This document provides details of a federal contract opportunity for replacement of steam pipes at the Edward Hines, Jr. VA Hospital in Hines, Illinois. The solicitation number is 36C25223R0026 and seeks to replace existing steam pipes between Vaults 9 and 7 and between Vault 9 and Pit 5 on the hospital campus. The work includes replacing sump pump controls, constructing new concrete box conduit steam tunnels and pipe racks, and must be completed within 730 calendar days of the notice to proceed. The project is set aside exclusively for verified Service-Disabled Veteran-Owned Small Businesses and falls under NAICS code 238220 with a small business size limit of $19.5 million. The solicitation and specifications will be posted to SAM.gov on May 22, 2023 and a pre-bid site visit will be held thereafter. The estimated value of construction is between $10-20 million.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CAST-IN-PLACE CONCRETE
STRUCTURAL STEEL
FOUNDATIONS
STRUCTURAL STEEL
CAST-IN-PLACE CONCRETE
MATERIALS
DESIGN CODE
MASONRY
GENERAL STRUCTURAL NOTESABBREVIATIONS
SUPPLEMENTAL NOTES
MAIN LATERAL FORCE RESISTING SYSTEM
CONCRETE MASONRY
STEEL REINFORCING
DESIGN LOADS
CLEAR COVER REQUIREMENTS:
MASONRY STRENGTH NOTES:
SIKA, HILTI, EPCON
F'c=3000 PSI AT 28 DAYS
ASTM A706 (GRADE 60)
ASTM A775 OR ASTM A934
ASTM F1554 (Fy=36 KSI)
ASTM A500, GRADE B (Fy=46 KSI) ASTM A36 (Fy=36 KSI)
F'c = 3500 PSI AT 28 DAYS (CONCRETE ON METAL DECK)
HEADED STUDS/SHEAR CONNECTORS
ADHESIVE ANCHORS/GROUT
ASTM A108
RECTANGULAR HSS
WELDED WIRE FABRIC
EPOXY-COATED REINFORCING BARS
DEFORMED BAR ANCHORS
WELDED BARS AND ANCHORS
REINFORCING BARS
MASONRY GROUT
CONCRETE MASONRY UNITS
PLATES AND SHAPES OTHER THAN W
F'c = 4000 PSI AT 28 DAYS (ALL OTHER CONCRETE)
ANCHOR RODS
BOLTS ASTM A325/ASTM A490
ASTM A185
ASTM A496
ASTM C90 TYPE "N-1"
ASTM A615 (GRADE 60)
STRUCTURE DESIGN MANUAL FOR ENERGY CENTER PROJECTS (LATEST INTERNATIONAL
BUILDING CODE W/ DEPARTMENT OF VETERANS AFFAIRS AMENDMENTS).
APPLY UNLESS NOTED OTHERWISE ON STRUCTURAL DRAWINGS OR SPECIFICATIONS.
CONCRETE
ON
METAL DECK
SLABS ON GRADE
WALLS
BEAMS, COLUMNS
WALLS, SLABS
FORMED SURFACES NOT IN CONTACT WITH EARTH OR
EXPOSED TO WEATHER:
#5 OR SMALLER
#6 OR LARGER
FORMED SURFACES IN CONTACT WITH EARTH OR
EXPOSED TO WEATHER:
SURFACES CAST AGAINST EARTH
1" 1 1/2"
1 1/2" 2"
3"
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
W
V
U
S
R
T
ANCHOR BOLT
ADDITIONAL
ADHESIVE
ADJUSTABLE
ADJACENT
ANCHOR(AGE)
ARCHITECT(URAL)
BOTTOM OF FOOTING ELEVATION
BEAM
BOTTOM
BRIDGING
BEARING
AMERICAN STANDARD CHANNEL
CAST IN PLACE
CONTROL/CONSTRUCTION JOINT
CENTER LINE
CLEAR(ANCE)
COLUMN
COMPOSITE
CONCRETE
CONTINU(E) (OUS) (ATION)
DEFORMED BAR ANCHOR
DECK BEARING ELEVATION
DETAIL
DIAMETER
DEAD LOAD
DITTO
DRAWING(S)
DOWEL (REBAR)
EACH
EACH FACE
EXPANSION JOINT (W/O COVER
ASSEMBLY)
ELEVATION
EQUAL
EACH WAY
EXISTING
FLOOR DRAIN
FOUNDATION
FINISH FLOOR ELEVATION
FLANGE
FOOTING
AB
ADDL
ADH
ADJ
ADJC
ANC
ARCH
BFE
BM
BOT
BRDG
BRG
C
CIP
CJ
CL
CLR
COL
COMP
CONC
CONT
DBA
DBE
DET
DIA
DL
DO
DWG(S)
DWL
EA
EF
EJ
EL
EQ
EW
EXG
FD
FDN
FFE
FLG
FTG
GAUGE
GALVANIZED
GLUE LAMINATED BEAM
GRADE
HORIZONTAL
INSIDE FACE
INFORMATION
JOIST BEARING ELEVATION
JOIST
JOINT
KIP (1000 POUNDS)
POUND
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL(LY)
LIGHTWEIGHT
LINTEL
MASONRY
MAXIMUM
MANUFACTURER
MINIMUM
NOT IN CONTRACT
NOMINAL
NEAR SIDE
NON-SHRINK GROUT
NOT TO SCALE
ON CENTER
OUTSIDE FACE
OPENING
OPPOSITE
PLATE
POUNDS PER LINEAL FOOT
PROJECT(ION) (OR)
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POST TENSION(ED) (ING)
PAINTED
GA
GALV
GLB
GR
HORIZ
IF
INFO
JBE
JST
JT
K
LB
LL
LLH
LLV
LONG
LW
LTL
MAS
MAX
MFR
MIN
NIC
NOM
NS
NSG
NTS
OC
OF
OPG
OPP
PL
PLF
PROJ
PSF
PSI
PT
PTD
ROOF DRAIN
REFER(ENCE)
REINFORC(E) (ED) (ING) (EMENT)
REQUIRED
S SHAPE
SIMILAR
SLAB ON GRADE
SPECIFICATION(S)
STANDARD
STEEL
STRUCTUR(E) (AL)
SYMMETR(Y) (ICAL)
TOP AND BOTTOM
TOP OF BEAM ELEVATION
TOP OF PILE CAP (DRILLED
PIER CAP) ELEVATION
TOP OF DECK ELEVATION
TEMPERATURE/TEMPORARY
TOP OF FOOTING ELEVATION
TOP OF JOIST ELEVATION
TOP OF LEDGE ELEVATION
TOP OF MASONRY ELEVATION
TOP OF PIER ELEVATION
TRANSVERSE
TOP OF SLAB ELEVATION
TOP OF WALL ELEVATION
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
VERIFY IN FIELD
WIND LOAD
WORK(ING) POINT
WEIGHT/STRUCTURAL TEE
WELDED WIRE FABRIC
RD
REF
REINF
REQD
S
SIM
SOG
SPEC(S)
STD
STL
STRUC
SYM
T&B
TBE
TCE
TDE
TEMP
TFE
TJE
TLE
TME
TPE
TRANSV
TSE
TWE
TYP
UNO
VERT
VIF
WL
WPT
WT
WWF
D&E DRILL AND EPOXY GROUT
W SHAPES (AND WT CUT FROM W SHAPES) ASTM A992 (Fy=50 KSI)
ARCHITECTURALLY EXPOSEDAES
FABRICATIONS STEEL
ARCHITECTURALLY EXPOSEDAESS
STRUCTURAL STEEL
ABOVE FINISHED FLOORAFF
FS FAR SIDE/FOOTING STEP
HPT HIGH POINT
HOLLOW STRUCTURAL SECTIONHSS
L ANGLE
LOW POINTLPT
MISCELLANEOUS CHANNELMC
NORMAL WEIGHTNW
SCHEDULESCHED
SPECIALLY ROUGHENEDSRCJ
CONSTRUCTION JOINT
W W SHAPE
COMPLETE JOINT PENETRATIONCJP
1.5SEISMIC IMPORTANCE FACTOR
SEISMIC DESIGN CATEGORY (SDC)
BASE SHEAR 181 KIPS
C
SPECTRAL RESPONSE COEFFICIENT, Sd1 SPECTRAL RESPONSE COEFFICIENT, Sds
INTERNAL PRESSURE COEFFICIENT
WIND IMPORTANCE FACTOR
BASIC WIND SPEED (3 SECOND GUST)
SNOW EXPOSURE FACTOR, Ce
(LIVE LOAD REDUCTION PER IBC 1607.9)
NOTES:
1. 400 PSF TYPICAL, EXCEPT WHERE NOTED ON PLAN
2. SEE PLANS FOR EXTENTS OF FLOOR LIVE LOADS
SITE CLASS
SPECTRAL RESPONSE ACCELERATION, Ss
SEISMIC DESIGN DATA
MEAN ROOF HEIGHT
WIND EXPOSURE CATEGORY
WIND LOAD
THERMAL FACTOR AT BUILDINGS, Ct
SNOW IMPORTANCE FACTOR
FLAT ROOF SNOW LOAD, Pf
SNOW LOAD
GROUND SNOW LOAD, Pg
MECHANICAL ROOM
CATWALKS/ EQUIPMENT PLATFORMS
AND STAIRS ACCESSING THEM
STAIRS AND EXITS
LOBBIES AND 1ST FLOOR CORRIDORS
OFFICES, LOCKER ROOMS
FLOOR LOCATION LIVE
C
0.070 0.148
±0.18
35.33 FT
B 1.15
90 MPH
1.0 1.0 1.2
24 PSF
25 PSF
NOTE 1 NO NA
40 PSF NO NA
100 PSF NO NA
100 PSF NO NA
100 PSF NO NA
PARTITIONSREDUCEDLOAD
FLOOR LIVE LOADS
MASONRY MORTAR ASTM C270 (TYPE S UNO)
CMU CONCRETE MASONRY UNIT
CA WATERSTOP
VR VAPOR RETARDER
FOUNDATION DESIGN PARAMETERS ARE BASED ON RECOMMENDATIONS
FROM THE "GEOTECHNICAL ENGINEERING SERVICES REPORT, PROPOSED
VAULTS AND TUNNEL PROJECT, HINES VA MEDICAL
CENTER, 5000 SOUTH 5TH AVENUE, HINES, ILLINOIS" PERPARED BY
PIONEER INC., DATED NOVEMBER 3, 2022.
