Copy of 5100195_Control-Repeater Panel M 4.3_M_EN_2018_H.pdf

PDF 2 MB Posted

Attached to
FY27 NOAA Ship Gordon Gunter Drydock REFERENCES Federal contract opportunity
Solicitation number
1305M226Q0144REF
Issued by
Department of Commerce National Oceanic and Atmospheric Administration

About this file

This is a technical data sheet for the Control/Repeater Panel M 4.3, a control panel manufactured by Consilium designed for marine and offshore fire detection and alarm systems across multiple platforms including cargo vessels, cruise ships, LNG carriers, offshore installations, ro-pax ferries, workboats, yachts, and naval vessels.

The Control/Repeater Panel M 4.3 features a 4.3-inch graphical color display (480×272 pixels TFT) for system management and supervision, operating at 19-30 VDC with normal current consumption of 100 mA at 24V and maximum consumption of 270 mA. The panel is rated IP22 for ingress protection and operates across a temperature range of -5°C to +55°C, weighing 1,250 grams. Connectivity includes 10/100 Mbit Ethernet with autosense, Backbone Bus Interface, RS-422/RS-485 interface, RS-232/RS-485 interface, three USB interfaces (one Host USB 1.1 front, one Host USB 1.1 back, one Device USB 1.1 back), two configurable powered I/Os rated at 24 VDC 5-70 mA input or 24 VDC maximum 70 mA output, and two programmable relay outputs rated at maximum 30 VDC 500 mA. Cable terminals accommodate 2.5 mm² wire, and optional SD Memory is available. The panel is certified to EN 54-2 (1999/A1:2006) and EN 60945, with RoHS compliance. Five part number variants are available for different vessel types (Cargo, Ro/Pax, Workboat, Yacht, and Cruise), and the unit supports both Controller Mode and Managed Mode operation with configurable DIP switches for module addressing and central system configuration. Installation requires connection to Terminal M via 20-pin and 10-pin flat cable connectors, with additional connections for door switches, Ethernet, USB expansion boards, and external buzzers.

