S02. Drawing - Outpatient Pharmacy Exhaust - EF-52.pdf

PDF 368 KB Posted

Attached to
Expand Primary Care for Pact Realignment Federal contract opportunity
Solicitation number
36C25020B0060_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document package includes a technical drawing for an outpatient pharmacy exhaust system renovation and the related federal contract opportunity solicitation.

The technical drawing outlines planned upgrades to the existing HVAC system serving the outpatient pharmacy, including installing new and relocating existing VAV boxes, extending ductwork, installing a new exhaust fan and ductwork to serve a new drug receiving area, and balancing various airflows. The opportunity solicitation is for expanding primary care spaces at the Louis Stokes Cleveland VA Medical Center to accommodate a patient aligned care team realignment. The project scope involves a 12,000 square foot expansion on three floors of an existing ambulatory care addition. The estimated value is between $10-15 million. The solicitation closes on August 12, 2021 and is a 100% set-aside for service-disabled veteran-owned small businesses.

View the file

Other files for this federal contract opportunity

Other files attached to Expand Primary Care for Pact Realignment, newest first.
File Type Posted
S02. Solicitation 36C25020B0060_1.pdf PDF
S02. Wage Determination.pdf PDF
S02. Bid Opening Instructions.pdf PDF
S02. BID ISSUE - SPECIFICATIONS.pdf PDF
S02. Brand Name or Equal Memo 2020-05-06.pdf PDF
S02. Drawing - 1-H27 - Basement Plan - Zoning.pdf PDF
S02. Drawing - 1-H54 - Basement Plan - Mechanical Room.pdf PDF
S02. Drawing - Pre-Testing Reference Update.pdf PDF
S02. Drawings - HVAC.pdf PDF
S02. Drawings - SITE LANDSCAPE.pdf PDF
S02. Drawings - STRUCTURAL.pdf PDF
S02. VA NOTICE OF LIMITATIONS ON SUBCONTRACTING.docx DOCX document
S02. Sole Source - Lenel - 2020-05-07_Redacted.pdf PDF
S02. Brand Name Spreadsheet 2020-05-07.pdf PDF
S02. Calculation of Self-Performed and Sub-Contracted Work.docx DOCX document
S02. Drawings - ARCHITECURAL.pdf PDF
S02. Drawings - CIVIL.pdf PDF
S02. Drawings - FIRE PROTECTION.pdf PDF
S02. Sole Source - Tridium - 2020-05-07_Redacted.pdf PDF
S02. Sole Source - Corbin Russwin Door Lock - 2020-05-07_Redacted.pdf PDF
S02. Safety.docx DOCX document
S02. RFI Form.docx DOCX document
S02. Drawing - 1-H46 - Second Floor Plan - ACC South.pdf PDF
S02. Drawings - ELECTRICAL.pdf PDF
S02. Drawings - PLUMBING.pdf PDF
S02. Drawings - RENDERINGS.pdf PDF
S02. Sole Source - Notifier Fire Alarm - 2020-05-07_Redacted.pdf PDF
S02. Sole Source - Hill-Rom Nurse Call - 2020-05-07_Redacted.pdf PDF
S02. Drawing - 1-H28 - First Floor Plan - Zoning.pdf PDF
S02. Drawing - 1-H29 - Second Floor Plan - Zoning.pdf PDF
S02. Drawing - 1-H34 - First Floor Plan - ACC North.pdf PDF
S02. Drawing - 1-H36 - First Floor Plan - ACC South.pdf PDF
S02. Drawing - 1-H44 - Second Floor Plan - ACC North.pdf PDF
S02. VAMC Health Requirements.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

T

16"x6"

"x

D

A

A

A

"ø

"x

8"

1.0

"ø

E

P

O

N1

N

M

L

KJ

53A

53525150 m

N3

K450.3

8E

8E

1.2

CODED NOTES

1. EXTEND EXISTING 12"⌀ SUPPLY DUCTWORK AS REQUIRED FROM POINT INDICATED TO ALLOW

FOR NEW SUPPLY INLETS TO BE ROUTED TO VAV BOXES.

2. INSTALL RELOCATED VAV BOX IN APPROXIMATELY THIS LOCATION. EXTEND INLET FROM

SUPPLY MAIN. EXTEND HEATING WATER PIPING FROM EXISTING MAINS AND INSTALL TRIM PER

DETAIL. EXTEND CONTROL WIRING AS REQUIRED. REBALANCE BOX TO PROVIDE A MAXIMUM

SUPPLY OF 375 CFM AND A MINIMUM OF 375 CFM. REBALANCE WATER FLOW RATE TO 1.2 GPM.

