This is a solicitation for a construction project to expand primary care at the Louis Stokes Cleveland VA Medical Center. The project scope includes adding 12,000 square feet of space across three floors by expanding into VA-owned land adjacent to an existing ambulatory care facility. The contractor will provide all labor, equipment, and supervision to complete the expansion. The project value is estimated between $10-15 million. The NAICS code is 236220 and business size standard is $39.5 million. The site visit will be conducted on specified dates in accordance with social distancing guidelines. The cut-off for requests for information is August 12, 2021. This project is fully set aside for Service-Disabled Veteran Owned Small Businesses. Offerors must be verified in VETBIZ and registered in SAM by the due date and award date to be eligible.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESCRIPTIONABBREVIATION SYMBOL
HWS
HWR
CWS
CWR
LPS
LPC
MPS
MPC
HPS
HPC
CPD
CD
MIN. GPM
MIN. CFM
XXX
CFM
B1 2 1/
FSD
1 2/
A.D.A.D.
HVAC SYMBOL LEGEND
HWS HEATING WATER SUPPLY
HWR HEATING WATER RETURN
CWS CHILLED WATER SUPPLY
CWR CHILLED WATER RETURN
LPS LOW PRESSURE STEAM SUPPLY (15# OR LESS)
LPC LOW PRESSURE STEAM CONDENSATE RETURN (15# OR LESS)
MPS MEDIUM PRESSURE STEAM SUPPLY (16# TO 75#)
MPC MEDIUM PRESSURE STEAM CONDENSATE RETURN (16# TO 75#)
HPS HIGH PRESSURE STEAM SUPPLY (76# OR MORE)
HPC HIGH PRESSURE STEAM CONDENSATE RETURN (76# OR MORE)
CPD STEAM CONDENSATE PUMPED DISCHARGE
CD A/C CONDENSATE DRAIN
GATE VALVE
GLOBE VALVE
BALL VALVE
BALANCE VALVE (SEE SPECIFICATIONS)
CHECK VALVE (SWING)
SPRV STEAM PRESSURE REGULATING VALVE
BUTTERFLY VALVE
RV RELIEF OR SAFETY VALVE
TWO WAY CONTROL VALVE
T STEAM TRAP
CONCENTRIC REDUCER/INCREASER
STRAINER WITH BLOWDOWN
UNION
FLANGED UNION
THERMOSTAT
THERMOMETER/TEMPERATURE GAUGE
PRESSURE GAUGE WITH GAUGE COCK AND SYPHON (STEAM)
PRESSURE GAUGE WITH BALL VALVE (WATER)
DRIP PAN ELBOW
DIFFUSER, REGISTER OR GRILLE (SEE SCHEDULE)
DUCTWORK INSULATION AND MATERIAL (SEE SCHEDULE)
TERMINAL UNIT (SEE SCHEDULE)
LOUVERS (SEE SCHEDULE)
CODED NOTE (SEE SCHEDULE)
E.C. E.C. ELECTRICAL CONTRACTOR
F.P.C. F.P.C. FIRE PROTECTION CONTRACTOR
G.C. G.C. GENERAL CONTRACTOR
H.C. H.C. HVAC CONTRACTOR
P.C. P.C. PLUMBING CONTRACTOR
T.C.C. T.C.C. TEMPERATURE CONTROL SUB-CONTRACTOR
A.D. A.D. ACCESS DOOR
A.F.F. A.F.F. ABOVE FINISHED FLOOR
A.L. A.L. ACTIVE LENGTH
MFR. MFR. MANUFACTURER
N.O. N.O. NORMALLY OPEN
N.C. N.C. NORMALLY CLOSED
TYP. TYP. TYPICAL
E.A. E.A. EXHAUST AIR
R.A. R.A. RETURN AIR
S.A. S.A. SUPPLY AIR
M.O.B.D. M.O.B.D. MANUAL OPPOSED BLADE DAMPER
O.B.D. O.B.D. OPPOSED BLADE DAMPER
FLOW DIRECTION INDICATOR (LIQUID)
FLOW DIRECTION INDICATOR (VAPOR) W/ CFM QUANTITY GIVEN
11/2B 1-1/2 HOUR TYPE B FIRE DAMPER
11/2FSD 1-1/2 HOUR COMBINATION FIRE/SMOKE DAMPER
ACCESS DOOR IN BOTTOM OF DUCT OR SIDE OF DUCT
90° ELBOW WITH TURNING VANES
SQUARE-TO-ROUND DUCT TRANSITION
TERMINAL UNIT WITH FLEXIBLE CONNECTION, SOUND ATTENUATOR AND REHEAT COIL
S.A. SOUND ATTENUATOR
MANUAL BALANCING DAMPER
AUTOMATIC CONTROL DAMPER
INDICATES TIE INTO EXISTING
INDICATES REMOVE TO POINT FOR RECONNECTION
INDICATES REMOVE TO POINT AND CAP
HVAC DEMOLITION GENERAL NOTES
1. THE GENERAL NOTES LISTED HERE APPLY TO ALL HVAC DEMOLITION DRAWINGS IN ADDITION TO ANY ADDITIONAL DEMOLITION DRAWING NOTES ON THE INDIVIDUAL DEMOLITION DRAWINGS.
2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.
3. FIELD VERIFY EXISTING CONDITIONS.
4. COORDINATE WITH GENERAL TRADES WORK, PLUMBING WORK, FIRE PROTECTION WORK,
ELECTRICAL WORK AND OTHER WORK.
5. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT
PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE,
DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY
FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE
PROPER SCALE AND THOSE DRAWINGS THAT HAVE BEEN PLOTTED.
6. PHASING - SEE DIVISION 1 PROJECT SPECIFICATION PHASING DOCUMENTS FOR SPECIFIC
PHASING INSTRUCTIONS. COORDINATE SHUT-DOWN OF ANY UTILITY IN ADVANCE WITH THE
OWNER. ACCOMPLISH DRAIN DOWN AND RE-FILL OF PIPING SYSTEMS AS REQUIRED. UNLESS
OTHERWISE SPECIFICALLY INDICATED, EXISTING CHILLED WATER SYSTEMS SHALL NOT BE
DISRUPTED DURING THE COOLING SEASON, AND HEATING SYSTEMS SHALL NOT BE DISRUPTED
WHEN REQUIRED FOR OCCUPANT COMFORT OR BUILDING FREEZE PROTECTION.
7. DARK, DASHED LINES INDICATE PIPING, DUCTWORK AND EQUIPMENT TO BE REMOVED.
8. SEE SPECIFICATIONS FOR GENERAL CUTTING AND PATCHING REQUIREMENTS REQUIRED
UNDER DEMOLITION. ALSO SEE DRAWINGS FOR MORE SPECIFIC REQUIREMENTS.
9. SEE SPECIFICATIONS FOR SALVAGE RIGHTS TO ANY EQUIPMENT OR MATERIALS BEING
REMOVED.
10. REMOVE ALL HANGERS AND SUPPORTS SERVING PIPING, DUCTWORK AND EQUIPMENT BEING
DEMOLISHED. PROVIDE AND/OR ADJUST EXISTING HANGERS TO SUPPORT ANY REMAINING
PIPING, DUCTWORK, OR EQUIPMENT ADJACENT TO DEMOLISHED.
11. CAP ALL REMAINING ACTIVE PIPING WITH SIMILAR MATERIALS TO MATCH EXISTING
WATERTIGHT. PIPE ENDS INDICATED TO BE CAPPED ARE NOT TO BE CRIMPED. INSULATED PIPING
SHALL BE INSULATED AT CAP WITH MATERIALS SPECIFIED FOR NEW WORK.
12. CAP ALL REMAINING ACTIVE DUCTWORK WITH SIMILAR MATERIALS TO MATCH EXISTING AND
SEALED AIRTIGHT. INSULATED DUCTWORK SHALL BE INSULATED AT CAP WITH MATERIALS
SPECIFIED FOR NEW WORK.
13. REMOVE ALL THERMOSTATS, TEMPERATURE CONTROL WIRING AND PIPING FROM
DEMOLISHED EQUIPMENT BACK TO MAIN SOURCE AND CAP CONTROL AIR PIPING AIRTIGHT.
CRIMPING SHALL NOT BE CONSIDERED ADEQUATE.
14. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL/REINSTALLATION OF
CEILING ASSOCIATED WITH DEMOLITION OF PIPING, DUCTWORK, AND EQUIPMENT. THE HVAC
CONTRACTOR SHALL TEMPORARILY SUPPORT ALL ASSOCIATED CEILING EQUIPMENT SUCH AS
LIGHTS, SMOKE DETECTORS, ETC. AS REQUIRED FOR THIS WORK.
15. WHERE EXISTING PIPING IS MAINTAINED AT WALLS SHOWN TO BE DEMOLISHED,
CONTRACTOR TO REMOVE ABANDONED SLEEVES ASSEMBLIES AND ANY ASSOCIATED
FIRESTOPPING MATERIALS ON PIPING. PIPING INSULATION WITHIN AND AROUND THE SLEEVE
ASSEMBLY IS TO BE REMOVED AND REPLACED WITH SIMILAR INSULATION MATERIALS, MATCHING
EXISTING.
HVAC NEW WORK GENERAL NOTES
1. THE GENERAL NOTES LISTED HERE APPLY TO ALL HVAC DRAWINGS IN ADDITION TO ANY
ADDITIONAL DRAWING NOTES ON THE INDIVIDUAL DRAWINGS.
2. REFER ALSO TO DUCTWORK MATERIAL SCHEDULE AND NOTES FOR ADDITIONAL GENERAL
NOTES APPLICABLE TO DUCTWORK.
3. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.
