S02. Drawings - FIRE PROTECTION.pdf

PDF 2 MB Posted

Attached to
Expand Primary Care for Pact Realignment Federal contract opportunity
Solicitation number
36C25020B0060_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This solicitation provides the details for an expansion project at the Louis Stokes Cleveland VA Medical Center to expand primary care for Patient Aligned Care Teams. The project scope includes providing an additional 12,000 square feet of space on three floors by expanding into an adjacent building on VA-owned land. The contractor shall provide all labor, equipment, and materials necessary to complete the expansion project. The project value is estimated between $10-15 million. The NAICS code is 236220 and the business size standard is $39.5 million.

The solicitation is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. Offerors must be verified in VETBIZ and registered in SAM by the offer due date and award date to be eligible. An organized site visit will be conducted on August 12th in accordance with FAR 52.236-27 and social distancing guidelines. The cut-off date to submit requests for information is August 12, 2021. The performance location is the Louis Stokes Cleveland VA Medical Center.

View the file

Other files for this federal contract opportunity

Other files attached to Expand Primary Care for Pact Realignment, newest first.
File Type Posted
S02. VA NOTICE OF LIMITATIONS ON SUBCONTRACTING.docx DOCX document
S02. Sole Source - Lenel - 2020-05-07_Redacted.pdf PDF
S02. Brand Name Spreadsheet 2020-05-07.pdf PDF
S02. Calculation of Self-Performed and Sub-Contracted Work.docx DOCX document
S02. Drawings - ARCHITECURAL.pdf PDF
S02. Drawings - CIVIL.pdf PDF
S02. Sole Source - Tridium - 2020-05-07_Redacted.pdf PDF
S02. Sole Source - Corbin Russwin Door Lock - 2020-05-07_Redacted.pdf PDF
S02. Safety.docx DOCX document
S02. RFI Form.docx DOCX document
S02. Drawing - 1-H46 - Second Floor Plan - ACC South.pdf PDF
S02. Drawing - Outpatient Pharmacy Exhaust - EF-52.pdf PDF
S02. Drawings - ELECTRICAL.pdf PDF
S02. Drawings - PLUMBING.pdf PDF
S02. Drawings - RENDERINGS.pdf PDF
S02. Sole Source - Notifier Fire Alarm - 2020-05-07_Redacted.pdf PDF
S02. Sole Source - Hill-Rom Nurse Call - 2020-05-07_Redacted.pdf PDF
S02. Drawing - 1-H28 - First Floor Plan - Zoning.pdf PDF
S02. Drawing - 1-H29 - Second Floor Plan - Zoning.pdf PDF
S02. Drawing - 1-H34 - First Floor Plan - ACC North.pdf PDF
S02. Drawing - 1-H36 - First Floor Plan - ACC South.pdf PDF
S02. Drawing - 1-H44 - Second Floor Plan - ACC North.pdf PDF
S02. VAMC Health Requirements.pdf PDF
S02. Solicitation 36C25020B0060_1.pdf PDF
S02. Wage Determination.pdf PDF
S02. Bid Opening Instructions.pdf PDF
S02. BID ISSUE - SPECIFICATIONS.pdf PDF
S02. Brand Name or Equal Memo 2020-05-06.pdf PDF
S02. Drawing - 1-H27 - Basement Plan - Zoning.pdf PDF
S02. Drawing - 1-H54 - Basement Plan - Mechanical Room.pdf PDF
S02. Drawing - Pre-Testing Reference Update.pdf PDF
S02. Drawings - HVAC.pdf PDF
S02. Drawings - SITE LANDSCAPE.pdf PDF
S02. Drawings - STRUCTURAL.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESCRIPTIONABBREVIATION SYMBOL

AS

DAS

F

FIRE PROTECTION SYMBOL LEGEND

IW INDIRECT WASTE (ABOVE OR BELOW FLOOR)

AS AUTOMATIC SPRINKLER LINE

DAS DRY AUTOMATIC SPRINKLER LINE

FIRE LINE

UPRIGHT SPRINKLER HEAD

PENDENT SPRINKLER HEAD

RECESSED OR CONCEALED SPRINKLER HEAD

SIDEWALL SPRINKLER HEAD

T&D TEST AND DRAIN WITH HOSE ADAPTOR

BALL DRIP

FLOW SWITCH - AUTOMATIC SPRINKLERS

VALVE WITH TAMPER SWITCH (SEE SPECIFICATIONS FOR TYPE)

PIPE SLEEVE (SEE SPECIFICATIONS FOR ADDIT. REQUIREMENTS)

VIBRATION CONNECTION (SEE SPECIFICATIONS)

BEP DOUBLE CHECK BACKFLOW PREVENTER WITH TAMPER SWITCHES

DDC DOUBLE DETECTOR CHECK VALVE WITH TAMPER SWITCHES

F.H.C. F.H.C. FIRE HOSE CABINET

F.D.V.C. F.D.V.C. FIRE DEPARTMENT VALVE CABINET

PRESSURE GAUGE WITH GAUGE COCK (WATER)

PRESSURE GAUGE WITH BALL VALVE (WATER)

E.C. E.C. ELECTRICAL CONTRACTOR

F.P.C. F.P.C. FIRE PROTECTION CONTRACTOR

G.C. G.C. GENERAL CONTRACTOR

H.C. H.C. HVAC CONTRACTOR

P.C. P.C. PLUMBING CONTRACTOR

A.D. A.D. ACCESS DOOR

A.F.F. A.F.F. ABOVE FINISHED FLOOR

MFR. MFR. MANUFACTURER

N.O. N.O. NORMALLY OPEN

N.C. N.C. NORMALLY CLOSED

TYP. TYP. TYPICAL

INDICATES TIE INTO EXISTING

INDICATES REMOVE TO POINT FOR RECONNECTION

INDICATES REMOVE TO POINT AND CAP

WALL SECTION

FLOOR SECTION

FURNISH AND INSTALL

FIRESTOP MATERIALS IN

ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS

TO MAINTAIN FIRE RESISTANCE

RATING

PIPE SLEEVE

DAMMING MATERIAL

(PER U.L. TESTED

SYSTEM DESIGN)

FLOOR SLAB; SEE

ARCHITECTURAL DRAWINGS

FOR FLOOR CONSTRUCTION

AND FIRE RATING

PIPE INSULATION

(WHERE SPECIFIED)

PENETRATING COMPONENT

FURNISH AND INSTALL FIRESTOP

MATERIALS IN ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS TO

MAINTAIN FIRE RESISTANCE RATING

PIPE SLEEVE (SLEEVE TO

EXTEND 2" ABOVE FLOOR

IN MECHANICAL EQUIPMENT

ROOMS.)

SEAL JOINT BETWEEN SLEEVE

AND FLOOR SLAB WITH MIN. 1/2"

BEAD FIRESTOP CAULK

SEE ARCHITECTURAL

DRAWINGS FOR WALL

CONSTRUCTION AND FIRE

RATING

PENETRATING COMPONENT

PIPE INSULATION

(WHERE SPECIFIED)

NOTES:

1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN

TESTED IN ACCORDANCE WITH U.L. 1479 OR ASTM E814.

2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING

MATERIALS AND U.L. SYSTEMS.

3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT

CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.

4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION

RESULTING FROM HIS WORK.

5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ARCHITECT, INCLUDING U.L. RATED SYSTEM

NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.

6. THE FIRESTOPPING SYSTEMS ARE TO BE INSTALLED BY EXPERIENCED, MANUFACTURER TRAINED, AND

UL CERTIFIED OR FM CERTIFIED PERSONNEL.

7. ALL FIRESTOPPING MATERIAL IS TO BE PROVIDED FROM A SINGLE MANUFACTURER FOR ALL

APPLICATIONS.

8. CONTRACTOR SHALL CONSULT MANUFACTURER'S TECHNICAL EXPERTS FOR ASSISTANCE IN SELECTING

APPROPRIATE FIRESTOPPING SYSTEM FOR EACH APPLICATION.

THROUGH FIRE-RATED CONSTRUCTIONS

N.T.S.

FIRESTOPPING DETAIL FOR PENETRATIONS

FIRE PROTECTION GENERAL NOTES

1. THE GENERAL NOTES LISTED HERE APPLY TO ALL FIRE PROTECTION DRAWINGS IN ADDITION

TO ANY ADDITIONAL DRAWING NOTES ON THE INDIVIDUAL DRAWINGS.

2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.

3. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.

4. COORDINATE WITH GENERAL TRADES WORK, HVAC WORK, PLUMBING WORK, ELECTRICAL

WORK AND OTHER WORK.

5. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED

STRUCTURES. SEE DETAILS AND SPECIFICATIONS FOR PIPE PENETRATION SEAL

REQUIREMENTS.

6. REFER TO ARCHITECTURAL DRAWINGS FOR ROOM DESIGNATIONS INCLUDING ALL STORAGE

AREAS. ALL STORAGE AREAS ARE TO BE SPRINKLERED AS ORDINARY HAZARD PER N.F.P.A.

