S02. Drawings - HVAC.pdf

PDF 9 MB Posted

Attached to
Expand Primary Care for Pact Realignment Federal contract opportunity
Solicitation number
36C25020B0060_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This is a solicitation for a construction project to expand primary care at the Louis Stokes Cleveland VA Medical Center. The project scope includes adding 12,000 square feet of space across three floors by expanding into VA-owned land adjacent to an existing ambulatory care facility. The contractor will provide all labor, equipment, and supervision to complete the expansion. The project value is estimated between $10-15 million. The NAICS code is 236220 and business size standard is $39.5 million. The site visit will be conducted on specified dates in accordance with social distancing guidelines. The cut-off for requests for information is August 12, 2021. This project is fully set aside for Service-Disabled Veteran Owned Small Businesses. Offerors must be verified in VETBIZ and registered in SAM by the due date and award date to be eligible.

View the file

Other files for this federal contract opportunity

Other files attached to Expand Primary Care for Pact Realignment, newest first.
File Type Posted
S02. Solicitation 36C25020B0060_1.pdf PDF
S02. Wage Determination.pdf PDF
S02. Bid Opening Instructions.pdf PDF
S02. BID ISSUE - SPECIFICATIONS.pdf PDF
S02. Brand Name or Equal Memo 2020-05-06.pdf PDF
S02. Drawing - 1-H27 - Basement Plan - Zoning.pdf PDF
S02. Drawing - 1-H54 - Basement Plan - Mechanical Room.pdf PDF
S02. Drawing - Pre-Testing Reference Update.pdf PDF
S02. Drawings - SITE LANDSCAPE.pdf PDF
S02. Drawings - STRUCTURAL.pdf PDF
S02. Sole Source - Tridium - 2020-05-07_Redacted.pdf PDF
S02. Sole Source - Corbin Russwin Door Lock - 2020-05-07_Redacted.pdf PDF
S02. Safety.docx DOCX document
S02. RFI Form.docx DOCX document
S02. Drawing - 1-H46 - Second Floor Plan - ACC South.pdf PDF
S02. Drawing - Outpatient Pharmacy Exhaust - EF-52.pdf PDF
S02. Drawings - ELECTRICAL.pdf PDF
S02. Drawings - PLUMBING.pdf PDF
S02. Drawings - RENDERINGS.pdf PDF
S02. Sole Source - Notifier Fire Alarm - 2020-05-07_Redacted.pdf PDF
S02. Sole Source - Hill-Rom Nurse Call - 2020-05-07_Redacted.pdf PDF
S02. Drawing - 1-H28 - First Floor Plan - Zoning.pdf PDF
S02. Drawing - 1-H29 - Second Floor Plan - Zoning.pdf PDF
S02. Drawing - 1-H34 - First Floor Plan - ACC North.pdf PDF
S02. Drawing - 1-H36 - First Floor Plan - ACC South.pdf PDF
S02. Drawing - 1-H44 - Second Floor Plan - ACC North.pdf PDF
S02. VAMC Health Requirements.pdf PDF
S02. VA NOTICE OF LIMITATIONS ON SUBCONTRACTING.docx DOCX document
S02. Sole Source - Lenel - 2020-05-07_Redacted.pdf PDF
S02. Brand Name Spreadsheet 2020-05-07.pdf PDF
S02. Calculation of Self-Performed and Sub-Contracted Work.docx DOCX document
S02. Drawings - ARCHITECURAL.pdf PDF
S02. Drawings - CIVIL.pdf PDF
S02. Drawings - FIRE PROTECTION.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESCRIPTIONABBREVIATION SYMBOL

HWS

HWR

CWS

CWR

LPS

LPC

MPS

MPC

HPS

HPC

CPD

CD

MIN. GPM

MIN. CFM

XXX

CFM

B1 2 1/

FSD

1 2/

A.D.A.D.

HVAC SYMBOL LEGEND

HWS HEATING WATER SUPPLY

HWR HEATING WATER RETURN

CWS CHILLED WATER SUPPLY

CWR CHILLED WATER RETURN

LPS LOW PRESSURE STEAM SUPPLY (15# OR LESS)

LPC LOW PRESSURE STEAM CONDENSATE RETURN (15# OR LESS)

MPS MEDIUM PRESSURE STEAM SUPPLY (16# TO 75#)

MPC MEDIUM PRESSURE STEAM CONDENSATE RETURN (16# TO 75#)

HPS HIGH PRESSURE STEAM SUPPLY (76# OR MORE)

HPC HIGH PRESSURE STEAM CONDENSATE RETURN (76# OR MORE)

CPD STEAM CONDENSATE PUMPED DISCHARGE

CD A/C CONDENSATE DRAIN

GATE VALVE

GLOBE VALVE

BALL VALVE

BALANCE VALVE (SEE SPECIFICATIONS)

CHECK VALVE (SWING)

SPRV STEAM PRESSURE REGULATING VALVE

BUTTERFLY VALVE

RV RELIEF OR SAFETY VALVE

TWO WAY CONTROL VALVE

T STEAM TRAP

CONCENTRIC REDUCER/INCREASER

STRAINER WITH BLOWDOWN

UNION

FLANGED UNION

THERMOSTAT

THERMOMETER/TEMPERATURE GAUGE

PRESSURE GAUGE WITH GAUGE COCK AND SYPHON (STEAM)

PRESSURE GAUGE WITH BALL VALVE (WATER)

DRIP PAN ELBOW

DIFFUSER, REGISTER OR GRILLE (SEE SCHEDULE)

DUCTWORK INSULATION AND MATERIAL (SEE SCHEDULE)

TERMINAL UNIT (SEE SCHEDULE)

LOUVERS (SEE SCHEDULE)

CODED NOTE (SEE SCHEDULE)

E.C. E.C. ELECTRICAL CONTRACTOR

F.P.C. F.P.C. FIRE PROTECTION CONTRACTOR

G.C. G.C. GENERAL CONTRACTOR

H.C. H.C. HVAC CONTRACTOR

P.C. P.C. PLUMBING CONTRACTOR

T.C.C. T.C.C. TEMPERATURE CONTROL SUB-CONTRACTOR

A.D. A.D. ACCESS DOOR

A.F.F. A.F.F. ABOVE FINISHED FLOOR

A.L. A.L. ACTIVE LENGTH

MFR. MFR. MANUFACTURER

N.O. N.O. NORMALLY OPEN

N.C. N.C. NORMALLY CLOSED

TYP. TYP. TYPICAL

E.A. E.A. EXHAUST AIR

R.A. R.A. RETURN AIR

S.A. S.A. SUPPLY AIR

M.O.B.D. M.O.B.D. MANUAL OPPOSED BLADE DAMPER

O.B.D. O.B.D. OPPOSED BLADE DAMPER

FLOW DIRECTION INDICATOR (LIQUID)

FLOW DIRECTION INDICATOR (VAPOR) W/ CFM QUANTITY GIVEN

11/2B 1-1/2 HOUR TYPE B FIRE DAMPER

11/2FSD 1-1/2 HOUR COMBINATION FIRE/SMOKE DAMPER

ACCESS DOOR IN BOTTOM OF DUCT OR SIDE OF DUCT

90° ELBOW WITH TURNING VANES

SQUARE-TO-ROUND DUCT TRANSITION

TERMINAL UNIT WITH FLEXIBLE CONNECTION, SOUND ATTENUATOR AND REHEAT COIL

S.A. SOUND ATTENUATOR

MANUAL BALANCING DAMPER

AUTOMATIC CONTROL DAMPER

INDICATES TIE INTO EXISTING

INDICATES REMOVE TO POINT FOR RECONNECTION

INDICATES REMOVE TO POINT AND CAP

HVAC DEMOLITION GENERAL NOTES

1. THE GENERAL NOTES LISTED HERE APPLY TO ALL HVAC DEMOLITION DRAWINGS IN ADDITION TO ANY ADDITIONAL DEMOLITION DRAWING NOTES ON THE INDIVIDUAL DEMOLITION DRAWINGS.

2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.

3. FIELD VERIFY EXISTING CONDITIONS.

4. COORDINATE WITH GENERAL TRADES WORK, PLUMBING WORK, FIRE PROTECTION WORK,

ELECTRICAL WORK AND OTHER WORK.

5. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT

PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE,

DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY

FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE

PROPER SCALE AND THOSE DRAWINGS THAT HAVE BEEN PLOTTED.

6. PHASING - SEE DIVISION 1 PROJECT SPECIFICATION PHASING DOCUMENTS FOR SPECIFIC

PHASING INSTRUCTIONS. COORDINATE SHUT-DOWN OF ANY UTILITY IN ADVANCE WITH THE

OWNER. ACCOMPLISH DRAIN DOWN AND RE-FILL OF PIPING SYSTEMS AS REQUIRED. UNLESS

OTHERWISE SPECIFICALLY INDICATED, EXISTING CHILLED WATER SYSTEMS SHALL NOT BE

DISRUPTED DURING THE COOLING SEASON, AND HEATING SYSTEMS SHALL NOT BE DISRUPTED

WHEN REQUIRED FOR OCCUPANT COMFORT OR BUILDING FREEZE PROTECTION.

7. DARK, DASHED LINES INDICATE PIPING, DUCTWORK AND EQUIPMENT TO BE REMOVED.

8. SEE SPECIFICATIONS FOR GENERAL CUTTING AND PATCHING REQUIREMENTS REQUIRED

UNDER DEMOLITION. ALSO SEE DRAWINGS FOR MORE SPECIFIC REQUIREMENTS.

9. SEE SPECIFICATIONS FOR SALVAGE RIGHTS TO ANY EQUIPMENT OR MATERIALS BEING

REMOVED.

10. REMOVE ALL HANGERS AND SUPPORTS SERVING PIPING, DUCTWORK AND EQUIPMENT BEING

DEMOLISHED. PROVIDE AND/OR ADJUST EXISTING HANGERS TO SUPPORT ANY REMAINING

PIPING, DUCTWORK, OR EQUIPMENT ADJACENT TO DEMOLISHED.