4. FIELD VERIFY EXISTING CONDITIONS.
5. COORDINATE WITH GENERAL TRADES WORK, PLUMBING WORK, FIRE PROTECTION WORK,
ELECTRICAL WORK AND OTHER WORK.
6. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT
PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE,
DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY
FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE
PROPER SCALE AND THOSE DRAWINGS THAT HAVE BEEN PLOTTED.
7. THE MECHANICAL DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW
EXACT LOCATION OF EQUIPMENT, PIPING AND DUCTWORK UNLESS DIMENSIONS ARE GIVEN OR
OTHERWISE IMPLIED FOR CLEARANCES, ETC. PIPING, DUCTWORK AND MECHANICAL EQUIPMENT
ARE TO BE INSTALLED ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN
MIND ACTUAL BUILDING CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK.
CONTRACTORS IN THEIR BIDS ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS AND
OTHER RELATED WORK NECESSARY TO PROVIDE MINOR OFFSETS IN MECHANICAL WORK AS
REQUIRED TO AVOID CONFLICT WITH OTHER WORK ON THIS PROJECT, OR AS REQUIRED IN
ORDER TO OBTAIN MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN SPACES.
8. PHASING - SEE DIVISION 1 PROJECT SPECIFICATION PHASING DOCUMENTS FOR SPECIFIC
PHASING INSTRUCTIONS. COORDINATE SHUT-DOWN OF ANY UTILITY IN ADVANCE WITH THE
OWNER. ACCOMPLISH DRAIN DOWN AND RE-FILL OF PIPING SYSTEMS AS REQUIRED. UNLESS
OTHERWISE SPECIFICALLY INDICATED, EXISTING CHILLED WATER SYSTEMS SHALL NOT BE
DISRUPTED DURING THE COOLING SEASON, AND HEATING SYSTEMS SHALL NOT BE DISRUPTED
WHEN REQUIRED FOR OCCUPANT COMFORT OR BUILDING FREEZE PROTECTION.
9. MAINTAIN REQUIRED RIGGING ACCESS CLEARANCES. COORDINATE CLEARANCE
REQUIREMENTS WITH OTHER TRADES.
10. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED
STRUCTURES. SEE DETAILS AND SPECIFICATIONS FOR PIPE PENETRATION SEAL
REQUIREMENTS.
11. H.C. IS TO COORDINATE ALL MASONRY PENETRATION LOCATIONS AND SIZES WITH G.C.
12. COORDINATE EXACT POSITIONING OF FLOOR DRAINS WITH PLUMBING CONTRACTOR TO
SERVE HVAC EQUIPMENT AS INTENDED, AND TO AVOID TRIPPING HAZARDS WITH ABOVE FLOOR
DRAIN PIPING.
13. DO NOT ROUTE DUCTWORK OR PIPING OVER ELECTRICAL EQUIPMENT.
14. BALANCE AIR QUANTITY FOR RETURN AIR INLETS TO EQUAL THE SUM OF SUPPLY AIR
INTRODUCED TO THE SPACE, UNLESS NOTED OTHERWISE.
15. UNLESS OTHERWISE INDICATED, ALL PIPING TO RUN GENERALLY BELOW DUCTWORK FOR
ACCESS TO VALVING. DO NOT OBSTRUCT EQUIPMENT OR ACCESS DOORS. AVOID DUCTWORK
OVER LIGHTS WHEREVER POSSIBLE.
16. EQUIPMENT CONNECTION ARRANGEMENTS, FLANGES, UNIONS, VALVING, ETC. ARE NOT
TYPICALLY SHOWN ON PLAN VIEWS. REFER TO DETAILS AND FLOW DIAGRAMS FOR
REQUIREMENTS. INSTALL ALL VALVES AND OTHER ITEMS REQUIRING OR FACILITATING
MAINTENANCE IN ACCESSIBLE LOCATIONS, AND SO AS TO NOT OBSTRUCT MAINTENANCE ON
EQUIPMENT SERVED.
17. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE SO THERE
WILL BE COUNTER FLOW BETWEEN WATER AND AIR.
18. NOT ALL AIR VENTS AND DRAINS HAVE BEEN SHOWN ON PIPING AS THEIR REQUIRED
LOCATION DEPENDS ON THE PIPING INSTALLATION. REFER TO SPECIFICATIONS FOR
REQUIREMENTS OF PIPING AIR VENTS AND DRAINS. PROVIDE AIR VENTS IN ALL HIGH POINTS AND
DRAIN VALVES AT ALL LOW POINTS IN PIPING SYSTEM.
19. SEE TEMPERATURE CONTROL DRAWINGS AND COORDINATE WITH TEMPERATURE CONTROL
CONTRACTORS FOR INSTRUMENTATION DEVICES REQUIRED TO BE INSTALLED IN PIPING AND
DUCTWORK, TOGETHER WITH NECESSARY CLEARANCES FOR SAME.
20. ALL HWS AND HWR BRANCH CONNECTIONS TO HEATING EQUIPMENT, TERMINAL UNITS AND
RADIANT PANELS TO BE 3/4" UNLESS OTHERWISE NOTED.
21. NO "BULL-HEAD" TEES ARE PERMITTED IN PIPING. FLOW IS NOT PERMITTED TO BE IN
OPPOSING DIRECTIONS IN THE SAME TEE FITTING.
22. ALL AIR TERMINAL UNITS, HEATING TERMINALS AND REHEAT COILS SHALL BE PROVIDED WITH
WALL-MOUNTED THERMOSTATS UNLESS NOTED ON THE PLANS OR SPECIFICATIONS TO BE
EQUIPPED WITH INTEGRAL THERMOSTATS. REFER TO PLANS FOR APPROXIMATE THERMOSTAT
LOCATIONS - COORDINATE WITH OTHER TRADES. IF A THERMOSTAT IS NOT SHOWN ON THE
PLANS, COORDINATE LOCATION WITH ENGINEER. CONTRACTOR SHALL SUBMIT A FLOOR PLAN
WITH APPROXIMATE LOCATIONS OF ALL THERMOSTATS.
OUTDOOR DESIGN
TEMPERATURES
(89.4°F Db SUMMER, 73.6°F Wb SUMMER, 4.6°F Db WINTER)
DESIGN ALTITUDE: 650 FT.
HVAC DESIGN DATA
INDOOR AREA DESIGN CONDITIONS
SUMMER WINTER
Db °F
MAX
RELATIVE
HUMIDITY
Db °F MIN RELATIVE
HUMIDITY (%)
WAITING ROOM 75 60 70 20
EXAM ROOM 75 60 70 20
CORRIDOR 75 60 70 20
OFFICE 75 60 70 20
BREAK ROOM 75 60 70 20
CONFERENCE ROOM 75 60 70 20
TOILET ROOM NA NA NA NA
CLEAN UTILITY/STORAGE ROOM NA NA NA NA
EXTERIOR STAIRS NA NA 50 NA
HOUSEKEEPING CLOSET NA NA NA NA
AIR HANDLING EQUIPMENT ROOM NA NA 50 NA
SOILED UTILITY AND STORAGE NA NA NA NA
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IS T E R
ED
E-62197
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
7/
/2
4:
:0
PM
H-001
HVAC GENERAL NOTES AND SYMBOL
LEGEND
EXPAND PRIMARY CARE FOR
PACT REALIGNMENT
10701 EAST BLVD. CLEVELAND, OHIO
541-376
NICK CARROZZA
8.1.21 CJS SRP
BID ISSUE SUBMISSION
8.1.21Revisions: Date:
DD SUBMISSION 5.3.19
65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19 100% CD's SUBMISSION 2.14.20
BID ISSUE SUBMISSION 8.1.21
NOTES:
FLOOR SECTION
WALL SECTION
PIPE INSULATION
(WHERE SPECIFIED)
1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN TESTED IN
ACCORDANCE WITH U.L. 1479 OR ASTM E814.
2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING
MATERIALS AND U.L. SYSTEMS.
3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT
CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.
4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION
RESULTING FROM HIS WORK.
5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ENGINEER, INCLUDING U.L. RATED SYSTEM
NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.
PENETRATING COMPONENT
SEE ARCHITECTURAL DRAWINGS
FOR WALL CONSTRUCTION AND
FIRE RATING
SEAL JOINT BETWEEN SLEEVE
AND FLOOR SLAB WITH MIN.
1/2" BEAD FIRESTOP CAULK
PIPE SLEEVE (SLEEVE TO
EXTEND 2" ABOVE FLOOR IN
MECHANICAL EQUIPMENT ROOMS)
FURNISH AND INSTALL FIRESTOP
MATERIALS IN ACCORDANCE
WITH APPROPRIATE U.L.
SYSTEMS TO MAINTAIN FIRE
RESISTANCE RATING
FURNISH AND INSTALL FIRESTOP
MATERIALS IN ACCORDANCE
WITH APPROPRIATE U.L.
SYSTEMS TO MAINTAIN FIRE
RESISTANCE RATING
DAMMING MATERIAL
(PER U.L. TESTED
SYSTEM DESIGN)
PIPE SLEEVE
PENETRATING COMPONENT
FLOOR SLAB; SEE
ARCHITECTURAL DRAWINGS FOR
FLOOR CONSTRUCTION AND
FIRE RATING
PIPE INSULATION
(WHERE SPECIFIED)
FIRESTOPPING DETAIL FOR
PENETRATIONS
THROUGH FIRE-RATED CONSTRUCTIONS
N.T.S.
INSERTION
LENGTH
STEM ADJUSTED TO SUIT EXTENDED
NECK REQUIREMENTS. SEE
SPECIFICATIONS FOR REQUIRED
INSULATION THICKNESSES.