7. THE FIRE PROTECTION DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO

SHOW EXACT LOCATION OF EQUIPMENT AND PIPING UNLESS DIMENSIONS ARE GIVEN OR

OTHERWISE IMPLIED FOR CLEARANCES, ETC. PIPING AND FIRE PROTECTION EQUIPMENT ARE TO

BE INSTALLED ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN MIND

ACTUAL BUILDING CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK. THIS

CONTRACTOR TO BE AWARE OF LIMITED SPACE ABOVE CEILING FOR NEW WORK AND SHOULD

MODIFY HIS WORK TO ACCOMMODATE OTHER TRADES. COORDINATE WORK WITH OTHER

TRADES PRIOR TO MAKING THE FINAL INSTALLATION DRAWING OR SYSTEM INSTALLATION. THE

CONTRACTORS IN THEIR BIDS ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS AND

OTHER RELATED WORK NECESSARY TO PROVIDE MINOR OFFSETS IN FIRE PROTECTION WORK

AS REQUIRED TO AVOID CONFLICT WITH OTHER WORK ON THIS PROJECT, OR AS REQUIRED IN

ORDER TO OBTAIN MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN SPACES.

8. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING, PATCHING,

REMOVAL, AND RE-INSTALLATION OF WALLS, CEILINGS, FLOORS, ETC. AND NEW MATERIALS FOR

THE INSTALLATION OF THEIR RESPECTIVE WORK AS SHOWN ON THE DRAWINGS OR

SPECIFICATIONS FOR AREAS OTHERWISE NOT INVOLVED IN THE GENERAL CONSTRUCTION

WORK.

9. ALL SPRINKLER HEADS ARE TO BE QUICK RESPONSE TYPE.

10. ALL FIRE PROTECTION PIPING AND CONDUIT SHALL FOLLOW THE INSTALLATION

REQUIREMENTS AS LISTED BELOW:

A. INSTALL TIGHT AGAINST BOTTOM OF ROOF AND FLOOR STRUCTURE.

B. INSTALL PARALLEL AND PERPENDICULAR TO BUILDING STRUCTURE.

C. INSTALL CONCEALED ABOVE CEILINGS OR INSIDE WALLS, UNLESS OTHERWISE NOTED.

11. SPRINKLER PIPING IS TO AVOID EQUIPMENT IN MECHANICAL AND ELECTRICAL ROOMS.

COORDINATE WITH H.C. AND E.C.

12. USE INTERMEDIATE LEVEL SPRINKLERS BELOW DUCTWORK AND STRUCTURAL MEMBERS,

WHERE APPLICABLE.

13. CONTRACTOR SHALL PAINT ALL EXPOSED FIRE PROTECTION PIPING INSIDE AND OUTSIDE

BUILDING WITH COLOR AS SELECTED BY ARCHITECT.

14. ALL VALVES, FLOW SWITCHES, AND ETC. ABOVE THE CEILING SHALL BE LABELED WITH

ENGRAVED LAMINATE TAG ATTACHED TO CEILING GRID WITH PRESSURE SENSITIVE TAPE. THE

(RED) LAMINATE TAG SHALL BE 1/2" WIDE WITH 1/4" HIGH ENGRAVED (WHITE) LETTERS.

15. FIRE PROTECTION CONTRACTOR TO COORDINATE FINAL PLACEMENT OF SPRINKLER HEADS

WITH REFLECTED CEILING PLANS. SPRINKLER HEADS SHALL BE INSTALLED IN STRAIGHT AND

PARALLEL LINES CENTERED IN A SYMMETRICAL AND UNIFORM PATTERN IN THE CEILING TILES

(TYP ALL HEADS).

16. SPRINKLER HEADS TO BE PROVIDED IN TYPES AND FINISHES AS SPECIFIED IN SPECIFICATION

SECTION 21100.

17. ALL WORK IS TO COMPLY WITH DESIGN AND INSTALLATION REQUIREMENTS PER NATIONAL

FIRE PROTECTION AGENCY 13, THE OHIO BUILDING CODE, AND THE OWNER'S INSURANCE

COMPANY. THE MOST STRINGENT REQUIREMENTS SHALL APPLY.

18. FIRE PROTECTION CONTRACTOR SHALL PERFORM WATER FLOW TEST PRIOR TO

PERFORMING HYDRAULIC CALCULATIONS AND SPRINKLER LAYOUT. TEST TO MEET N.F.P.A.

REQUIREMENTS. CONTRACTOR SHALL COORDINATE WHEN TEST IS TO BE PERFORMED WITH

OWNER AND COPY TEST RESULTS TO PROJECT ENGINEER AND OWNER.

19. FIRE PROTECTION CONTRACTOR SHALL HYDRAULICALLY CALCULATE AUTOMATIC SPRINKLER

SYSTEM AND INSTALL NEW SYSTEM AS REQUIRED BY NEW CALCULATIONS AND DESIGN. THE

FIRE PROTECTION CONTRACTOR SHALL DESIGN THE SYSTEM, SUBMIT AND ETC. AS LISTED

BELOW:

A. COMPLETE AND RETURN TO A/E A COPY OF THE AUTOMATIC SPRINKLER SYSTEM SHOP

DRAWINGS INCLUDING:

1. THE PLANS SHALL SHOW THE WATER SUPPLY REQUIREMENTS FOR THE HYDRAULICALLY MOST

DEMANDING AREA. THE DESIGN CALCULATIONS SHALL SUBSTANTIATE THAT THE AVAILABLE

WATER SUPPLY WILL FULFILL THE SYSTEM REQUIREMENTS.

2. THE WATER SUPPLY REQUIREMENTS SHALL BE DETERMINED ACCORDING TO HAZARD

CLASSIFICATION AS OUTLINED IN N.F.P.A. 13 HYDRAULICALLY DESIGNED SYSTEMS.

3. WHEN SPRINKLER SYSTEMS ARE CONNECTED TO CITY WATER MAINS, FLOW TEST RESULTS

SHALL BE SUBMITTED. THE PLANS SHALL SHOW THE FOLLOWING INFORMATION ON WATER

FLOW DATA WITH EXISTING OR PROPOSED WATER SUPPLY, DEAD END OR CIRCULATING:

a. LOCATION AND ELEVATION OF STATIC AND RESIDUAL TEST GAGE WITH RELATION TO THE

RISER REFERENCE POINT.

b. FLOW LOCATION.

c. STATIC PRESSURE, PSI

d. RESIDUAL PRESSURE, PSI

e. FLOW, GPM

f. DATE

g. TIME

h. TEST CONDUCTED BY OR INFORMATION SUPPLIED BY

i. PLOTTED GRAPH SHOWING WATER SUPPLY CURVES AND SYSTEM REQUIREMENTS IN ACCORDANCE WITH SECTIONS 6-3, 6-2.4, AND A-7-2.1 OF N.F.P.A. 13, APPROVED ADDITION.

20. FIRE MAIN TO BE HYDRAULICALLY CALCULATED AND SIZED TO DESIGN INSTALLATION

REQUIREMENTS AS PER N.F.P.A., SECTIONS 13.

21. STAIRWAYS TO BE PROTECTED PER N.F.P.A. 13.

22. INSTALL TEST AND DRAIN, SEE DETAIL AND NOTES ON DRAWING. BALL VALVE TO HAVE A 1/2"

ROUND CORROSION RESISTANT SMOOTH BORE OUTLET GIVING THE EQUIVALENT FLOW OF ONE

SPRINKLER HEAD.

23. ALL OCCUPIED AREAS OF THE BUILDING ARE TO HAVE A WET PIPE SPRINKLER SYSTEM,

HYDRAULICALLY CALCULATED AND SIZED TO DESIGN INSTALLATION REQUIREMENTS OF N.F.P.A.

SECTIONS 13. FOR LIGHT HAZARD OCCUPANCY UNLESS NOTED OTHERWISE.

24. IF THE FIRE PROTECTION CONTRACTOR REQUIRES ACCESS PANELS, THE FIRE PROTECTION

CONTRACTOR SHALL FURNISH THE ACCESS PANELS WITH INSTALLATION COSTS ASSUMED BY

THE FIRE PROTECTION CONTRACTOR, BUT INSTALLED BY THE GENERAL CONTRACTOR. ANY

ACCESS PANELS PURCHASED DURING CONSTRUCTION BY THE FIRE PROTECTION CONTRACTOR

SHALL MATCH THOSE ALREADY PURCHASED BY THE GENERAL CONTRACTOR.

25. SEAL ALL PIPING PENETRATIONS THROUGH NON-RATED FLOORS TO PREVENT PASSAGE OF

SMOKE.

26. EXISTING SPRINKLER SYSTEM TO REMAIN ACTIVE WITHIN WORK AREAS DURING

CONSTRUCTION.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:0

PM

FP-001

FIRE PROTECTION NOTES, DETAILS AND

SYMBOL LEGEND

EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS JAV

BID ISSUE SUBMISSION

8.1.21Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19 100% CD's SUBMISSION 2.14.20

BID ISSUE SUBMISSION 8.1.21

49 50 50.3 51 52 53

J

K

K4

L

M

M.8

N

N.1

N.2

N.3

O

P

575654.554.153A 54

4" FIRE

4" FIRE

4" FIRE

4" FIRE

6" FIRE 6" FIRE

4" FIRE

4" F

IR

E

4" F

IR

E

BAC318 BAC317

BAC316

BS1 BAC309

BAC308

BAC307

BA109A

BA111-1

BS5-1BA109

BA109C

BS3

BAC306

BAC303

BAC302

BAC301A

BAC301BAC312BAC313

BAC311

BAC330

BAC285

BAC281

BAC282

BAC280

BAC283 BAC253

BAC260B

BAC252 BAC251

BAC250

BAC256

BAC257

BAC258

BAC259

BAC255BAC254

BAC286BAC329

AS

CODED NOTES

1. EXISTING FIRE DEPARTMENT CONNECTION PIPING UP TO FIRST FLOOR TO BE DEMOLISHED

BACK TO POINT INDICATED AND TIED INTO NEW 4" FIRE PIPING.