11. CAP ALL REMAINING ACTIVE PIPING WITH SIMILAR MATERIALS TO MATCH EXISTING

WATERTIGHT. PIPE ENDS INDICATED TO BE CAPPED ARE NOT TO BE CRIMPED. INSULATED PIPING

SHALL BE INSULATED AT CAP WITH MATERIALS SPECIFIED FOR NEW WORK.

12. CAP ALL REMAINING ACTIVE DUCTWORK WITH SIMILAR MATERIALS TO MATCH EXISTING AND

SEALED AIRTIGHT. INSULATED DUCTWORK SHALL BE INSULATED AT CAP WITH MATERIALS

SPECIFIED FOR NEW WORK.

13. REMOVE ALL THERMOSTATS, TEMPERATURE CONTROL WIRING AND PIPING FROM

DEMOLISHED EQUIPMENT BACK TO MAIN SOURCE AND CAP CONTROL AIR PIPING AIRTIGHT.

CRIMPING SHALL NOT BE CONSIDERED ADEQUATE.

14. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL/REINSTALLATION OF

CEILING ASSOCIATED WITH DEMOLITION OF PIPING, DUCTWORK, AND EQUIPMENT. THE HVAC

CONTRACTOR SHALL TEMPORARILY SUPPORT ALL ASSOCIATED CEILING EQUIPMENT SUCH AS

LIGHTS, SMOKE DETECTORS, ETC. AS REQUIRED FOR THIS WORK.

15. WHERE EXISTING PIPING IS MAINTAINED AT WALLS SHOWN TO BE DEMOLISHED,

CONTRACTOR TO REMOVE ABANDONED SLEEVES ASSEMBLIES AND ANY ASSOCIATED

FIRESTOPPING MATERIALS ON PIPING. PIPING INSULATION WITHIN AND AROUND THE SLEEVE

ASSEMBLY IS TO BE REMOVED AND REPLACED WITH SIMILAR INSULATION MATERIALS, MATCHING

EXISTING.

HVAC NEW WORK GENERAL NOTES

1. THE GENERAL NOTES LISTED HERE APPLY TO ALL HVAC DRAWINGS IN ADDITION TO ANY

ADDITIONAL DRAWING NOTES ON THE INDIVIDUAL DRAWINGS.

2. REFER ALSO TO DUCTWORK MATERIAL SCHEDULE AND NOTES FOR ADDITIONAL GENERAL

NOTES APPLICABLE TO DUCTWORK.

3. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.

4. FIELD VERIFY EXISTING CONDITIONS.

5. COORDINATE WITH GENERAL TRADES WORK, PLUMBING WORK, FIRE PROTECTION WORK,

ELECTRICAL WORK AND OTHER WORK.

6. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT

PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE,

DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY

FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE

PROPER SCALE AND THOSE DRAWINGS THAT HAVE BEEN PLOTTED.

7. THE MECHANICAL DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW

EXACT LOCATION OF EQUIPMENT, PIPING AND DUCTWORK UNLESS DIMENSIONS ARE GIVEN OR

OTHERWISE IMPLIED FOR CLEARANCES, ETC. PIPING, DUCTWORK AND MECHANICAL EQUIPMENT

ARE TO BE INSTALLED ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN

MIND ACTUAL BUILDING CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK.

CONTRACTORS IN THEIR BIDS ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS AND

OTHER RELATED WORK NECESSARY TO PROVIDE MINOR OFFSETS IN MECHANICAL WORK AS

REQUIRED TO AVOID CONFLICT WITH OTHER WORK ON THIS PROJECT, OR AS REQUIRED IN

ORDER TO OBTAIN MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN SPACES.

8. PHASING - SEE DIVISION 1 PROJECT SPECIFICATION PHASING DOCUMENTS FOR SPECIFIC

PHASING INSTRUCTIONS. COORDINATE SHUT-DOWN OF ANY UTILITY IN ADVANCE WITH THE

OWNER. ACCOMPLISH DRAIN DOWN AND RE-FILL OF PIPING SYSTEMS AS REQUIRED. UNLESS

OTHERWISE SPECIFICALLY INDICATED, EXISTING CHILLED WATER SYSTEMS SHALL NOT BE

DISRUPTED DURING THE COOLING SEASON, AND HEATING SYSTEMS SHALL NOT BE DISRUPTED

WHEN REQUIRED FOR OCCUPANT COMFORT OR BUILDING FREEZE PROTECTION.

9. MAINTAIN REQUIRED RIGGING ACCESS CLEARANCES. COORDINATE CLEARANCE

REQUIREMENTS WITH OTHER TRADES.

10. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED

STRUCTURES. SEE DETAILS AND SPECIFICATIONS FOR PIPE PENETRATION SEAL

REQUIREMENTS.

11. H.C. IS TO COORDINATE ALL MASONRY PENETRATION LOCATIONS AND SIZES WITH G.C.

12. COORDINATE EXACT POSITIONING OF FLOOR DRAINS WITH PLUMBING CONTRACTOR TO

SERVE HVAC EQUIPMENT AS INTENDED, AND TO AVOID TRIPPING HAZARDS WITH ABOVE FLOOR

DRAIN PIPING.

13. DO NOT ROUTE DUCTWORK OR PIPING OVER ELECTRICAL EQUIPMENT.

14. BALANCE AIR QUANTITY FOR RETURN AIR INLETS TO EQUAL THE SUM OF SUPPLY AIR

INTRODUCED TO THE SPACE, UNLESS NOTED OTHERWISE.

15. UNLESS OTHERWISE INDICATED, ALL PIPING TO RUN GENERALLY BELOW DUCTWORK FOR

ACCESS TO VALVING. DO NOT OBSTRUCT EQUIPMENT OR ACCESS DOORS. AVOID DUCTWORK

OVER LIGHTS WHEREVER POSSIBLE.

16. EQUIPMENT CONNECTION ARRANGEMENTS, FLANGES, UNIONS, VALVING, ETC. ARE NOT

TYPICALLY SHOWN ON PLAN VIEWS. REFER TO DETAILS AND FLOW DIAGRAMS FOR

REQUIREMENTS. INSTALL ALL VALVES AND OTHER ITEMS REQUIRING OR FACILITATING

MAINTENANCE IN ACCESSIBLE LOCATIONS, AND SO AS TO NOT OBSTRUCT MAINTENANCE ON

EQUIPMENT SERVED.

17. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE SO THERE

WILL BE COUNTER FLOW BETWEEN WATER AND AIR.

18. NOT ALL AIR VENTS AND DRAINS HAVE BEEN SHOWN ON PIPING AS THEIR REQUIRED

LOCATION DEPENDS ON THE PIPING INSTALLATION. REFER TO SPECIFICATIONS FOR

REQUIREMENTS OF PIPING AIR VENTS AND DRAINS. PROVIDE AIR VENTS IN ALL HIGH POINTS AND

DRAIN VALVES AT ALL LOW POINTS IN PIPING SYSTEM.

19. SEE TEMPERATURE CONTROL DRAWINGS AND COORDINATE WITH TEMPERATURE CONTROL

CONTRACTORS FOR INSTRUMENTATION DEVICES REQUIRED TO BE INSTALLED IN PIPING AND

DUCTWORK, TOGETHER WITH NECESSARY CLEARANCES FOR SAME.

20. ALL HWS AND HWR BRANCH CONNECTIONS TO HEATING EQUIPMENT, TERMINAL UNITS AND

RADIANT PANELS TO BE 3/4" UNLESS OTHERWISE NOTED.

21. NO "BULL-HEAD" TEES ARE PERMITTED IN PIPING. FLOW IS NOT PERMITTED TO BE IN

OPPOSING DIRECTIONS IN THE SAME TEE FITTING.

22. ALL AIR TERMINAL UNITS, HEATING TERMINALS AND REHEAT COILS SHALL BE PROVIDED WITH

WALL-MOUNTED THERMOSTATS UNLESS NOTED ON THE PLANS OR SPECIFICATIONS TO BE

EQUIPPED WITH INTEGRAL THERMOSTATS. REFER TO PLANS FOR APPROXIMATE THERMOSTAT

LOCATIONS - COORDINATE WITH OTHER TRADES. IF A THERMOSTAT IS NOT SHOWN ON THE

PLANS, COORDINATE LOCATION WITH ENGINEER. CONTRACTOR SHALL SUBMIT A FLOOR PLAN

WITH APPROXIMATE LOCATIONS OF ALL THERMOSTATS.

OUTDOOR DESIGN

TEMPERATURES

(89.4°F Db SUMMER, 73.6°F Wb SUMMER, 4.6°F Db WINTER)

DESIGN ALTITUDE: 650 FT.

HVAC DESIGN DATA

INDOOR AREA DESIGN CONDITIONS

SUMMER WINTER

Db °F

MAX

RELATIVE

HUMIDITY

Db °F MIN RELATIVE

HUMIDITY (%)

WAITING ROOM 75 60 70 20

EXAM ROOM 75 60 70 20

CORRIDOR 75 60 70 20

OFFICE 75 60 70 20

BREAK ROOM 75 60 70 20

CONFERENCE ROOM 75 60 70 20

TOILET ROOM NA NA NA NA

CLEAN UTILITY/STORAGE ROOM NA NA NA NA

EXTERIOR STAIRS NA NA 50 NA

HOUSEKEEPING CLOSET NA NA NA NA

AIR HANDLING EQUIPMENT ROOM NA NA 50 NA

SOILED UTILITY AND STORAGE NA NA NA NA

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:0

PM

H-001

HVAC GENERAL NOTES AND SYMBOL

LEGEND

EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS SRP

BID ISSUE SUBMISSION

8.1.21Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19 100% CD's SUBMISSION 2.14.20

BID ISSUE SUBMISSION 8.1.21

NOTES:

FLOOR SECTION

WALL SECTION

PIPE INSULATION

(WHERE SPECIFIED)

1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN TESTED IN

ACCORDANCE WITH U.L. 1479 OR ASTM E814.