REFER TO THE GEOTECHNICAL REPORT FOR SOIL CLASSIFICATION 33-63-00-A
COLUMN FOOTINGS HAVE BEEN DESIGNED FOR A NET SOIL BEARING
PRESSURE OF 7000 PSF.
IF THE SOIL AT THE FOUNDATION OR SLAB-ON-GRADE ELEVATIONS
SHOWN IS OF QUESTIONABLE BEARING VALUE, THE
ARCHITECT/ENGINEER SHALL BE NOTIFIED AT ONCE FOR RESOLUTION.
ALL FOUNDATIONS SHALL BE CENTERED ON WALLS OR COLUMNS UNO.
WALLS RETAINING SOIL HAVE BEEN DESIGNED FOR AN EQUIVALENT FLUID
PRESSURE OF 99 POUNDS PER CUBIC FOOT FOR "AT REST" CONDITIONS.
THIS ASSUMES FULL HYDROSTATIC PRESSURE FROM SOIL THAT HAS BEEN
FULLY SATURATED TO GRADE LEVEL.
WHERE FILL MATERIAL IS PLACED ON BOTH SIDES OF WALLS, IT SHALL
BE PLACED IN LAYERS ALTERNATELY ON OPPOSITE SIDES TO MAINTAIN
LEVELS THAT WILL AVOID DISPLACEMENT OF, OR DAMAGE TO, THE
WALLS.
WHERE FILL MATERIAL IS PLACED ON ONE SIDE OF A WALL, THE WALL
SHALL BE ADEQUATELY SHORED AND BRACED OR THE MATERIAL SHALL
NOT BE PLACED UNTIL SUPPORTING FLOOR SLABS, INCLUDING SLABS-
ON-GRADE, HAVE BEEN POURED AND SET.
CONTINUOUS FOOTINGS SHALL BE STEPPED AT A SLOPE OF ONE
VERTICAL TO TWO HORIZONTAL.
PROTECT IN-PLACE FOUNDATIONS AND SLABS ON GRADE FROM FROST
PENETRATION UNTIL PROJECT COMPLETION.
SLOPE BETWEEN ADJACENT FOOTINGS OR EXCAVATIONS SHALL NOT
EXCEED ONE VERTICAL TO TWO HORIZONTAL. STEP FOOTINGS DOWN AS
NECESSARY TO MAINTAIN THIS SLOPE.
CODE FOR REINFORCED CONCRETE DESIGN AND CONSTRUCTION - ACI 318 LATEST EDITION
ARRANGEMENT AND BENDING OF REINFORCING STEEL SHALL BE IN
ACCORDANCE WITH ACI DETAILING MANUAL, LATEST EDITION.
REINFORCING STEEL SHALL BE NEW DEFORMED BARS.
CONCRETE COVER TO REINFORCING STEEL, UNLESS NOTED
OTHERWISE, SHALL BE AS FOLLOWS:
NON-CONTINUOUS ENDS OF TOP BARS IN BEAMS AND SLABS
SHALL TERMINATE IN A STANDARD HOOK, UNLESS DETAILED
OTHERWISE. BAR LENGTHS INDICATED DO NOT INCLUDE
HOOKS WHERE THEY OCCUR.
WHERE REINFORCING BARS ARE SHOWN CONTINUOUS, PROVIDE
CLASS B TENSION LAP SPLICES (12" MINIMUM) EXCEPT WHERE
NOTED OR DETAILED OTHERWISE. LAP WWF WIRE SPACING
PLUS 2" (6" MINIMUM).
DETAIL AND PROVIDE SUITABLE WIRE SPACERS, CHAIRS, TIES, ETC.,
FOR SUPPORTING REINFORCING STEEL IN THE PROPER POSITION
WHILE PLACING CONCRETE.
ALL CHAIRS SUPPORTED BY GRADE SHALL INCLUDE SAND PLATES.
BAR SUPPORTS WHICH COME IN CONTACT WITH EXPOSED SURFACES
SHALL HAVE PLASTIC OR RUBBER TIPS OR BE STAINLESS STEEL.
PROVIDE DOWELS OF SAME SIZE AND SPACING AS VERTICAL
WALL OR COLUMN PIER REINFORCING AT THE FOUNDATION,
UNLESS NOTED OTHERWISE. DOWELS SHALL BE TIED IN PLACE
PRIOR TO CONCRETE PLACEMENT.
PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH
HORIZONTAL BARS AT CORNERS AND INTERSECTIONS OF
WALLS, BEAMS, AND FOOTINGS.
CONTINUOUS TOP BARS IN WALLS, BEAMS AND GRADE BEAMS
SHALL BE SPLICED AT MIDSPAN AND BOTTOM BARS OVER
SUPPORTS, UNLESS NOTED OTHERWISE.
DRAWINGS SHOWING LOCATION OF CONSTRUCTION AND
CONTROL JOINTS AND PLACING SEQUENCE SHALL BE
SUBMITTED FOR ENGINEER'S REVIEW PRIOR TO PREPARATION
OF THE REINFORCING STEEL SHOP DRAWINGS.
HORIZONTAL CONSTRUCTION JOINTS ARE NOT PERMITTED IN
CONCRETE MEMBERS UNLESS SHOWN ON THE DRAWINGS OR
APPROVED IN ADVANCE. VERTICAL CONSTRUCTION JOINTS OR
BULKHEADS SHALL BE MADE AT MIDSPAN OR POINTS OF
MINIMUM SHEAR.
SIZE OF CONCRETE POURS BETWEEN CONSTRUCTION JOINTS
SHALL BE LIMITED TO:
MAXIMUM LENGTH 100 FT WITH
INTERMEDIATE CONTROL JOINTS AT
APPROXIMATELY 30 FT. DO NOT
LOCATE WITHIN 5 FT OF A CORNER OR
COLUMN. COORDINATE LOCATIONS
WITH VENEER JOINTS.
3600 SQUARE FT WITH MAXIMUM
DIMENSION OF 60 FT; PLACE IN LANE
OR STRIP FASHION WITH
INTERMEDIATE CONTROL JOINTS AT
APPROXIMATELY 20 FT OR 15 FT FOR
EXPOSED CONCRETE SURFACES.
COORDINATE LOCATIONS WITH
FLOOR FINISHES.
10000 SQUARE FT WITH MAXIMUM DIMENSION
OF 100 FT.
VERIFY LOCATION OF OPENINGS SHOWN THROUGH CONCRETE
SLABS OR WALLS AND COORDINATE ANY ADDITIONAL
REQUIRED OPENINGS WITH OTHER TRADES AND THE
ARCHITECT/ENGINEER.
CONCRETE EXPOSED TO FREEZING AND THAWING SHALL
CONTAIN 6% (PLUS OR MINUS 1.5%) ENTRAINED AIR.
THICKEN SLABS ON GRADE BELOW NON-BEARING INTERIOR
MASONRY WALLS.
ALUMINUM CONDUIT OR PIPING MAY NOT BE EMBEDDED IN ANY CONCRETE.
CALCIUM CHLORIDE IS NOT PERMITTED AS A CONCRETE ADDITIVE.
PROVIDE REINFORCING BARS AT LOCATIONS INDICATED ON THE
DRAWINGS. LAP 48 BAR DIAMETERS AT SPLICES UNLESS NOTED
OTHERWISE.
GROUT CORES WITH MASONRY GROUT IN 5'-0" MAXIMUM LIFTS. GROUT
LIFT SHALL TERMINATE 1 1/2" BELOW BED JOINT IN WALL. LIFTS SHALL
BE CONSOLIDATED USING MECHANICAL VIBRATION.