2. TIE NEW 4" FIRE DEPARTMENT CONNECTION PIPING IN TO EXISTING FIRE MAIN AND EXTEND UP

TO FIRST FLOOR TO NEW FIRE DEPARTMENT CONNECTION LOCATED ON ADDITION EXTERIOR

WALL.

3. ROUTE 4" FIRE PIPING TO STAIRWELL RISER. PROVIDE 2-1/2" FIRE LINE TO FIRE DEPARTMENT VALVE AT 36" ABOVE FINISHED FLOOR. CONTINUE 4" RISER UP WITHIN STAIRWELL TO FLOORS

ABOVE.

4. EXTEND EXISTING SPRINKLER ZONE IN ADJACENT MECHANICAL ROOM TO SERVE NEW

MECHANICAL ROOM. SPRINKLE USING ORDINARY HAZARD CLASSIFICATIONS. CONTRACTOR

SHALL ENSURE OBSTRUCTION RULES ARE FOLLOWED AND HEADS ARE ADDED UNDER

DUCTWORK AND EQUIPMENT AS REQUIRED BY NFPA 13.

5. INSTALL DRY TYPE SIDEWALL SPRINKER HEADS TO SERVE OUTSIDE AIR SHAFTS VIA WET PIPE

SPRINKLER SYSTEM.

6. TIE NEW 4" FIRE PIPING INTO 6" FIRE MAIN.

7. INSTALL NEW 4" FIRE DEPARTMENT CONNECTION WITH BALL DRIP VALVE AND EXTEND PIPING

UP TO FIRST FLOOR TO NEW FIRE DEPARTMENT CONNECTION LOCATED ON ADDITION EXTERIOR

WALL.

8. EXISTING FLOOR CONTROL VALVE ASSEMBLY TO REMAIN.

9. TIE NEW AS LINE INTO EXISTING AS LINE AND EXTEND TO NEW ADDITION.

PLAN NOTES

A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE

DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.

B. SEE SHEET FP-001 FOR FIRE PROTECTION SYMBOL LEGEND, FIRE PROTECTION GENERAL

NOTES, AND FIRE PROTECTION DETAILS.

C. AREAS WITH NO CEILINGS SUCH THAT THE AUTOMATIC SPRINKLER PIPING IS EXPOSED, THE

AUTOMATIC SPRINKLER PIPING SHALL BE INSTALLED TO FOLLOW ALONG THE STRUCTURE.

REFER TO ARCHITECTURAL PLANS.

D. OFFSET PIPING AROUND STRUCTURAL MEMBERS, LIGHTING, DUCTWORK, AND PLUMBING

PIPING AS REQUIRED TO MAINTAIN FINAL ROOM DIMENSIONS. COORDINATE EXACT PIPE ROUTING

WITH ALL TRADES.

E. SPRINKLER HEAD TYPES AT DESIGNATED AREAS: THE INSTALLATION OF SPRINKLER HEADS IN 2'X2' ACOUSTICAL TILE CEILINGS ARE TO BE CENTERED AND EITHER CENTERED AT HALFWAY OR QUARTER POINTS IN 2'X4' TILES. IN GYPSUM AND EXPOSED CEILING, INSTALL SPRINKLER HEADS

SYMMETRICALLY IN A STRAIGHT LINE. MAINTAIN A SYMMETRICAL PATTERN FOR ALL CEILING

TYPES FOR AN AESTHETICALLY PLEASING EFFECT. COORDINATE WITH ARCHITECTURAL

REFLECTED CEILING PLAN.

FINISHED CEILINGS (SUSPENDED LAY-IN AND GYPSUM): SPRINKLERS ARE TO BE CONCEALED

TYPE WITH WHITE COVERS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN.

EXPOSED CEILINGS: SPRINKLERS ARE TO BE UPRIGHT TYPE. PROVIDE SPRINKLER HEAD GUARDS

IN ALL AREAS SUBJECTED TO DAMAGE SUCH AS MECHANICAL ROOMS, ELECTRICAL ROOMS,

GYMNASIUM, AND STORAGE ROOMS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING

PLAN.

F. THE FIRE PROTECTION CONTRACTOR SHALL REMOVE OIL AND PREPARE AUTOMATIC

SPRINKLER PIPING AND DRAINS IN EXPOSED AREAS FOR PAINTING. THE FIRE PROTECTION

CONTRACTOR SHALL THEN PLACE PLASTIC BAGS OVER SPRINKLER HEADS. THE GENERAL

CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING THE AUTOMATIC SPRINKLER PIPING,

DRAINS, AND THEN REMOVE PLASTIC BAGS FROM SPRINKLER HEADS. COORDINATE PIPE

PREPARATION AND PAINTING REQUIREMENTS WITH ARCHITECT.

G. THE FIRE PROTECTION SYSTEM FOR THIS PROJECT SHALL BE DESIGNED BY THE INSTALLING

CONTRACTOR. THE INTENT OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS IS TO

PROVIDE BASIC INFORMATION ON MATERIALS AS WELL AS TO SHOW LOCATIONS OF VALVES,

PIPING MAINS, AND RISERS THAT HAVE ALREADY BEEN DIAGRAMMATICALLY COORDINATED INTO

THE BUILDING DESIGN. IT IS UNDERSTOOD THAT THE FIRE PROTECTION SYSTEM MUST BE

DESIGNED PRIOR TO INSTALLATION TO ASSURE THAT THE REQUIRED WATER FLOW RATES ARE

ACHIEVED AT ALL OF THE SPRINKLER HEADS.

H. IN THE CASE OF THIS PROJECT, DUE TO VERY LIMITED SPACE FOR MECHANICAL AND

ELECTRICAL SYSTEMS, IT WILL BE NECESSARY FOR THE FIRE PROTECTION SYSTEM DESIGNER

TO OBTAIN AND SHOW ON THE FIRE PROTECTION INSTALLATION DRAWINGS THE LOCATIONS OF

MAJOR DUCTWORK, PIPING AND ELECTRICAL MAINS, AND TO SHOW HOW THE FIRE PROTECTION

PIPING IS COORDINATED WITH THESE SYSTEMS. IT SHALL BE UNDERSTOOD THAT THE FIRE

PROTECTION DESIGNER SHALL MAKE REVISIONS TO THE INSTALLATION DRAWINGS AS

NECESSARY, BOTH DURING THE SHOP DRAWING REVIEW PROCESS AND DURING THE

INSTALLATION, AS REQUIRED TO INSTALL THE FIRE PROTECTION PIPING SYSTEMS INTO THE

SPACE AVAILABLE. THE AVAILABLE SPACE CAN BE DETERMINED BY REFERENCING THE

ARCHITECTURAL, STRUCTURAL, HVAC, PLUMBING, AND ELECTRICAL DRAWINGS. TO MAKE SURE

THAT THERE IS NO CONFUSION ON THIS ISSUE, ON THIS PROJECT, THE FIRE PROTECTION PIPING

SHALL BE INSTALLED AROUND THE BUILDING SYSTEMS AND NOT VICE VERSA.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:0

PM

FP-0-1

BASEMENT LEVEL PHASE I FIRE PROTECTION

IMPROVEMENT PLAN

EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS JAV

BID ISSUE SUBMISSION

8.1.21

N 1/8" = 1'-0"

BASEMENT LEVEL PHASE I FIRE PROTECTION IMPROVEMENT PLAN

ROOM LEGEND

BA109 Mechanical Room

BA109A Areawell Access BA109C Office BA110-1 Outside Air Enclosure-1 BA111-1 Mechanical Room-1 BAC250 Waiting

BAC250B Passage BAC251 Triage BAC252 Exam BAC253 Exam BAC254 Exam BAC255 Exam BAC256 Records BAC257 Office BAC258 Soiled Holding BAC259 Clean Supply

BAC260B Passage BAC280 Anti-Coagulation Clinic Open Office BAC281 Office BAC282 Copy File/Work BAC283 Break Room BAC285 Storage, File Room BAC286 Conference Room BAC301 Storage

BAC301A HD Storage Room

BAC302 HAC

BAC303 Staff Lockers/Break BAC306 Office BAC307 Work Room BAC308 Comm BAC309 Electrical Closet BAC311 Outpatient Pharmacy BAC312 Tech Sup. Mail Order BAC313 Consult Room BAC316 Supervisor BAC317 Tech Supply BAC318 Controlled Sub,/ Sec Disp BAC325 Elevator Lobby BAC326 Waiting BAC327 Corridor BAC328 Corridor BAC329 Womens BAC330 Mens

BS1 Stair 1 BS3 Stair 3

BS5-1 Stair 5-1

Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19

FEC

FE

C

FEC

REF

CODED NOTES

1. EXISTING FIRE DEPARTMENT CONNECTION TO BE DEMOLISHED BACK TO FLOOR BELOW.

2. INSTALL NEW FIRE DEPARTMENT CONNECTION IN APPROXIMATELY THIS LOCATION.

3. EXTEND EXISTING SPRINKLER ZONE SERVING FIRST FLOOR AREA TO SERVE ADDITION FIRST

FLOOR PER NFPA 13. SPRINKLE USING LIGHT HAZARD CLASSIFICATIONS; UNLESS NOTED

OTHERWISE.