EXTENSION NECK
(SIZE PER INSULATED
THICKNESS)
PIPE
ADJUSTABLE ANGLE
HINGE
THERMOMETER (SEE
SPECIFICATIONS FOR
REQUIREMENTS)
HALF COUPLING
NOTE:
18-36
PIPE SIZE
CENTERLINE
7" 11"
5" 7" 7"
5"
THERMOMETER AND WELL TAP DETAIL
N.T.S.
NOTE:
PIPE CL
STRUCTURAL FRAMING NOTE:
SUPPLY ADDITIONAL
SUPPORT STEEL AS REQUIRED
HEX NUTS (4 REQUIRED)
THREADED ROD (SEE
SPECIFICATIONS FOR
DIAMETER)
ADJUSTABLE CLEVIS HANGER
PIPE WITH INSULATION AND
JACKET (AS APPLICABLE).
SEE SPECIFICATIONS FOR
REQUIREMENTS.
SADDLE (SEE SPECIFICATIONS)
INSULATE VOID SPACE
BETWEEN SADDLE AND PIPE
REFER TO HANGER SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
BEAM CLAMP
AMBIENT TEMPERATURE)
(FOR MEDIUM HIGHER THAN
CLEVIS HANGER PIPE SUPPORT
N.T.S.
CONCRETE INSERT
STRUCTURAL
CONCRETE
NOTE:
PIPE ROLLER HANGER
INSULATE VOID BETWEEN
SADDLE AND PIPE
SADDLE (SEE SPECIFICATIONS)
INSULATION (SEE
SPECIFICATIONS FOR
REQUIREMENTS)
THREADED ROD. SEE
SPECIFICATIONS FOR
DIAMETER.
REFER TO HANGER SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
BEAM CLAMP
STRUCTURAL FRAMING
NOTE: SUPPLY ADDITIONAL
SUPPORT STEEL AS REQUIRED
AMBIENT TEMPERATURE)
(FOR MEDIUM HIGHER THAN
PIPE ROLLER HANGER SUPPORT
N.T.S.
CONCRETE INSERT
STRUCTURAL
CONCRETE
PIPE CL
NOTE:
STRUCTURAL FRAMING NOTE:
SUPPLY ADDITIONAL
SUPPORT STEEL AS REQUIRED
ADJUSTABLE CLEVIS HANGER
THREADED ROD (SEE SPECIFICATIONS
FOR DIAMETER)
HEX NUTS (4 REQUIRED)
PIPE WITH INSULATION AND
JACKET (AS APPLICABLE).
SEE SPECIFICATIONS FOR
REQUIREMENTS.
INSULATION PROTECTION SHIELD
CURVED SUPPORT BLOCK OR
THERMAL INSERT (SEE SPECIFICATIONS)
REFER TO HANGER SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
BEAM CLAMP
(FOR MEDIUM LOWER THAN
AMBIENT TEMPERATURE)
CLEVIS HANGER PIPE SUPPORT
N.T.S.
CONCRETE INSERT
STRUCTURAL
CONCRETE
NOTE:
BEAM CLAMP
THREADED ROD. SEE
SPECIFICATIONS FOR
DIAMETER.
STRUCTURAL FRAMING
NOTE: SUPPLY ADDITIONAL
SUPPORT STEEL AS REQUIRED
PIPE ROLLER HANGER
INSULATION PROTECTION SHIELD
CURVED SUPPORT BLOCK OR
THERMAL INSERT (SEE
SPECIFICATIONS)
INSULATION (SEE
SPECIFICATIONS FOR
REQUIREMENTS)
REFER TO HANGER SPECIFICATION
FOR ADDITIONAL REQUIREMENTS.
(FOR MEDIUM LOWER THAN
AMBIENT TEMPERATURE)
PIPE ROLLER HANGER SUPPORT
N.T.S.
CONCRETE INSERT
STRUCTURAL
CONCRETE
LINE SIZE 4" 6" 8" 10" 12" 14" 16" 20"18"
"B" PLATE
"C" PIPE
THREADED CONNECTION
FOR HEIGHT ADJUSTMENT
SUFFICIENT DEPTH OF
THREAD TO SUPPORT PIPING
"A" PIPE. INSULATED WHERE
SERVING INSULATED PIPING
NOTE:
FOR TERMINATED VERTICAL PIPING
DROPS, WELD PIPE SUPPORT AT
PIPE CENTERLINE.
14"x14" CONCRETE PAD TO
LEVEL, DEPTH AS REQUIRED
"B"
"C"
DIAMETER
SCH
SQUARE
2"
4"
"A"
THICKNESS
SCH
DIAMETER
1/2"
2"
3"
6"
4"
6"
6"
8"
6"
8"
1/2"
3"
1/2"
4"
1/2"
6"
1/2"
6"
GROUT AND ANCHOR BOLT
TO BASE
TACKWELD, WELD SIZE TO
EQUAL THINNEST MATERIAL
TO BE WELDED
WELD
CL
8"
10"
8"
10"
10"
12"
8"
10" 5/8"
5/8"
8"
5/8"
8"
3/4"
10"
8"
FLOOR PIPE ELBOW SUPPORT
N.T.S.
STRAINER BLOW DOWN
GLOBE VALVE
GATE VALVE
TO CONDENSATE
RETURN MAIN - SEE
PROJECT PLANS
UNION
INVERTED BUCKET
TRAP
UNION
CHECK VALVE
GATE VALVE
CONDENSATE
FLOW
NIPPLE
NIPPLE
1/2"
STRAINER
STEAM MAIN
STEAM FLOW
PITCH DOWN
SEE PLANS FOR PIPE
SIZES AND DRIP TRAP
LOCATIONS.
TEST GLOBE VALVE
NOTE:
DIRT LEG
CAP OR BLIND
FLANGE
TRAP TEE
DETAIL OF THE MEDIUM AND HIGH PRESSURE DRIP TRAP ASSEMBLY
N.T.S.
NOTE:
AIR
FLOW
1. COMBINATION FIRE AND SMOKE
DAMPERS TO BE U.L. LABELED.
2. SEE SPECIFICATIONS FOR
DAMPER TYPE.
FIRE RATED
WALL/AND/ OR SMOKE
BARRIER
1/4" CLEARANCE ALL
FOUR SIDES (SEAL WITH
FIRE RESISTANT CAULKING)
NEGATOR SPRING
ACCESS DOOR. SEE PLANS
FOR APPROXIMATE LOCATION.
LOCATE FOR FUSIBLE LINK
MAINTENANCE AND SMOKE
DETECTOR INSPECTION.
PROVIDE MULTIPLE ACCESS
DOORS WHERE REQUIRED.
DUCTWRAP INSULATION SEALED
AT SLEEVE WITH TAPE (FOR
INSULATED DUCTS ONLY)
SEAL CONTINUOUSLY AROUND
DOWNSTREAM PERIMETER OF
DAMPER WITH FIRE RESISTANT
CAULKING MATERIAL
MINIMUM 1-1/2"x1-1/2"x14 GA.
ANGLES, TACKWELD TO SLEEVE 8"
O.C. (DO NOT ATTACH TO WALL) 1"
MINIMUM OVERLAP ALL FOUR SIDES
LINTELS AS REQUIREDATTACH DAMPER TO 16
GA. BLACK STEEL SLEEVE
PER MANUFACTURERS
REQUIREMENTS OR PROVIDE
INTEGRAL SLEEVE
SLEEVE TO BE 6" WIDER
THAN WALL
ATTACH DUCT TO SLEEVE
WITH BREAKAWAY
CONNECTIONS AND SEAL
WITH MASTIC
FUSIBLE LINK WITH LOCK
SMOKE DETECTOR
(BY E.C.)
SEE DUCT MATERIAL SCHEDULE AND
SPECIFICATIONS FOR INSULATION
REQUIREMENTS
DAMPER ACTUATOR
OUTSIDE OF AIRSTREAM
(SEE SPECIFICATIONS FOR
REQUIREMENTS)
WALL MOUNTED - RECTANGULAR DUCT
COMBINATION FIRE/SMOKE DAMPER
N.T.S.
CHECK VALVE (TYP)
GATE VALVE (TYP)
UNION (TYP)
REDUCER AS REQUIRED
USE ELBOWS 45° OR
LESS
1. MOUNT PUMP LEVEL ON EQUIPMENT PAD IN PIT.
2. SEE PLANS FOR CONTINUATION OF PIPING AND PIPE SIZING.
3. ROUTE VENT AS INDICATED ON PLANS PITCHED UPWARD WITHOUT
POCKETS.
4. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS, INCLUDING
INSULATION.
5. CONNECT ALL PIPING TO PUMP WITH UNIONS OR FLANGES.
NOTES:
SIGHT GLASS
FLOOR LINE
CONDENSATE
RETURN FROM RECEIVER
PRESSURE GAUGE
WITH GAUGE COCK
AND SIPHON
DIRT LEG WITH END
CAP
TO STEAM PIPING
SOURCE
3/4" DRAIN VALVE WITH
HOSE ADAPTOR
AND CAP
CPD
DN
STEAM POWERED CONDENSATE
RETURN PUMP PIPING DETAIL
N.T.S.
T-2
DRAIN HOLE
DRAIN TO SPILL INTO
FLOOR DRAIN
DRAIN
CONNECT TO DRIP
PAN ELBOW DRAIN
CONNECTION AND
INCREASE AS
REQUIRED
DRIP PAN ELBOW
SIZED TO ACCEPT
SAFETY VALVE
OUTLET SIZE
DRAIN GAP
OUTLET FLANGE
OR SCREWED
CONNECTION
STEAM SAFETY
VALVE
SAFETY VALVE
DISCHARGE PIPING.