2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING

MATERIALS AND U.L. SYSTEMS.

3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT

CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.

4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION

RESULTING FROM HIS WORK.

5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ENGINEER, INCLUDING U.L. RATED SYSTEM

NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.

PENETRATING COMPONENT

SEE ARCHITECTURAL DRAWINGS

FOR WALL CONSTRUCTION AND

FIRE RATING

SEAL JOINT BETWEEN SLEEVE

AND FLOOR SLAB WITH MIN.

1/2" BEAD FIRESTOP CAULK

PIPE SLEEVE (SLEEVE TO

EXTEND 2" ABOVE FLOOR IN

MECHANICAL EQUIPMENT ROOMS)

FURNISH AND INSTALL FIRESTOP

MATERIALS IN ACCORDANCE

WITH APPROPRIATE U.L.

SYSTEMS TO MAINTAIN FIRE

RESISTANCE RATING

FURNISH AND INSTALL FIRESTOP

MATERIALS IN ACCORDANCE

WITH APPROPRIATE U.L.

SYSTEMS TO MAINTAIN FIRE

RESISTANCE RATING

DAMMING MATERIAL

(PER U.L. TESTED

SYSTEM DESIGN)

PIPE SLEEVE

PENETRATING COMPONENT

FLOOR SLAB; SEE

ARCHITECTURAL DRAWINGS FOR

FLOOR CONSTRUCTION AND

FIRE RATING

PIPE INSULATION

(WHERE SPECIFIED)

FIRESTOPPING DETAIL FOR

PENETRATIONS

THROUGH FIRE-RATED CONSTRUCTIONS

N.T.S.

INSERTION

LENGTH

STEM ADJUSTED TO SUIT EXTENDED

NECK REQUIREMENTS. SEE

SPECIFICATIONS FOR REQUIRED

INSULATION THICKNESSES.

EXTENSION NECK

(SIZE PER INSULATED

THICKNESS)

PIPE

ADJUSTABLE ANGLE

HINGE

THERMOMETER (SEE

SPECIFICATIONS FOR

REQUIREMENTS)

HALF COUPLING

NOTE:

18-36

PIPE SIZE

CENTERLINE

7" 11"

5" 7" 7"

5"

THERMOMETER AND WELL TAP DETAIL

N.T.S.

NOTE:

PIPE CL

STRUCTURAL FRAMING NOTE:

SUPPLY ADDITIONAL

SUPPORT STEEL AS REQUIRED

HEX NUTS (4 REQUIRED)

THREADED ROD (SEE

SPECIFICATIONS FOR

DIAMETER)

ADJUSTABLE CLEVIS HANGER

PIPE WITH INSULATION AND

JACKET (AS APPLICABLE).

SEE SPECIFICATIONS FOR

REQUIREMENTS.

SADDLE (SEE SPECIFICATIONS)

INSULATE VOID SPACE

BETWEEN SADDLE AND PIPE

REFER TO HANGER SPECIFICATIONS

FOR ADDITIONAL REQUIREMENTS.

BEAM CLAMP

AMBIENT TEMPERATURE)

(FOR MEDIUM HIGHER THAN

CLEVIS HANGER PIPE SUPPORT

N.T.S.

CONCRETE INSERT

STRUCTURAL

CONCRETE

NOTE:

PIPE ROLLER HANGER

INSULATE VOID BETWEEN

SADDLE AND PIPE

SADDLE (SEE SPECIFICATIONS)

INSULATION (SEE

SPECIFICATIONS FOR

REQUIREMENTS)

THREADED ROD. SEE

SPECIFICATIONS FOR

DIAMETER.

REFER TO HANGER SPECIFICATIONS

FOR ADDITIONAL REQUIREMENTS.

BEAM CLAMP

STRUCTURAL FRAMING

NOTE: SUPPLY ADDITIONAL

SUPPORT STEEL AS REQUIRED

AMBIENT TEMPERATURE)

(FOR MEDIUM HIGHER THAN

PIPE ROLLER HANGER SUPPORT

N.T.S.

CONCRETE INSERT

STRUCTURAL

CONCRETE

PIPE CL

NOTE:

STRUCTURAL FRAMING NOTE:

SUPPLY ADDITIONAL

SUPPORT STEEL AS REQUIRED

ADJUSTABLE CLEVIS HANGER

THREADED ROD (SEE SPECIFICATIONS

FOR DIAMETER)

HEX NUTS (4 REQUIRED)

PIPE WITH INSULATION AND

JACKET (AS APPLICABLE).

SEE SPECIFICATIONS FOR

REQUIREMENTS.

INSULATION PROTECTION SHIELD

CURVED SUPPORT BLOCK OR

THERMAL INSERT (SEE SPECIFICATIONS)

REFER TO HANGER SPECIFICATIONS

FOR ADDITIONAL REQUIREMENTS.

BEAM CLAMP

(FOR MEDIUM LOWER THAN

AMBIENT TEMPERATURE)

CLEVIS HANGER PIPE SUPPORT

N.T.S.

CONCRETE INSERT

STRUCTURAL

CONCRETE

NOTE:

BEAM CLAMP

THREADED ROD. SEE

SPECIFICATIONS FOR

DIAMETER.

STRUCTURAL FRAMING

NOTE: SUPPLY ADDITIONAL

SUPPORT STEEL AS REQUIRED

PIPE ROLLER HANGER

INSULATION PROTECTION SHIELD

CURVED SUPPORT BLOCK OR

THERMAL INSERT (SEE

SPECIFICATIONS)

INSULATION (SEE

SPECIFICATIONS FOR

REQUIREMENTS)

REFER TO HANGER SPECIFICATION

FOR ADDITIONAL REQUIREMENTS.

(FOR MEDIUM LOWER THAN

AMBIENT TEMPERATURE)

PIPE ROLLER HANGER SUPPORT

N.T.S.

CONCRETE INSERT

STRUCTURAL

CONCRETE

LINE SIZE 4" 6" 8" 10" 12" 14" 16" 20"18"

"B" PLATE

"C" PIPE

THREADED CONNECTION

FOR HEIGHT ADJUSTMENT

SUFFICIENT DEPTH OF

THREAD TO SUPPORT PIPING

"A" PIPE. INSULATED WHERE

SERVING INSULATED PIPING

NOTE:

FOR TERMINATED VERTICAL PIPING

DROPS, WELD PIPE SUPPORT AT

PIPE CENTERLINE.

14"x14" CONCRETE PAD TO

LEVEL, DEPTH AS REQUIRED

"B"

"C"

DIAMETER

SCH

SQUARE

2"

4"

"A"

THICKNESS

SCH

DIAMETER

1/2"

2"

3"

6"

4"

6"

6"

8"

6"

8"

1/2"

3"

1/2"

4"

1/2"

6"

1/2"

6"

GROUT AND ANCHOR BOLT

TO BASE

TACKWELD, WELD SIZE TO

EQUAL THINNEST MATERIAL

TO BE WELDED

WELD

CL

8"

10"

8"

10"

10"

12"

8"

10" 5/8"

5/8"

8"

5/8"

8"

3/4"

10"

8"

FLOOR PIPE ELBOW SUPPORT

N.T.S.

STRAINER BLOW DOWN

GLOBE VALVE

GATE VALVE

TO CONDENSATE

RETURN MAIN - SEE

PROJECT PLANS

UNION

INVERTED BUCKET

TRAP

UNION

CHECK VALVE

GATE VALVE

CONDENSATE

FLOW

NIPPLE

NIPPLE

1/2"

STRAINER

STEAM MAIN

STEAM FLOW

PITCH DOWN

SEE PLANS FOR PIPE

SIZES AND DRIP TRAP

LOCATIONS.

TEST GLOBE VALVE

NOTE:

DIRT LEG

CAP OR BLIND

FLANGE

TRAP TEE

DETAIL OF THE MEDIUM AND HIGH PRESSURE DRIP TRAP ASSEMBLY

N.T.S.

NOTE:

AIR

FLOW

1. COMBINATION FIRE AND SMOKE

DAMPERS TO BE U.L. LABELED.

2. SEE SPECIFICATIONS FOR

DAMPER TYPE.

FIRE RATED

WALL/AND/ OR SMOKE

BARRIER

1/4" CLEARANCE ALL

FOUR SIDES (SEAL WITH

FIRE RESISTANT CAULKING)

NEGATOR SPRING

ACCESS DOOR. SEE PLANS

FOR APPROXIMATE LOCATION.

LOCATE FOR FUSIBLE LINK

MAINTENANCE AND SMOKE

DETECTOR INSPECTION.

PROVIDE MULTIPLE ACCESS

DOORS WHERE REQUIRED.

DUCTWRAP INSULATION SEALED

AT SLEEVE WITH TAPE (FOR

INSULATED DUCTS ONLY)

SEAL CONTINUOUSLY AROUND

DOWNSTREAM PERIMETER OF

DAMPER WITH FIRE RESISTANT

CAULKING MATERIAL

MINIMUM 1-1/2"x1-1/2"x14 GA.

ANGLES, TACKWELD TO SLEEVE 8"

O.C. (DO NOT ATTACH TO WALL) 1"

MINIMUM OVERLAP ALL FOUR SIDES

LINTELS AS REQUIREDATTACH DAMPER TO 16

GA. BLACK STEEL SLEEVE

PER MANUFACTURERS

REQUIREMENTS OR PROVIDE

INTEGRAL SLEEVE

SLEEVE TO BE 6" WIDER

THAN WALL

ATTACH DUCT TO SLEEVE

WITH BREAKAWAY

CONNECTIONS AND SEAL

WITH MASTIC

FUSIBLE LINK WITH LOCK

SMOKE DETECTOR

(BY E.C.)

