S02 - Attachment 5 - Butler EHRM IU - Drawing - Telecom 2 of 2 R 1.pdf
PDF 11 MB Posted
- Attached to
- EHRM | Butler VA HCS 529-22-700 | Construct Infrastructure Upgrades Federal contract opportunity
- Solicitation number
- 36C77625R0057
About this file
These are telecommunications detail drawings for the EHRM Infrastructure Upgrades project at the Butler VA Healthcare Center. The drawings include multiple technical specifications for telecommunications infrastructure across various buildings, with detailed plans for:
- Typical telecommunications room (TR) installations, including room locations, sizes, and configurations across Buildings 02, 04, 06, 07, 20, 21, 30, 46, 47, and 48. Each building's plans show proposed TR locations, noting specific requirements such as minimum 100 square foot area and 10'x10' footprint recommendations. The drawings include detailed network cabling strategies, fiber optic backbone pathways, server cabinet layouts, and horizontal distribution areas with A-side and B-side redundancy planning. Additional technical details cover security door card reader installations, authentication systems, and fire alarm riser diagrams with device mounting specifications.
View the file
Other files for this federal contract opportunity
Show all 42
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CEILING STRUCTURE
THREADED ROD, DIAMETER
DEPENDENT ON J-HOOK SIZE
J-HOOK WITH COLORED ID, SIZE PER
CABLE CAPACITY, EATON B SERIES
COLORED J HOOK OR EQUIVALENT
CABLING PER PLAN
VELCRO CABLE TIE
J-HOOK COLORED ID, ID
COLOR SHALL MATCH VA
CABLING STANDARDS
18" MINIMUM
ACCESSIBLE CEILING
VARIES
DETAIL NOTES:
SPACE J-HOOKS MAXIMUM 4'
APART FROM ONE ANOTHER
FASTENER TO SUSPEND ROD
WIRING TABLE
PIGTAIL-
WIRE COLOR
TERM STRIP -
CONNECTION
CIRCUIT
FUNCTION
YELLOW
ORANGE
BLACK
RED
DRAIN
BROWN
BLUE
GRAY
PINK
GREEN
WHITE
VIOLET
TAN
RED/GREEN
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P2-1
P2-2
P2-3
P2-4
P2-5
P2-6
P2-7
NO CONNECT
NO CONNECT
RTN
+VDC
NO CONNECT
NO CONNECT
NO CONNECT
RS485 / TXA
RS485 / TXB
NO CONNECT
NO CONNECT
NO CONNECT
RS485 / RXB
RS485 / RXA
PIV ENABLED TWO-FACTOR AUTHENTICATION KEY PAD
AND CONTACTLESS AUTHENTICATION, HID pivCLASS
#RK40 OR EQUIVALENT
BEEP
GRN
RTN
+VDC
SHLD
RED
HOLD
GP101
GP102
OC/TMPR
DATA1
DATA0
GP103
GP104
FIBER PATHWAY CHANNEL AND COVERS (PANDUIT FR4X4/FRHC4/FRSHC4 OR EQUIVALENT):
4X4" CHANNEL COVER
SOLID COVER
SPLIT HINGED COVER
FIBER PATHWAY MOUNTING BRACKET (PANDUIT FR6TRBE/FR6TBN OR EQUIVALENT):
BRACKET TO MOUNT TO EXISTING THREADED ROD OR
BRACKET TO MOUNT TO NEW THREADED ROD
JUNCTION BOX, 8" x 8" x 4"
MINIMUM
TO SECURE LOCAL
ACCESS CONTROL
PANEL, 1-1/2" CONDUIT
3/4" CONDUIT
ELECTRIC STRIKE / MORTISE LOCK
PER SYSTEM REQUIREMENTS,
PROVIDE BACKBOX AS REQUIRED
BY MANUFACTURER
DUAL AUTHENTICATION CARD
READER AND KEYPAD, 42" AFF,
HID pivCLASS #RK40 OR
EQUIVALENT, PROVIDE
BACKBOX AS REQUIRED BY
MANUFACTURER
SUSPENDED CEILING
FLOOR
SIREN WIRING, 3/4" CONDUIT
REQUEST-TO-EXIT
WIRING, 3/4" CONDUIT
DOOR POSITION
SWITCH AND MAGNET
REQUEST-TO-EXIT
PIR MOTION SENSOR
REQUEST-TO-EXIT,
PUSH BUTTON
SIREN
DETAILS NOTES:
1. DETAIL IS SHOWN FOR GENERAL
DIAGRAMMATICAL PURPOSES. PROVIDE
ALL REQUIRED EQUIPMENT AND
HARDWARE FOR ALL DOOR TYPES
(SINGLE DOOR, DOUBLE DOOR, ETC.) AS
REQUIRED.