SEE PLANS FOR
SIZE AND ROUTING.
SUPPORT OVERHEAD
1- 1/
2" M
IN
STEAM SAFETY VALVE DRIP PAN ELBOW DETAIL
N.T.S.
RELIEF VALVE
DISCHARGE PIPE
SIZE "A"
DESIGNER NOTES:
DISCHARGE
PIPE SIZE "B"
2" 3"
"B"
"A"
NOTES:
J
1. SEE SPECIFICATIONS FOR ADDITIONAL FLOW MEASURING STATION
REQUIREMENTS.
2. BRANCH OUTLET AND PIPE SIZE PER MANUFACTURER'S RECOMMENDATIONS.
3. SEE MANUFACTURER'S INSTALLATION REQUIREMENTS WHICH MAY DIFFER OR
EXCEED THE REQUIREMENTS OF THIS DETAIL.
4. MAINTAIN MANUFACTURER'S RECOMMENDED UPSTREAM AND DOWNSTREAM
CLEARANCES FOR LOCATIONS OF FLOW MEASURING STATIONS. WHERE THIS IS
NOT POSSIBLE, REVIEW SUCH LOCATIONS WITH ENGINEER.
5. FOR FLOW MEASURING STATIONS MOUNTED IN VERTICAL PIPING, ORIENT
COUPLING DIRECTION SO AS TO NOT OBSTRUCT ACCESS AROUND PIPING.
6. FOR FLOW MEASURING STATIONS MOUNTED IN HORIZONTAL PIPING, ORIENT
COUPLING IN VERTICAL IF POSSIBLE, BUT IN ALL CASES ORIENT COUPLING TO
ALLOW REMOVAL OF FLOW ELEMENT.
CONTROL WIRING
TO CONTROL PANEL
JUNCTION BOX
WATERTIGHT CONDUIT
1/3 PIPE DIA.
OVER 4" PIPE
WELD
3000# HALF
COUPLING
BRANCH OUTLET
2" FULL PORT
BALL VALVE
MIN
5-1/2"
FLOW ELEMENT
FLOW MEASURING STATION INSTALLATION DETAIL
N.T.S.
COIL
BALANCE VALVE
UNION (TYP.)
BALL VALVE
AIR VENT
CONTROL VALVE
FANS AND MOTOR
FILTER
SECURE TO STRUCTURE
PER MANUFACTURER'S
RECOMMENDATIONS
COIL
1. SEE PLANS FOR COIL HAND CONNECTION
LOCATION, PIPE SIZES AND LOCATIONS.
2. SEE SPECIFICATIONS AND DRAWINGS FOR
CONTROL VALVE REQUIREMENTS.
3. PIPING MUST BE CONCEALED WHEREVER
POSSIBLE.
NOTES:
HYDRONIC WITH 2-WAY CONTROL VALVE
SURFACE MOUNTED CABINET HEATER
N.T.S.
GLOBE VALVE
REDUCER (TYPICAL)
IF REQUIRED
PILOT CONTROL LINE
VENT TO
ATMOSPHERE
SEE "STEAM SAFETY
VALVE DIP PAN ELBOW
DETAIL"
SV-1
3"
SEE PLANS FOR
CONTINUATION
3"
PRESSURE GAUGE (TYP.)
SIPHON (TYP.)
3"
PRESSURE REGULATING VALVE. INSTALL ORIFICE
DIRECTLY DOWNSTREAM OF STEAM REGULATING
VALVE WITH FLANGED REDUCER. SEE SCHEDULE
FOR MORE INFORMATION.
1-1/2"
SPRV-1
3/4"
3"
1-1/2"
STEAM PRESSURE REDUCING STATION
N.T.S.
V
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IS T E R
ED
E-62197
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
7/
/2
4:
:4
PM
H-002
HVAC DETAILS EXPAND PRIMARY CARE FOR
PACT REALIGNMENT
10701 EAST BLVD. CLEVELAND, OHIO
541-376
NICK CARROZZA
8.1.21 CJS SRP
BID ISSUE SUBMISSION
8.1.21Revisions: Date:
DD SUBMISSION 5.3.19
65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19
#18 GAUGE SHEET METAL
HOUSING BY MECHANICAL
CONTRACTOR, CONTINUOUS
AROUND PERIMETER
MINIMAL EXTENSION
INTO ROOM
COMPLETE GALVANIZED
PERIMETER ANGLE
CLOSURE BY MECHANICAL
CONTRACTOR. CAULK AND
SEAL WEATHERTIGHT.
WALL COLLAR BY
FAN MFR.
OSHA APPROVED
GUARD BY FAN MFR.
INSULATED BLADE BACKDRAFT
DAMPER BY FAN MFG.
WALL MOUNTED PROP. FAN
N.T.S.
(RF-57)
FLOW
AIR
FIRE RATED
WALL/AND/ OR SMOKE
BARRIER
1/4" CLEARANCE ALL FOUR SIDES
(SEAL WITH FIRE RESISTANT
CAULKING)
NEGATOR SPRING
ACCESS DOOR. SEE PLANS FOR
APPROXIMATE LOCATION. LOCATE
FOR FUSIBLE LINK MAINTENANCE
AND SMOKE DETECTOR
INSPECTION. PROVIDE MULTIPLE
ACCESS DOORS WHERE REQUIRED.
SMOKE DETECTOR (BY
E.C.)
SEAL CONTINUOUSLY
AROUND DOWNSTREAM
PERIMETER OF DAMPER WITH
FIRE RESISTANT CAULKING
MATERIAL
MINIMUM 1-1/2"x1-1/2"x14 GA.
ANGLES, TACKWELD TO SLEEVE 8"
O.C. (DO NOT ATTACH TO WALL) 1"
MINIMUM OVERLAP ALL FOUR SIDES
LINTELS AS REQUIRED
DAMPER ACTUATOR
OUTSIDE OF AIRSTREAM
(SEE SPECIFICATIONS FOR
REQUIREMENTS)
INSULATION, SEAL ALL
LOOSE ENDS WITH TAPE
ATTACH DUCT TO SLEEVE
WITH DRAWBAND BREAKAWAY
CONNECTIONS AND SEAL WITH
MASTIC
FUSIBLE LINK WITH LOCK
SLEEVE TO BE 6"
WIDER THAN WALL
ATTACH DAMPER TO 16
GA. BLACK STEEL SLEEVE
PER MANUFACTURERS
REQUIREMENTS OR
PROVIDE INTEGRAL SLEEVE
NOTES:
1. COMBINATION FIRE AND SMOKE DAMPERS
TO BE U.L. LABELED.
2. SEE SPECIFICATIONS FOR DAMPER TYPE.
WALL MOUNTED - ROUND OR OVAL DUCT
COMBINATION FIRE/SMOKE DAMPER
N.T.S.
NOTES:
FL
O
W A
IR
1. COMBINATION FIRE AND SMOKE
DAMPERS TO BE U.L. LABELED.
2. SEE SPECIFICATIONS FOR DAMPER
TYPE.
3. SEE PLANS FOR AIR FLOW ORIENTATION.
MINIMUM 1-1/2"x1-1/2"x14 GA. ANGLES, TACKWELD TO SLEEVE 8" O.C. (DO
NOT ATTACH TO WALL) 1" MINIMUM
OVERLAP ALL FOUR SIDES
1/4" CLEARANCE ALL
FOUR SIDES (SEAL WITH
FIRE RESISTANT CAULKING)
NEGATOR SPRING
FLOOR LINE
DUCTWRAP INSULATION SEALED
AT SLEEVE WITH TAPE (FOR
INSULATED DUCTS ONLY)
ACCESS DOOR. SEE PLANS FOR
APPROXIMATE LOCATION.
LOCATE FOR FUSIBLE LINK
MAINTENANCE AND SMOKE
DETECTOR INSPECTION.
PROVIDE MULTIPLE ACCESS
DOORS WHERE REQUIRED.
SEE DUCT MATERIAL
SCHEDULE AND
SPECIFICATIONS FOR
INSULATION
REQUIREMENTS
DAMPER ACTUATOR
OUTSIDE OF AIRSTREAM
(SEE SPECIFICATIONS FOR
REQUIREMENTS)
SEAL CONTINUOUSLY
AROUND DOWNSTREAM
PERIMETER OF DAMPER WITH
FIRE RESISTANT CAULKING
MATERIAL
ATTACH DAMPER TO 16 GA.
BLACK STEEL SLEEVE
PER MANUFACTURERS
REQUIREMENTS OR
PROVIDE INTEGRAL SLEEVE
SLEEVE TO EXTEND
4" BEYOND FLOOR,
BOTH SIDES
ATTACH DUCT TO SLEEVE
WITH BREAKAWAY
CONNECTIONS AND
SEAL WITH MASTIC
FUSIBLE LINK WITH LOCK
SMOKE DETECTOR
(BY E.C.)
FLOOR MOUNTED - RECTANGULAR DUCT
COMBINATION FIRE/SMOKE DAMPER
N.T.S.
FLOW
AIR
FLOW
AIR
MOTOR AND BELT GUARD (SEE
SPECIFICATIONS); COORDINATE
LOCATION FOR BEST ACCESS
FLEXIBLE DUCT
CONNECTION (TYP.)
ROUND-TO-RECTANGULAR
TRANSITION (PER SMACNA
REQUIREMENTS - TYPICAL)
ACCESS DOOR
OUTLET SOUND ATTENUATION
(SEE PLANS AND SCHEDULES)
THRUST RESTRAINT (TYP.
BOTH SIDES)
FLANGED FAN CONNECTION (TYP.)