SEE DUCT MATERIAL SCHEDULE AND

SPECIFICATIONS FOR INSULATION

REQUIREMENTS

DAMPER ACTUATOR

OUTSIDE OF AIRSTREAM

(SEE SPECIFICATIONS FOR

REQUIREMENTS)

WALL MOUNTED - RECTANGULAR DUCT

COMBINATION FIRE/SMOKE DAMPER

N.T.S.

CHECK VALVE (TYP)

GATE VALVE (TYP)

UNION (TYP)

REDUCER AS REQUIRED

USE ELBOWS 45° OR

LESS

1. MOUNT PUMP LEVEL ON EQUIPMENT PAD IN PIT.

2. SEE PLANS FOR CONTINUATION OF PIPING AND PIPE SIZING.

3. ROUTE VENT AS INDICATED ON PLANS PITCHED UPWARD WITHOUT

POCKETS.

4. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS, INCLUDING

INSULATION.

5. CONNECT ALL PIPING TO PUMP WITH UNIONS OR FLANGES.

NOTES:

SIGHT GLASS

FLOOR LINE

CONDENSATE

RETURN FROM RECEIVER

PRESSURE GAUGE

WITH GAUGE COCK

AND SIPHON

DIRT LEG WITH END

CAP

TO STEAM PIPING

SOURCE

3/4" DRAIN VALVE WITH

HOSE ADAPTOR

AND CAP

CPD

DN

STEAM POWERED CONDENSATE

RETURN PUMP PIPING DETAIL

N.T.S.

T-2

DRAIN HOLE

DRAIN TO SPILL INTO

FLOOR DRAIN

DRAIN

CONNECT TO DRIP

PAN ELBOW DRAIN

CONNECTION AND

INCREASE AS

REQUIRED

DRIP PAN ELBOW

SIZED TO ACCEPT

SAFETY VALVE

OUTLET SIZE

DRAIN GAP

OUTLET FLANGE

OR SCREWED

CONNECTION

STEAM SAFETY

VALVE

SAFETY VALVE

DISCHARGE PIPING.

SEE PLANS FOR

SIZE AND ROUTING.

SUPPORT OVERHEAD

1- 1/

2" M

IN

STEAM SAFETY VALVE DRIP PAN ELBOW DETAIL

N.T.S.

RELIEF VALVE

DISCHARGE PIPE

SIZE "A"

DESIGNER NOTES:

DISCHARGE

PIPE SIZE "B"

2" 3"

"B"

"A"

NOTES:

J

1. SEE SPECIFICATIONS FOR ADDITIONAL FLOW MEASURING STATION

REQUIREMENTS.

2. BRANCH OUTLET AND PIPE SIZE PER MANUFACTURER'S RECOMMENDATIONS.

3. SEE MANUFACTURER'S INSTALLATION REQUIREMENTS WHICH MAY DIFFER OR

EXCEED THE REQUIREMENTS OF THIS DETAIL.

4. MAINTAIN MANUFACTURER'S RECOMMENDED UPSTREAM AND DOWNSTREAM

CLEARANCES FOR LOCATIONS OF FLOW MEASURING STATIONS. WHERE THIS IS

NOT POSSIBLE, REVIEW SUCH LOCATIONS WITH ENGINEER.

5. FOR FLOW MEASURING STATIONS MOUNTED IN VERTICAL PIPING, ORIENT

COUPLING DIRECTION SO AS TO NOT OBSTRUCT ACCESS AROUND PIPING.

6. FOR FLOW MEASURING STATIONS MOUNTED IN HORIZONTAL PIPING, ORIENT

COUPLING IN VERTICAL IF POSSIBLE, BUT IN ALL CASES ORIENT COUPLING TO

ALLOW REMOVAL OF FLOW ELEMENT.

CONTROL WIRING

TO CONTROL PANEL

JUNCTION BOX

WATERTIGHT CONDUIT

1/3 PIPE DIA.

OVER 4" PIPE

WELD

3000# HALF

COUPLING

BRANCH OUTLET

2" FULL PORT

BALL VALVE

MIN

5-1/2"

FLOW ELEMENT

FLOW MEASURING STATION INSTALLATION DETAIL

N.T.S.

COIL

BALANCE VALVE

UNION (TYP.)

BALL VALVE

AIR VENT

CONTROL VALVE

FANS AND MOTOR

FILTER

SECURE TO STRUCTURE

PER MANUFACTURER'S

RECOMMENDATIONS

COIL

1. SEE PLANS FOR COIL HAND CONNECTION

LOCATION, PIPE SIZES AND LOCATIONS.

2. SEE SPECIFICATIONS AND DRAWINGS FOR

CONTROL VALVE REQUIREMENTS.

3. PIPING MUST BE CONCEALED WHEREVER

POSSIBLE.

NOTES:

HYDRONIC WITH 2-WAY CONTROL VALVE

SURFACE MOUNTED CABINET HEATER

N.T.S.

GLOBE VALVE

REDUCER (TYPICAL)

IF REQUIRED

PILOT CONTROL LINE

VENT TO

ATMOSPHERE

SEE "STEAM SAFETY

VALVE DIP PAN ELBOW

DETAIL"

SV-1

3"

SEE PLANS FOR

CONTINUATION

3"

PRESSURE GAUGE (TYP.)

SIPHON (TYP.)

3"

PRESSURE REGULATING VALVE. INSTALL ORIFICE

DIRECTLY DOWNSTREAM OF STEAM REGULATING

VALVE WITH FLANGED REDUCER. SEE SCHEDULE

FOR MORE INFORMATION.

1-1/2"

SPRV-1

3/4"

3"

1-1/2"

STEAM PRESSURE REDUCING STATION

N.T.S.

V

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:4

PM

H-002

HVAC DETAILS EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS SRP

BID ISSUE SUBMISSION

8.1.21Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19

#18 GAUGE SHEET METAL

HOUSING BY MECHANICAL

CONTRACTOR, CONTINUOUS

AROUND PERIMETER

MINIMAL EXTENSION

INTO ROOM

COMPLETE GALVANIZED

PERIMETER ANGLE

CLOSURE BY MECHANICAL

CONTRACTOR. CAULK AND

SEAL WEATHERTIGHT.

WALL COLLAR BY

FAN MFR.

OSHA APPROVED

GUARD BY FAN MFR.

INSULATED BLADE BACKDRAFT

DAMPER BY FAN MFG.

WALL MOUNTED PROP. FAN

N.T.S.

(RF-57)

FLOW

AIR

FIRE RATED

WALL/AND/ OR SMOKE

BARRIER

1/4" CLEARANCE ALL FOUR SIDES

(SEAL WITH FIRE RESISTANT

CAULKING)

NEGATOR SPRING

ACCESS DOOR. SEE PLANS FOR

APPROXIMATE LOCATION. LOCATE

FOR FUSIBLE LINK MAINTENANCE

AND SMOKE DETECTOR

INSPECTION. PROVIDE MULTIPLE

ACCESS DOORS WHERE REQUIRED.

SMOKE DETECTOR (BY

E.C.)

SEAL CONTINUOUSLY

AROUND DOWNSTREAM

PERIMETER OF DAMPER WITH

FIRE RESISTANT CAULKING

MATERIAL

MINIMUM 1-1/2"x1-1/2"x14 GA.

ANGLES, TACKWELD TO SLEEVE 8"

O.C. (DO NOT ATTACH TO WALL) 1"

MINIMUM OVERLAP ALL FOUR SIDES

LINTELS AS REQUIRED

DAMPER ACTUATOR

OUTSIDE OF AIRSTREAM

(SEE SPECIFICATIONS FOR

REQUIREMENTS)

INSULATION, SEAL ALL

LOOSE ENDS WITH TAPE

ATTACH DUCT TO SLEEVE

WITH DRAWBAND BREAKAWAY

CONNECTIONS AND SEAL WITH

MASTIC

FUSIBLE LINK WITH LOCK

SLEEVE TO BE 6"

WIDER THAN WALL

ATTACH DAMPER TO 16

GA. BLACK STEEL SLEEVE

PER MANUFACTURERS

REQUIREMENTS OR

PROVIDE INTEGRAL SLEEVE

NOTES:

1. COMBINATION FIRE AND SMOKE DAMPERS

TO BE U.L. LABELED.

2. SEE SPECIFICATIONS FOR DAMPER TYPE.

WALL MOUNTED - ROUND OR OVAL DUCT

COMBINATION FIRE/SMOKE DAMPER

N.T.S.

NOTES:

FL

O

W A

IR

1. COMBINATION FIRE AND SMOKE

DAMPERS TO BE U.L. LABELED.

2. SEE SPECIFICATIONS FOR DAMPER

TYPE.

3. SEE PLANS FOR AIR FLOW ORIENTATION.

MINIMUM 1-1/2"x1-1/2"x14 GA. ANGLES, TACKWELD TO SLEEVE 8" O.C. (DO

NOT ATTACH TO WALL) 1" MINIMUM

OVERLAP ALL FOUR SIDES

1/4" CLEARANCE ALL

FOUR SIDES (SEAL WITH

FIRE RESISTANT CAULKING)

NEGATOR SPRING

FLOOR LINE

DUCTWRAP INSULATION SEALED

AT SLEEVE WITH TAPE (FOR

INSULATED DUCTS ONLY)

ACCESS DOOR. SEE PLANS FOR

APPROXIMATE LOCATION.

LOCATE FOR FUSIBLE LINK

MAINTENANCE AND SMOKE

DETECTOR INSPECTION.

PROVIDE MULTIPLE ACCESS

DOORS WHERE REQUIRED.

SEE DUCT MATERIAL

SCHEDULE AND

SPECIFICATIONS FOR

INSULATION

REQUIREMENTS

DAMPER ACTUATOR

OUTSIDE OF AIRSTREAM

(SEE SPECIFICATIONS FOR

REQUIREMENTS)

SEAL CONTINUOUSLY

AROUND DOWNSTREAM

PERIMETER OF DAMPER WITH

FIRE RESISTANT CAULKING

MATERIAL

ATTACH DAMPER TO 16 GA.