4. 4" FIRE RISER UP FROM FLOOR BELOW. PROVIDE 2-1/2" FIRE DEPARTMENT VALVE AT 36" A.F.F.

CONTINUE 4" FIRE RISER UP TO FLOOR ABOVE.

5. EXISTING FIRE RISER AND ZONE VALVE SERVING FIRST FLOOR AREA.

6. RELOCATE EXISTING FIRE STANDPIPE DRAIN TO APPROXIMATELY THIS LOCATION.

7. SPRINKLE USING ORDINARY HAZARD CLASSIFICATIONS.

8. EXISTING FLOOR CONTROL VALVE ASSEMBLY TO REMAIN.

9. TIE NEW AS LINE INTO EXISTING AS LINE AND EXTEND TO NEW ADDITION.

PLAN NOTES

A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE

DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.

B. SEE SHEET FP-001 FOR FIRE PROTECTION SYMBOL LEGEND, FIRE PROTECTION GENERAL

NOTES, AND FIRE PROTECTION DETAILS.

C. AREAS WITH NO CEILINGS SUCH THAT THE AUTOMATIC SPRINKLER PIPING IS EXPOSED, THE

AUTOMATIC SPRINKLER PIPING SHALL BE INSTALLED TO FOLLOW ALONG THE STRUCTURE.

REFER TO ARCHITECTURAL PLANS.

D. OFFSET PIPING AROUND STRUCTURAL MEMBERS, LIGHTING, DUCTWORK, AND PLUMBING

PIPING AS REQUIRED TO MAINTAIN FINAL ROOM DIMENSIONS. COORDINATE EXACT PIPE ROUTING

WITH ALL TRADES.

E. SPRINKLER HEAD TYPES AT DESIGNATED AREAS: THE INSTALLATION OF SPRINKLER HEADS IN 2'X2' ACOUSTICAL TILE CEILINGS ARE TO BE CENTERED AND EITHER CENTERED AT HALFWAY OR QUARTER POINTS IN 2'X4' TILES. IN GYPSUM AND EXPOSED CEILING, INSTALL SPRINKLER HEADS

SYMMETRICALLY IN A STRAIGHT LINE. MAINTAIN A SYMMETRICAL PATTERN FOR ALL CEILING

TYPES FOR AN AESTHETICALLY PLEASING EFFECT. COORDINATE WITH ARCHITECTURAL

REFLECTED CEILING PLAN.

FINISHED CEILINGS (SUSPENDED LAY-IN AND GYPSUM): SPRINKLERS ARE TO BE CONCEALED

TYPE WITH WHITE COVERS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN.

EXPOSED CEILINGS: SPRINKLERS ARE TO BE UPRIGHT TYPE. PROVIDE SPRINKLER HEAD GUARDS

IN ALL AREAS SUBJECTED TO DAMAGE SUCH AS MECHANICAL ROOMS, ELECTRICAL ROOMS,

GYMNASIUM, AND STORAGE ROOMS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING

PLAN.

F. THE FIRE PROTECTION CONTRACTOR SHALL REMOVE OIL AND PREPARE AUTOMATIC

SPRINKLER PIPING AND DRAINS IN EXPOSED AREAS FOR PAINTING. THE FIRE PROTECTION

CONTRACTOR SHALL THEN PLACE PLASTIC BAGS OVER SPRINKLER HEADS. THE GENERAL

CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING THE AUTOMATIC SPRINKLER PIPING,

DRAINS, AND THEN REMOVE PLASTIC BAGS FROM SPRINKLER HEADS. COORDINATE PIPE

PREPARATION AND PAINTING REQUIREMENTS WITH ARCHITECT.

G. THE FIRE PROTECTION SYSTEM FOR THIS PROJECT SHALL BE DESIGNED BY THE INSTALLING

CONTRACTOR. THE INTENT OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS IS TO

PROVIDE BASIC INFORMATION ON MATERIALS AS WELL AS TO SHOW LOCATIONS OF VALVES,

PIPING MAINS, AND RISERS THAT HAVE ALREADY BEEN DIAGRAMMATICALLY COORDINATED INTO

THE BUILDING DESIGN. IT IS UNDERSTOOD THAT THE FIRE PROTECTION SYSTEM MUST BE

DESIGNED PRIOR TO INSTALLATION TO ASSURE THAT THE REQUIRED WATER FLOW RATES ARE

ACHIEVED AT ALL OF THE SPRINKLER HEADS.

H. IN THE CASE OF THIS PROJECT, DUE TO VERY LIMITED SPACE FOR MECHANICAL AND

ELECTRICAL SYSTEMS, IT WILL BE NECESSARY FOR THE FIRE PROTECTION SYSTEM DESIGNER

TO OBTAIN AND SHOW ON THE FIRE PROTECTION INSTALLATION DRAWINGS THE LOCATIONS OF

MAJOR DUCTWORK, PIPING AND ELECTRICAL MAINS, AND TO SHOW HOW THE FIRE PROTECTION

PIPING IS COORDINATED WITH THESE SYSTEMS. IT SHALL BE UNDERSTOOD THAT THE FIRE

PROTECTION DESIGNER SHALL MAKE REVISIONS TO THE INSTALLATION DRAWINGS AS

NECESSARY, BOTH DURING THE SHOP DRAWING REVIEW PROCESS AND DURING THE

INSTALLATION, AS REQUIRED TO INSTALL THE FIRE PROTECTION PIPING SYSTEMS INTO THE

SPACE AVAILABLE. THE AVAILABLE SPACE CAN BE DETERMINED BY REFERENCING THE

ARCHITECTURAL, STRUCTURAL, HVAC, PLUMBING, AND ELECTRICAL DRAWINGS. TO MAKE SURE

THAT THERE IS NO CONFUSION ON THIS ISSUE, ON THIS PROJECT, THE FIRE PROTECTION PIPING

SHALL BE INSTALLED AROUND THE BUILDING SYSTEMS AND NOT VICE VERSA.

49 50 50.3 51 52 53

J

K

K4

L

M

M.8

N

N.1

N.2

N.3

O

P

575654.554.153A 54

1A104-1

1S1-1 1A113-1 1A114-1

1A115-1 1A116-1 1A117-1 1A118-1 1A119-1

1A120-2

1A121-1

1A130-1

1A129-1

1A122-1 1A123-1

1A128-1

1A127-1

1A124-1 1A125-1

1A126-1

1A100A-1

1A112

1A111C

1A111A

1A111

1A108-1

1A109

1A110

1A111B

1A105-1

1A138

1A139-1 1A137B

1A137A

1A137D-1

1A137C-1 1A140-1

1A136-1

1A135-1

1A141-1 1A142-1

1A134-1

1A100C-1

1A132-1

1A144-1

1A143-1

1A133-1

1A100D-1

1A148-1

1A1661A164

1A149-11A150-1

1A162-1 1A160

1A151-11A152

1A158

1A217-1

1A155-1

1A154 1A153A-1

1A153B-1

1A156

1A171-1 1A170 1A169-1

1A157A-1

1A157 1A159

1A161-1 1A163-1 1A165

1A100E-1

1A105-1

1A102-1

1A216-1

1A214-1

1A100G-1

1AC290-1

1AC288-1

1AC289A-1

1AC289B-1

1AC220-1

1AC221-1 1AC222-1

1AC223-1

1AC220A-1

1A100F-1

1S3-1

1A181-1

1AC226-1

1AC291-1

1A213-1

1A129

1A134-2 1A133-2

1A132-1 1A131-1

1A136-1 1A137-1 1A138-1

1A139-1

1S5A-1

1S5-1

1A140-1

1A141-1

1A142-1

1A143-1

1A143A-11A144-1

1A145-1

1A146-1

AS

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:1

PM

FP-1-1

FIRST FLOOR LEVEL PHASE I FIRE

PROTECTION IMPROVEMENT PLAN

EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS JAV

BID ISSUE SUBMISSION

8.1.21

ROOM LEGEND

1A100A-1 Corridor-1 1A100C-1 Corridor-1 1A100D-1 Corridor-1 1A100E-1 Corridor-1 1A100F-1 Corridor-1 1A100G-1 Corridor-1 1A102-1 Reception-1 1A104-1 Lobby-1 1A105-1 Waiting Room-1 1A105-1 Waiting-1 1A108-1 Toilet-1 1A109 LPN Work Area 1A110 LPN Work Area 1A111 LPN Work Area

1A111A Office 1A111B Office 1A111C Lockers 1A112 Soiled Utility

1A113-1 Electrical-1 1A114-1 Telecomm-1 1A115-1 Exam/Treatment Room-1 1A116-1 Exam/Treatment Room-1 1A117-1 Exam/Treatment Room-1 1A118-1 Exam/Treatment Room-1 1A119-1 Exam/Treatment Room-1 1A120-2 Precepting Room-2 1A121-1 Clean Utility-1 1A122-1 Exam/Treatment Room-1 1A123-1 Exam/Treatment Room-1 1A124-1 Exam/Treatment Room-1 1A125-1 Exam/Treatment Room-1 1A126-1 Exam/Treatment Room-1 1A127-1 Exam/Treatment Room-1 1A128-1 Exam/Treatment Room-1 1A129 PACT Team Hub - North