VIBRATION ISOLATOR (TYP.) SEE
SPECIFICATIONS FOR
REQUIREMENTS
1/2" Ø THREADED HANGER ROD
(QUANTITY PER MANUFACTURER'S
REQUIREMENTS)
PROVIDE MISCELLANEOUS STEEL
AND SUPPORT FROM
STRUCTURAL MEMBERS AS
REQUIRED
VANEAXIAL FAN
INLET SOUND ATTENUATION
(SEE PLANS AND SCHEDULES)
ACCESS DOOR
INSPECTION ACCESS DOOR -
HINGED WHERE POSSIBLE - CAM
LOCK WHERE SPACE DOES NOT
PERMIT
VANEAXIAL FAN DETAIL
N.T.S.
NOTES:
1. SET FAN DEAD LEVEL BOTH DIRECTIONS.
2. ADJUST ISOLATORS AND FLEXIBLE CONNECTIONS TO AVOID VIBRATION
TRANSMISSION.
3. MAINTAIN MAXIMUM POSSIBLE CLEARANCE UNDER FAN AND DUCTWORK
UNLESS OTHERWISE TRANSMISSION.
4. THIS DETAIL MAY NOT INDICATE ALL REQUIRED FAN OPTIONS OR EXACT
ARRANGEMENT, SEE PLANS AND SPECIFICATIONS.
HWS
STRAIGHT LENGTH
FLEXIBLE CONNECTION
(6" LONG MINIMUM,
24" LONG MAXIMUM
UNLESS OTHERWISE
INDICATED)
CONTROL ASSEMBLY
3/4" DRAIN VALVE SEE
SPECIFICATIONS
AIRFLOW
AIRFLOW
4. LOCATE HANGERS TO SUPPORT TERMINAL UNIT
AND PIPING INDEPENDENTLY.
5. LOCATE AIR VENTS IN HIGH POINTS OF MAIN
PIPING.
6. PROVIDE ACCESS DOOR UPSTREAM OF REHEAT
COIL.
1. ALL PIPING AND VALVING SIZES TO MATCH RUNOUT
SIZE INDICATED ON PLANS.
2. SUSPEND COIL LEVEL AND PLUMB TO PERMIT FULL
DRAINAGE.
3. SEE PLANS FOR COIL HAND CONNECTIONS.
NOTES:
BALL VALVE
UNION (TYP.)
TWO-WAY CONTROL
VALVE
BALANCE VALVE
LOW VELOCITY SUPPLY
AIR DUCT
REHEAT COIL SIZED TO
MATCH TERMINAL UNIT
UNLESS OTHERWISE
INDICATED
SOUND ATTENUATOR
SECTION BY VAV
TERMINAL UNIT MFR.
SECURE WITH BANDS.
COVER EXPOSED
INSULATION WITH DUCT
TAPE (TYP.)
SUPPLY AIR DUCT
(SEE PLANS FOR
TYPE AND ROUTING)
VAV TERMINAL UNIT DETAIL
N.T.S.
SOUND ATTENUATOR AND HYDRONIC REHEAT COIL WITH 2-WAY CONTROL VALVE
ACCESS DOOR
HWR
AIR VENT AT HIGH POINT
STRAINER WITH BLOWDOWN VALVE
(TYPICAL)
PRESSURE AND
TEMPERATURE GAUGE
CONNECTOR PLUG (TYPICAL).
TRANSITION PIPING TO
COIL CONNECTION SIZE
AS NEEDED
COIL DRAIN
FLOW
PRESSURE GAUGE WITH
SHUT-OFF VALVE
(TYPICAL)
3/4" VENT WITH BALL
VALVE AND CAP
(TYPICAL)
AIR VENT AT HIGH POINT
UNION OR FLANGE
(TYPICAL)
C W
R
C W
S
AIR
CWR
THERMOMETER OR
TEMPERATURE GAUGE
(SEE SPECIFICATIONS)
(TYPICAL)
COOLING COIL
3/4" DRAIN WITH HOSE
ADAPTER AND CAP
(TYPICAL)
REDUCER - IF
REQUIRED (TYPICAL)
BALANCE VALVE
(TYPICAL)
BALL VALVE FOR PIPE
SIZES 2" AND UNDER,
BUTTERFLY VALVE FOR
PIPE SIZES 2-1/2" AND
ABOVE.
TWO-WAY CONTROL VALVE
1. PIPING INSTALLATION SHALL ALLOW FOR EQUIPMENT ACCESS AND COIL PULL.
2. SCHEMATIC IS APPLICABLE TO UNITS WITH ONE COIL. IF THE UNIT HAS MULTIPLE COILS
HEADER PIPING SHALL BE FULL SIZE; EACH COIL SHALL HAVE UNIONS OR FLANGES; EACH
COIL SHALL HAVE SHUT-OFF VALVES ON THE COIL INLET AND BALANCE VALVES ON THE COIL
OUTLET; EACH COIL SHALL HAVE THERMOMETERS AND PRESSURE GAUGES ON THE COIL
INLET AND OUTLET.
3. SEE PLANS FOR PIPING DROPS AND COIL CONNECTION LOCATIONS.
NOTES:
AIR HANDLING UNIT - 2 WAY VALVE
CHILLED WATER COIL PIPING SCHEMATIC - SINGLE COIL
N.T.S.
A
AIR HANDLER PIPE
A
AC-56
AC-57
2.5" 2"
TEST PLUG
(TYPICAL)
STRAINER WITH BLOWDOWN
PITCH DN. TOWARD DRAIN
DIELECTRIC UNION
B
UNIT DRAIN PAN
A
TERMINATE OVER DRAIN AS
INDICATED ON PLANS WITH AN AIR
GAP.
PLUGGED TEE CLEANOUT (TYP.)
PIPE OPEN TO ATMOSPHERE
UNIT TYPE A B
DRAW THROUGH X/2"
BLOW THROUGH
WHERE X = POSITIVE VALUE OF STATIC PRESSURE
DIFFERENCE BETWEEN PAN SECTION AND TRAP LOCATION
X"+1"
X"+2"
1" MINIMUM
NOTES:
1. LOCATE TRAP AS CLOSE AS POSSIBLE TO AHU DRAIN OUTLET WITH BOTTOM BELOW
SUPPORT STRUCTURE.
2. SIZE OF TRAP PIPING TO BE LARGER OF
EQUIPMENT OUTLET SIZE OR DIMENSION ON PLANS.
3. SEE SPECIFICATIONS FOR INSULATION REQUIREMENTS
4. NOTIFY ENGINEER BEFORE FABRICATING IF PHYSICAL CONDITIONS PROHIBIT
INSTALLATION OF DEPTH SHOWN.
AIR HANDLING UNIT
STANDARD A/C CONDENSATE TRAP DETAIL
N.T.S.
A
AIR HANDLER PIPE
A
AC-56
AC-57
1.5" 1.25"
6" (TYP.) DRIP LEG WITH CAP
24" MIN. (TYP.)
1. SEE PLANS FOR HAND ORIENTATION, PIPE ROUTING AND
PIPE SIZING.
2. INSTALL AND SUPPORT PER MANUFACTURER'S
RECOMMENDATIONS WITH PARTICULAR ATTENTION TO LEVEL
REQUIREMENTS AND REQUIRED ABSORPTION DISTANCE.
3. TRAP ARRANGEMENT INDICATED MAY VARY WITH
MANUFACTURER. UNLESS OTHERWISE INDICATED, SIZE
TRAPS AND CONDENSATE PIPING PER MANUFACTURER'S
REQUIREMENTS.
ROUTE PIPING TO PUMP
TRAP DISCHARGE
PITCH DOWN
NOTES:
F & T TRAP BY HUMIDIFIER
MFR. (TYP.)
STEAM SUPPLY PIPING.
PROVIDE DRIP TRAPPING
ARRANGEMENTS PER PLANS
TO PROVIDE DRY STEAM TO
HUMIDIFIER.
GATE VALVE (TYP.)
STRAINER WITH BLOWDOWN
VALVE (TYP.)
REDUCER (IF REQUIRED)
INCREASER (IF REQUIRED)
CONTROL VALVE (FURNISHED BY
HUMIDIFIER MFR.)
UNION (TYP.)
PITCH DOWN
AIRFLOW
HEADER ENCLOSURE (TYP.)
HORIZONTALLY ORIENTED
STEAM PANEL TYPE HUMIDIFIER DETAIL
N.T.S.
6" M
IN
AIR HANDLING UNIT WALL
PENETRATION TO BE SEALED TO
ELIMINATE AIR LEAKS PER
MANUFACTURER'S
RECOMMENDATIONS. SEE
PLANS FOR RECOMMENDED
PENETRATION LOCATION.
PIPE SIZE TO MATCH COIL
HEADER SIZE WITH
THREADED CONNECTION AND
REMOVABLE CAP AT
BOTTOM
UNION OR FLANGE (TYP.)
AIR FLOW
LPCR PIPING
FLEXIBLE CONNECTOR
1/2" VACUUM BREAKER
(TYP. FOR 2)
GLOBE VALVE BYPASS
1% MIN. SLOPE
SLOPE
1% MIN.
SEE PLANS FOR MAIN
SIZES AND ROUTING
UNION (TYP.)
CHECK VALVE (TYP.)
TRAP IS NOT REQUIRED
DUE TO USING OF THE
RECEIVER AND PUMPING
TRAP T-2.
DAMPER MOTOR AND
DRIVE ASSEMBLY
PRESSURE GAUGE
GATE VALVE (TYP.)
STRAINER WITH BLOW DOWN
GLOBE VALVE AND CAP (TYP.)
