. For detailed instructions, see Mute a
Fire Alarm, page 21 and Reset a Fire Alarm, page 22.
4.4.5 Type of Fire Alarms from Conventional Zones
The fire detection system will display whether it was a single detector or a manual call point/multiple detectors that generated the fire alarm. If two or more detectors are activated in the same zone, the fire alarm will be presented as a manual call point/multiple detectors.
4.5 Fault Alarm
4.5.1 Information Displayed when “Fault” is Flashing
WARNING!
In case of a fault alarm use the information viewed on the display to verify and reset the fault.
Use the list of fault codes in the manual for more information about cause and remedy.
If the problem remains take the appropriate actions to restore the functionality of the fire detection system.
WARNING!
If an internal hardware or software fault has occurred it has to be restored as prompt as possible in order to secure the functionality of the complete fire detection system.
The detection of a dangerous fault shall result in either:
• a specified action to achieve or maintain a safe state; or
• the repair of the faulty system within the mean repair time (MRT). During this time the continuing safety shall be ensured by additional measures and constraints. The safety integrity provided by these measures and constraints shall be at least equal to the safety integrity provided by the FDS in the absence of any faults.
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 23
The following sections describe the information that is displayed when a fault occurs, and how to mute and reset a fault.
Figure 9. A fault is detected in the system.
The following information is displayed in the Control Panel:
• Number of detected fault(s)
• Type of fault
• Identification of the faulty loop unit or module
• Supplementary text for the faulty loop unit or module (defined in system configuration)
Press for more details:
• Time when the fault occurred
• Date when the fault occurred
• Supplementary text about the location of the fault (defined in system configuration)
4.5.2 Mute a Fault
1 Press to silence internal buzzer and mute all faults in the list.
2 Press for more details.
4.5.3 Reset a Fault
1 Press to reset the current fault alarm. NOTE!
If the cause of the fault alarm remains, the alarm cannot be reset. Check the fault code in the Fault Code List to solve the problem.
24 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
4.5.4 Reset a Fault from the Fault List
All faults in the system are shown in the fault list.
1 Go to the fault list under: Menu » 1Fault Alarms » 1 Fault List 2 Choose the fault in the fault list and then press to reset the fault alarm.
NOTE!
If the cause of the fault alarm remains, the alarm cannot be reset. Check the problem, solve it, and reset the fault.
4.5.5 Reset All Faults
1 Go to: Menu » 1 Fault Alarms » 3 Reset All Faults 2 Press The system will make an attempt to reset all faults.
4.5.6 Fault Messages
WARNING!
In case of a fault alarm use the information viewed on the display to verify and reset the fault.
If the problem remains take the appropriate actions to restore the functionality of the fire detection system.
The control panel displays a fault with information about where in the system the fault occurred and a short description of that fault.
Hint!
See the Fault Code list for further information about cause and remedy.
The fault message is also added to the fault list found under: 1 Fault Alarms » 1 Fault List.
4.5.7 Warnings
NOTE!
The user shall monitor and act on warning messages according to the presented information about the state of the system. (Warnings are not as serious as faults and only of informative nature.)
• Perform suitable maintenance if needed.
The warnings priority level is lower than the ordinary fault alarm level.
The warning is also added to the Warning list found under: Menu » 1 Fault Alarms » 2 Warnings.
A warning will remain in the Warnings list until the fault condition is under the level for warnings.
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 25
4.6 Disablements
4.6.1 About Disablements
WARNING!
To secure the functionality of the fire detection system only authorised persons should be given access to disablement privileges in the system.
It is possible to disable different devices attached to the system, such as detectors, manual call points, alarm devices, external control devices, and loops.
The available disablements (permanent, timer, clock and periodic) are described in the next chapter.
All disablements are presented in a disablement list.
NOTE!
The yellow Disablements indicator is lit on the control panel when at least one disablement is activated in the system and remains lit until all disablements are reconnected.
To perform a disablement you must enter access level 2B or higher.
DANGER!
When a fire detector or zone is disabled, the fire detection system will not be able to detect any occurring fire in that area. It is therefore important that disablements are minimized in terms of quantity of disabled units and duration of time.
Hint!
If dual detectors heat/smoke are installed, it is possible to disable only the smoke detection part of the detector and keep the heat detecting part active or vice versa.
4.6.2 Available Types of Disablements
1 Permanent disablement 2 Timer disablement 3 Clock disablement 4 Periodic disablement
There are four different types of disablements available.
Permanent disablement The device is permanently disabled until it is manually enabled.
NOTE!
It is possible to limit the disablement time by defining a maximum disablement time in the configuration program.
Timer disablement Disablement is instantaneous and lasts for the time period entered (hh:mm).
Maximum disablement time is 23 hours 59 minutes. Maximum disablement time can be limited depending on rules and regulations.
26 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
Clock disablement Enter a reconnection time. Disablement is instantaneous and the reconnection will take place next time the entered time occurs. The maximum disablement time is 23 hours 59 minutes.
Take the time entered under consideration on vehicles/trains/ships going through different time zones. If the system time is not synchronized with the vehicle/train/ship's central time, adjust the time manually or connect the system to a central clock via the serial interface.