1A129-1 Exam/Treatment Room-1 1A130-1 Exam/Treatment Room-1 1A131-1 Exam/Treatment Room-1 1A132-1 Diabetes Education Office-1 1A132-1 Exam/Treatment Room-1 1A133-1 Exam/Treatment Room-1 1A133-2 Exam/Treatment Room-2 1A134-1 Exam/Treatment Room-1 1A134-2 Exam/Treatment Room-2 1A135-1 Exam/Treatment Room-1 1A136-1 Social Work Office-1 1A136-1 Exam/Treatment Room-1 1A137-1 Exam/Treatment Room-1 1A137A GS6 Office 1A137B GS9 Office

1A137C-1 Check-Out-1 1A137D-1 Check-Out-1

1A138 Mas Reception 1 1A138-1 Exam/Treatment Room-1 1A139-1 Mas Reception 2-1 1A139-1 Exam/Treatment Room-1 1A140-1 Social Work Office-1 1A140-1 PACT Team Hub - South-1 1A141-1 Exam/Treatment Room-1 1A141-1 Nurse Managers Office-1 1A142-1 Exam/Treatment Room-1 1A142-1 Director's Office-1 1A143-1 Exam/Treatment Room-1 1A143-1 Precepting Room-1

1A143A-1 Elec. Closet-1 1A144-1 Break Room-1 1A144-1 Staff Toilet-1 1A145-1 Exam/Treatment Room-1 1A146-1 Exam/Treatment Room-1 1A148-1 Exam/Treatment Room-1 1A149-1 Exam/Treatment Room-1 1A150-1 Exam/Treatment Room-1 1A151-1 Exam/Treatment Room-1 1A152 Exam/Treatment Room

1A153A-1 Consult.-1 1A153B-1 Consult.-1

1A154 Men's 1A155-1 RR Alcove-1 1A156 Women's 1A157 Lead Techs Work Room

1A157A-1 Staff Toilet-1 1A158 Exam/Treatment Room 1A159 Exam/Treatment Room 1A160 Exam/Treatment Room

1A161-1 Exam/Treatment Room-1 1A162-1 Exam/Treatment Room-1 1A163-1 Exam/Treatment Room-1 1A164 Exam/Treatment Room 1A165 Exam/Treatment Room 1A166 Exam/Treatment Room

1A169-1 On-Call Room-1 1A170 Program Support Asst.

1A171-1 Nurse Manager-1 1A181-1 Comm Clos-1 1A213-1 Restroom Alcove-1 1A214-1 Womens-1 1A216-1 Vending-1 1A217-1 Elevator Lobby-1

1AC220-1 Waiting Room-1 1AC220A-1 Passage-1 1AC221-1 Reception-1 1AC222-1 Toilet-1 1AC223-1 Radiology 1-1 1AC226-1 View Sort-1 1AC288-1 Fast Track Exam 2-1

1AC289A-1 Conference Room-1 1AC289B-1 Staff Lounge-1 1AC290-1 Fast Track Exam 3-1 1AC291-1 Corridor-1

1S1-1 Stair 1-1 1S3-1 Stair 3-1 1S5-1 Stair 5-1

1S5A-1 Stair 5 Vest.-1

N 1/8" = 1'-0"

FIRST FLOOR LEVEL PHASE I FIRE PROTECTION IMPROVEMENT PLAN

Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19

FE

C

FEC

FEC

REF

49 50 50.3 51 52 53

J

K

K4

L

M

M.8

N

N.1

N.2

N.3

O

P

575654.554.153A 54

1A104-3

1S1-3 1A113-3

1A114-3 1A115-3

1A116-3 1A117-3

1A118-3

1A119-3

1A120-3

1A100A-3

1A121-2

1A122-3

1A123-31A124-3 1A125-3

1A126-2

1A127-3 1A128-2 1A129-2

1A130-3

1A108-3

1A112-2

1A111A-2

1A111-2

1A105-3

1A138-1 1A110-2

1A139-2

1A217-3

1A155-3

1A154-2

1A156-2

1A171-3

1A170-2 1A169-2

1A157A-2

1A153B-2

1A153A-2

1A137C-2

1A100C-2

1A136-2

1A140-2

1A135-3

1A141-2

1A134-4

1A142-2

1A133-4

1A143-2

1A132-2

1A144-2

1A130A-2

1S5-3

1A134-5

1A133-5

1A132-3 1A131-3

1A100H-2

1A136-3 1A137-3

1A138-3 1A139-3

1S5A-3

1A140-3

1A141-3

1A142-3

1A143-3

1A143A-3 1A144-3

1A145-3

1A146-3

1A153-2

1A148-3

1A147-2

1A100I-2

1A151-3 1A150-3 1A149-3

1A163-3 1A162-31A161-3

1A167-2 1A166-2 1A165-2 1A164-2 1A157-2

1S3-3

1A152-2

1A100F-3

1A181-3

1AC223-3

1A100G-3

1AC222-31AC221-3

1AC220-3

1AC289B-3

1AC290-3

1A216-3

1AC288-3

1A213-3

1A214-3

1A105-3

1A100D-5

1A137D-3

CODED NOTES

1. REWORK EXISTING SPRINKLER SYSTEM TO ACCOMMODATE RENOVATED ARCHITECTURAL

LAYOUT PER NFPA 13. ADD/RELOCATE HEADS AS REQUIRED. SPRINKLE USING LIGHT HAZARD

CLASSIFICATIONS; UNLESS NOTED OTHERWISE.

2. SPRINKLE USING ORDINARY HAZARD CLASSIFICATIONS.

PLAN NOTES

A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE

DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.

B. SEE SHEET FP-001 FOR FIRE PROTECTION SYMBOL LEGEND, FIRE PROTECTION GENERAL

NOTES, AND FIRE PROTECTION DETAILS.

C. AREAS WITH NO CEILINGS SUCH THAT THE AUTOMATIC SPRINKLER PIPING IS EXPOSED, THE

AUTOMATIC SPRINKLER PIPING SHALL BE INSTALLED TO FOLLOW ALONG THE STRUCTURE.

REFER TO ARCHITECTURAL PLANS.

D. OFFSET PIPING AROUND STRUCTURAL MEMBERS, LIGHTING, DUCTWORK, AND PLUMBING

PIPING AS REQUIRED TO MAINTAIN FINAL ROOM DIMENSIONS. COORDINATE EXACT PIPE ROUTING

WITH ALL TRADES.

E. SPRINKLER HEAD TYPES AT DESIGNATED AREAS: THE INSTALLATION OF SPRINKLER HEADS IN 2'X2' ACOUSTICAL TILE CEILINGS ARE TO BE CENTERED AND EITHER CENTERED AT HALFWAY OR QUARTER POINTS IN 2'X4' TILES. IN GYPSUM AND EXPOSED CEILING, INSTALL SPRINKLER HEADS

SYMMETRICALLY IN A STRAIGHT LINE. MAINTAIN A SYMMETRICAL PATTERN FOR ALL CEILING

TYPES FOR AN AESTHETICALLY PLEASING EFFECT. COORDINATE WITH ARCHITECTURAL

REFLECTED CEILING PLAN.

FINISHED CEILINGS (SUSPENDED LAY-IN AND GYPSUM): SPRINKLERS ARE TO BE CONCEALED

TYPE WITH WHITE COVERS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN.

EXPOSED CEILINGS: SPRINKLERS ARE TO BE UPRIGHT TYPE. PROVIDE SPRINKLER HEAD GUARDS

IN ALL AREAS SUBJECTED TO DAMAGE SUCH AS MECHANICAL ROOMS, ELECTRICAL ROOMS,

GYMNASIUM, AND STORAGE ROOMS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING

PLAN.

F. THE FIRE PROTECTION CONTRACTOR SHALL REMOVE OIL AND PREPARE AUTOMATIC

SPRINKLER PIPING AND DRAINS IN EXPOSED AREAS FOR PAINTING. THE FIRE PROTECTION

CONTRACTOR SHALL THEN PLACE PLASTIC BAGS OVER SPRINKLER HEADS. THE GENERAL

CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING THE AUTOMATIC SPRINKLER PIPING,

DRAINS, AND THEN REMOVE PLASTIC BAGS FROM SPRINKLER HEADS. COORDINATE PIPE

PREPARATION AND PAINTING REQUIREMENTS WITH ARCHITECT.

G. THE FIRE PROTECTION SYSTEM FOR THIS PROJECT SHALL BE DESIGNED BY THE INSTALLING

CONTRACTOR. THE INTENT OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS IS TO

PROVIDE BASIC INFORMATION ON MATERIALS AS WELL AS TO SHOW LOCATIONS OF VALVES,

PIPING MAINS, AND RISERS THAT HAVE ALREADY BEEN DIAGRAMMATICALLY COORDINATED INTO

THE BUILDING DESIGN. IT IS UNDERSTOOD THAT THE FIRE PROTECTION SYSTEM MUST BE

DESIGNED PRIOR TO INSTALLATION TO ASSURE THAT THE REQUIRED WATER FLOW RATES ARE

ACHIEVED AT ALL OF THE SPRINKLER HEADS.