INCREASER (IF REQUIRED)
STEAM CONTROL VALVE
REDUCER (IF REQUIRED)
SEE PLANS FOR SIZES
NOTES:
1. PIPING AND COIL SUPPORT INSTALLATION SHALL ALLOW FOR COIL PULL AND SHALL NOT OBSTRUCT UNIT
ACCESSIBILITY.
2. CLOSE OFF AREA IN AIR HANDLER AROUND COIL TO FORCE ALL AIR THROUGH COIL.
3. THIS DETAIL IS SCHEMATIC. SEE PLANS FOR ACTUAL ORIENTATION OF PIPING, VALVING, ETC.
4. SUPPORT PIPING INSIDE AIR HANDLING UNIT PER MANUFACTURER'S RECOMMENDATIONS. DO NOT SUPPORT
PIPING FROM COIL.
5. REFER TO PLANS OR SECTIONS FOR PIPE SIZES NOT INDICATED THIS DETAIL.
6. INSTALL COIL LEVEL.
AIR HANDLING UNIT - VERTICAL TUBE INTEGRAL FACE AND BY-PASS
STEAM HEATING COIL SCHEMATIC
N.T.S.
(FULL CAPACITY STEAM VALVE)
A
A
B C B
B
AIR HANDLER TRAP.
NO. A B C
PIPE TAG
AC-56
AC-57
2" 2" 2" 1" 1.5" 1.5"
T-1 T-1
FLOW
UVC EMITTER LAMP IN QUANTITY AND
SPACING DETERMINED BY FINAL MFR. IN
ACCORDANCE WITH SPECIFICATIONS
AND IN COORDINATION WITH AHU COIL
SIZING. TYP.
TOP OF AHU
COOLING COIL
1. FINAL DESIGN, QUANTITY, AND SPACING BY UVC SYSTEM MANUFACTURER.
2. CONTRACTOR SHALL MOUNT SYSTEM IN ACCORDANCE WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
3. COORDINATE FINAL LOCATION OF CONTROL PANEL AND POWER SUPPLY WITH E.C.
4. ACCESS SECTION SHALL INCLUDE WIRED DOOR SWITCHES TO DE-ENERGIZE UVC
EMITTER IF DOOR IS OPENED. ACCESS SECTION SHALL ALSO INCLUDE A CAUTION SIGN ON
DOOR NOTIFYING PERSONNEL OF THE PRESENCE OF THE UVC EMITTER.
4. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
NOTES:
UVC EMITTER SCHEMATIC
N.T.S.
UVC EMITTER LAMP MOUNT PROVIDED
BY UVC SYSTEM MFR. TYP.
UVC EMITTER LAMP CONTROL PANEL
MOUNTED OUTSIDE THE AHU. MOUNT IN
ACCORDANCE WITH MFR INSTALLATION
INSTRUCTIONS. EXTEND OUTPUTS FOR
TIE IN TO BAS SYSTEM. REFER TO
TEMEPRATURE CONTROLS DRAWINGS
FOR POINTS.
BOTTOM OF AHU
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IS T E R
ED
E-62197
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
7/
/2
4:
:1
PM
H-003
HVAC DETAILS EXPAND PRIMARY CARE FOR
PACT REALIGNMENT
10701 EAST BLVD. CLEVELAND, OHIO
541-376
NICK CARROZZA
8.1.21 CJS SRP
BID ISSUE SUBMISSION
8.1.21Revisions: Date:
DD SUBMISSION 5.3.19
65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19
Hardware Points Software Points
Point Name AI AO BI BO Trend Show On
Graphic Supply Air Static Pressure x x x x
Return Airflow x x x
Supply Airflow ( Fans 1-4) 4 4 4
Outside Airflow x x x x
Supply Air Humidity x x x
Prefilter Status x x x
Final Filter Status x x x
UVC Emitter Status x x x x
Mixed Air Temp x x x
Return Air Humidity x x x
Return Air Temp x x x
Supply Air Temp x x x
Return Air Static Pressure x x
Relief Air Airflow x x
Outdoor Air Temp x x
Outside Air Humidity x x
Pre Heat Air Temp x x
Chilled Water Coil Air Temp Sensor x x
Return Fan VFD x x x
Supply Fan VFD -(1-4) 4 4 4
Return Fan VFD Speed x x x
Supply Fan VFD Speed -(1-4) 4 4 4
Preheating Steam Valve x x x
Cooling Valve x x x
Return Air Dampers x x x
Humidifier x x x
Relief Air Damper x x
Outside Air Damper x x
Bypass Damper (Steam Coil) x x
Freezestat x x x x
UVC Emitter Alarm x x x x
High Static Shutdown x x x x
Return Air Smoke Detector x x x x
Supply Air Smoke Detector x x x x
Return Fan VFD Fault x x x
Supply Fan VFD Fault -(1-4) 4 4 4
Return Fan Status x x x
Supply Fan Status (1-4) 4 4 4
Low Static Shutdown (Return Fan) x x x
Return Fan VFD HOA x x
Supply Fan VFD HOA -(1-4) 4 4
Low Static Shutdown Supply Fan x x
Return Fan Start/Stop x x x
Supply Fan Start/Stop (1-4) 4 4 4
Humidifier Enable x x
Supply Fan Isolation Damper (1-4) 4 4
Supply Air Static Pressure Setpoint x x
Return Airflow Setpoint x x
Preheating Mixed Air Temp Setpoint x x
Supply Air Temp Setpoint x x
Economizer Mixed Air Temp Setpoint x x
Outside Airflow Setpoint x x
Humidifier Setpoint x
Emergency Shutdown x x x
High Supply Air Static Pressure x
Low Supply Air Static Pressure x
Supply Fan Failure x
Supply Fan in Hand x
Supply Fan Runtime Exceeded x
Return Fan Failure x
Return Fan in Hand x
High Return Airflow x
Low Return Airflow x
High Outdoor Airflow x
Low Outdoor Airflow x
High Supply Air Temp x
Low Supply Air Temp x
High Supply Air Humidity x
Low Supply Air Humidity x
Prefilter Change Required 2 2
Final Filter Change Required x x
High Mixed Air Temp x
Low Mixed Air Temp x
High Return Air Humidity x
Low Return Air Humidity x
High Return Air Temp x
Low Return Air Temp x
High Supply Air Temp x
Low Supply Air Temp x
Chilled Water Flow Rate x x
Instantaneous Voltage: Phase to Phase x x
Instantaneous Voltage: Phase to Neutral x x
Demand KVA (Last 15 Minute Window) x x
Peak Demand with Date and Time Stamp x x
ABBREVIATION DESCRIPTION REMARKS
D-1
D-1
D-1
P
T-5
VE-9
P
VFD
TLL-1 VPS-1 SPS-2
DA-1DA-10
DA-10
DA-9
SPS-1
VFD
P
T-1 VPS-1 FSD-1
T-2
VE-5
T-1
SPS-3
T-1
(R.A.)
VE-17
H-1
H-1 (R.A.)
VE-12
T-1 H-1 (O.A.)(O.A.)
T-1 FSD-1
P
FM
UVC
CONTROL
PANEL
SUPPLY
AIR
CH
CHR
C
C
N.0.
P
C
SUPPLY
FAN
PRE-FILTER
FAN
RETURN RETURN
AIR
EXTERIOR BLDG. WALL
RELIEF
AIR
AIR
OUTDOOR
AFM-1
MPS
MPR N.C.
AFM-1
G
(S.A.)
NORMALLY OPEN
NORMALLY CLOSED
MANUFACTURER
N.O.
N.C.
MFR.
DUCT HUMIDITY SENSOR
DUCT SMOKE DETECTOR WITH AUXILIARY CONTACT
ELECTRICAL CONTRACTOR
NORMALLY OPEN (N.O.) ELECTRIC MODULATING DAMPER ACTUATOR
NORMALLY CLOSED (N.C.) ELECTRIC MODULATING DAMPER ACTUATOR
H-1
FSD-1
E.C.
DA-9
DA-10 SEE PLANS FOR VOLTAGE
SEE PLANS FOR VOLTAGE
AIRFLOW MEASURING STATION - FAN INLET TYPEAFM-1
DIFFERENTIAL PRESSURE SENSOR FOR AIRFLOW (BINARY) P
G MAGNETIC PRESSURE GAUGE SEE SPECIFICATIONS
AFM-2 AIRFLOW MEASURING STATION - DUCT MOUNTED TYPE
MPS
OPPOSED BLADE LOW LEAKAGE CONTROL DAMPERD-1
MIXED AIR DUCT TEMPERATURE SENSOR WITH EXTENDED ELEMENT
ROOM TEMPERATURE SENSOR (WITHOUT LOCAL ADJUSTABLE SETPOINT)
ROOM TEMPERATURE SENSOR (WITH LOCAL ADJUSTABLE SETPOINT)
OUTDOOR AIR TEMPERATURE SENSOR
DUCT TEMPERATURE SENSOR
STATIC PRESSURE SENSOR FOR AIRFLOW - LOW LIMIT - (ANALOG)
STATIC PRESSURE SENSOR FOR AIRFLOW - HIGH LIMIT - (ANALOG)
STATIC PRESSURE SENSOR FOR AIRFLOW (ANALOG)
T-5
T-4
T-3
T-2
T-1
SPS-3
SPS-2
SPS-1
SHIELDED
TEMPERATURE CONTROL CONTRACTORT.C.C.
FREEZESTAT WITH AUXILIARY CONTACTS AND LOCAL MANUAL RESETTLL-1
FURNISHED WITH AIRFLOW
MEASURING STATION.