PROVIDE BAR POSITIONERS AT OR NEAR TOP AND BOTTOM OF LIFT TO
MAINTAIN BAR POSITION WHILE GROUTING. BARS MUST BE IN PLACE
PRIOR TO GROUTING. PLACEMENT OF STEEL REINFORCEMENT INTO
WET GROUT WILL NOT BE PERMITTED.
PROVIDE (2) #5 VERTICAL BELOW BEAM AND LINTEL BEARINGS AND
GROUT CORE FULL HEIGHT. BEARING DISTANCE SHALL BE A MINIMUM
OF 8".
PLACE CONSTRUCTION JOINTS IN MASONRY WALLS SUCH THAT NO
STRAIGHT RUN OF MASONRY EXCEEDS 40'-0", UNLESS NOTED
OTHERWISE.
CORES CONTAINING VERTICAL REINFORCING SHALL BE GROUTED
SOLID WITH MASONRY GROUT. FILLING CORES WITH MORTAR IS NOT
ACCEPTABLE.
PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH HORIZONTAL
BARS AT CORNERS AND INTERSECTIONS OF WALLS AND BOND BEAMS.
F'm = 1500 PSI, EXCEPT WHERE NOTED OTHERWISE ON DRAWINGS.
THE REQUIRED STRENGTH SHALL BE VERIFIED BY THE UNIT
STRENGTH METHOD PER IBC 2105.2.2.1. COMPRESSIVE STRENGTH
OF MASONRY UNITS SHALL BE AS REQUIRED PER IBC TABLE
2105.2.2.1.2 FOR TYPE 'M' OR 'S' MORTAR.
IF THE MASONRY DOES NOT MEET THE REQUIREMENTS FOR
APPLICATION OF THE UNIT STRENGTH METHOD, PRISM TESTING
PER IBC 2105.2.2.2 AND ASTM C1314 SHALL BE USED. THE
COMPRESSIVE STRENGTH OF THE MASONRY SHALL BE TAKEN AS
THE AVERAGE STRENGTH OF THREE PRISMS.
LATEST A.I.S.C. MANUAL AND SPECIFICATIONS APPLY.
WELDING ELECTRODES SHALL BE 70 KSI.
ALL WELDING AND TESTING OF WELDS SHALL BE IN ACCORDANCE
WITH AMERICAN WELDING SOCIETY CODES AND RECOMMENDATIONS.
ALL WELDING SHALL BE BY WELDERS HOLDING CURRENT VALID
CERTIFICATES IN THE TYPE OF WELD REQUIRED.
COMPOSITE BEAMS ARE DESIGNED AS UNSHORED.
CONTRACTOR SHALL PROVIDE THE NECESSARY BRACING DURING
ERECTION AND UNTIL ALL STEEL IS PLUMB AND SECURED.
FIELD CUTTING OR OTHER FIELD MODIFICATIONS TO STRUCTURAL
STEEL SHALL NOT BE MADE WITHOUT SPECIFIC PRIOR WRITTEN
APPROVAL OF THE ARCHITECT/ENGINEER.
ALL BEAM COPES MUST BE MADE TO A RADIUS (1/2" MINIMUM).
STRUCTURAL STEEL FRAMING SHALL BE TRUE AND PLUMB BEFORE
CONNECTIONS ARE FINALLY BOLTED OR WELDED.
INSTALL EXPANSION BOLTS IN ACCORDANCE WITH THE
MANUFACTURER RECOMMENDATIONS.
ANCHOR RODS ARE NOT DESIGNED TO SUPPORT ERECTION LOADS.
STEEL FABRICATOR SHALL COMPLY WITH OSHA STANDARDS IN
DETAILING AND FABRICATING STEEL FOR ERECTION.
EXAMINE ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL
DRAWINGS TO DETERMINE LOCATION AND DIMENSIONS OF CHASES,
INSERTS, OPENINGS, SLEEVES, REVEALS, DEPRESSIONS AND OTHER
PROJECT REQUIREMENTS NOT SHOWN ON STRUCTURAL DRAWINGS.
BEFORE FABRICATION AND ERECTION OF ANY MATERIALS, FIELD
VERIFY ALL EXISTING ELEVATIONS, DIMENSIONS AND CONDITIONS AS
SHOWN ON THE DRAWINGS AND REPORT ANY DISCREPANCIES TO
THE ARCHITECT/ENGINEER AT ONCE FOR RESOLUTION.
STRUCTURAL MEMBERS ARE DESIGNED FOR "IN PLACE" LOADS.
CONTRACTOR IS RESPONSIBLE FOR BRACING, WITHOUT
OVERSTRESSING, ALL STRUCTURAL ELEMENTS (AS REQUIRED AT ANY
STAGE OF CONSTRUCTION) UNTIL COMPLETION OF THIS PROJECT.
FOLLOW OSHA SAFETY STANDARDS FOR STEEL ERECTION AND METAL
DECKING ERECTION.
CONN CONNECTION
LOCAT(E)(ION)LOC
PJP PARTIAL JOINT PENETRATION
STIF STIFFENER
SS STAINLESS STEEL
OCCUPANCY CATEGORY
OCCUPANCY CATEGORY
NATURE OF OCCUPANCY
IV
BOILER PLANT
THERMAL FACTOR AT CANOPIES, Ct 1.2
0.185
SPECTRAL RESPONSE ACCELERATION, S1 0.062
SEISMIC RESPONSE COEFFICIENT, Cs 0.107 (MASONRY SHEAR WALLS)
STEEL BRACED FRAMES AND MASONRY SHEAR WALLS IN EACH DIRECTION
RESIST LATERAL LOADS. ROOF DECK ACTS AS A DIAPHRAGM TO TRANSFER
LATERAL LOADS TO THE BRACED FRAMES.
ANCHORS TO CONCRETE
EXPANSION ANCHORS HILTI KWIK BOLT TZ,
SIMPSON STRONG-BOLT
ADHESIVE ANCHORS HILTI HIT RE 500-SD,
SIMPSON SET-XP
ANCHORS TO MASONRY
EXPANSION ANCHORS HILTI KWIK BOLT 3,
SIMPSON WEDGE-ALL
ADHESIVE ANCHORS HILTI HY 150 MAX,
POWERS POWER-FAST,
SIMPSON SET
ANCHORAGE TO CONCRETE AND GROUTED MASONRY
MECHANICAL ANCHORS TO CONCRETE SHALL HAVE CURRENT ICC-
ES REPORT APPROVAL FOR USE WITH CRACKED CONCRETE IN
ACCORDANCE WITH ACCEPTANCE CRITERIA AC193.
ADHESIVE ANCHORS TO CONCRETE SHALL HAVE CURRENT ICC-ES
REPORT APPROVAL FOR USE WITH CRACKED CONCRETE IN
ACCORDANCE WITH ACCEPTANCE CRITERIA AC308.
MECHANICAL ANCHORS TO MASONRY SHALL HAVE CURRENT ICC-ES
REPORT APPROVAL FOR USE WITH GROUTED MASONRY IN
ACCORDANCE WITH ACCEPTANCE CRITERIA AC01.
ADHESIVE ANCHORS TO MASONRY SHALL HAVE CURRENT ICC-ES
REPORT APPROVAL FOR USE WITH GROUTED MASONRY IN
ACCORDANCE WITH ACCEPTANCE CRITERIA AC58, INCLUDING CREEP
TESTING.
CURRENT ICC-ES REPORTS SHALL BE SUBMITTED UPON REQUEST.
ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
REQUIREMENTS GIVEN IN THE ICC-ES REPORTS FOR THE SPECIFIC
ANCHORS AND APPLICATIONS.
ALL PERSONNEL INSTALLING ADHESIVE AND MECHANICAL ANCHORS
SHALL BE TRAINED BY THE MANUFACTURER ON PROPER INSTALLATION
TECHNIQUE. CERTIFICATION FROM THE MANUFACTURER SHALL BE
AVAILABLE UPON REQUEST.
COORDINATE CONSTRUCTION SUCH THAT INTERFERENCE OF
REINFORCING STEEL WITH CONCRETE ANCHOR PLACEMENT DOES
NOT OCCUR. IF REINFORCING STEEL IS ENCOUNTERED DURING
DRILLING, ADJUST THE ANCHOR LOCATION IF POSSIBLE AND NOTIFY
THE STRUCTURAL ENGINEER. DO NOT CUT OR DAMAGE REINFORCING
STEEL DURING DRILLING, UNLESS EXPLICITLY PERMITTED BY THE
STRUCTURAL ENGINEER OF RECORD.