Periodic disablement A disablement for a certain time period during certain days of the week. Example:
Disable zone 1 each Tuesday and Friday between 7.00 - 17.00.
Take the time entered under consideration on vehicles/trains/ships going through different time zones. If the system time is not synchronized with the vehicle/train/ship's central time, adjust the time manually or connect the system to a central clock via the serial interface.
4.6.3 Acknowledgement of a New Disablement
Once a new disablement is correctly entered, an acknowledgement is presented on the control panel. The Disablements key indicates with steady yellow light, use it to activate the Disablements list.
The new disablement is also added in the disablements list under: Menu » 3 Disablements » 2 Disablement list
4.6.4 Disabling Zones
(Access level 2B or higher)
Disabling a Conventional Zone
1 Select Menu » 3 Disablements » 1 New disablement » 1 Zones 2 Choose Zone (Zone number) 3 Choose disablement type (Permanent, Timer, Clock or Periodic) 4 Enter time (if Timer, Clock or Periodic was chosen in the previous step)
Disabling an Addressable Zone
1 Select Menu » 3 Disablements » 1 New disablement » 1 Zones 2 Choose Zone (Zone number) 3 Choose detector type (Smoke detectors, All detectors, Heat detectors, Flame detectors, or Manual Call Points) 4 Choose disablement type (Permanent, Timer, Clock or Periodic) 5 Enter time (if Timer, Clock or Periodic was chosen in the previous step)
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 27
4.6.5 Disabling Addressable Detectors & Manual Call
Points (Access level 2B or higher)
NOTE!
Disabling of individual detectors is only possible on addressable loops.
1 Select Menu » 3 Disablements » 1 New Disablement » 2 Detectors & Manual Call Points
2 Choose zone (Zone number) 3 Choose unit type (Smoke detectors, All detectors, Heat detectors, Flame detectors, or
Manual Call Points)
NOTE!
For some systems all units, regardless of their type, will be presented even though one type is chosen in the disablement menu.
4 Choose unit address or interval (address number(s)) 5 Choose disablement type (Permanent, Timer, Clock, or Periodic) 6 Enter time (if Timer, Clock, or Periodic was chosen in the previous step)
Hint!
It is also possible to disable detectors from the Fire List.
4.6.6 Disabling Alarm Devices
(Access level 2B or higher)
Examples of alarm devices are bells, buzzers and flash lights.
Disablements of alarm devices:
1 Select Menu » 3 Disablements » 1 New Disablement » 4 Alarm Device (Bells etc.)
4.6.7 Old Disablements
Use this menu to reactivate previously performed disablements.
NOTE!
Only permanent disablements can be reactivated.
1 Select Menu » 3 Disablements » 4 List old disablements 2 Mark the appropriate old disablement in the list and and press “0” to reactivate the disablement.
4.6.8 Alarm Delay
An alarm delay function will delay the activation of alarm devices in case of a fire alarm. The delay time is programmable.
28 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
The alarm delay may be disabled which means that there will be no delay between the fire alarm and the activation of the alarm device outputs.
1 Select Menu » 3 Disablements » 6 Alarm Delay 2 Select central.
3 Select type of delay (Permanent, Timer, Clock or Periodic) See Available Types of Disablements, page 25 for explanation.
Set delay time (Access level 3 or higher):
NOTE!
Delay time is only possible to set if no time is set in the configuration program.
1 Select Menu » 5 Settings » 5 Alarm Delay Times » 1 Alarm Delay Time 1 (mute)
Alarm Delay Time 2 (reset) is only used for special applications.
4.6.9 Disabling External Control Groups
(Access level 2B or higher)
Examples of external control groups are fans or outputs controlling fire doors.
1 Select Menu » 3 Disablements » 1 New Disablement » 3 External Controls » 1 External Controls
2 Select an output category to be disabled. All groups = all categories of doors, ventilation, etc.
3 Select System or Central. Press OK. It is possible to disable all the external controls in the entire system or in individual centrals.
4 Press
4.6.10 Disabling an Alarm Transfer Output
(Access level 2B or higher)
Disablements of the alarm transfer output, used in industrial installations to alert the fire brigade in case of a fire alarm:
1 Select Menu » 3 Disablements » 1 New Disablement » 3 External Controls » 2 Alarm Transfer
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 29
4.7 Reconnecting
4.7.1 Reconnecting Disabled Items
All disablements in the system are presented in the disablement list. Any reconnection is made from this list.
1 Select Menu » 3 Disablements » 2 List disablements 2 Choose the disablement you want to cancel.
3 Press
4.7.2 Reconnecting Periodic Disablements
Periodic disablements in the system are presented in the periodic disablement list.
Reconnecting is made from this list:
1 Select Menu » 3 Disablements » 3 List periodic disablements 2 Choose the periodic disblement you want to cancel.
3 Press
4.7.3 Reconnecting Disabled Alarm Delays
All disabled alarm delays in the system are presented in the alarm delays list. Any reconnection is made from this list.