BLACK STEEL SLEEVE

PER MANUFACTURERS

REQUIREMENTS OR

PROVIDE INTEGRAL SLEEVE

SLEEVE TO EXTEND

4" BEYOND FLOOR,

BOTH SIDES

ATTACH DUCT TO SLEEVE

WITH BREAKAWAY

CONNECTIONS AND

SEAL WITH MASTIC

FUSIBLE LINK WITH LOCK

SMOKE DETECTOR

(BY E.C.)

FLOOR MOUNTED - RECTANGULAR DUCT

COMBINATION FIRE/SMOKE DAMPER

N.T.S.

FLOW

AIR

FLOW

AIR

MOTOR AND BELT GUARD (SEE

SPECIFICATIONS); COORDINATE

LOCATION FOR BEST ACCESS

FLEXIBLE DUCT

CONNECTION (TYP.)

ROUND-TO-RECTANGULAR

TRANSITION (PER SMACNA

REQUIREMENTS - TYPICAL)

ACCESS DOOR

OUTLET SOUND ATTENUATION

(SEE PLANS AND SCHEDULES)

THRUST RESTRAINT (TYP.

BOTH SIDES)

FLANGED FAN CONNECTION (TYP.)

VIBRATION ISOLATOR (TYP.) SEE

SPECIFICATIONS FOR

REQUIREMENTS

1/2" Ø THREADED HANGER ROD

(QUANTITY PER MANUFACTURER'S

REQUIREMENTS)

PROVIDE MISCELLANEOUS STEEL

AND SUPPORT FROM

STRUCTURAL MEMBERS AS

REQUIRED

VANEAXIAL FAN

INLET SOUND ATTENUATION

(SEE PLANS AND SCHEDULES)

ACCESS DOOR

INSPECTION ACCESS DOOR -

HINGED WHERE POSSIBLE - CAM

LOCK WHERE SPACE DOES NOT

PERMIT

VANEAXIAL FAN DETAIL

N.T.S.

NOTES:

1. SET FAN DEAD LEVEL BOTH DIRECTIONS.

2. ADJUST ISOLATORS AND FLEXIBLE CONNECTIONS TO AVOID VIBRATION

TRANSMISSION.

3. MAINTAIN MAXIMUM POSSIBLE CLEARANCE UNDER FAN AND DUCTWORK

UNLESS OTHERWISE TRANSMISSION.

4. THIS DETAIL MAY NOT INDICATE ALL REQUIRED FAN OPTIONS OR EXACT

ARRANGEMENT, SEE PLANS AND SPECIFICATIONS.

HWS

STRAIGHT LENGTH

FLEXIBLE CONNECTION

(6" LONG MINIMUM,

24" LONG MAXIMUM

UNLESS OTHERWISE

INDICATED)

CONTROL ASSEMBLY

3/4" DRAIN VALVE SEE

SPECIFICATIONS

AIRFLOW

AIRFLOW

4. LOCATE HANGERS TO SUPPORT TERMINAL UNIT

AND PIPING INDEPENDENTLY.

5. LOCATE AIR VENTS IN HIGH POINTS OF MAIN

PIPING.

6. PROVIDE ACCESS DOOR UPSTREAM OF REHEAT

COIL.

1. ALL PIPING AND VALVING SIZES TO MATCH RUNOUT

SIZE INDICATED ON PLANS.

2. SUSPEND COIL LEVEL AND PLUMB TO PERMIT FULL

DRAINAGE.

3. SEE PLANS FOR COIL HAND CONNECTIONS.

NOTES:

BALL VALVE

UNION (TYP.)

TWO-WAY CONTROL

VALVE

BALANCE VALVE

LOW VELOCITY SUPPLY

AIR DUCT

REHEAT COIL SIZED TO

MATCH TERMINAL UNIT

UNLESS OTHERWISE

INDICATED

SOUND ATTENUATOR

SECTION BY VAV

TERMINAL UNIT MFR.

SECURE WITH BANDS.

COVER EXPOSED

INSULATION WITH DUCT

TAPE (TYP.)

SUPPLY AIR DUCT

(SEE PLANS FOR

TYPE AND ROUTING)

VAV TERMINAL UNIT DETAIL

N.T.S.

SOUND ATTENUATOR AND HYDRONIC REHEAT COIL WITH 2-WAY CONTROL VALVE

ACCESS DOOR

HWR

AIR VENT AT HIGH POINT

STRAINER WITH BLOWDOWN VALVE

(TYPICAL)

PRESSURE AND

TEMPERATURE GAUGE

CONNECTOR PLUG (TYPICAL).

TRANSITION PIPING TO

COIL CONNECTION SIZE

AS NEEDED

COIL DRAIN

FLOW

PRESSURE GAUGE WITH

SHUT-OFF VALVE

(TYPICAL)

3/4" VENT WITH BALL

VALVE AND CAP

(TYPICAL)

AIR VENT AT HIGH POINT

UNION OR FLANGE

(TYPICAL)

C W

R

C W

S

AIR

CWR

THERMOMETER OR

TEMPERATURE GAUGE

(SEE SPECIFICATIONS)

(TYPICAL)

COOLING COIL

3/4" DRAIN WITH HOSE

ADAPTER AND CAP

(TYPICAL)

REDUCER - IF

REQUIRED (TYPICAL)

BALANCE VALVE

(TYPICAL)

BALL VALVE FOR PIPE

SIZES 2" AND UNDER,

BUTTERFLY VALVE FOR

PIPE SIZES 2-1/2" AND

ABOVE.

TWO-WAY CONTROL VALVE

1. PIPING INSTALLATION SHALL ALLOW FOR EQUIPMENT ACCESS AND COIL PULL.

2. SCHEMATIC IS APPLICABLE TO UNITS WITH ONE COIL. IF THE UNIT HAS MULTIPLE COILS

HEADER PIPING SHALL BE FULL SIZE; EACH COIL SHALL HAVE UNIONS OR FLANGES; EACH

COIL SHALL HAVE SHUT-OFF VALVES ON THE COIL INLET AND BALANCE VALVES ON THE COIL

OUTLET; EACH COIL SHALL HAVE THERMOMETERS AND PRESSURE GAUGES ON THE COIL

INLET AND OUTLET.

3. SEE PLANS FOR PIPING DROPS AND COIL CONNECTION LOCATIONS.

NOTES:

AIR HANDLING UNIT - 2 WAY VALVE

CHILLED WATER COIL PIPING SCHEMATIC - SINGLE COIL

N.T.S.

A

AIR HANDLER PIPE

A

AC-56

AC-57

2.5" 2"

TEST PLUG

(TYPICAL)

STRAINER WITH BLOWDOWN

PITCH DN. TOWARD DRAIN

DIELECTRIC UNION

B

UNIT DRAIN PAN

A

TERMINATE OVER DRAIN AS

INDICATED ON PLANS WITH AN AIR

GAP.

PLUGGED TEE CLEANOUT (TYP.)

PIPE OPEN TO ATMOSPHERE

UNIT TYPE A B

DRAW THROUGH X/2"

BLOW THROUGH

WHERE X = POSITIVE VALUE OF STATIC PRESSURE

DIFFERENCE BETWEEN PAN SECTION AND TRAP LOCATION

X"+1"

X"+2"

1" MINIMUM

NOTES:

1. LOCATE TRAP AS CLOSE AS POSSIBLE TO AHU DRAIN OUTLET WITH BOTTOM BELOW

SUPPORT STRUCTURE.

2. SIZE OF TRAP PIPING TO BE LARGER OF

EQUIPMENT OUTLET SIZE OR DIMENSION ON PLANS.

3. SEE SPECIFICATIONS FOR INSULATION REQUIREMENTS

4. NOTIFY ENGINEER BEFORE FABRICATING IF PHYSICAL CONDITIONS PROHIBIT

INSTALLATION OF DEPTH SHOWN.

AIR HANDLING UNIT

STANDARD A/C CONDENSATE TRAP DETAIL

N.T.S.

A

AIR HANDLER PIPE

A

AC-56

AC-57

1.5" 1.25"

6" (TYP.) DRIP LEG WITH CAP

24" MIN. (TYP.)

1. SEE PLANS FOR HAND ORIENTATION, PIPE ROUTING AND

PIPE SIZING.

2. INSTALL AND SUPPORT PER MANUFACTURER'S

RECOMMENDATIONS WITH PARTICULAR ATTENTION TO LEVEL

REQUIREMENTS AND REQUIRED ABSORPTION DISTANCE.

3. TRAP ARRANGEMENT INDICATED MAY VARY WITH

MANUFACTURER. UNLESS OTHERWISE INDICATED, SIZE

TRAPS AND CONDENSATE PIPING PER MANUFACTURER'S

REQUIREMENTS.

ROUTE PIPING TO PUMP

TRAP DISCHARGE

PITCH DOWN

NOTES:

F & T TRAP BY HUMIDIFIER

MFR. (TYP.)

STEAM SUPPLY PIPING.

PROVIDE DRIP TRAPPING

ARRANGEMENTS PER PLANS

TO PROVIDE DRY STEAM TO

HUMIDIFIER.

GATE VALVE (TYP.)

STRAINER WITH BLOWDOWN

VALVE (TYP.)

REDUCER (IF REQUIRED)

INCREASER (IF REQUIRED)

CONTROL VALVE (FURNISHED BY

HUMIDIFIER MFR.)

UNION (TYP.)

PITCH DOWN

AIRFLOW

HEADER ENCLOSURE (TYP.)

HORIZONTALLY ORIENTED

STEAM PANEL TYPE HUMIDIFIER DETAIL

N.T.S.

6" M

IN

AIR HANDLING UNIT WALL

PENETRATION TO BE SEALED TO

ELIMINATE AIR LEAKS PER

MANUFACTURER'S

RECOMMENDATIONS. SEE

PLANS FOR RECOMMENDED

PENETRATION LOCATION.