SEE SCHEDULESVARIABLE FREQUENCY DRIVE (FOR MOTOR SPEED ADJUSTMENT)
ELECTRIC HUMIDIFIER CONTROL VALVE (FURNISHED WITH HUMIDIFIER)
VELOCITY PRESSURE SENSORVPS-1
VFD
VE-17
NORMALLY OPEN (N.O.) ELECTRIC MODULATING TWO-WAY HYDRONIC CONTROL VALVE
NORMALLY CLOSED (N.C.) ELECTRIC MODULATING TWO-WAY HYDRONIC CONTROL VALVE
NORMALLY OPEN (N.O.) ELECTRIC MODULATING STEAM CONTROL VALVE
NORMALLY CLOSED (N.C.) ELECTRIC TWO POSITION STEAM CONTROL VALVEVE-12
VE-9
VE-5
VE-1
AFM-2
AFM-2
INTEGRAL FACE AND
BY-PASS DAMPER BY
AIR HANDLER MFR.
(N.O.)
STEAM
HUMIDIFIER
TO RETURN AND
SUPPLY FAN
VFD SAFETY
CIRCUIT
LOCATE 2/3 DOWN
LONGEST DUCT RUN IN
LOCATION APPROVED
BY ENGINEER.
OUTDOOR AIR SENSOR
MOUNT AT A SHIELDED
LOCATION EXTERIOR TO
BUILDING. (PREFERABLY
ON THE NORTH FACE)
AWAY FROM ANY
EXHAUST OR RELIEF AIR.
TO FIRE ALARM
(SEE
ELECTRICAL
DRAWINGS)
HARDWARE TO
SAFETY CIRCUIT
TO FIRE ALARM
(SEE
ELECTRICAL
DRAWINGS)
HARDWARE TO
SAFETY CIRCUIT
T.C.C.TO PROVIDE ELECTRICAL METERING OF
UNIT MOTOR. ELECTRICAL USAGE
INFORMATION SHALL BE SENT TO THE EXISTING
BAS.
FINAL-FILTER
G
T.C.C. SHALL EXTEND OUTPUTS FROM NEW
CHILLED WATER METER AND TIE IN TO
EXISTING BAS. GRAPHICS SHALL BE UPDATED.
T.C.C. SHALL EXTEND
OUTPUTS FROM NEW UVC
EMITTER AND TIE IN TO
EXISTING BAS. GRAPHICS
SHALL BE UPDATED.
TEMPERATURE CONTROL LEGEND
AIR HANDLING UNIT AHU-48 CONTROL DIAGRAM
AHU-48 SEQUENCE OF OPERATIONS
1. RUN CONDITIONS - SCHEDULED
1.1 THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.
2. FREEZE PROTECTION
2.1 WHEN THE FREEZE STAT SENSES A TEMPERATURE BELOW 40 DEG. F THE
FOLLOWING SEQUENCE SHALL OCCUR:
2.1.1 THE UNIT SHALL SHUTDOWN AND GENERATE AN ALARM
2.1.2 THE OUTSIDE AIR AND ECONOMIZER DAMPERS SHALL CLOSE
2.1.3 STEAM PREHEAT COIL VALVE SHALL OPEN TO 100%(ADJ)
2.1.4 COOLING COIL VALVE SHALL OPEN TO 50%(ADJ)
3. HIGH/LOW STATIC SAFETY SHUTDOWN
3.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH
STATIC SHUTDOWN SIGNAL. HIGH STATIC ALARM SETPOINT SHALL BE 1" BELOW
DUCTWORK PRESSURE CLASS.
3.2 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A LOW
STATIC SHUTDOWN SIGNAL. LOW STATIC ALARM SETPOINT SHALL BE NEGATIVE 2"
S.P.
4. SMOKE DETECTION
4.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON A DETECTOR TRIP
ON RETURN AIR SMOKE DETECTOR.
5. SUPPLY FAN(S)
5.1 THE SUPPLY FAN ISOLATION DAMPER SHALL OPEN AND THE SUPPLY FAN SHALL
RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES.
TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE
(ADJ.) MINIMUM RUNTIME. MULTIPLE FANS SHALL RUN IN UNISON. IF A FAN SHOULD
FAIL, ITS ASSOCIATED ISOLATION DAMPER SHALL CLOSE AND REMAINING FANS SHALL
RAMP-UP TO MAINTAIN SETPOINT.
5.2 ALARMS:
SUPPLY FAN FAILURE
6. SUPPLY AIR DUCT STATIC PRESSURE CONTROL
6.1 THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL
MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN THE DUCT STATIC PRESSURE
SETPOINT. THE SUPPLY FAN VFD SPEED SHALL NOT DROP BELOW 30%(ADJ.). THE
INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE COORDINATE WITH THE TAB
CONTRACTOR, AND BE ADJUSTED UP DURING THE BALANCING PROCESS. THE FINAL
DUCT STATIC PRESSURE SETPOINT SHALL BE DETERMINED, SET, AND DOCUMENTED
BY THE BALANCING CONTRACTOR. THE SETPOINT SHALL BE SUFFICIENT TO MEET THE
VAV BOX AIRFLOW REQUIREMENTS DURING DESIGN CONDITIONS AND SHALL NOT BE
SET LOWER THAN 0.5".
6.2 ALARMS:
HIGH SUPPLY FAN STATIC PRESSURE
LOW SUPPLY FAN STATIC PRESSURE
SUPPLY FAN VFD FAULT
RETURN AIR TEMP - MIXED AIR TEMP
%OA= RETURN AIR TEMP - OUTSIDE AIR TEMP X 100
7. RETURN FAN(S)
7.1 THE RETURN FAN ISOLATION DAMPER SHALL OPEN AND THE RETURN FAN SHALL
RUN WHENEVER THE SUPPLY FAN RUNS.
7.2 ALARMS
RETURN FAN FAILURE
RETURN FAN VFD FAULT
8. RETURN AIRFLOW
8.1 THE RETURN FAN VFD SHALL MODULATE IN UNISON WITH THE SUPPLY FAN VFD.
RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO SUPPLY AIR FLOW MINUS 10%(ADJ.)
AND MINUS EXHAUST AIR FLOW (500 CFM). THE RETURN FAN VFD SPEED SHALL NOT
DROP BELOW 20%(ADJ.)
8.2 ALARMS
HIGH RETURN AIRFLOW (10% ABOVE SUPPLY AIRFLOW)
LOW RETURN AIRFLOW (30% BELOW SUPPLY AIRFLOW)
9. PREHEAT COIL
9.1 THE CONTROLLER SHALL MEASURE THE PREHEAT SECTION AIR TEMPERATURE
AND MODULATE THE PREHEAT COIL VALVE AND BYPASS DAMPER TO MAINTAIN ITS
SETPOINT. THE PREHEAT SECTION TEMPERATURE SETPOINT SHALL EQUAL THE
SUPPLY AIR TEMPERATURE SETPOINT MINUS THE FAN HEAT OFFSET VALUE.
9.2 PREHEAT COIL SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 50 DEG(ADJ),
AND THE ECONOMIZER IS DISABLED
AND THE SUPPLY FAN STATUS IS ON
9.3 THE PREHEAT COIL SHALL OPEN FOR FREEZE PROTECTION WHENEVER:
MIXED AIR TEMPERATURE DROPS BELOW 36 DEG F (ADJ.)
OR THE FREEZESTAT IS ON.
9.4 IF OUTDOOR TEMPERATURE IS BELOW 30 DEG F (ADJ) AND HEAT IS REQUIRED,
THEN THE STEAM VALVE FOR HEATING SHALL BE FULLY OPEN AND TEMPERATURE
CONTROL SHALL BE BY MODULATION OF THE FACE/BYPASS DAMPER.
10. SUPPLY AIR TEMPERATURE SETPOINT
10.1 THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL
MAINTAIN A SUPPLY AIR TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING
AND HEATING REQUIREMENTS.
10.2 THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING
BASED ON ZONE COOLING REQUIREMENTS AS FOLLOWS: THE INITIAL SUPPLY AIR
TEMPERATURE SETPOINT SHALL BE 55 DEG F(ADJ.) AS COOLING DEMAND
INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF
53 DEG F(ADJ.) AS COOLING DEMAND DECREASES, THE SETPOINT SHALL
INCREMENTALLY RESET UP TO A MAXIMUM OF 58 DEG F(ADJ.).
11. COOLING COIL
11.1 THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND
MODULATE THE COOLING COIL VALVE TO MAINTAIN THE SUPPLY AIR TEMPERATURE
SETPOINT.
11.2 THE COOLING SHALL BE ENABLED WHENEVER: OUTSIDE AIR TEMPERATURE IS
GREATER THAN 50 DEGREES AND THE SUPPLY FAN STATUS IS ON AND THE HEATING
IS NOT ACTIVE
11.4 THE COOLING COIL VALVE SHALL OPEN TO 50%(ADJ.) WHENEVER THE
FREEZESTAT IS ON.
11.5 ALARMS
11.5.1 HIGH SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL ALARM IF
THE SUPPLY AIR TEMPERATURE IS 5 DEG F(ADJ.) GREATER THAN THE SUPPLY AIR
SETPOINT.
11.5.2 LOW SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL ALARM IF
THE SUPPLY AIR TEMPERATURE IS LESS THAN 45 DEG F(ADJ.).
12. ECONOMIZER
12.1 THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND
MODULATE THE OUTSIDE AIR DAMPER TO MAINTAIN THE ECONOMIZER
TEMPERATURE SETPOINT. THE ECONOMIZER TEMPERATURE SETPOINT IS EQUAL TO
THE SUPPLY AIR TEMPERATURE SETPOINT MINUS THE FAN HEAT OFFSET VALUE.
THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION TO
MAINTAIN MINIMUM OUTSIDE AIR REQUIRED.