View the file

Other files for this federal contract opportunity

Other files attached to FY27 NOAA Ship Gordon Gunter Drydock REFERENCES, newest first.
File Type Posted
SE_85_085-6233567_RevH_Sht2 OF 2_N_A_GENERAL ARRANGEMENT FORECASTLE DECK AND ABOVE SHT 2.pdf PDF
TAGO_NONE_150-6233562_RevK_Sht1 THRU 9_N_A_MODULE NO. 9A STRL ASSY.pdf PDF
T9555-BC-MMO-010_0_0.PDF PDF
GU_NONE_NONE_RevNONE_Sht1THRU2_N_A_GENERALARRANGEMENTMAINDECK_BELOW.pdf PDF
Copy of 110-6233550.pdf PDF
NOAA Gangway Test.docx DOCX document
AMC-505-1B Valve Overhaul and Test 4 pages.pdf PDF
s0700-3 Dry Dock Certification-1.pdf PDF
8KatoGenerator.pdf PDF
SE_NONE_NONE_RevNONE_Sht1 OF 1_N_A_OS-342-6233813-1.pdf PDF
GU_NONE_GU-KA-568-01_RevNONE_Sht1 THRU 76_N_A_GU-KA-568-01 TUNNEL THRUSTER MODEL S-300-L SERIAL NOS. 86.000.435 AND 86.000.436.pdf PDF
Profile References Modules and Erection Sequence.docx DOCX document
90RMC050-D-610_REV- Carrier Operation and Maintenance Manual.pdf PDF
mk-line-2nd-1-26.pdf PDF
524-6233814 (1).pdf PDF
528-6233824.pdf PDF
6233762_G (1).PDF PDF
620-6233548.pdf PDF
GU_NONE_NONE_RevNONE_Sht1 THRU 2_N_A_GENERAL ARRANGEMENT MAIN DECK _ BELOW.pdf PDF
529-001 Revision A (1).pdf PDF
EconoAir General Arrangement Drawing.pdf PDF
E100 Rev -1 Gunter.pdf PDF
DD GU Reference 1 MOC-300-3_General_Requirements_for_Electrical_Electronic_Items_SEP_2000.pdf PDF
AMC-573-1C Weight Handling Gear Testing.pdf PDF
AMC-583-1B General Requirements for Liferaft Inspections.pdf PDF
GU-436-015 37442.03.01 - Connection drawings.pdf PDF
NOAA Standard Specification 0002.0.docx.pdf PDF
NOAA_Weight_Reporting_Spreadsheet.xlsx XLSX spreadsheet
NOAA Standard Specification 0863.0.docx.pdf PDF
SSPC-SP-1-Solvent-Wipe.pdf PDF
233-3 Main Engine Overhaul.pdf PDF
Steyr Motor Marine Engines SE SERIES 4 Cylinders 6 Cylinders Operation Maintenance and Warranty Manual P_N 707245 1st Edition February 2021..pdf PDF
Zodiac Hurricane H638 SOLAS Manual MB10247 Rev 11-8-2016.pdf PDF
GU-436-011Rev - Fire Detection Install_123880286.pdf PDF
529-6233819.pdf PDF
620-6233557.pdf PDF
NOAA Ships General Arrangement with camera locations (1).pdf PDF
GU_NONE_T0965-LP-109-1010_Rev1_Sht1 THRU 158_N_A_GU-KA-437-04 TANK LEVEL INDICATING TLI SYSTEM TYPE NO. 36000.pdf PDF
GU-555-001_-.pdf PDF
SFLC-Std-Spec-6310-(2020) - Requirements for Preservations of Ships Structures.pdf PDF
593-6233812.pdf PDF
1005-01 - NOAA Ship Health Plan (public).docx DOCX document
111-001.pdf PDF
NOAA Standard Specification 0000.1.docx.pdf PDF
437-6233672.pdf PDF
Drager Aerotest Navy Drager Tubes Pamphlet 9046651.pdf PDF
Gordon Gunter FY21 Cable Testing.xlsx XLSX spreadsheet
NOAA Ship Gordon Gunter Drawing Index List.xlsx XLSX spreadsheet
SSPC-SP-11-Power-Tool-To-Bare-Metal.pdf PDF
2 Bottle Vertical Inline Rack - UN_ISO Cylinders.pdf PDF
Show all 50

FY27 NOAA Ship Gordon Gunter Drydock REFERENCES has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1(5) DATA SHEET

The specifications described herein are subject to change without notice. Data sheet no. 5100195_Control-Repeater Panel M 4.3_M_EN_2018_H www.consilium.se

Control/Repeater

Panel M 4.3 Part no. 5100195

System: Salwico Cargo, Salwico Cruise, Salwico LNG,Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish

General Description The Control/Repeater Panel M 4.3 is a control panel with a 4.3" graphical colour display used to manage and supervise a system. Control/Repeater Panel M 4.3 mounts on any flat surface independently from a fire alarm cabinet.

Control/Repeater Panel M 4.3 is equipped with communication buses for connecting to the system, and it provides the following features:

• A backlit 4.3" graphical colour display

• Alarm buzzer

• LED status indicators

• Backbone Bus Interface

• Ethernet connection

• RS-422/RS-485 interface

• RS-232/RS-485 interface

• Three USB interfaces

• Two configurable powered I/Os

• Two programmable relay outputs

Refer to the User Guide for more information on operating Control/Repeater M 4.3.

For details on assembling a system and definitions of common system terms, refer to the Installation Manual.

Part No.

Control/Repeater M 4.3 Cargo 5100195-20A

Control/Repeater M 4.3 Ro/Pax 5100195-30A

Control/Repeater M 4.3 Workboat 5100195-40A

Control/Repeater M 4.3 Yacht 5100195-50A

Control/Repeater M 4.3 Cruise 5100195-80A

Data Operating voltage range

19-30 VDC

Current consumption (at 24V)

Normal 100 mA Max. 270 mA

Ingress protection IP22

Operating temperature range

-5°C to +55°C

Weight 1250g

Display 4.3", 480×272 pixels, TFT

Ethernet 10/100 Mbit, autosense

USB Host USB 1.1 1 in front, 1 on back

USB Device USB 1.1 1 on back

Relays rating Max. 30 VDC, 500 mA

I/O 70 (as input) 24 VDC 5-70 mA

I/O 70 (as output) 24 VDC Max. 70 mA

Cable terminals 2.5 mm²

SD Memory (Optional)

Certified according to ROHS

EN 54-2 (1999/A1:2006)

EN 60945

2531/yy yy = year of production

Indicators Control/Repeater Panel M 4.3 indicators display system status. Refer to the User Guide for more information.