PIPE SIZE TO MATCH COIL

HEADER SIZE WITH

THREADED CONNECTION AND

REMOVABLE CAP AT

BOTTOM

UNION OR FLANGE (TYP.)

AIR FLOW

LPCR PIPING

FLEXIBLE CONNECTOR

1/2" VACUUM BREAKER

(TYP. FOR 2)

GLOBE VALVE BYPASS

1% MIN. SLOPE

SLOPE

1% MIN.

SEE PLANS FOR MAIN

SIZES AND ROUTING

UNION (TYP.)

CHECK VALVE (TYP.)

TRAP IS NOT REQUIRED

DUE TO USING OF THE

RECEIVER AND PUMPING

TRAP T-2.

DAMPER MOTOR AND

DRIVE ASSEMBLY

PRESSURE GAUGE

GATE VALVE (TYP.)

STRAINER WITH BLOW DOWN

GLOBE VALVE AND CAP (TYP.)

INCREASER (IF REQUIRED)

STEAM CONTROL VALVE

REDUCER (IF REQUIRED)

SEE PLANS FOR SIZES

NOTES:

1. PIPING AND COIL SUPPORT INSTALLATION SHALL ALLOW FOR COIL PULL AND SHALL NOT OBSTRUCT UNIT

ACCESSIBILITY.

2. CLOSE OFF AREA IN AIR HANDLER AROUND COIL TO FORCE ALL AIR THROUGH COIL.

3. THIS DETAIL IS SCHEMATIC. SEE PLANS FOR ACTUAL ORIENTATION OF PIPING, VALVING, ETC.

4. SUPPORT PIPING INSIDE AIR HANDLING UNIT PER MANUFACTURER'S RECOMMENDATIONS. DO NOT SUPPORT

PIPING FROM COIL.

5. REFER TO PLANS OR SECTIONS FOR PIPE SIZES NOT INDICATED THIS DETAIL.

6. INSTALL COIL LEVEL.

AIR HANDLING UNIT - VERTICAL TUBE INTEGRAL FACE AND BY-PASS

STEAM HEATING COIL SCHEMATIC

N.T.S.

(FULL CAPACITY STEAM VALVE)

A

A

B C B

B

AIR HANDLER TRAP.

NO. A B C

PIPE TAG

AC-56

AC-57

2" 2" 2" 1" 1.5" 1.5"

T-1 T-1

FLOW

UVC EMITTER LAMP IN QUANTITY AND

SPACING DETERMINED BY FINAL MFR. IN

ACCORDANCE WITH SPECIFICATIONS

AND IN COORDINATION WITH AHU COIL

SIZING. TYP.

TOP OF AHU

COOLING COIL

1. FINAL DESIGN, QUANTITY, AND SPACING BY UVC SYSTEM MANUFACTURER.

2. CONTRACTOR SHALL MOUNT SYSTEM IN ACCORDANCE WITH MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

3. COORDINATE FINAL LOCATION OF CONTROL PANEL AND POWER SUPPLY WITH E.C.

4. ACCESS SECTION SHALL INCLUDE WIRED DOOR SWITCHES TO DE-ENERGIZE UVC

EMITTER IF DOOR IS OPENED. ACCESS SECTION SHALL ALSO INCLUDE A CAUTION SIGN ON

DOOR NOTIFYING PERSONNEL OF THE PRESENCE OF THE UVC EMITTER.

4. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

NOTES:

UVC EMITTER SCHEMATIC

N.T.S.

UVC EMITTER LAMP MOUNT PROVIDED

BY UVC SYSTEM MFR. TYP.

UVC EMITTER LAMP CONTROL PANEL

MOUNTED OUTSIDE THE AHU. MOUNT IN

ACCORDANCE WITH MFR INSTALLATION

INSTRUCTIONS. EXTEND OUTPUTS FOR

TIE IN TO BAS SYSTEM. REFER TO

TEMEPRATURE CONTROLS DRAWINGS

FOR POINTS.

BOTTOM OF AHU

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:1

PM

H-003

HVAC DETAILS EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS SRP

BID ISSUE SUBMISSION

8.1.21Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19

Hardware Points Software Points

Point Name AI AO BI BO Trend Show On

Graphic Supply Air Static Pressure x x x x

Return Airflow x x x

Supply Airflow ( Fans 1-4) 4 4 4

Outside Airflow x x x x

Supply Air Humidity x x x

Prefilter Status x x x

Final Filter Status x x x

UVC Emitter Status x x x x

Mixed Air Temp x x x

Return Air Humidity x x x

Return Air Temp x x x

Supply Air Temp x x x

Return Air Static Pressure x x

Relief Air Airflow x x

Outdoor Air Temp x x

Outside Air Humidity x x

Pre Heat Air Temp x x

Chilled Water Coil Air Temp Sensor x x

Return Fan VFD x x x

Supply Fan VFD -(1-4) 4 4 4

Return Fan VFD Speed x x x

Supply Fan VFD Speed -(1-4) 4 4 4

Preheating Steam Valve x x x

Cooling Valve x x x

Return Air Dampers x x x

Humidifier x x x

Relief Air Damper x x

Outside Air Damper x x

Bypass Damper (Steam Coil) x x

Freezestat x x x x

UVC Emitter Alarm x x x x

High Static Shutdown x x x x

Return Air Smoke Detector x x x x

Supply Air Smoke Detector x x x x

Return Fan VFD Fault x x x

Supply Fan VFD Fault -(1-4) 4 4 4

Return Fan Status x x x

Supply Fan Status (1-4) 4 4 4

Low Static Shutdown (Return Fan) x x x

Return Fan VFD HOA x x

Supply Fan VFD HOA -(1-4) 4 4

Low Static Shutdown Supply Fan x x

Return Fan Start/Stop x x x

Supply Fan Start/Stop (1-4) 4 4 4

Humidifier Enable x x

Supply Fan Isolation Damper (1-4) 4 4

Supply Air Static Pressure Setpoint x x

Return Airflow Setpoint x x

Preheating Mixed Air Temp Setpoint x x

Supply Air Temp Setpoint x x

Economizer Mixed Air Temp Setpoint x x

Outside Airflow Setpoint x x

Humidifier Setpoint x

Emergency Shutdown x x x

High Supply Air Static Pressure x

Low Supply Air Static Pressure x

Supply Fan Failure x

Supply Fan in Hand x

Supply Fan Runtime Exceeded x

Return Fan Failure x

Return Fan in Hand x

High Return Airflow x

Low Return Airflow x

High Outdoor Airflow x

Low Outdoor Airflow x

High Supply Air Temp x

Low Supply Air Temp x

High Supply Air Humidity x

Low Supply Air Humidity x

Prefilter Change Required 2 2

Final Filter Change Required x x

High Mixed Air Temp x

Low Mixed Air Temp x

High Return Air Humidity x

Low Return Air Humidity x

High Return Air Temp x

Low Return Air Temp x

High Supply Air Temp x

Low Supply Air Temp x

Chilled Water Flow Rate x x

Instantaneous Voltage: Phase to Phase x x

Instantaneous Voltage: Phase to Neutral x x

Demand KVA (Last 15 Minute Window) x x

Peak Demand with Date and Time Stamp x x

ABBREVIATION DESCRIPTION REMARKS

D-1

D-1

D-1

P

T-5

VE-9

P

VFD

TLL-1 VPS-1 SPS-2

DA-1DA-10

DA-10

DA-9

SPS-1

VFD

P

T-1 VPS-1 FSD-1

T-2

VE-5

T-1

SPS-3

T-1

(R.A.)

VE-17

H-1

H-1 (R.A.)

VE-12

T-1 H-1 (O.A.)(O.A.)

T-1 FSD-1

P

FM

UVC

CONTROL

PANEL

SUPPLY

AIR

CH

CHR

C

C

N.0.

P

C

SUPPLY

FAN

PRE-FILTER

FAN

RETURN RETURN

AIR

EXTERIOR BLDG. WALL

RELIEF

AIR

AIR

OUTDOOR

AFM-1

MPS

MPR N.C.

AFM-1

G

(S.A.)

NORMALLY OPEN

NORMALLY CLOSED

MANUFACTURER

N.O.

N.C.

MFR.

DUCT HUMIDITY SENSOR

DUCT SMOKE DETECTOR WITH AUXILIARY CONTACT

ELECTRICAL CONTRACTOR

NORMALLY OPEN (N.O.) ELECTRIC MODULATING DAMPER ACTUATOR

NORMALLY CLOSED (N.C.) ELECTRIC MODULATING DAMPER ACTUATOR

H-1

FSD-1

E.C.

DA-9

DA-10 SEE PLANS FOR VOLTAGE

SEE PLANS FOR VOLTAGE

AIRFLOW MEASURING STATION - FAN INLET TYPEAFM-1

DIFFERENTIAL PRESSURE SENSOR FOR AIRFLOW (BINARY) P

G MAGNETIC PRESSURE GAUGE SEE SPECIFICATIONS

AFM-2 AIRFLOW MEASURING STATION - DUCT MOUNTED TYPE

MPS

OPPOSED BLADE LOW LEAKAGE CONTROL DAMPERD-1

MIXED AIR DUCT TEMPERATURE SENSOR WITH EXTENDED ELEMENT

ROOM TEMPERATURE SENSOR (WITHOUT LOCAL ADJUSTABLE SETPOINT)

ROOM TEMPERATURE SENSOR (WITH LOCAL ADJUSTABLE SETPOINT)

OUTDOOR AIR TEMPERATURE SENSOR

DUCT TEMPERATURE SENSOR

STATIC PRESSURE SENSOR FOR AIRFLOW - LOW LIMIT - (ANALOG)

STATIC PRESSURE SENSOR FOR AIRFLOW - HIGH LIMIT - (ANALOG)

STATIC PRESSURE SENSOR FOR AIRFLOW (ANALOG)

T-5

T-4

T-3

T-2

T-1

SPS-3

SPS-2

SPS-1

SHIELDED

TEMPERATURE CONTROL CONTRACTORT.C.C.