EXPANSION ANCHORS INDICATED IN THE DRAWINGS ARE BASED
UPON DESIGN VALUES FOR CARBON STEEL HILTI KWIK BOLT TZ
EXPANSION ANCHORS WITH THE FOLLOWING MINIMUM EFFECTIVE
EMBEDMENTS UNO:
EXPANSION ANCHORS TO CONCRETE
3/4" DIA 4 3/4"
5/8" DIA 4"
1/2" DIA 3 1/4"
3/8" DIA 2"
EXPANSION ANCHORS OTHER THAN HILTI KWIK BOLT TZ MAY
REQUIRE REVISION OF ANCHOR SIZE, SPACING, AND/OR MINIMUM
EMBEDMENT. PRIOR TO USE OF ALTERNATE EXPANSION ANCHORS,
SUBMIT A CURRENT ICC-ES REPORT TO THE STRUCTURAL ENGINEER
OF RECORD FOR SIZE, SPACING, AND/OR EMBEDMENT DEPTH
REVISIONS.
ADHESIVE ANCHORS INDICATED IN THE DRAWINGS ARE BASED UPON
DESIGN VALUES FOR HILTI HIT-RE 500-SD ADHESIVE AND HILTI
STANDARD HAS THREADED RODS OR ASTM A615 REINFORCING BARS
WITH MINIMUM EFFECTIVE EMBEDMENTS AS INDICATED IN THE
DRAWINGS.
ADHESIVE ANCHORS TO CONCRETE
ADHESIVE ANCHORS OTHER THAN HILTI HIT-RE 500-SD MAY REQUIRE
REVISION OF ANCHOR SIZE, SPACING, AND/OR MINIMUM EMBEDMENT.
PRIOR TO USE OF ALTERNATE ADHESIVE ANCHORS, SUBMIT A
CURRENT ICC-ES REPORT TO THE STRUCTURAL ENGINEER OF
RECORD FOR SIZE, SPACING, AND/OR EMBEDMENT DEPTH REVISIONS.
ANCHORAGE IN HOLLOW-CORE CONCRETE MASONRY UNITS
SLEEVE ANCHORS INDICATED IN THE DRAWINGS ARE BASED UPON
VALUES FOR CARBON STEEL HILTI HLC SLEEVE ANCHORS.
SLEEVE ANCHORS
SLEEVE ANCHORS OTHER THAN HILTI MAY REQUIRE REVISION OF
ANCHOR SIZE AND/OR SPACING. SUBMIT ENGINEERING DATA AND
DOCUMENTATION TO THE STRUCTURAL ENGINEER PRIOR TO USE OF
ALTERNATE SLEEVE ANCHORS FOR SIZE AND/OR SPACING
REVISIONS.
CONCRETE CORE DRILLING
SLABS
VERTICAL CORE DRILLING IS PERMITTED THROUGH CONCRETE SLABS
FOR HOLES OF 8" DIAMETER OR LESS. VERTICAL CORE DRILLING OF
LARGER DIAMETER HOLES IS ONLY ALLOWED WITH EXPLICIT
PERMISSION OF THE STRUCTURAL ENGINEER. MAINTAIN SOUND
CONCRETE BETWEEN SUCCESSIVE CORES EQUAL TO THE LARGER
DIAMETER CORE ON EITHER SIDE.
WALLS
HORIZONTAL CORE DRILLING IS NOT PERMITTED THROUGH
CONCRETE WALLS. HOLES THROUGH WALLS SHALL BE SLEEVED TO
AVOID WALL REINFORCING. HORIZONTAL CORE DRILLING IN WALL
LOCATIONS IS ONLY ALLOWED WITH EXPLICIT PERMISSION OF THE
STRUCTURAL ENGINEER. MAINTAIN SOUND CONCRETE BETWEEN
SUCCESSIVE CORES EQUAL TO THE LARGER DIAMETER CORE ON
EITHER SIDE.
SEISMIC RESPONSE COEFFICIENT, Cs 0.071 (STEEL BRACED FRAMES)
CONTINUOUS WALL FOOTINGS AND TUNNELS HAVE BEEN DESIGNED FOR A
NET SOIL BEARING PRESSURE OF 6000 PSF.
PRECAST CONCRETE
THE DESIGN AND MANUFACTURE OF ALL PRECAST CONCRETE
UNITS SHALL CONFORM TO ACI 318.
PRECAST MEMBERS ARE DESIGNED FOR "IN PLACE"
LOADS. IT SHALL BE THE RESPONSIBILITY OF THE PRERCAST
MANUFACTURER TO TRANSPORT AND ERECT THE PRECAST
MEMBERS WITHOUT OVERSTRESSING OR OTHERWISE DISTRESSING
THEM IN ANY MANNER.
DESIGN MUST INCLUDE ALL CONCENTRATED LOADS FROM
MECHANICAL EQUIPMENT, HEADERS, ETC.
PROVIDE 1/8" THICK CONTINUOUS MULTIMONOMER PLASTIC
BEARING STRIPS BETWEEN HOLLOW CORE SLABS AND MASONRY
OR CONCRETE SUPPORTS.EXTENSIONEXT
FOUNDATION ELEVATIONS HAVE BEEN DETERMINED BASED ON A FROST
DEPTH OF 3'-6" BELOW FINISHED GRADE, PER GEOTECHNICAL REPORT.
SHOP DETAILING NOTES
1. SHOP DRAWINGS SHALL BE SUBMITTED BY THE
FABRICATOR FOR APPROVAL AND SHALL CONFORM TO
PROJECT SPECIFICATIONS. THE ENGINEERS REVIEW OF
SHOP DRAWINGS SHALL BE FOR CONFORMANCE TO THE
DESIGN INTENT OF THE CONTRACT DRAWINGS AND SHALL
NOT BE CONSTRUED AS A COMPLETE DIMENSIONAL CHECK
AND SHALL NOT RELIEVE THE FABRICATOR/DETAILER
FROM HIS RESPONSIBILITY FOR THE ACCURACY OF DETAIL
DIMENSIONS AND COMPLETENESS OF THESE SHOP
DRAWINGS, NOR THE GENERAL FIT-UP OF PARTS TO BE
ASSEMBLED IN THE FIELD.
2. ALL WELDS SHALL BE CONTINUOUS. STITCH WELDING IS
NOT PERMITTED. UNLESS NOTED.
3. FILLET WELD SIZE SHALL CONFORM TO AISC 360-10 TABLE
J2.4, MINIMUM FILLET WELD IS 3/16".
4. TYPICAL FIELD WELDS SHOULD BE 3
16 FILLET OR AS SHOWN
ON DESIGN DRAWINGS.
5. WELDING OF HIGH STRENGTH BOLTS AND NUTS IS NOT
PERMITTED.
6. BEAM CONNECTIONS:
USE CLIP ANGLES AT BEAM TO BEAM CONNECTIONS. ALL
OTHERS SHALL BE SHEAR PLATES. MATERIAL SHALL BE
5/16" MINIMUM THICKNESS. THE MINIMUM CONNECTION
SHALL BE TWO 3/4" DIAMETER BOLTS IN SINGLE SHEAR OR
EQUIVALENT WELD. WHEN REACTIONS ARE NOT
INDICATED, SELECT A CONNECTION CAPABLE OF
SUPPORTING ONE HALF OF THE TOTAL ALLOWABLE
UNIFORM LOAD CAPACITY OF THE GIVEN MEMBER FOR
SPAN AND GRADE OF STEEL USING ALLOWABLE UNIFORM
LOAD TABLES IN THE AISC MANUAL OF STEEL
CONSTRUCTION (LATEST EDITION).
7. BRACING CONNECTIONS:
BRACING SHALL BE CONNECTED TO ALL INTERSECTING
MEMBERS. TURN VERICIAL ELEMENTS OF ANGLES AND
TEES DOWN. BACK TO BACK PLACEMENT OF ELEMENTS IS
PROHIBITED UNLESS SPECIFICALLY INDICATED.
8. WELDED CONNECTIONS:
FRAMED BEAM CONNECTIONS SHALL BE SHOP WELDED/
FIELD BOLTED CONNECTIONS UNLESS OTHERWISE NOTED.
9. FOR DOUBLE BEAM CONNECTIONS AT COLUMN WEBS, THE
FABRICATOR MUST SUPPLY A BEAM SEAT OR EQUAL WITH
A MEANS OF POSITIVE ATTACHMENT TO SUPPORT THE
FIRST BEAM WHILE THE SECOND BEAM IS BEING ERECTED.
10. ONE SIDED OR OTHER TYPES OF ECCENTRIC
CONNECTIONS WILL NOT BE PERMITTED, UNLESS NOTED.
11. ALL STRUCTURAL SHAPES, PLATES AND BARS ATTACHED
TO BASE PLATES, STUB COLUMN OR CAP PLATES SHALL BE
MILLED TO PROVIDE FULL BEARING.
12. ALL GALVANIZED SECTIONS WILL BE REPAIRED WITH ZINC
RICH COATINGS.
13. ALL EXPOSED STEEL SHALL BE GALVANIZED AND PAINTED
TO MATCH VA FACILITY STANDARD GREY.
FABRICATION AND FIELD ERECTION NOTES
1. STRUCTURAL STEEL SHALL BE ERECTED, IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
2. FIELD ERECTION BY CONTRACTOR.
3. FIELD ERECTION AIDS, IF REQUIRED, SHALL BE FURNISHED
AND INSTALLED BY THE ERECTOR. AFTER ERECTION, ALL
ERECTION AIDS SHALL BE REMOVED BY THE ERECTOR.