2. CONTRACTOR TO FURNISH AND INSTALL
ALL SECURITY AND PACS HARDWARE AS
REQUIRED PER PHYSICAL SECURITY AND
RESILIENCY DESIGN MANUAL AND
ASSOCIATED APPENDICES. COORDINATE
WITH ARCHITECT AND DOOR
MANUFACTURER TO PROVIDE A
COMPLETE AND FULLY FUNCTIONAL
ELECTRIFIED AND SECURED DOOR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
TN503
TELECOMMUNICATIONS DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES (FOR THIS SHEET ONLY)
KEY NOTES (FOR THIS SHEET ONLY)
- NTS
1 TYPICAL J-HOOK INSTALLATION DETAIL
- NTS
3 TYPICAL CONTACTLESS AUTHENTICATION AND PINPAD DEVICE DETAIL
DUAL AUTHENTICATION CARD READER AND KEYPAD MUST BE CAPABLE
OF INTERFACING WITH EXISTING VA ACCESS CONTROL SYSTEM.
- NTS
4 TYPICAL DATA CENTER FIBER PATHWAY DETAIL
- NTS
2 SECURITY DOOR CARD READER INSTALLATION DETAIL
Revisions: Date:
D = 43.3"
VERTICAL EXHAUST DUCT.
COORDINATE WITH
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
SERVER CABINET
H
.6
W = 23.60"
1st LEVEL BACKBONE
24 DUPLEX LC (FOUR 12-STRAND
MPO CABLES) TO MDA B SIDE
24 DUPLEX LC (FOUR 12-STRAND
MPO CABLES) TO MDA A SIDE
48 CAT 6A TO SAME SIDE MDA
HORIZONTAL FIBER
DISTRIBUTION FROM THE ED IN
EACH CABINET IN THE ROW
HORIZONTAL UTP DISTRIBUTION
FROM THE ED IN EACH CABINET
IN THE ROW
HORIZONTAL DISTRIBUTION
28 RU FOR LAN ELEMENTS
AND LEAF OR ACCESS LAYER
SWITCHES
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
RESERVED FOR
A-SIDE (OR "B" SIDE)
DISTRIBUTION
TO TR's
RESERVED FOR
CORE,
SECURITY AND
WAN ELEMENTS
"A" SIDE
(OR "B" SIDE)
FO BACKBONE
RESERVED FOR
SPINE,
AGGREGATION
AND OOB
SWITCHES AND
LAN ELEMENTS
"A" SIDE (OR "B" SIDE)
UTP BACKBONE PATCH PANELS
FOR 10 GbE
1 2 3 4 5 6 7 8 9 10 11 12
31 32 33 34 35 36
22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
13 14 15 16 17 18 19 20 21
25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 4725 26 27 28 29 30 31 32 33 34 35 36 48
13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 4725 26 27 28 29 30 31 32 33 34 35 36 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 4725 26 27 28 29 30 31 32 33 34 35 36 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 4725 26 27 28 29 30 31 32 33 34 35 36 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 4725 26 27 28 29 30 31 32 33 34 35 36 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 4725 26 27 28 29 30 31 32 33 34 35 36 48
SERVER RACK, TYP. CONDUIT FOR FIBER
AND CATEGORY CABLE A/B
DIVERSE PATHWAY TO
TELECOMMUNICATION
ROOMS
LADDER RACK
TELECOMMUNICATIONS
GROUND BUSBAR
TERMINATED TO CLOSEST
ELECTRICAL SERVICE PANEL
4"X4" MINIMUM
FIBER OPTIC
BACKBONE TRAY
GROUND BAR AT THE TOP,
BACKSIDE OF RACK 6
TN501
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:0 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
TN504
TELECOMMUNICATIONS DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- 3/64" = 1'-0"
1 TYPICAL DATA CENTER SERVER CABINET WITH VERTICAL EXHAUST DUCT (VED) DETAIL
- 3/64" = 1'-0"
2 TYPICAL END OF ROW HORIZONTAL DISRIBUTION AREA (A & B SIDES)
- NTS
3 DATA CENTER MAIN DISTRIBUTION AREA (A & B SIDES)
- NTS
4 TYPICAL ENTRANCE ROOM ELEVATION
GENERAL NOTES
1. THIS SHEET SHALL BE PRINTED IN COLOR TO
PROVIDE ALL NECESSARY INFORMATION.