H. IN THE CASE OF THIS PROJECT, DUE TO VERY LIMITED SPACE FOR MECHANICAL AND

ELECTRICAL SYSTEMS, IT WILL BE NECESSARY FOR THE FIRE PROTECTION SYSTEM DESIGNER

TO OBTAIN AND SHOW ON THE FIRE PROTECTION INSTALLATION DRAWINGS THE LOCATIONS OF

MAJOR DUCTWORK, PIPING AND ELECTRICAL MAINS, AND TO SHOW HOW THE FIRE PROTECTION

PIPING IS COORDINATED WITH THESE SYSTEMS. IT SHALL BE UNDERSTOOD THAT THE FIRE

PROTECTION DESIGNER SHALL MAKE REVISIONS TO THE INSTALLATION DRAWINGS AS

NECESSARY, BOTH DURING THE SHOP DRAWING REVIEW PROCESS AND DURING THE

INSTALLATION, AS REQUIRED TO INSTALL THE FIRE PROTECTION PIPING SYSTEMS INTO THE

SPACE AVAILABLE. THE AVAILABLE SPACE CAN BE DETERMINED BY REFERENCING THE

ARCHITECTURAL, STRUCTURAL, HVAC, PLUMBING, AND ELECTRICAL DRAWINGS. TO MAKE SURE

THAT THERE IS NO CONFUSION ON THIS ISSUE, ON THIS PROJECT, THE FIRE PROTECTION PIPING

SHALL BE INSTALLED AROUND THE BUILDING SYSTEMS AND NOT VICE VERSA.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:2

PM

FP-1-2

FIRST FLOOR LEVEL PHASE II FIRE

PROTECTION IMPROVEMENT PLAN

EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS JAV

BID ISSUE SUBMISSION

8.1.21

N 1/8" = 1'-0"

FIRST FLOOR LEVEL PHASE II FIRE PROTECTION IMPROVEMENT PLAN

ROOM LEGEND

1A100D-4 Space 1A100D-6 Space 1A100D-7 Space 1A100D-8 Space 1A100D-9 Space

1A100D-10 Space 1A100D-11 Space 1A100D-12 Space 1A100D-13 Space 1A100D-14 Space 1A100D-15 Space 1A100D-16 Space 1A100D-17 Space 1A100D-18 Space 1A100D-19 Space 1A100D-20 Space 1A100D-21 Space 1A100D-22 Space 1A100D-23 Space 1A100D-24 Space 1A100D-25 Space 1A100D-26 Space 1A100D-27 Space 1A100D-28 Space 1A100D-29 Space 1A100D-30 Space 1A100D-31 Space 1A100D-32 Space 1A100D-33 Space 1A100D-34 Space 1A100D-35 Space 1A100D-36 Space 1A100D-37 Space 1A100D-38 Space 1A100D-39 Space 1A100D-40 Space 1A100D-41 Space 1A100D-42 Space 1A100D-43 Space 1A100D-44 Space 1A100D-45 Space 1A100D-46 Space 1A100D-47 Space 1A100D-48 Space

BA110-2 Outside Air Enclosure-2 BA111-2 Mechanical Room-2 BS5-2 Stair 5-2

1A100A-3 Corridor-3 1A100C-2 Corridor-2 1A100D-5 Corridor-5 1A100F-3 Corridor-3 1A100G-3 Corridor-3 1A100H-2 Corridor-2 1A100I-2 Corridor-2 1A104-3 Lobby-3 1A105-3 Waiting Room-3 1A105-3 Waiting-3 1A108-3 Toilet-3 1A110-2 GS6/GS9 Office-2 1A111-2 SMA Conference Room-2

1A111A-2 SMA Storage Room-2 1A112-2 Exam/Treatment Room-2 1A113-3 Electrical-3 1A114-3 Telecomm-3 1A115-3 Exam/Treatment Room-3 1A116-3 Exam/Treatment Room-3 1A117-3 Exam/Treatment Room-3 1A118-3 Exam/Treatment Room-3 1A119-3 Exam/Treatment Room-3 1A120-3 Precepting Room-3 1A121-2 Clean Utility-2 1A122-3 Exam/Treatment Room-3 1A123-3 Exam/Treatment Room-3 1A124-3 Exam/Treatment Room-3 1A125-3 Exam/Treatment Room-3 1A126-2 Exam/Treatment Room-2 1A127-3 Exam/Treatment Room-3 1A128-2 Exam/Treatment Room-2 1A129-2 Exam/Treatment Room-2 1A130-3 Exam/Treatment Room-3

1A130A-2 Exam/Treatment Room-2 1A131-3 Exam/Treatment Room-3 1A132-2 Diabetes Education Office-2 1A132-3 Exam/Treatment Room-3 1A133-4 Exam/Treatment Room-4 1A133-5 Exam/Treatment Room-5 1A134-4 Exam/Treatment Room-4 1A134-5 Exam/Treatment Room-5 1A135-3 Exam/Treatment Room-3 1A136-2 Social Work Office-2 1A136-3 Exam/Treatment Room-3 1A137-3 Exam/Treatment Room-3

1A137C-2 Check-Out-2 1A137D-3 Check-Out-3 1A138-1 Mas. Reception 1-1 1A138-3 Exam/Treatment Room-3 1A139-2 Mas Reception 2-2 1A139-3 Exam/Treatment Room-3 1A140-2 Social Work Office-2 1A140-3 PACT Team Hub - South-3 1A141-2 Exam/Treatment Room-2 1A141-3 Nurse Managers Office-3 1A142-2 Exam/Treatment Room-2 1A142-3 Director's Office-3 1A143-2 Exam/Treatment Room-2 1A143-3 Precepting Room-3

1A143A-3 Elec. Closet-3 1A144-2 Break Room-2 1A144-3 Staff Toilet-3 1A145-3 Exam/Treatment Room-3 1A146-3 Exam/Treatment Room-3 1A147-2 Exam/Treatment Room-2 1A148-3 Exam/Treatment Room-3 1A149-3 Exam/Treatment Room-3 1A150-3 Exam/Treatment Room-3 1A151-3 Exam/Treatment Room-3 1A152-2 Storage-2 1A153-2 Soiled Holding-2

1A153A-2 Consult.-2 1A153B-2 Consult.-2 1A154-2 Mens-2 1A155-3 RR Alcove-3 1A156-2 Womens-2 1A157-2 Clean Utility-2

1A157A-2 Staff Toilet-2 1A161-3 Exam/Treatment Room-3 1A162-3 Exam/Treatment Room-3 1A163-3 Exam/Treatment Room-3 1A164-2 Mental Health Consult./Diabetes Education-2 1A165-2 Mental Health Consult.-2 1A166-2 Mental Health Consult.-2 1A167-2 Mental Health Consult.-2 1A169-2 On-Call Room-2 1A170-2 Program Support Ass't-2 1A171-3 Nurse Manager-3 1A181-3 Comm Clos-3 1A213-3 Restroom Alcove-3 1A214-3 Womens-3 1A216-3 Vending-3 1A217-3 Elevator Lobby-3

1AC220-3 Waiting Room-3 1AC221-3 Reception-3 1AC222-3 Toilet-3 1AC223-3 Radiology 1-3 1AC288-3 Fast Track Exam 2-3

1AC289B-3 Staff Lounge-3 1AC290-3 Fast Track Exam 3-3

1S1-3 Stair 1-3 1S3-3 Stair 3-3 1S5-3 Stair 5-3

1S5A-3 Stair 5 Vest.-3

Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19

C

FEC

FEC

FEC

R

EF

FE

C

49 50 50.3 51 52 53

J

K

K4

L

M

M.8

N

N.1

N.2

N.3

O

P

575654.554.153A 54

1A104-4

1S1-4

1A113-4 1A114-4 1A115-4

1A116-4

1A117-4

1A118-4 1A119-4 1A126A-2

1A108-4

1A111A-3

1A112-3

1A111-3

1A138-2 1A110-3

1A139-3

1A125-4

1A124-4 1A123-4 1A122-4

1A129-3

1A128-31A127-4 1A126-3

1A100D-3

1A100A-4

1A127-5

1A129-2

1A130A-3

1S5-4

1A134-6

1A133-6

1A131-4

1A131-5

1A130-4

1A100H-3

1A135-4

1A136-4 1A137-4

1A138-4

1A139-4

1S5A-4

1A140-4

1A141-4

1A142-4

1A143-4

1A143A-4

1A144-4

1A145-4

1A146-4

1A100I-3

1A153-3

1A148-4

1A147-3

1A105-4

1A217-4

1A117-5

1A118-5

1A119-3 1A122-5

1A120-2 1A121-2 1A121A-2

1A137C-3

1A154-3

1A155-4

1A156-3

1A153B-3

1A153A-3

1A137D-2

1A151-4 1A150-4 1A149-4

1A163-4

1A162-41A161-4

1A171-4

1A170-3

1A157A-3

1A169-3

1A166-31A167-3 1A165-3

1A164-3 1A157-3

1A100F-4

1A152-3

1S3-4

1AC223-4

1A100G-4

1AC220-4

1AC221-4

1AC222-4

1AC289B-4

1AC290-4

1AC288-4

1A213-4

1A214-4

1A216-4

1A105-4

CODED NOTES

1. REWORK EXISTING SPRINKLER SYSTEM TO ACCOMMODATE RENOVATED ARCHITECTURAL

LAYOUT PER NFPA 13. ADD/RELOCATE HEADS AS REQUIRED. SPRINKLE USING LIGHT HAZARD

CLASSIFICATIONS; UNLESS NOTED OTHERWISE.

2. SPRINKLE USING ORDINARY HAZARD CLASSIFICATIONS.

PLAN NOTES

A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE

DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.

B. SEE SHEET FP-001 FOR FIRE PROTECTION SYMBOL LEGEND, FIRE PROTECTION GENERAL

NOTES, AND FIRE PROTECTION DETAILS.