12.2 THE ECONOMIZER SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 60 DEG F(ADJ) AND THE OA
TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE AND THE OA
ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY AND THE SUPPLY FAN STATUS
IS ON.
12.3 THE OUTSIDE AIR DAMPER SHALL CLOSE WHENEVER: MIXED AIR TEMPERATURE
DROPS BELOW 36 DEG F(ADJ.) OR THE FREEZESTAT IS ON OR THE SUPPLY FAN
STATUS IS OFF.
12.4 THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR
DAMPER SHALL OPEN WHEN THE UNIT IS OFF.
13. HUMIDIFIER CONTROL
13.1 THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND MODULATE
THE HUMIDIFIER TO MAINTAIN A SETPOINT OF 40% RH(ADJ.). THE HUMIDIFIER SHALL
BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON AND THE OUTSIDE AIR
TEMPERATURE IS BELOW 65 DEGREES.
13.2 THE HUMIDIFIER SHALL TURN OFF WHENEVER: SUPPLY AIR HUMIDITY
MEASURERS 90% OR WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 65 DEGREES OR
ON A LOSS OF SUPPLY FAN STATUS
13.3 ALARMS
HIGH SUPPLY AIR HUMIDITY 90%(ADJ)
LOW SUPPLY AIR HUMIDITY 30%(ADJ)
14. AIRFLOW CONTROL
14.1 THE CONTROL SYSTEM SHALL MONITOR AND DISPLAY SUPPLY AIR FLOW,
RETURN AIR FLOW, AND MIXED AIR FLOW IN CFM. IT WILL CALCULATE, AND DISPLAY
OUTDOOR AIR PERCENTAGE FROM THE MEASURED VALUES BASED ON THE
FOLLOWING FORMULA:
%OA = (RAT-MAT)/(RAT-OAT) X 100
14.2 THE MINIMUM OUTSIDE AIR DAMPER SHALL BE CONTROLLED AS FOLLOWS:
14.2.1 WHEN OUTSIDE AIR TEMPERATURE IS BELOW 50 DEGREES AND THE
ECONOMIZER CONTROL SEQUENCE HAS REDUCED THE OUTSIDE
18.2.7 FIVE MINUTES AFTER SUPPLY/RETURN FAN-ON STATUS HAS BEEN PROVEN,
OA FAN SHALL DELIVER 5% OF CFM RA AND EX DAMPERS SHOULD OPEN/CLOSE
SIMULTANEOUSLY WITH OA DAMPER. (OA=5% RA= 95% EX=5%).
18.2.8 FIVE MINUTES AFTER OA FAN STARTED DELIVERING 5%, RELEASE OA, RA,
RELIEF AIR DAMPERS TO CONTROL TO MEET MIXED AIR SETPOINT.
18.2.9 LOWER MIXED SET POINT TO 60 DEGREES FOR 10 MINUTES.
18.2.10 RELEASE MIXED AIR SET POINT BACK TO ORIGINAL SETTING.
AIRFLOW DOWN TO THE MINIMUM OUTSIDE AIR FLOW RATE, THE OUTSIDE AIR
DAMPER SHALL CLOSE TO THE MINIMUM POSITION.
14.2.2 WHEN THE AIR HANDLING UNIT CONTROLS ARE OPERATING IN ECONOMIZER
MODE, THE ECONOMIZER CONTROL SEQUENCE WILL MODULATE THE ECONOMIZER
DAMPER, WHILE THE OUTSIDE AIR DAMPER MAINTAINS MINIMUM OUTDOOR AIR
POSITION TO MAINTAIN THE MIXED AIR ECONOMIZER TEMPERATURE SETPOINT.
THE OUTSIDE AIR CALCULATION ABOVE IN 14.1 SHALL DISPLAY THE OUTSIDE AIR
PERCENTAGE BUT WILL NOT BE USED TO CONTROL THE OUTSIDE AIR DAMPER IN
THE ECONOMIZER MODE.
14.2.3 WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 60 DEGREES AND THE
ECONOMIZER IS NOT ENABLED BASED ON THE OUTSIDE AIR TEMPERATURE OR
ENTHALPY PER 12.2 ABOVE, THE CONTROL SEQUENCE SHALL REDUCE THE
OUTSIDE AIRFLOW DOWN TO THE MINIMUM OUTSIDE AIR FLOW RATE. THE OUTSIDE
METER SHALL MEASURE THE OUTSIDE AIR FLOW. CALCULATION ABOVE IN 14.1
SHALL DISPLAY THE OUTSIDE AIR PERCENTAGE BUT WILL NOT BE USED TO
CONTROL THE OUTSIDE AIR DAMPER. WHEN THE OUTSIDE AIR TEMPERATURE AND
THE RETURN TEMPERATURE ARE EQUAL, ADJUST THE RETURN AIR TEMPERATURE
UPWARD BY 0.1 DEGREE F TO ENABLE THE OUTSIDE AIR CALCULATION TO
FUNCTION.
15. FILTERS
15.1 ALARMS
15.1.1 PREFILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN
FILTER
15.1.2. FINAL FILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN
FILTER
16. FAN HEAT OFFSET VALUE
16.1 FAN HEAT OFFSET (0-5)- THE BCS SHALL RESET THE FAN HEAT OFFSET VALUE
BASED UPON THE DIFFERENCE BETWEEN SUPPLY AIR SETPOINT AND SUPPLY AIR
TEMPERATURE. THE LOWER LIMIT SHALL BE 0. THE UPPER LIMIT SHALL BE 5.
16.2 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF 2°F
BELOW THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL SUBTRACT 1 FROM THE
FAN HEAT OFFSET VALUE. IF THE FAN HEAT OFFSET VALUE IS GREATER THAN 0,
THEN THE FAN HEAT OFFSET SHALL BE SET TO 0. AFTER AN ADJUSTABLE PERIOD
OF 15 MINUTES THE PID LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO
THE SETPOINT AND ADJUST THE VALUE.
16.3 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE + OR -
2°F OF THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL ADD ZERO TO THE FAN
HEAT OFFSET VALUE. AFTER AN ADJUSTABLE PERIOD OF 15 MINUTES THE PID
LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO THE SETPOINT AND ADJUST
THE VALUE.
16.4 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF 2°F
ABOVE THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL ADD 1 TO THE FAN HEAT
OFFSET VALUE. IF THE FAN HEAT OFFSET VALUE IS GREATER THAN 5, THEN THE
FAN HEAT OFFSET SHALL BE SET TO 5. AFTER AN ADJUSTABLE PERIOD OF 15
MINUTES THE PID LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO THE
SETPOINT AND ADJUST THE VALUE.
17. CONTINUOUS COMMISSIONING ALARMS
17.1 IF IN COOLING MODE (OUTSIDE AIR IS GREATER THAN 50 DEGREES): PREHEAT
SECTION TEMP IS GREATER THAN MIXED AIR TEMPERATURE BY 1 DEG F, OR MORE,
THEN ALARM "STEAM VALVE OPEN IN COOLING MODE"
17.2 IF IN HEATING MODE (OUTSIDE AIR IS LESS THAN 50 DEGREES): COOLING
DISCHARGE TEMP IS LESS THAN PREHEAT TEMP BY 1 DEG F, OR MORE, THEN
ALARM "CHILLED WATER VALVE IS OPEN IN HEATING MODE"
18. COLD START SEQUENCE
18.1 WHENEVER UNIT IS STARTED AND OUTDOOR AIR TEMPERATURE IS BELOW 30
DEG F INITIATE THE FOLLOWING SEQUENCE.
18.2.1 OA DAMPER SHALL BE CLOSED (MIN OA FAN SHALL BE OFF), RELIEF AIR
DAMPER SHALL BE CLOSED, RETURN AIR DAMPER SHALL BE 100% OPEN
(ECONOMIZER DISABLED).
18.2.2 COMMAND ON STEAM PREHEAT VALVE.
18.2.3 STEAM PREHEAT VALVE SHALL MAINTAIN 80 DEGREE SUPPLY AIR
TEMPERATURE.
18.2.4 SMOKE DAMPER SHALL BE OPEN.
18.2.5 COMMAND ON SUPPLY AND RETURN (DRIVE) ALLOW TO RAMP UP NORMALLY.
18.2.6 SET MIXED AIR SETPOINT TO 70 DEG F ONCE SUPPLY/RETURN FAN ON
STATUS HAS BEEN PROVEN.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IS T E R
ED
E-62197
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
7/
/2
4:
:1
PM
H-004
HVAC TEMPERATURE CONTROLS EXPAND PRIMARY CARE FOR
PACT REALIGNMENT
10701 EAST BLVD. CLEVELAND, OHIO
541-376
NICK CARROZZA
8.1.21 CJS SRP
BID ISSUE SUBMISSION
8.1.21Revisions: Date:
DD SUBMISSION 5.3.19
65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19 100% CD's SUBMISSION 2.14.20
BID ISSUE SUBMISSION 8.1.21
NOTE: ALL REFERENCES TO THE
EXISTING BAS ARE REFERRING TO
THE EXISTING TRIDIUM SYSTEM IN
THE BUILDING. REFER TO
SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
Hardware Points Software Points
Point Name AI AO BI BO Trend Show On
Graphic Supply Air Static Pressure x x x x
Return Airflow x x x
Supply Airflow x x x
Outside Airflow x x x x
Prefilter Status x x x
UVC Emitter Status x x x x
Mixed Air Temp x x x
Return Air Humidity x x x
Return Air Temp x x x
Supply Air Temp x x x
Return Air Static Pressure x x
Relief Air Airflow x x
Outdoor Air Temp x x
Outside Air Humidity x x
Pre Heat…