4. MARKED END OF PIECES TO COORESPOND WITH LOCATION
OF PIECE MARKS AS SHOWN ON ERECTION PIECE MARK
DRAWINGS. MARKS ARE GENERALLY ON THE LEFT END OF
THE PIECE.
5. WELDING PER PROJECT SPECIFICATIONS. WELDING
PROCEDURES AND WELDER QUALIFICATION TEST REPORT
SHALL BE SUBMITTED FOR ALL NON-PREQUALIFIED WELDS
PER AWS D1.1. WELDING ELECTRODES SHALL BE E7018
LOW HYDROGEN.
6. FIELD TOUCH UP OF SHOP PRIMER PAINT AT FIELD
SPLICES, BRACING GUSSET PLATE CONNECTIONS, BEAM
CONNECTIONS OR ANY OTHER MISCELLANEOUS AREAS
AROUND BOLT HOLES IS THE RESPONSIBILITY OF THE
FIELD PAINTING CONTRACTOR.
7. ALL RIGGING EQUIPMENT SHALL MEET CURRENT (OSHA) 29
CFR 1910 REQUIREMENTS. ALL RIGGING SHALL BE
PERFORMED BY EXPERIENCED AND QUALIFIED RIGGING
PERSONNEL.
SHOP DETAILING AND FABRICATION NOTES
SHOP DETAILING NOTES
1. SHOP DRAWINGS SHALL BE SUBMITTED BY THE
FABRICATOR FOR APPROVAL AND SHALL CONFORM TO
PROJECT SPECIFICATIONS. FOR STRUCTURAL STEEL
MEMBER END CONNECTIONS NOT CALLED OUT ON
BUILDING 1 WALKWAY PIPE RACK, THE CONTRACTOR AND
FABRICATOR SHALL PROVIDE A STAMPED AND SIGNED
DESIGN CALCULATIONS AND FABRICATION DRAWING FOR
REVIEW AND APPROVAL OF ENGINEER OF RECORD (EOR)
2. THE EOR SHALL REVIEW SHOP DRAWINGS FOR
CONFORMANCE TO THE DESIGN INTENT OF THE
CONTRACT DRAWINGS AND SHALL NOT BE CONSTRUED AS
A COMPLETE DIMENSIONAL CHECK AND SHALL NOT
RELIEVE THE FABRICATOR/DETAILER FROM HIS
RESPONSIBILITY FOR THE ACCURACY OF DETAIL
DIMENSIONS AND COMPLETENESS OF THESE SHOP
DRAWINGS, NOR THE GENERAL FIT-UP OF PARTS TO BE
ASSEMBLED IN THE FIELD.
REINFORCED CONCRETE BLOCK LINTELS
(NON-LOAD BEARING)
PROVIDE STEEL BAR REINFORCED CONCRETE BLOCK LINTELS
OVER ALL OPENINGS IN MASONRY WALLS OF THE FOLLOWING
SIZES UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS.
MASONRY BEARING SHALL BE MINIMUM 8" ON EACH END.
OPENINGS 4'-0" TO 10'-0" W8x18 STEEL LINTEL.
SEE DETAIL 3/SF513
OPENINGS 8" TO 4'-0" USE 8" DEEP LINTEL
WITH (2)-#5 CONT
OPENINGS 10'-0" TO 14'-0" W8x24 STEEL LINTEL.
SEE DETAIL 3/SF513
1. PROVIDE STEEL ANGLE LINTELS FOR MASONRY OPENINGS OF THE
FOLLOWING SIZES UNLESS NOTED OR DETAILED OTHERWISE
ON DRAWINGS. LINTELS SHALL BE LOOSE UNLESS OTHERWISE
SHOWN AND BEARING SHALL BE MINIMUM 8" ON EACH END.
4" MASONRY TO 4' - 0" L 3 1/2" x 3 1/2" x 5/16" 4" MASONRY 4' - 0" TO 6' - 0" L 6" x 3 1/2" x 5/16" (LLV)
EXTERIOR LINTELS AND RELIEF ANGLES SHALL BE GALVANIZED.
2. AT CONTROL JOINTS IN MASONRY WALLS, WHICH OCCUR ABOVE
OPENINGS IN LINE WITH THE JAMB OF THE OPENING, PROVIDE
BOND
BREAK AT THE LINTEL BY WRAPPING THE END EXTENDING
ACROSS
THE CONTROL JOINT WITH POLYETHYLENE SHEET.
STEEL LOOSE LINTELS
(NON-LOAD
BEARING)
NOTES:
1. PROVIDE DOWELS FROM PIER TO FOOTING THAT LAP AND
ARE THE SAME SIZE AND NUMBER AS VERTICAL BARS.
2. PROVIDE 4 SETS OF TIES @ 3" OC AT TOP OF PIER.
3. SEE PLAN FOR TOP OF PIER ELEVATION.
4. AT SINGLE TIE LEGS, ALTERNATE LOCATIONS OF 135°
HOOKED ENDS.
8 BAR LAYOUT
3 TIES/SET
12 BAR LAYOUT
3 TIES/SET
RECTANGULAR 16 BAR LAYOUT
4 TIES/SET
SH
O
R T
SI
D
E
LONG SIDE
S001
PIER SCHEDULE
TYPE SIZE REINFORCING TIES
P1 2'-0"x2'-0" (8) #9 #4 AT 16" P2 2'-6"x2'-6" (12) #9 #4 AT 16" P3 3'-4"x2'-6" (14) #9 #4 AT 16" P4 2'-6"x2'-9" (12) #9 #4 AT 16" P5 4'-2"x2'-6" (14) #9 #4 AT 16"
FOOTING SCHEDULE
TYPE SIZE DEPTH REINFORCING
F4 4'-0"x4'-0" 1'-6" (5) #6 EW F5 5'-0"x5'-0" 1'-6" (6) #6 EW F6 6'-0"x6'-0" 1'-6" (7) #6 EW F8 8'-0"x8'-0" 2'-0" (9) #7 EW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
4/21/23
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127 015284/21/2023ISSUED FOR BID
STRUCTURAL -SYMBOLS NOTES
AND ABBREVIATIONS
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
DS
AutoCAD SHX Text
BB
SS132
1 & 2
AT FDN
AT ROOF
SS130
SS131
AT FDN
AT ROOF
SS130
SS131
1AT FDN
SB501
VAULT#9.2
VAULT#9.1
7.5'
PLAN NOTES
1. SEE SI001 FOR GENERAL STRUCTURAL NOTES AND ABBREVIATIONS.
2. REFER TO CIVIL DRAWINGS FOR BOX CONDUIT, TUNNEL AND VAULT
ELEVATIONS AND LOCATIONS.
3. CONTRACTOR TO VERIFY EXISTING CONDITIONS, REPORT ANY
DISCREPANCIES TO ENGINEER FOR RESOLUTION.
4. REFER TO EARTH WORK SPECIFICATIONS FOR BOX CONDUIT, TUNNEL
AND VAULT EXCAVATION.
5. CONTRACTOR TO PROVIDE TEMPORARY SHORING DURING
EXCAVATION ADJACENT TO EXISTING BUILDING STRUCTURES.
SHORING SYSTEM TO BE DESIGNED BY SHORING CONTRACTOR.
6. SEE CIVIL, MECHANICAL AND PLUMBING DRAWINGS FOR SUMP
SYSTEM
7. SEE STRUCTURAL FOR WATERPROOFING INFORMATION.
8. ALL MEMBERS AND CONNECTIONS AT PIPE SUPPORT ANCHOR POINTS
IN THE BOX CONDUIT, TUNNEL, AND VAULTS ARE SHOWN AND
DESIGNED IN THE MECHANICAL DRAWINGS. REFER TO SPEC SECTION
230511,232211 AND 336300 FOR ADDITIONAL INFORMATION.
9. PROVIDE 10" SLAB ON GRADE FOR NEW VAULTS 5.1, 5.2, 9.1,9.2. SIZE
OF PAD TO BE 16' X 13'. COORDINATE WITH MECHANICAL AND STEM
EXTENSIONS LOCATIONS. PROVIDE 6FT HIGH CHAIN LINK FENCING OF
APPROXIMATELY 12' X 15' FOR ALL NEW VAULTS INCLUDING 5.3.
10. PROVIDE 10" SLAB ON GRADE EQUAL TO THE HEIGHT OF THE VAULT
TOP FOR NEW SUMP PUMP CONTROL PANELS FOR ALL EXISTING
VAULTS 6-8-10-11-12. PROVIDE 6FT HIGH CHAIN LINK FENCING FOR ALL
EXISTING VAULTS 6-8-10-11-12 AROUND SUMP PUMP CONTROL
PANELS.
11. CHAIN-LINK WITH BLACK POLYMER COATED STEEL, 6' HIGH, NO
BARBED WIRE, SWING GATES WILL SWING OUT, SINGLE-SWING TYPE.