C. AREAS WITH NO CEILINGS SUCH THAT THE AUTOMATIC SPRINKLER PIPING IS EXPOSED, THE

AUTOMATIC SPRINKLER PIPING SHALL BE INSTALLED TO FOLLOW ALONG THE STRUCTURE.

REFER TO ARCHITECTURAL PLANS.

D. OFFSET PIPING AROUND STRUCTURAL MEMBERS, LIGHTING, DUCTWORK, AND PLUMBING

PIPING AS REQUIRED TO MAINTAIN FINAL ROOM DIMENSIONS. COORDINATE EXACT PIPE ROUTING

WITH ALL TRADES.

E. SPRINKLER HEAD TYPES AT DESIGNATED AREAS: THE INSTALLATION OF SPRINKLER HEADS IN 2'X2' ACOUSTICAL TILE CEILINGS ARE TO BE CENTERED AND EITHER CENTERED AT HALFWAY OR QUARTER POINTS IN 2'X4' TILES. IN GYPSUM AND EXPOSED CEILING, INSTALL SPRINKLER HEADS

SYMMETRICALLY IN A STRAIGHT LINE. MAINTAIN A SYMMETRICAL PATTERN FOR ALL CEILING

TYPES FOR AN AESTHETICALLY PLEASING EFFECT. COORDINATE WITH ARCHITECTURAL

REFLECTED CEILING PLAN.

FINISHED CEILINGS (SUSPENDED LAY-IN AND GYPSUM): SPRINKLERS ARE TO BE CONCEALED

TYPE WITH WHITE COVERS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN.

EXPOSED CEILINGS: SPRINKLERS ARE TO BE UPRIGHT TYPE. PROVIDE SPRINKLER HEAD GUARDS

IN ALL AREAS SUBJECTED TO DAMAGE SUCH AS MECHANICAL ROOMS, ELECTRICAL ROOMS,

GYMNASIUM, AND STORAGE ROOMS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING

PLAN.

F. THE FIRE PROTECTION CONTRACTOR SHALL REMOVE OIL AND PREPARE AUTOMATIC

SPRINKLER PIPING AND DRAINS IN EXPOSED AREAS FOR PAINTING. THE FIRE PROTECTION

CONTRACTOR SHALL THEN PLACE PLASTIC BAGS OVER SPRINKLER HEADS. THE GENERAL

CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING THE AUTOMATIC SPRINKLER PIPING,

DRAINS, AND THEN REMOVE PLASTIC BAGS FROM SPRINKLER HEADS. COORDINATE PIPE

PREPARATION AND PAINTING REQUIREMENTS WITH ARCHITECT.

G. THE FIRE PROTECTION SYSTEM FOR THIS PROJECT SHALL BE DESIGNED BY THE INSTALLING

CONTRACTOR. THE INTENT OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS IS TO

PROVIDE BASIC INFORMATION ON MATERIALS AS WELL AS TO SHOW LOCATIONS OF VALVES,

PIPING MAINS, AND RISERS THAT HAVE ALREADY BEEN DIAGRAMMATICALLY COORDINATED INTO

THE BUILDING DESIGN. IT IS UNDERSTOOD THAT THE FIRE PROTECTION SYSTEM MUST BE

DESIGNED PRIOR TO INSTALLATION TO ASSURE THAT THE REQUIRED WATER FLOW RATES ARE

ACHIEVED AT ALL OF THE SPRINKLER HEADS.

H. IN THE CASE OF THIS PROJECT, DUE TO VERY LIMITED SPACE FOR MECHANICAL AND

ELECTRICAL SYSTEMS, IT WILL BE NECESSARY FOR THE FIRE PROTECTION SYSTEM DESIGNER

TO OBTAIN AND SHOW ON THE FIRE PROTECTION INSTALLATION DRAWINGS THE LOCATIONS OF

MAJOR DUCTWORK, PIPING AND ELECTRICAL MAINS, AND TO SHOW HOW THE FIRE PROTECTION

PIPING IS COORDINATED WITH THESE SYSTEMS. IT SHALL BE UNDERSTOOD THAT THE FIRE

PROTECTION DESIGNER SHALL MAKE REVISIONS TO THE INSTALLATION DRAWINGS AS

NECESSARY, BOTH DURING THE SHOP DRAWING REVIEW PROCESS AND DURING THE

INSTALLATION, AS REQUIRED TO INSTALL THE FIRE PROTECTION PIPING SYSTEMS INTO THE

SPACE AVAILABLE. THE AVAILABLE SPACE CAN BE DETERMINED BY REFERENCING THE

ARCHITECTURAL, STRUCTURAL, HVAC, PLUMBING, AND ELECTRICAL DRAWINGS. TO MAKE SURE

THAT THERE IS NO CONFUSION ON THIS ISSUE, ON THIS PROJECT, THE FIRE PROTECTION PIPING

SHALL BE INSTALLED AROUND THE BUILDING SYSTEMS AND NOT VICE VERSA.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

REG IS T E R

ED

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

STRUCTURAL ENGINEERING:

THORSON BAKER + ASSOCIATES

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

CIVIL/MECH./ELEC./PLUMBING ENGINEERING:

SCHEESER BUCKLEY MAYFIELD, LLC

1540 CORPORATE WOODS PKWY.

UNIONTOWN, OH 44111

P. 330.526.2700

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

LANDSCAPE ARCHITECTURE:

JAMES S. MCKNIGHT

P.O. BOX 14158

CLEVELAND, OH 44114

P. 216.952.2408

HAZARDOUS MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOCIATES, INC.

30628 DETROIT RD., NO. 258

WESTLAKE, OH 44145

P. 216.781.0060

C :\U se rs

\a m ca le es e\

D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ am ca le es e.

rv t

7/

/2

4:

:2

PM

FP-1-3

FIRST FLOOR LEVEL PHASE III FIRE

PROTECTION IMPROVEMENT PLAN

EXPAND PRIMARY CARE FOR

PACT REALIGNMENT

10701 EAST BLVD. CLEVELAND, OHIO

541-376

NICK CARROZZA

8.1.21 CJS JAV

BID ISSUE SUBMISSION

8.1.21

N 1/8" = 1'-0"

FIRST FLOOR LEVEL PHASE III FIRE PROTECTION IMPROVEMENT PLAN

ROOM LEGEND

1A129 PACT Team Hub - North

1A138-11 Space 1A138-22 Space 1A138-49 Space 1A138-53 Space 1A138-3 Space 1A138-5 Space 1A138-6 Space 1A138-7 Space 1A138-8 Space 1A138-9 Space 1A138-10 Space 1A138-12 Space 1A138-13 Space 1A138-14 Space 1A138-15 Space 1A138-16 Space 1A138-17 Space 1A138-18 Space 1A138-19 Space 1A138-20 Space 1A138-21 Space 1A138-23 Space 1A138-24 Space 1A138-25 Space 1A138-26 Space 1A138-27 Space 1A138-28 Space 1A138-29 Space 1A138-30 Space 1A138-31 Space 1A138-32 Space 1A138-33 Space 1A138-34 Space 1A138-35 Space 1A138-36 Space 1A138-37 Space 1A138-38 Space 1A138-39 Space 1A138-40 Space 1A138-41 Space 1A138-42 Space 1A138-43 Space 1A138-44 Space 1A138-45 Space 1A138-46 Space 1A138-47 Space 1A138-48 Space 1A138-50 Space 1A138-51 Space 1A138-52 Space 1A100A-4 Corridor-4 1A100D-3 Corridor-3 1A100F-4 Corridor-4 1A100G-4 Corridor-4 1A100H-3 Corridor-3 1A100I-3 Corridor-3 1A104-4 Lobby-4 1A105-4 Waiting Room-4 1A105-4 Waiting-4 1A108-4 Toilet-4 1A110-3 GS6/GS9 Office-3 1A111-3 SMA Conference Room-3

1A111A-3 SMA Storage Room-3 1A112-3 Exam/Treatment Room-3 1A113-4 Electrical-4 1A114-4 Telecomm-4 1A115-4 Exam/Treatment Room-4 1A116-4 Exam/Treatment Room-4 1A117-4 Exam/Treatment Room-4 1A117-5 Exam/Treatment Room-5 1A118-4 Exam/Treatment Room-4 1A118-5 Exam/Treatment Room-5 1A119-3 PACT Team Hub - West-3 1A119-4 Exam/Treatment Room-4 1A120-2 Exam/Treatment Room-2 1A121-2 Exam/Treatment Room-2

1A121A-2 Meds. Alcove-2 1A122-4 Exam/Treatment Room-4 1A122-5 Exam/Treatment Room-5 1A123-4 Exam/Treatment Room-4 1A124-4 Exam/Treatment Room-4 1A125-4 Exam/Treatment Room-4 1A126-3 Exam/Treatment Room-3

1A126A-2 Locker Area-2 1A127-4 Exam/Treatment Room-4 1A127-5 Exam/Treatment Room-5 1A128-3 Exam/Treatment Room-3 1A129-2 PACT Team Hub - North-2 1A129-3 Exam/Treatment Room-3 1A130-4 Exam/Treatment Room-4

1A130A-3 Exam/Treatment Room-3 1A131-4 Exam/Treatment Room-4 1A131-5 Exam/Treatment Room-5 1A133-6 Exam/Treatment Room-6 1A134-6 Exam/Treatment Room-6 1A135-4 Exam/Treatment Room-4 1A136-4 Exam/Treatment Room-4 1A137-4 Exam/Treatment Room-4