FREEZESTAT WITH AUXILIARY CONTACTS AND LOCAL MANUAL RESETTLL-1

FURNISHED WITH AIRFLOW

MEASURING STATION.

SEE SCHEDULESVARIABLE FREQUENCY DRIVE (FOR MOTOR SPEED ADJUSTMENT)

ELECTRIC HUMIDIFIER CONTROL VALVE (FURNISHED WITH HUMIDIFIER)

VELOCITY PRESSURE SENSORVPS-1

VFD

VE-17

NORMALLY OPEN (N.O.) ELECTRIC MODULATING TWO-WAY HYDRONIC CONTROL VALVE

NORMALLY CLOSED (N.C.) ELECTRIC MODULATING TWO-WAY HYDRONIC CONTROL VALVE

NORMALLY OPEN (N.O.) ELECTRIC MODULATING STEAM CONTROL VALVE

NORMALLY CLOSED (N.C.) ELECTRIC TWO POSITION STEAM CONTROL VALVEVE-12

VE-9

VE-5

VE-1

AFM-2

AFM-2

INTEGRAL FACE AND

BY-PASS DAMPER BY

AIR HANDLER MFR.

(N.O.)

STEAM

HUMIDIFIER

TO RETURN AND

SUPPLY FAN

VFD SAFETY

CIRCUIT

LOCATE 2/3 DOWN

LONGEST DUCT RUN IN

LOCATION APPROVED

BY ENGINEER.

OUTDOOR AIR SENSOR

MOUNT AT A SHIELDED

LOCATION EXTERIOR TO

BUILDING. (PREFERABLY

ON THE NORTH FACE)

AWAY FROM ANY

EXHAUST OR RELIEF AIR.

TO FIRE ALARM

(SEE

ELECTRICAL

DRAWINGS)

HARDWARE TO

SAFETY CIRCUIT

TO FIRE ALARM

(SEE

ELECTRICAL

DRAWINGS)

HARDWARE TO

SAFETY CIRCUIT

T.C.C.TO PROVIDE ELECTRICAL METERING OF

UNIT MOTOR. ELECTRICAL USAGE

INFORMATION SHALL BE SENT TO THE EXISTING

BAS.

FINAL-FILTER

G

T.C.C. SHALL EXTEND OUTPUTS FROM NEW

CHILLED WATER METER AND TIE IN TO

EXISTING BAS. GRAPHICS SHALL BE UPDATED.

T.C.C. SHALL EXTEND

OUTPUTS FROM NEW UVC

EMITTER AND TIE IN TO

EXISTING BAS. GRAPHICS

SHALL BE UPDATED.

TEMPERATURE CONTROL LEGEND

AIR HANDLING UNIT AHU-48 CONTROL DIAGRAM

AHU-48 SEQUENCE OF OPERATIONS

1. RUN CONDITIONS - SCHEDULED

1.1 THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.

2. FREEZE PROTECTION

2.1 WHEN THE FREEZE STAT SENSES A TEMPERATURE BELOW 40 DEG. F THE

FOLLOWING SEQUENCE SHALL OCCUR:

2.1.1 THE UNIT SHALL SHUTDOWN AND GENERATE AN ALARM

2.1.2 THE OUTSIDE AIR AND ECONOMIZER DAMPERS SHALL CLOSE

2.1.3 STEAM PREHEAT COIL VALVE SHALL OPEN TO 100%(ADJ)

2.1.4 COOLING COIL VALVE SHALL OPEN TO 50%(ADJ)

3. HIGH/LOW STATIC SAFETY SHUTDOWN

3.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH

STATIC SHUTDOWN SIGNAL. HIGH STATIC ALARM SETPOINT SHALL BE 1" BELOW

DUCTWORK PRESSURE CLASS.

3.2 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A LOW

STATIC SHUTDOWN SIGNAL. LOW STATIC ALARM SETPOINT SHALL BE NEGATIVE 2"

S.P.

4. SMOKE DETECTION

4.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON A DETECTOR TRIP

ON RETURN AIR SMOKE DETECTOR.

5. SUPPLY FAN(S)

5.1 THE SUPPLY FAN ISOLATION DAMPER SHALL OPEN AND THE SUPPLY FAN SHALL

RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES.

TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE

(ADJ.) MINIMUM RUNTIME. MULTIPLE FANS SHALL RUN IN UNISON. IF A FAN SHOULD

FAIL, ITS ASSOCIATED ISOLATION DAMPER SHALL CLOSE AND REMAINING FANS SHALL

RAMP-UP TO MAINTAIN SETPOINT.

5.2 ALARMS:

SUPPLY FAN FAILURE

6. SUPPLY AIR DUCT STATIC PRESSURE CONTROL

6.1 THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL

MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN THE DUCT STATIC PRESSURE

SETPOINT. THE SUPPLY FAN VFD SPEED SHALL NOT DROP BELOW 30%(ADJ.). THE

INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE COORDINATE WITH THE TAB

CONTRACTOR, AND BE ADJUSTED UP DURING THE BALANCING PROCESS. THE FINAL

DUCT STATIC PRESSURE SETPOINT SHALL BE DETERMINED, SET, AND DOCUMENTED

BY THE BALANCING CONTRACTOR. THE SETPOINT SHALL BE SUFFICIENT TO MEET THE

VAV BOX AIRFLOW REQUIREMENTS DURING DESIGN CONDITIONS AND SHALL NOT BE

SET LOWER THAN 0.5".

6.2 ALARMS:

HIGH SUPPLY FAN STATIC PRESSURE

LOW SUPPLY FAN STATIC PRESSURE

SUPPLY FAN VFD FAULT

RETURN AIR TEMP - MIXED AIR TEMP

%OA= RETURN AIR TEMP - OUTSIDE AIR TEMP X 100

7. RETURN FAN(S)

7.1 THE RETURN FAN ISOLATION DAMPER SHALL OPEN AND THE RETURN FAN SHALL

RUN WHENEVER THE SUPPLY FAN RUNS.

7.2 ALARMS

RETURN FAN FAILURE

RETURN FAN VFD FAULT

8. RETURN AIRFLOW

8.1 THE RETURN FAN VFD SHALL MODULATE IN UNISON WITH THE SUPPLY FAN VFD.

RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO SUPPLY AIR FLOW MINUS 10%(ADJ.)

AND MINUS EXHAUST AIR FLOW (500 CFM). THE RETURN FAN VFD SPEED SHALL NOT

DROP BELOW 20%(ADJ.)

8.2 ALARMS

HIGH RETURN AIRFLOW (10% ABOVE SUPPLY AIRFLOW)

LOW RETURN AIRFLOW (30% BELOW SUPPLY AIRFLOW)

9. PREHEAT COIL

9.1 THE CONTROLLER SHALL MEASURE THE PREHEAT SECTION AIR TEMPERATURE

AND MODULATE THE PREHEAT COIL VALVE AND BYPASS DAMPER TO MAINTAIN ITS

SETPOINT. THE PREHEAT SECTION TEMPERATURE SETPOINT SHALL EQUAL THE

SUPPLY AIR TEMPERATURE SETPOINT MINUS THE FAN HEAT OFFSET VALUE.

9.2 PREHEAT COIL SHALL BE ENABLED WHENEVER:

OUTSIDE AIR TEMPERATURE IS LESS THAN 50 DEG(ADJ),

AND THE ECONOMIZER IS DISABLED

AND THE SUPPLY FAN STATUS IS ON

9.3 THE PREHEAT COIL SHALL OPEN FOR FREEZE PROTECTION WHENEVER:

MIXED AIR TEMPERATURE DROPS BELOW 36 DEG F (ADJ.)

OR THE FREEZESTAT IS ON.

9.4 IF OUTDOOR TEMPERATURE IS BELOW 30 DEG F (ADJ) AND HEAT IS REQUIRED,

THEN THE STEAM VALVE FOR HEATING SHALL BE FULLY OPEN AND TEMPERATURE

CONTROL SHALL BE BY MODULATION OF THE FACE/BYPASS DAMPER.

10. SUPPLY AIR TEMPERATURE SETPOINT

10.1 THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL

MAINTAIN A SUPPLY AIR TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING

AND HEATING REQUIREMENTS.

10.2 THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING

BASED ON ZONE COOLING REQUIREMENTS AS FOLLOWS: THE INITIAL SUPPLY AIR

TEMPERATURE SETPOINT SHALL BE 55 DEG F(ADJ.) AS COOLING DEMAND

INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF

53 DEG F(ADJ.) AS COOLING DEMAND DECREASES, THE SETPOINT SHALL

INCREMENTALLY RESET UP TO A MAXIMUM OF 58 DEG F(ADJ.).

11. COOLING COIL

11.1 THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND

MODULATE THE COOLING COIL VALVE TO MAINTAIN THE SUPPLY AIR TEMPERATURE

SETPOINT.

11.2 THE COOLING SHALL BE ENABLED WHENEVER: OUTSIDE AIR TEMPERATURE IS

GREATER THAN 50 DEGREES AND THE SUPPLY FAN STATUS IS ON AND THE HEATING

IS NOT ACTIVE

11.4 THE COOLING COIL VALVE SHALL OPEN TO 50%(ADJ.) WHENEVER THE

FREEZESTAT IS ON.

11.5 ALARMS

11.5.1 HIGH SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL ALARM IF

THE SUPPLY AIR TEMPERATURE IS 5 DEG F(ADJ.) GREATER THAN THE SUPPLY AIR

SETPOINT.

11.5.2 LOW SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL ALARM IF

THE SUPPLY AIR TEMPERATURE IS LESS THAN 45 DEG F(ADJ.).