DATA SHEET 2(5)

The specifications described herein are subject to change without notice. Data sheet no. 5100195_Control-Repeater Panel M 4.3_M_EN_2018_H www.consilium.se

Hot-Swap Replacement of the Module Replace this module following these steps:

1. Remove all cable connections form the module.

2. Address the Module DIP-Switch settings using old module as a guide.

3. Move the Micro SD memory from the old module, if installed, to new module.

4. Plug in all cable connections back.

Address Switch This switch (see SW2 in figure Connection board) identifies modules in the system and sets the function.

Control modules can serve as Bus Masters, i.e., operate in Controller Mode or in Managed Mode, for example repeaters and protocol converters. Address 1 and 2 are dedicated for control modules in Controller Mode. One control module per central shall be set in Controller Mode. If the system shall be reduntant it is required to have a second control module, also set in Controller Mode. Modes for Managed and Controller are set with DIP switches as described in the following table:

Managed Mode Controller Mode

DIP 8 Controller Mode (off) Controller Mode (on)

DIP 7 Module Address (3-125)

Spare

DIP 6 Master (on/off)

DIP 5 Central Address (1-30)

DIP 4

DIP 3

DIP 2

DIP 1

Control Modules have two different modes of operation, as determined by their DIP settings (normally pre-set from factory):

Controller Mode

Single Central System:

Central 1 Primary (automatically module address 1)

Central 1 Secondary (optional) (automatically module address 2)

Multi Central System:

Central 1 Primary (automatically module address 1)

3(5) DATA SHEET

The specifications described herein are subject to change without notice. Data sheet no. 5100195_Control-Repeater Panel M 4.3_M_EN_2018_H www.consilium.se

Central 1 Secondary (optional) (automatically module address 2)

Central 30 Primary (automatically module address 1)

Central 30 Secondary (optional) (automatically module address 2)

Managed Mode

Module Address 3-125

Connections Control/Repeater Panel M 4.3 mounts outside of the central. Using ribbon cables, connect the Control/Repeater Panel M 4.3 to Terminal M (pre-fitted inside the Control/Repeater Panel M 4.3 casing, see Module Dimensions (mm)). All Control/Repeater Panel M 4.3 connections are made on the Connection board, located at the back of the front panel. See figure Connection board.

Figure 1. Connection board

Connector no. Function Description

P4 Connection to Terminal M 20-pol. Flat Cable *

P5 Connection to Terminal M 10-pol. Flat Cable *

P6 Door Switch

P7 Ethernet

P8 Type A/ Host USB

P9 USB Expansion Board

P10 Type B/ Device USB

P11 External Buzzer (24V)

* See illustration below for connection to Terminal M.

DATA SHEET 4(5)

The specifications described herein are subject to change without notice. Data sheet no. 5100195_Control-Repeater Panel M 4.3_M_EN_2018_H www.consilium.se

Figure 2. Terminal M

* Do not connect to this terminal!

** Terminal 23 is signal ground for channel 4, marked "GNDB" on PCB.

*** Terminal 38 is signal ground for channel 3, marked "GNDA" on PCB.

RS485 Termination of Serial Interface 3 & 4 For RS485 termination of channel 3 and channel 4 the built-in resistor (120 ohm) can be activated with the RS485 DIP switch located on the Connection board (see figure in section Connections).

For recommendations and examples on RS485 termination, refer to the Installation Manual.

Table 1. DIP switch for RS485 termination

DIP

Switch No.

Description ON OFF

1 Channel 3 Active Deactivated

2 Channel 4 Active Deactivated

5(5) DATA SHEET

The specifications described herein are subject to change without notice. Data sheet no. 5100195_Control-Repeater Panel M 4.3_M_EN_2018_H www.consilium.se

Module Dimensions (mm)

Mounting Dimensions (mm)

File details come from the government source that posted it. Updated .