1A137C-3 Check-Out-3 1A137D-2 Check-Out-2 1A138-2 Mas. Reception 1-2 1A138-4 Exam/Treatment Room-4 1A139-3 Mas Reception 2-3 1A139-4 Exam/Treatment Room-4 1A140-4 PACT Team Hub - South-4 1A141-4 Nurse Managers Office-4 1A142-4 Director's Office-4 1A143-4 Precepting Room-4

1A143A-4 Elec. Closet-4 1A144-4 Staff Toilet-4 1A145-4 Exam/Treatment Room-4 1A146-4 Exam/Treatment Room-4 1A147-3 Exam/Treatment Room-3 1A148-4 Exam/Treatment Room-4 1A149-4 Exam/Treatment Room-4 1A150-4 Exam/Treatment Room-4 1A151-4 Exam/Treatment Room-4 1A152-3 Storage-3 1A153-3 Soiled Holding-3

1A153A-3 Consult.-3 1A153B-3 Consult.-3 1A154-3 Mens-3 1A155-4 RR Alcove-4 1A156-3 Womens-3 1A157-3 Clean Utility-3

1A157A-3 Staff Toilet-3 1A161-4 Exam/Treatment Room-4 1A162-4 Exam/Treatment Room-4 1A163-4 Exam/Treatment Room-4 1A164-3 Mental Health Consult./Diabetes Education-3 1A165-3 Mental Health Consult.-3 1A166-3 Mental Health Consult.-3 1A167-3 Mental Health Consult.-3 1A169-3 On-Call Room-3 1A170-3 Program Support Ass't-3 1A171-4 Nurse Manager-4 1A213-4 Restroom Alcove-4 1A214-4 Womens-4 1A216-4 Vending-4 1A217-4 Elevator Lobby-4

1AC220-4 Waiting Room-4 1AC221-4 Reception-4 1AC222-4 Toilet-4 1AC223-4 Radiology 1-4 1AC288-4 Fast Track Exam 2-4

1AC289B-4 Staff Lounge-4 1AC290-4 Fast Track Exam 3-4

1S1-4 Stair 1-4 1S3-4 Stair 3-4 1S5-4 Stair 5-4

1S5A-4 Stair 5 Vest.-4

Revisions: Date:

DD SUBMISSION 5.3.19

65% CD's SUBMISSION 6.14.19 90% CD's SUBMISSION 8.9.19

C

FEC

FEC

FEC

R

EF

FE

C

49 50 50.3 51 52 53

J

K

K4

L

M

M.8

N

N.1

N.2

N.3

O

P

575654.554.153A 54

1A104-5

1S1-5

1A113-5

1A114-5 1A115-5 1A116-5 1A117-6 1A118-6

1A128A

1A119-5

1A128-4

1A115-6

1A100D-4

1A112-4

1A108-5

1A111A-4

1A111-4

1A138-3 1A110-4

1A139-4

1A137C-4 1A118-7

1A117-7

1A116-6

1A124-5

1A123-5

1A122-6

1A119-4

1A120-3 1A121-3

1A121A-3

1A127-6

1A129-3

1A130A-4

1A130-5

1A131 1A132-4 1A132-5

1A134-7

1S5-51S5A-5

1A100H-4

1A135-5 1A136-5 1A137-5

1A138-5 1A139-5

1A140-5

1A147-4

1A148-5

1A153-4

1A146-5

1A100I-4

1A145-5

1A144-5

1A143-5 1A142-5

1A141-5

1A217-5

1A155-5

1A154-4

1A105-5

1A158-2 1A151-5 1A150-5 1A149-5

1A163-51A162-51A161-51A160-2

1A159-2

1A168-21A156-4

1A169

1A171-5 1A170-4

1A167-4 1A166-4 1A165-4

1A164-4 1A157-4

1A152-4

1S3-51A100F-5 1A100G-5

1A216-5

1A213-5

1A214-5

1AC290-5

1AC288-5

1AC289B-5

1AC220-5

1AC221-5

1AC222-5 1AC223-5

CODED NOTES

1. REWORK EXISTING SPRINKLER SYSTEM TO ACCOMMODATE RENOVATED ARCHITECTURAL

LAYOUT PER NFPA 13. ADD/RELOCATE HEADS AS REQUIRED. SPRINKLE USING LIGHT HAZARD

CLASSIFICATIONS; UNLESS NOTED OTHERWISE.

2. SPRINKLE USING ORDINARY HAZARD CLASSIFICATIONS.

PLAN NOTES

A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE

DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.

B. SEE SHEET FP-001 FOR FIRE PROTECTION SYMBOL LEGEND, FIRE PROTECTION GENERAL

NOTES, AND FIRE PROTECTION DETAILS.

C. AREAS WITH NO CEILINGS SUCH THAT THE AUTOMATIC SPRINKLER PIPING IS EXPOSED, THE

AUTOMATIC SPRINKLER PIPING SHALL BE INSTALLED TO FOLLOW ALONG THE STRUCTURE.

REFER TO ARCHITECTURAL PLANS.

D. OFFSET PIPING AROUND STRUCTURAL MEMBERS, LIGHTING, DUCTWORK, AND PLUMBING

PIPING AS REQUIRED TO MAINTAIN FINAL ROOM DIMENSIONS. COORDINATE EXACT PIPE ROUTING

WITH ALL TRADES.

E. SPRINKLER HEAD TYPES AT DESIGNATED AREAS: THE INSTALLATION OF SPRINKLER HEADS IN 2'X2' ACOUSTICAL TILE CEILINGS ARE TO BE CENTERED AND EITHER CENTERED AT HALFWAY OR QUARTER POINTS IN 2'X4' TILES. IN GYPSUM AND EXPOSED CEILING, INSTALL SPRINKLER HEADS

SYMMETRICALLY IN A STRAIGHT LINE. MAINTAIN A SYMMETRICAL PATTERN FOR ALL CEILING

TYPES FOR AN AESTHETICALLY PLEASING EFFECT. COORDINATE WITH ARCHITECTURAL

REFLECTED CEILING PLAN.

FINISHED CEILINGS (SUSPENDED LAY-IN AND GYPSUM): SPRINKLERS ARE TO BE CONCEALED

TYPE WITH WHITE COVERS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN.

EXPOSED CEILINGS: SPRINKLERS ARE TO BE UPRIGHT TYPE. PROVIDE SPRINKLER HEAD GUARDS

IN ALL AREAS SUBJECTED TO DAMAGE SUCH AS MECHANICAL ROOMS, ELECTRICAL ROOMS,

GYMNASIUM, AND STORAGE ROOMS. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING

PLAN.

F. THE FIRE PROTECTION CONTRACTOR SHALL REMOVE OIL AND PREPARE AUTOMATIC

SPRINKLER PIPING AND DRAINS IN EXPOSED AREAS FOR PAINTING. THE FIRE PROTECTION

CONTRACTOR SHALL THEN PLACE PLASTIC BAGS OVER SPRINKLER HEADS. THE GENERAL

CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING THE AUTOMATIC SPRINKLER PIPING,

DRAINS, AND THEN REMOVE PLASTIC BAGS FROM SPRINKLER HEADS. COORDINATE PIPE

PREPARATION AND PAINTING REQUIREMENTS WITH ARCHITECT.

G. THE FIRE PROTECTION SYSTEM FOR THIS PROJECT SHALL BE DESIGNED BY THE INSTALLING

CONTRACTOR. THE INTENT OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS IS TO

PROVIDE BASIC INFORMATION ON MATERIALS AS WELL AS TO SHOW LOCATIONS OF VALVES,

PIPING MAINS, AND RISERS THAT HAVE ALREADY BEEN DIAGRAMMATICALLY COORDINATED INTO

THE BUILDING DESIGN. IT IS UNDERSTOOD THAT THE FIRE PROTECTION SYSTEM MUST BE

DESIGNED PRIOR TO INSTALLATION TO ASSURE THAT THE REQUIRED WATER FLOW RATES ARE

ACHIEVED AT ALL OF THE SPRINKLER HEADS.

H. IN THE CASE OF THIS PROJECT, DUE TO VERY LIMITED SPACE FOR MECHANICAL AND

ELECTRICAL SYSTEMS, IT WILL BE NECESSARY FOR THE FIRE PROTECTION SYSTEM DESIGNER

TO OBTAIN AND SHOW ON THE FIRE PROTECTION INSTALLATION DRAWINGS THE LOCATIONS OF

MAJOR DUCTWORK, PIPING AND ELECTRICAL MAINS, AND TO SHOW HOW THE FIRE PROTECTION

PIPING IS COORDINATED WITH THESE SYSTEMS. IT SHALL BE UNDERSTOOD THAT THE FIRE

PROTECTION DESIGNER SHALL MAKE REVISIONS TO THE INSTALLATION DRAWINGS AS

NECESSARY, BOTH DURING THE SHOP DRAWING REVIEW PROCESS AND DURING THE

INSTALLATION, AS REQUIRED TO INSTALL THE FIRE PROTECTION PIPING SYSTEMS INTO THE

SPACE AVAILABLE. THE AVAILABLE SPACE CAN BE DETERMINED BY REFERENCING THE

ARCHITECTURAL, STRUCTURAL, HVAC, PLUMBING, AND ELECTRICAL DRAWINGS. TO MAKE SURE

THAT THERE IS NO CONFUSION ON THIS ISSUE, ON THIS…