VAULT#5.1VAULT#5.2VAULT#5.3
EX PIT#5
VAULT#9.2
VAULT#9.1
SS100
STRUCTURAL SITE PLAN- CLIN 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
12/16/22
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127 0152812/16/2022ISSUED FOR BID
M
AT
C H
L
IN
E- C
O N
TI
N
U
ED
O N
S H
EE
T
SS
SCALE: 1" = 20'-0"
Structural New Work Plan1
N
Key Plan
SS100 SS200
SB502
SB502
SB502
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
FR/DS
AutoCAD SHX Text
AMH/BB
AutoCAD SHX Text
NOTE 9 & 11
NOTE 9 & 11
ANCHOR
LOWER ROOF
FROM SS100
UNDERGROUND FROM
VAULT 9
ANCHOR
ANCHOR
BUILDING 1
TO SS 104 AND SS105
BUILDING 1
BUILDING 221
BUILDING 221 /217 WALKWAY
B1 W 14x
16B1 W 14x
B7 W 16x
B7 W 16x
B7 W 16x
B4 W 14x
B7 W 16x
B4 W 14x
B4 W 14x
26B4 W14x26
B1 W12x16
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
W18x40
W18x40
W18x40
W18x40
W
W x4
W x4
W x2
W x2
ANCHOR
MECH PH WALL
BUILDING 221
ALL BEAMS ARE
EXISTING
ALL BEAMS ARE
EXISTING
ALL BEAMS ARE
EXISTING
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W W
NE
W W
NE
W W
NE
W W
NE
W W
NE
W W
NE
W W
B7 W 16x
B7 W 16x
B7 W 16x
B7 W 16x
B4 W 14x
B4 W 14x
B7 W 16x
B4 W 14x
B17 W14x53
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B5 W x3
B1 W 14x
W10x
W10x
W10x 17W10x
W18x40
W21x50
ALL BEAMS ARE
EXISTING
B5 W x3
B1 1 W x4
B1 1 W x4
B1 1 W x4
B1 1 W x4
B9 W x3
W x1
B1 W12x16
B3 W14x22
B3 W14x22
B3 W14x22 B3 W14x22 B3 W14x22 B3 W14x22 B3 W14x22
BU
ILD
IN
G
EX
P
JO
IN
T
B7 W 16x
B4 W 14x
B4 W 14x
B3 W14x22
B18 W14x43
ANCHOR
TO SS 102
BUILDING 217
TO SS 103
BUILDING 217-221 Walkway
B3 W14x22
B3 W14x22
B3 W14x22B3 W14x22
B3 W14x22
B3 W14x22
B1 7 W x5
B4 W x2
B4 W x2
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17 1.18 1.19 1.20
1.9
ANCHOR
LOCATE PIPE SUPPORTS
AT HALFWAY POINTS
BUILDING 1 CONNECTING WALKWAY
NE
W
W
1.1
T/ S
TE
EL
3'2
1/2
NEW W8
NEW W8
NEW W8
SCALE: 1/16" = 1'-0"
1 - STRUCTURAL PLAN - New Work1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
4/21/23
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127 015284/21/2023ISSUED FOR BID
STRUCTURAL KEY PLANS -
BUILDING 217/221 AND WALKWAY
SS101
N
NOTES
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT C
AutoCAD SHX Text
UNIT C
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text 7'-4 "1316"
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text J
AutoCAD SHX Text K
AutoCAD SHX Text M
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 16.1
AutoCAD SHX Text 10.1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N19
AutoCAD SHX Text N17
AutoCAD SHX Text N161
AutoCAD SHX Text N151
AutoCAD SHX Text F1
AutoCAD SHX Text S2
AutoCAD SHX Text S3
AutoCAD SHX Text S4
AutoCAD SHX Text S5
AutoCAD SHX Text S6
AutoCAD SHX Text S7
AutoCAD SHX Text S8
AutoCAD SHX Text S9
AutoCAD SHX Text S11
AutoCAD SHX Text S10
AutoCAD SHX Text Q
AutoCAD SHX Text P
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text 24'-11 "38"
AutoCAD SHX Text 49'-10 "716"
AutoCAD SHX Text 7'-11 "1516"
AutoCAD SHX Text 22'-10 "732"
AutoCAD SHX Text 32'-4 "1516"
AutoCAD SHX Text
PA-
AutoCAD SHX Text 2A
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
FR
AutoCAD SHX Text
AMH
AutoCAD SHX Text
SS102
AutoCAD SHX Text
SS103
SS103
FROM SS100
UNDERGROUND FROM
VAULT 9
ANCHOR
B1 W 14x
16B1 W 14x
B7 W 16x
B7 W 16x
B7 W 16x
B4 W 14x
B7 W 16x
B4 W 14x
B4 W 14x
26B4 W14x26
B1 W12x16
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
ALL BEAMS ARE
EXISTING
ALL BEAMS ARE
EXISTING
B7 W 16x
B7 W 16x
B7 W 16x
B7 W 16x
B4 W 14x
B4 W 14x
B7 W 16x
B4 W 14x
B17 W14x53
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B3 W14x22
B5 W x3
B1 W 14x
W10x
W10x
W10x 17W10x
W18x40
W21x50
ALL BEAMS ARE
EXISTING
B5 W x3
B1 1 W x4
B1 1 W x4
B1 1 W x4
B1 1 W x4
B9 W x3
W x1
B1 W12x16
B3 W14x22
B3 W14x22
B3 W14x22 B3 W14x22 B3 W14x22 B3 W14x22 B3 W14x22
BU
ILD
IN
G
EX
P
JO
IN
T
B7 W 16x
B4 W 14x
B4 W 14x
B3 W14x22
B18 W14x43
ANCHOR
TO SS 103
BUILDING 217-221 Walkway
B3 W14x22
B3 W14x22
B3 W14x22B3 W14x22
B3 W14x22
B3 W14x22
B1 7 W x5
B4 W x2
B4 W x2
1.20
ANCHOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
4/21/23
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127 015284/21/2023ISSUED FOR BID
STRUCTURAL PLAN - ROOF
BUILDING 217
SS102
N SCALE: 1/8" = 1'-0"1 STRUCTURAL PLAN - New Work - Building 217
SB511
SB511
SB511
SB512
TYP. PIPE
SUPPORT
SB512
SB512
SB512
SB512
SB512
SB512
SB512B
PLAN NOTES:
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT C
AutoCAD SHX Text
UNIT C
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text 7'-4 "1316"
AutoCAD SHX Text 15'-0 "316"
AutoCAD SHX Text 15'-3 "1116"
AutoCAD SHX Text 15'-11 "12"
AutoCAD SHX Text 14'-7 "916"
AutoCAD SHX Text 15'-3 "58"
AutoCAD SHX Text 6'-3 "716"
AutoCAD SHX Text 13'-1 "78"
AutoCAD SHX Text 45°
AutoCAD SHX Text 17'
AutoCAD SHX Text 7'-5 "1116"
AutoCAD SHX Text 13'-10 "716"
AutoCAD SHX Text 17'-5 "516"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 4'-11 "716"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 11'-2 "58"
AutoCAD SHX Text 10'-8"
AutoCAD SHX Text 14'-7 "78"
AutoCAD SHX Text 17'
AutoCAD SHX Text 10'-3 "316"
AutoCAD SHX Text 130'-10 "34"
AutoCAD SHX Text 92'
AutoCAD SHX Text 39'-0 "38"
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text 6'-11"
AutoCAD SHX Text 2'-8 "78"
AutoCAD SHX Text 19'-8 "1316"
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text 10'-11 "78"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 16.1
AutoCAD SHX Text 10.1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N19
AutoCAD SHX Text N18
AutoCAD SHX Text N17
AutoCAD SHX Text N161
AutoCAD SHX Text N151
AutoCAD SHX Text F1
AutoCAD SHX Text S1
AutoCAD SHX Text S2
AutoCAD SHX Text S3
AutoCAD SHX Text S4
AutoCAD SHX Text S5
AutoCAD SHX Text S6
AutoCAD SHX Text S7
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text 11B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 11B
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text 15A
AutoCAD SHX Text
PS-
AutoCAD SHX Text 15A
AutoCAD SHX Text
PS-
AutoCAD SHX Text 17B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 17B
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text 8B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 8B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 11A
AutoCAD SHX Text
PS-
AutoCAD SHX Text 11A
AutoCAD SHX Text 3'-9 "716"