3. INSTALL NEW VAV BOX IN APPROXIMATELY THIS LOCATION. EXTEND INLET FROM SUPPLY

MAIN. EXTEND HEATING WATER PIPING FROM EXISTING MAINS AND INSTALL TRIM PER DETAIL.

INSTALL NEW THERMOSTAT IN LOCATION INDICATED AND EXTEND CONTROL WIRING AS

REQUIRED.

4. INSTALL NEW 16"X6" EXHAUST DUCTWORK AND TIE IN TO EXISTING 16"X8" MAIN IN

APPROXIMATE LOCATION SHOWN. EXTEND 16"X6" DUCT TO SERVE NEW DRUG RECEIVING AREA.

TRANSITION TO 10"X10" AT APPROXIMATE LOCATION INDICATED. TRANSITION USING 45 DEGREE

OFFSETS ALONG ROUTE TO AVOID EXISTING CONDITIONS. ALL DUCTWORK SEAMS SHALL BE

FULLLY SEALED

5. INSTALL NEW RETURN AIR GRILLE AND EXTEND EXISTING ABOVE CEIING RETURN DUCTWORK

AS REQUIRED.

6. INSTALL REPLACEMENT EXHAUST FAN IN APPROXIMATELY THE SAME LOCATION AS THE

PREVIOUSLY DEMOLIHSED UNIT. ALTER EXISTING CURB/SUPPORTS AS REQUIRED. EXTEND AND

RECONNECT EXISTING DUCTWORK. FABRICATE AND INSTALL NEW STACK OUTLET AND

TRANSITION TO NEW FAN OUTLET AS REQUIRED.

7. INSTALL NEW EXHAUST VAV TERMINAL IN APPROXIMATELY THIS LOCATION. EXTEND OUTLET

TO SERVE NEW EXISTING GRILLE OR HOOD AS INDICATED. REFER TO SHEET H-200 FOR

ASSOCIATED TEMPERATURE CONTROL SEQUENCES.

8. ROUTE 10"⌀ DOWN TO HOOD CONNECTION. BALANCE HOOD EXHAUST OUTLET TO 400 CFM.

PLAN NOTES

A. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION.

B. COORDINATE ANY REQUIRED SHUTDOWNS WITH THE OWNER 7 DAYS IN ADVANCE.

C. ALL EXISTING DUCTWORK, EQUIPMENT, PIPING, ETC. SHALL REMAIN UNLESS NOTED

OTHERWISE. PROTECT DURING CONSTRUCTION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING HEPA FILTRATION UNITS TO SERVE

CONSTRUCTION AREAS AS REQUIRED BY ICRA. CONFORM TO ALL APPLICABLE GUIDELINES FOR

AIRFLOWS, DISCHARGE, ETC.

24"x20"

EF-52

P

O

N

M

L 53525150

50.3

DATESIGNATURE

SCHOONOVER

C. J.

ST

ATE OF OHIO

P R

O

FESS IO N

A L EN G

IN

E E

R

R EG IS T E RED

E-62197

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project Number

Drawing Number on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne fo ot on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne f oo t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT:CONSULTANTS:

Office of

Construction and Facilities Management

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

1468 WEST 9TH STREET #400 CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

/2

8/

0:

:0

AM

C

:\U se rs \S

P av lik \D oc um en ts

\1

_M

EP

_C

E N

TR

AL

F

IL

E_ sp av lik

.rv t VETERANS AFFAIRS MEDICAL CENTER

RENOVATE PHARMACY TO COMPLY WITH

USP DIRECTIVES

5.30.19

BASEMENT LEVEL PHASE I HVAC

IMPROVEMENT PLAN - OUTPATIENT

PHARMACY

H-OP.1

541-19-103

10701 EAST BLVD. CLEVELAND, OHIO

CJS SRP

5.30.19

N 1/8" = 1'-0"

BASEMENT LEVEL PHASE I HVAC IMPROVEMENT PLAN - OUTPATIENT PHARMACY

N 1/8" = 1'-0"

5TH FLOOR/ROOF PHASE I HVAC IMPROVEMENT PLAN - OUTPATIENT PHARMACY

Revisions Date

2 RFI-004 RESPONSE 10.28.19

BID ISSUE SUBMISSION 5.30.19

100% CD'S SUBMISSION 12.21.18

90% CD'S SUBMISSION 11.16.18

65% CD'S SUBMISSION 10.12.18

35% CD'S SUBMISSION 8.20.18

HOOD IS

CURRENTLY NOT

INSTALLED.

File details come from the government source that posted it. Updated .