1 Select Menu » 3 Disablements » 7 List Alarm Delays 2 Choose the disablement you want to cancel.
3 Press
4.7.4 Remove All Disablements
This menu removes all active disablements presented in the Disablement list.
1 Select Menu » 3 Disablements » 5 Remove all disablements 2 Confirm with OK to remove (reset) all active disablements in the system.
NOTE!
Periodic disablements are not permanently removed.
Only the periodic disablement's active period is removed.
4.8 Service Menu
4.8.1 About the Service Menu
(Access level 2 for basic functions, but access level 4 is needed to perform advanced service options.)
30 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
The Service menu is used for configuring the system in the commissioning phase, as well as for troubleshooting and making updates when the system is in operation.
The menu has functions for loading and saving information from/to an approved USB memory stick (available from an authorised dealer).
The Service menu displays a list of the 9 service menu alternatives, as shown below.
1 System Details 2 Centrals 3 Modules 4 Zones 5 Loops 6 Configuration 7 Firmware 8 System Log 9 I/O lists
Please refer to the Service and Maintenance manual for detailed information about the Service menu.
4.8.2 Save the System Log to a USB Memory Stick
If you want to check the information saved in the system log you can download it from the central unit. The system log files contain information generated for evaluating the system, such as lists of system components, system software and key events.
Table 12. The following lists are included in the log
Centrals list Key events Disablement list Modules list Fault list Periodic disablement list Fire alarm list Pre alarm list History list Warning list
The system log files can be downloaded using an approved USB memory stick (available from an authorised dealer).
CAUTION!
Do not remove the USB memory stick until the download is finished.
1 Connect the USB memory stick to the USB port on the Control M 4.3 panel.
2 Choose Menu » 6 Service Menu » 8 System Log » 1 Save syslog.
3 Press OK to save the systems log files to the USB memory stick.
4 The system will now download the system log files. Wait until this process is complete!
5 Disconnect the USB memory stick and copy the system log files to a PC.
File name example: sysLog_no_YYYY-MM-DD-xxxxxx
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 31
4.8.3 How to report a fault
In case it is not possible to troubleshoot and solve a specific problem, please follow these guidelines when contacting an authorized service office.
• Describe the fault symptom, be specific
• Describe how the fault situation can be generated
• Attach a system log file (instructions for download from the Fire detection system can be found in section Save the System Log to a USB Memory Stick, page 30)
• Attach the configuration file (instructions for download from the Fire detection system can be found in the Service & Maintenance manual or in the Configuration manual)
• Attach the backbone log if applicable
• Add your contact information
32 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
User Guide 5 Testing
5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD 33
5 Testing
5.1 About Testing
CAUTION!
Perform visual inspection of all fire detectors as often as needed to find detectors which have deliberately been covered (vandalised). Because a covered detector will not be able to detect a fire and the fire detection system can't detect if a detector has been covered.
CAUTION!
Check for contaminated detectors. Use the Control panel menu system to display a list showing in which condition the detectors are.
For additional information about testing, please refer to the Service and Maintenance Manual.
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be extra-long after a new installation, commissioning or major maintenance work (depending on the configuration of the data definition file).
NOTE!
A warning will be displayed on the menu screen as long as the system is not running Cause/Effect, which is the two first minutes after the system has been powered up
5.2 Test mode overview
The system has a special test mode function which makes the testing easier.
When a zone is in test mode:
• External alarm devices and controls are by default not activated in case of a fire.
Hint!
This functionality can be turned off if controls are to be tested while the tested zone is in test mode.
(Menu » 3 Disablements » 1 New Disablement » 3 External Controls)
• The alarm level is lowered to give a quick response to detector test equipment.
• LED indicators on loop units are blinking.
• Each tested loop unit will indicate activation with a steady LED indicator.
• Key events (as well as information of system components and system software) will be stored in the system log which can be saved on a USB memory stick. If a printer is connected to the system, alarms will automatically be printed as a result of the tested units.
5 Testing User Guide
34 5100332-01_Salwico Cargo Addressable_User Guide_M_EN_2021_AD
• The units in alarm are automatically reset when the heat or smoke concentration is under the alarm level, or when the test key is removed from the manual call point.
NOTE!
Fire alarm from zones not in test mode will be handled normally by the fire detection system.
The zone in test mode will automatically return to normal operation after two hours.
5.3 Testing a Fire-detecting Zone
The functions of the FDS shall be tested at the interval stated in each application specific documentation.
CAUTION!
During system start-up the smoke detectors perform a 15 minutes calibration according to the level of particles in the air. No tests should be done during this period.
1 Put the zone into test mode under: Menu » 3 Disablements » 1 New disablement » 5 Test Mode .
Access level 2B is required.
2 Select a zone and confirm by pressing the key.
The Disablements, Test, and Zone/Unit indicators light to confirm that they are in test mode.
Each detector, manual call point and input in this fire zone can be tested during the next two hours. Refer to Test mode overview, page 33 for further information about a zone in test mode.
All alarms are listed under: Menu » 7 History » 1 Fire History List .
To return the tested zone to its normal condition, refer to Reset Test Mode, page 35.
CAUTION!
If…