AutoCAD SHX Text 16'-8 "1316"
AutoCAD SHX Text 12'-2 "116"
AutoCAD SHX Text 17'
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RD
AutoCAD SHX Text 24'-11 "38"
AutoCAD SHX Text 49'-10 "716"
AutoCAD SHX Text 7'-11 "1516"
AutoCAD SHX Text 22'-10 "732"
AutoCAD SHX Text 32'-4 "1516"
AutoCAD SHX Text
PS-
AutoCAD SHX Text 15B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 15B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 17A
AutoCAD SHX Text
PS-
AutoCAD SHX Text 17A
AutoCAD SHX Text
PA-
AutoCAD SHX Text 2A
AutoCAD SHX Text 9'-5 "1116"
AutoCAD SHX Text 2'-10 "12"
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text 8A
AutoCAD SHX Text
PS-
AutoCAD SHX Text 8A
AutoCAD SHX Text 13'-7"
AutoCAD SHX Text 17'
AutoCAD SHX Text
PS-
AutoCAD SHX Text 16B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 16B
AutoCAD SHX Text
PS-
AutoCAD SHX Text 16A
AutoCAD SHX Text
PS-
AutoCAD SHX Text 16A
AutoCAD SHX Text
PS-
AutoCAD SHX Text 16C
AutoCAD SHX Text
PS-
AutoCAD SHX Text 16C
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
1_[SPH-3]
AutoCAD SHX Text
PS-
AutoCAD SHX Text
1_[SPH-3]
AutoCAD SHX Text
SPRING HANGERS
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
FR
AutoCAD SHX Text
DS
AutoCAD SHX Text INSTALL PS-25 WITH A 1" OFFSET TO THE SOUTH INSTALL PS-2 WITH A 1" OFFSET TO THE SOUTHWEST INSTALL PS-7 WITH A 1" OFFSET TO THE NORTHEAST
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ANCHOR
LOWER ROOF
ANCHOR
BUILDING 1
TO SS 104 AND SS105
BUILDING 1
BUILDING 221
BUILDING 221 /217 WALKWAY
W18x40
W18x40
W18x40
W18x40
W
W x4
W x4
W x2
W x2
ANCHOR
MECH PH WALL
BUILDING 221
ALL BEAMS ARE
EXISTING
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W W
NE
W W
NE
W W
NE
W W
NE
W W
NE
W W
NE
W W
TO SS 102
BUILDING 217
TO SS 103
BUILDING 217-221 Walkway
1.2 1.3 1.4 1.5 1.6 1.7 1.8
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17 1.18 1.19 1.20
1.9
LOCATE PIPE SUPPORTS
AT HALFWAY POINTS
NEW W8
NEW W8
NEW W8
SCALE: 1/8" = 1'-0"
1 - New Work - Building 217/221 Walkway and Building 2211
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
4/21/23
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127 015284/21/2023ISSUED FOR BID
STRUCTURAL PLAN - BUILDING
217/221 WALKWAY
SS103
N
BEAM DESIGNATION
W8 - W8 X 18
SEE SB505 FOR DETAILS
SB505
A-A
SB514
SB515
PLAN NOTES:
AutoCAD SHX Text
UNIT A
AutoCAD SHX Text
UNIT B
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text 15'-11 "38"
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text 30°27'38"
AutoCAD SHX Text 12'-6 "12"
AutoCAD SHX Text 15'
AutoCAD SHX Text 13'-10"
AutoCAD SHX Text
5 SPACES AT 16'-0" SPACES =80'
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text 13'-8 "12"
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
17 SPACES @ 17'-0" SPACING EACH
AutoCAD SHX Text 17'
AutoCAD SHX Text 17'
AutoCAD SHX Text 17'
AutoCAD SHX Text 26'-3 "78"
AutoCAD SHX Text 1'-3 "38"
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text
PA-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text 45G
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text 15'
AutoCAD SHX Text 15'
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text 16'
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text 10'-11 "78"
AutoCAD SHX Text
PS-
AutoCAD SHX Text 36A
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text Q
AutoCAD SHX Text P
AutoCAD SHX Text 131'-6 "516"
AutoCAD SHX Text 107'-11 "18"
AutoCAD SHX Text 12'
AutoCAD SHX Text 13'-6"
AutoCAD SHX Text 152'-0 "532"
AutoCAD SHX Text 135'-0 "732"
AutoCAD SHX Text 4'
AutoCAD SHX Text 14'-6 "132"
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
9 SPACES AT 9'0" = 81'
AutoCAD SHX Text 42'-7"
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text 45A
AutoCAD SHX Text
INSTALL PIPE SUPPORTS FOR BOTH HPS AND PC
AutoCAD SHX Text 16'
AutoCAD SHX Text 17'-6 "1332"
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text 45D
AutoCAD SHX Text
PS-
AutoCAD SHX Text 45D
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
GUI-
AutoCAD SHX Text
AutoCAD SHX Text
GUI-
AutoCAD SHX Text
AutoCAD SHX Text
GUI-
AutoCAD SHX Text
AutoCAD SHX Text
GUI-
AutoCAD SHX Text
AutoCAD SHX Text
GUI-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text
PS-
AutoCAD SHX Text
AutoCAD SHX Text 7'-5"
AutoCAD SHX Text
PS-
AutoCAD SHX Text 45F
AutoCAD SHX Text
PS-
AutoCAD SHX Text 45B
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
BB/DS
AutoCAD SHX Text
AMH
AutoCAD SHX Text INSTALL PS-28 WITH A 1" OFFSET TO THE WEST INSTALL PS-45F ON 6" PIPE ONLY INSTALL PS-81 AND PS-82 OFFSET TO THE SOUTH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
B
VAULT#7
BUILDING 1 CONNECTING WALKWAY
BUILDING 4
E W
.V
SAN MH
10" ST
10" SAN
6" SAN
6" SAN
12" ST
10" ST
10" ST
ST MH
SAN MH SAN MH SAN MH SAN MH10" SAN10" SAN
6" SAN
ELEC MH
UG DIRECT BURY STEAM NOTE SHOWN
STEAM BELOW GRADE (NOT SHOWN)
TO VAULT #7 TUNNEL TO BE REMOVED
PRIOR TO NEW PIERS
BUILDING 1 WALKWAY
8" ST
FROM PARKING LOT
BUILDING 3 CONNECTING WALKWAY
1 2 3 4 5 6 7 8 10 119
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
UG SAN NOTE SHOWN
UG SAN NOTE SHOWN
UG SAN NOTE SHOWN
BUILDING 229
BUILDING 1 CONNECTING WALKWAY
OKLAHOMA PARKING LOT
10" ST
SAN MH SAN MH
SAN MH
SAN MH
SAN MH
SAN MH
6" SAN
10" SAN
10" SAN
10" SAN 10" SAN10" SAN
6" SAN
W .V
W .V
E ELEC MH
UG DIRECT BURY STEAM
BUILDING 3 CONNECTING WALKWAY
11 12 13 14 15 16 17
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
HSS12
BUILDING 1 WALKWAY
UG SAN NOTE SHOWN
UG DIRECT BURY STEAM AND SAN NOTE SHOWN
SCALE: 1/8" = 1'-0"
Structural New Work Foundation Plan2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
4/21/23
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127 015284/21/2023ISSUED FOR BID
STRUCTURAL SITE PLAN - ABOVE
BUILDING 1 WALKWAY -
FOUNDATION PLAN
SS104
N
SCALE: 1/8" = 1'-0"
Structural New Work Foundation Plan1N
MA
TC
H
LIN
E- C
ON
TI
NU
ED
A
BO
VE
LE
FT
MA
TC
H
LIN
E- C
ON
TI
NU
ED
B
EL
OW
R
IG
HT
NOTES
FOR UNDERGROUND UTILITIES, NOT SHOWN
SEE CIVIL DRAWINGS
COORDINATE NEW PIER FOOTER INSTALL
WITH PHASE DEMO OF EXISTING
UNDERGROUND STEAM LINE- SEE G101
COLUMNS
ALL COLUMNS ARE HSS 12 X 12 X 5
16" EXCEPT
COLUMN LINES 4 AND 5 WHICH ARE TO BE
HSS 12 X 12X 1/2"
GENERAL REVISION FOR CLARITY OF THE
DRAWING AND DEFINITION FOR PIER
LOCATIONS WORK
MA
TC
H
LIN