12. ECONOMIZER

12.1 THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND

MODULATE THE OUTSIDE AIR DAMPER TO MAINTAIN THE ECONOMIZER

TEMPERATURE SETPOINT. THE ECONOMIZER TEMPERATURE SETPOINT IS EQUAL TO

THE SUPPLY AIR TEMPERATURE SETPOINT MINUS THE FAN HEAT OFFSET VALUE.

THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION TO

MAINTAIN MINIMUM OUTSIDE AIR REQUIRED.

12.2 THE ECONOMIZER SHALL BE ENABLED WHENEVER:

OUTSIDE AIR TEMPERATURE IS LESS THAN 60 DEG F(ADJ) AND THE OA

TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE AND THE OA

ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY AND THE SUPPLY FAN STATUS

IS ON.

12.3 THE OUTSIDE AIR DAMPER SHALL CLOSE WHENEVER: MIXED AIR TEMPERATURE

DROPS BELOW 36 DEG F(ADJ.) OR THE FREEZESTAT IS ON OR THE SUPPLY FAN

STATUS IS OFF.

12.4 THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR

DAMPER SHALL OPEN WHEN THE UNIT IS OFF.

13. HUMIDIFIER CONTROL

13.1 THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND MODULATE

THE HUMIDIFIER TO MAINTAIN A SETPOINT OF 40% RH(ADJ.). THE HUMIDIFIER SHALL

BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON AND THE OUTSIDE AIR

TEMPERATURE IS BELOW 65 DEGREES.

13.2 THE HUMIDIFIER SHALL TURN OFF WHENEVER: SUPPLY AIR HUMIDITY

MEASURERS 90% OR WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 65 DEGREES OR

ON A LOSS OF SUPPLY FAN STATUS

13.3 ALARMS

HIGH SUPPLY AIR HUMIDITY 90%(ADJ)

LOW SUPPLY AIR HUMIDITY 30%(ADJ)

14. AIRFLOW CONTROL

14.1 THE CONTROL SYSTEM SHALL MONITOR AND DISPLAY SUPPLY AIR FLOW,

RETURN AIR FLOW, AND MIXED AIR FLOW IN CFM. IT WILL CALCULATE, AND DISPLAY

OUTDOOR AIR PERCENTAGE FROM THE MEASURED VALUES BASED ON THE

FOLLOWING FORMULA:

%OA = (RAT-MAT)/(RAT-OAT) X 100

14.2 THE MINIMUM OUTSIDE AIR DAMPER SHALL BE CONTROLLED AS FOLLOWS:

14.2.1 WHEN OUTSIDE AIR TEMPERATURE IS BELOW 50 DEGREES AND THE

ECONOMIZER CONTROL SEQUENCE HAS REDUCED THE OUTSIDE

18.2.7 FIVE MINUTES AFTER SUPPLY/RETURN FAN-ON STATUS HAS BEEN PROVEN,

OA FAN SHALL DELIVER 5% OF CFM RA AND EX DAMPERS SHOULD OPEN/CLOSE

SIMULTANEOUSLY WITH OA DAMPER. (OA=5% RA= 95% EX=5%).

18.2.8 FIVE MINUTES AFTER OA FAN STARTED DELIVERING 5%, RELEASE OA, RA,

RELIEF AIR DAMPERS TO CONTROL TO MEET MIXED AIR SETPOINT.

18.2.9 LOWER MIXED SET POINT TO 60 DEGREES FOR 10 MINUTES.

18.2.10 RELEASE MIXED AIR SET POINT BACK TO ORIGINAL SETTING.

AIRFLOW DOWN TO THE MINIMUM OUTSIDE AIR FLOW RATE, THE OUTSIDE AIR

DAMPER SHALL CLOSE TO THE MINIMUM POSITION.

14.2.2 WHEN THE AIR HANDLING UNIT CONTROLS ARE OPERATING IN ECONOMIZER

MODE, THE ECONOMIZER CONTROL SEQUENCE WILL MODULATE THE ECONOMIZER

DAMPER, WHILE THE OUTSIDE AIR DAMPER MAINTAINS MINIMUM OUTDOOR AIR

POSITION TO MAINTAIN THE MIXED AIR ECONOMIZER TEMPERATURE SETPOINT.

THE OUTSIDE AIR CALCULATION ABOVE IN 14.1 SHALL DISPLAY THE OUTSIDE AIR

PERCENTAGE BUT WILL NOT BE USED TO CONTROL THE OUTSIDE AIR DAMPER IN

THE ECONOMIZER MODE.

14.2.3 WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 60 DEGREES AND THE

ECONOMIZER IS NOT ENABLED BASED ON THE OUTSIDE AIR TEMPERATURE OR

ENTHALPY PER 12.2 ABOVE, THE CONTROL SEQUENCE SHALL REDUCE THE

OUTSIDE AIRFLOW DOWN TO THE MINIMUM OUTSIDE AIR FLOW RATE. THE OUTSIDE

METER SHALL MEASURE THE OUTSIDE AIR FLOW. CALCULATION ABOVE IN 14.1

SHALL DISPLAY THE OUTSIDE AIR PERCENTAGE BUT WILL NOT BE USED TO

CONTROL THE OUTSIDE AIR DAMPER. WHEN THE OUTSIDE AIR TEMPERATURE AND

THE RETURN TEMPERATURE ARE EQUAL, ADJUST THE RETURN AIR TEMPERATURE

UPWARD BY 0.1 DEGREE F TO ENABLE THE OUTSIDE AIR CALCULATION TO

FUNCTION.

15. FILTERS

15.1 ALARMS

15.1.1 PREFILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN

FILTER

15.1.2. FINAL FILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN

FILTER

16. FAN HEAT OFFSET VALUE

16.1 FAN HEAT OFFSET (0-5)- THE BCS SHALL RESET THE FAN HEAT OFFSET VALUE

BASED UPON THE DIFFERENCE BETWEEN SUPPLY AIR SETPOINT AND SUPPLY AIR

TEMPERATURE. THE LOWER LIMIT SHALL BE 0. THE UPPER LIMIT SHALL BE 5.

16.2 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF 2°F

BELOW THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL SUBTRACT 1 FROM THE

FAN HEAT OFFSET VALUE. IF THE FAN HEAT OFFSET VALUE IS GREATER THAN 0,

THEN THE FAN HEAT OFFSET SHALL BE SET TO 0. AFTER AN ADJUSTABLE PERIOD

OF 15 MINUTES THE PID LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO

THE SETPOINT AND ADJUST THE VALUE.

16.3 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE + OR -

2°F OF THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL ADD ZERO TO THE FAN

HEAT OFFSET VALUE. AFTER AN ADJUSTABLE PERIOD OF 15 MINUTES THE PID

LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO THE SETPOINT AND ADJUST

THE VALUE.

16.4 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF 2°F

ABOVE THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL ADD 1 TO THE FAN HEAT

OFFSET VALUE. IF THE FAN HEAT OFFSET VALUE IS GREATER THAN 5, THEN THE

FAN HEAT OFFSET SHALL BE SET TO 5. AFTER AN ADJUSTABLE PERIOD OF 15

MINUTES THE PID LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO THE

SETPOINT AND ADJUST THE VALUE.

17. CONTINUOUS COMMISSIONING ALARMS

17.1 IF IN COOLING MODE (OUTSIDE AIR IS GREATER THAN 50 DEGREES): PREHEAT

SECTION TEMP IS GREATER THAN MIXED AIR TEMPERATURE BY 1 DEG F, OR MORE,

THEN ALARM "STEAM VALVE OPEN IN COOLING MODE"

17.2 IF IN HEATING MODE (OUTSIDE AIR IS LESS THAN 50 DEGREES): COOLING

DISCHARGE TEMP IS LESS THAN PREHEAT TEMP BY 1 DEG F, OR MORE, THEN

ALARM "CHILLED WATER VALVE IS OPEN IN HEATING MODE"

18. COLD START SEQUENCE

18.1 WHENEVER UNIT IS STARTED AND OUTDOOR AIR TEMPERATURE IS BELOW 30

DEG F INITIATE THE FOLLOWING SEQUENCE.

18.2.1 OA DAMPER SHALL BE CLOSED (MIN OA FAN SHALL BE OFF), RELIEF AIR

DAMPER SHALL BE CLOSED, RETURN AIR DAMPER SHALL BE 100% OPEN

(ECONOMIZER DISABLED).

18.2.2 COMMAND ON STEAM PREHEAT VALVE.

18.2.3 STEAM PREHEAT VALVE SHALL MAINTAIN 80 DEGREE SUPPLY AIR

TEMPERATURE.

18.2.4 SMOKE DAMPER SHALL BE OPEN.

18.2.5 COMMAND ON SUPPLY AND RETURN (DRIVE) ALLOW TO RAMP UP NORMALLY.

18.2.6 SET MIXED AIR SETPOINT TO 70 DEG F ONCE SUPPLY/RETURN FAN ON

STATUS HAS BEEN PROVEN.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:1

PM

H-004

HVAC TEMPERATURE CONTROLS EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS SRP

BID ISSUE SUBMISSION

8.1.21Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19 100% CD's SUBMISSION 2.14.20

BID ISSUE SUBMISSION 8.1.21

NOTE: ALL REFERENCES TO THE

EXISTING BAS ARE REFERRING TO

THE EXISTING TRIDIUM SYSTEM IN

THE BUILDING. REFER TO

SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

Hardware Points Software Points

Point Name AI AO BI BO Trend Show On

Graphic Supply Air Static Pressure x x x x

Return Airflow x x x

Supply Airflow x x x

Outside Airflow x x x x

Prefilter Status x x x

UVC Emitter Status x x x x

Mixed Air Temp x x x

Return Air Humidity x x x

Return Air Temp x x x

Supply Air Temp x x x

Return Air Static Pressure x x

Relief Air Airflow x x

Outdoor Air Temp x x

Outside Air Humidity x x

Pre Heat…