E- S
EE
S
S1
B
UI
LIS
NG
1/2
W
AL
KW
AY
CONCRETE SURFACE
AutoCAD SHX Text 74'-4 "58"
AutoCAD SHX Text 15'-0 "38"
AutoCAD SHX Text 15'-0 "58"
AutoCAD SHX Text 15'-0 "38"
AutoCAD SHX Text 7'-6 "12"
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 15'
AutoCAD SHX Text 75'
AutoCAD SHX Text 15'
AutoCAD SHX Text 15'
AutoCAD SHX Text 15'
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 12'-9 "38"
AutoCAD SHX Text 12'-9 "58"
AutoCAD SHX Text 12'-9 "38"
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 75'
AutoCAD SHX Text 55'-4 "78"
AutoCAD SHX Text 13'
AutoCAD SHX Text 30'
AutoCAD SHX Text 26'
AutoCAD SHX Text 28'
AutoCAD SHX Text 55'-4 "78"
AutoCAD SHX Text 28'
AutoCAD SHX Text 20'
AutoCAD SHX Text 28'
AutoCAD SHX Text 16'
AutoCAD SHX Text 16'
AutoCAD SHX Text 2'-6 "116"
AutoCAD SHX Text 13'
AutoCAD SHX Text 5'
AutoCAD SHX Text 6'
AutoCAD SHX Text 18'
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 15'
AutoCAD SHX Text 75'
AutoCAD SHX Text 15'
AutoCAD SHX Text 15'
AutoCAD SHX Text 15'
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 15'
AutoCAD SHX Text 75'
AutoCAD SHX Text 15'
AutoCAD SHX Text 15'
AutoCAD SHX Text 15'
AutoCAD SHX Text 7'-6"
AutoCAD SHX Text 74'-4 "58"
AutoCAD SHX Text 7'-1"
AutoCAD SHX Text 14'-7 "12"
AutoCAD SHX Text 15'-0 "38"
AutoCAD SHX Text 15'-0 "58"
AutoCAD SHX Text 120'
AutoCAD SHX Text 10'
AutoCAD SHX Text 30'
AutoCAD SHX Text 30'
AutoCAD SHX Text 30'
AutoCAD SHX Text 30'
AutoCAD SHX Text 30'
AutoCAD SHX Text 28'
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
DS
AutoCAD SHX Text
BB
AutoCAD SHX Text X-X
SB507
NE
W
W
BUILDING 4
BUILDING 1 CONNECTING COORIDOR
BUILDING 3 CONNECTING WALKWAY
NE
W
M C1
NEW W12
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NEW W12
NEW W14
NEW W14
NEW W14
NEW W14
NEW W24
NEW W24
NE
W
W
NE
W
W
NE
W
W
NE
W
W
WT5 WT5
WT5 WT5
WT5
WT5
NE
W
W
WT5 WT5 WT5
WT5
WT5 WT5
WT5 WT5
WT5
WT5 WT5
WT5
B
A
2 3 4 5 6 7 8 10 11
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W12
NEW W12
NE
W
W
NE
W
W
NE
W
10WT5
SB507
SB506
NE
W
W
PIPE ANCHOR CENTER ON 11
112' - 0"
PIPE ANCHOR CENTER ON 2
113' - 4 1/4"
NE
W
W
PA-7
SB509
NE
W
W
NE
W
M C1
NE
W
M C1
W
X
BUILDING 229
BUILDING 1 CONNECTING WALKWAY
BUILDING 3 CONNECTING WALKWAY
BUILDING 1 CONNECTING WALKWAY
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
NE
W
W
WT5 WT5
WT5
NEW W12
NEW W12
WT5 WT5
WT5 WT5
WT5
WT5 WT5 WT5
11 12 13 14 15 16 17
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NEW W14
NE
W
NE
W
NE
W
NE
W
NE
W
10WT5
SB504
NE
W
W
1.1
T/ S
TE
EL
1'
T/ S
TE
EL
3'2
1/2
PIPE ANCHOR CENTER ON 17
111' - 4"PIPE ANCHOR CENTER ON 11
112' - 0"
NE
W
M C1
NE
W W
NE
W
M C1
SB509B
SB510
NE
W
M C1
NE
W
M C1
SCALE: 1/8" = 1'-0"
Structural New Work Roof Plan2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
4/21/23
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127 015284/21/2023ISSUED FOR BID
STRUCTURAL SITE PLAN - ABOVE
BUILDING 1 WALKWAY - ROOF
PLAN
SS105
N
SCALE: 1/8" = 1'-0"
Structural New Work Roof Plan- Above Building 1 Walkway1N
MA
TC
H
LIN
E- C
ON
TI
NU
ED
A
BO
VE
LE
FT
MA
TC
H
LIN
E- C
ON
TI
NU
ED
B
EL
OW
R
IG
HT
HORIZONTAL BRACING
WT 5 - WT 5 X 13
WT 6 - WT 6 X 15
BEAM DESIGNATION
W10 - W10 X 22 W12- W12 X 26 W14-W14 X 34 W16-W16X45 W18-W18X 45 W24-W24X68
CHANNEL DESIGNATION
MC13 - MC13 X 31.8
T/ STEEL EL. 111'-0" (13'-0)
AFS U.N.O.
MA
TC
H
LIN
E- S
EE
S
S1
B
UI
LIS
NG
1/2
W
AL
KW
AY
NOTES
WORK THIS DRAWING WITH SS103, SS104
T/ STEEL EL. 111'-0" (13'-0)
AFS U.N.O.
AutoCAD SHX Text 28'
AutoCAD SHX Text 20'
AutoCAD SHX Text 28'
AutoCAD SHX Text 28'
AutoCAD SHX Text 13'
AutoCAD SHX Text 55'-4 "78"
AutoCAD SHX Text 16'
AutoCAD SHX Text 30'
AutoCAD SHX Text 26'
AutoCAD SHX Text 13'-0"
AutoCAD SHX Text 16'
AutoCAD SHX Text 56'-4 "38"
AutoCAD SHX Text 74'-6"
AutoCAD SHX Text 30'
AutoCAD SHX Text 30'
AutoCAD SHX Text 30'
AutoCAD SHX Text 30'
AutoCAD SHX Text 10'
AutoCAD SHX Text 30'
AutoCAD SHX Text 28'
AutoCAD SHX Text 18'
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
DS
AutoCAD SHX Text
BB
AutoCAD SHX Text A-A
AutoCAD SHX Text
SB505
AutoCAD SHX Text A-A
AutoCAD SHX Text
SB504
AutoCAD SHX Text 1-1
AutoCAD SHX Text
SB507
AutoCAD SHX Text 1-1
SB507
AT ROOF
VAULT#5.2VAULT#5.3
AT FD
N
AT R
O
O F
SS130
SS131
AT FDN
AT ROOF
SS130
SS131
7.5'
VAULT#5.1
EX PIT#5
AT FDN AT ROOFSS130
SS133
AT FDN
AT ROOF
SS130
SS131
SS133
VAULT#5.1VAULT#5.2VAULT#5.3
EX PIT#5
VAULT#9.2
VAULT#9.1
PLAN NOTES
1. SEE SI001 FOR GENERAL STRUCTURAL NOTES AND ABBREVIATIONS.
2. REFER TO CIVIL DRAWINGS FOR BOX CONDUIT, TUNNEL AND VAULT
ELEVATIONS AND LOCATIONS.
3. CONTRACTOR TO VERIFY EXISTING CONDITIONS, REPORT ANY
DISCREPANCIES TO ENGINEER FOR RESOLUTION.
4. REFER TO EARTH WORK SPECIFICATIONS FOR BOX CONDUIT, TUNNEL
AND VAULT EXCAVATION.
5. CONTRACTOR TO PROVIDE TEMPORARY SHORING DURING
EXCAVATION ADJACENT TO EXISTING BUILDING STRUCTURES.
SHORING SYSTEM TO BE DESIGNED BY SHORING CONTRACTOR.
6. SEE CIVIL, MECHANICAL AND PLUMBING DRAWINGS FOR SUMP
SYSTEM
7. SEE STRUCTURAL FOR WATERPROOFING INFORMATION.
8. ALL MEMBERS AND CONNECTIONS AT PIPE SUPPORT ANCHOR POINTS
IN THE BOX CONDUIT, TUNNEL, AND VAULTS ARE SHOWN AND
DESIGNED IN THE MECHANICAL DRAWINGS. REFER TO SPEC SECTION
230511,232211 AND 336300 FOR ADDITIONAL INFORMATION.
9. PROVIDE 10" SLAB ON GRADE FOR NEW VAULTS 5.1, 5.2, 9.1,9.2. SIZE
OF PAD TO BE 16' X 13'. COORDINATE WITH MECHANICAL AND STEM
EXTENSIONS LOCATIONS. PROVIDE 6FT HIGH CHAIN LINK FENCING OF
APPROXIMATELY 12' X 15' FOR ALL NEW VAULTS INCLUDING 5.3.
10. PROVIDE 10" SLAB ON GRADE EQUAL TO THE HEIGHT OF THE VAULT
TOP FOR NEW SUMP PUMP CONTROL PANELS FOR ALL EXISTING
VAULTS 6-8-10-11-12. PROVIDE 6FT HIGH CHAIN LINK FENCING FOR ALL
EXISTING VAULTS 6-8-10-11-12 AROUND SUMP PUMP CONTROL
PANELS.
11. CHAIN-LINK WITH BLACK POLYMER COATED STEEL, 6' HIGH, NO
BARBED WIRE, SWING GATES WILL SWING OUT, SINGLE-SWING TYPE.
12. “TEMPORARY” CHAIN-LINK GATE AT 5TH AVE./17TH AVE. INTERSECTION
WILL BE DOUBLE-SWING TYPE
SS200
STRUCTURAL SITE PLAN- CLIN 2A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
POC: Aslam Husain
REPLACE STEAM PIPE-
SOUTH LEG
Edward Hines Jr. VAMC Hines, Illinois
578-17-027
221,217,1 Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
12/16/22
4/14/202230% SCHEMATIC DESIGN
P: 937-224-0861 www.heapy.com
PROJECT NO. STATE COA FIRM
NO.
2017-05127…