120VAC
EMERGENCY POWER
L
N
G INTEGRAL BATTERIES
NAC CIRCUIT
ELECTRICAL
RM 110
MECHANICAL
RM 109
ENTRANCE
ROOM #2
RM 108
DATA
CENTER
RM 114
DATA
CENTER
RM 114
GENERATOR
ROOM
RM 116
ENTRANCE
ROOM #1
RM 105
FUTURE
RM 106
UNPACKING/
PACKING
RM 112
STORAGE
RM 107
DATA
COMMUNICATION
TO MAIN FACP
LOCATED IN BUILDING 48
INPUT LOOP
FSFSFSFS
DATA CENTER
DATA CENTER
UNPACKING/
PACKING
CORRIDOR
CORRIDOR
CORRIDOR
FIRE ALARM
CONTROL PANEL
FIBER-OPTIC CABLING
MECH
GENERATOR
ENCLOSURE
DATA CENTER
DATA CENTER
DATA CENTER
DATA CENTER
HD
FIRE RISER
FIRE RISER
FIRE RISER
COMM CABLE CLEAN AGENT
SYSTEM PANEL
EOL
OUTPUTS
COORDINATE WITH DATA CENTER HVAC SHUTDOWN
SWITCH WIRING DIAGRAM ON SHEET 'EP503', DETAIL '4'.
HD
ELECTRICAL
ROOM
5-FT.MIN,
6-FT MAX
FIRE
FIRE
FIRE
90-INCH MIN
Heat Detector Ceiling mounted
6-INCH MIN
SECURITY
HORN/SIREN
Smoke Detector Ceiling mounted
1'-6"
3'-6"
WIRELESS ACCESS POINT
CEILING MOUNTED
8'-0"
CARD READER FA PULL
STATION
WAO
FIRE ALARM
ANNUNCIATOR
FIRE ALARM
CONTROL PANEL
(4) MPO-12 TO MPO-12 OM4 TRUNK CABLES [(8) MPO-12/DUPLEX LC CASSETTES] - A-SIDE
(4) MPO-12 TO MPO-12 OM4 TRUNK CABLES [(8) MPO-12/DUPLEX LC CASSETTES] - B-SIDE
48 CAT 6A - A-SIDE
48 CAT 6A - B-SIDE
(2) MPO-12 TO MPO-12 OM4 TRUNK CABLES [(4) MPO-12/DUPLEX LC CASSETTES]/24 CAT 6A-A-SIDE
(2) MPO-12 TO MPO-12 OM4 TRUNK CABLES [(4) MPO-12/DUPLEX LC CASSETTES]/24 CAT 6A-B-SIDE
B-SIDEB-SIDEB-SIDEA-SIDEA-SIDEA-SIDE
A-SIDE B-SIDE
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
FIBER OPTIC
PATCH PANEL
RESERVED FOR
A-SIDE
DISTRIBUTION TO
TR's
RESERVED FOR
CORE, SECURITY
AND WAN
ELEMENTS
RESERVED FOR
SPINE,
AGGREGATION
AND OOB
SWITCHES AND
LAN ELEMENTS
RESERVED FOR
SPINE,
AGGREGATION
AND OOB
SWITCHES AND
LAN ELEMENTS
RESERVED FOR
CORE, SECURITY
AND WAN
ELEMENTS
RESERVED FOR
B-SIDE
DISTRIBUTION TO
TR's
"B"- SIDE FO
BACKBONE
"A"- SIDE FO
BACKBONE
MDA-A MDA-B
HDA-A SERVER CABINETS HDA-B
SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL
REQUIRED INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:3
:1 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
TN505
TELECOMMUNICATIONS DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
1 DATA CENTER FIRE ALARM RISER DIAGRAM AND I/O MATRIX
DETAIL NOTES(S):
1. REFERENCE SHEET 137TN101 FOR EXACT DEVICE QUANTITIES AND LOCATIONS.
2. FIRE ALARM RISER DIAGRAM SHOWN FOR INFORMATIONAL PURPOSES ONLY. COORDINATE WITH EXISTING FACILITY
INFRASTRUCTURE, EQUIPMENT, NATIONAL/LOCAL CODES AND MANUFACTURE TO PROVIDE A COMPLETE AND FULLY
FUNCTIONAL SYSTEM AS REQUIRED.
3. PROVIDE FIRE ALARM DEVICES IN FIELD AS REQUIRED. COORDINATE FIELD CONNECTIONS WITH ALL EQUIPMENT;
PROVIDE CONNECTIONS, CABLING AND TERMINATIONS AS REQUIRED.
4. PROVIDE 3/4" CONDUIT FOR ALL NEW CABLE AS REQUIRED. ALL FIRE ALARM CONDUIT SHALL BE PAINTED RED.
5. COORDINATE WITH CIVIL AND COMMUNICATIONS DRAWINGS FOR FIBER-OPTIC CABLING.
6. COORDINATE WITH MECHANICAL DRAWINGS FOR CLEAN AGENT SYSTEM PANEL CONNECTIONS AND REQUIREMENTS.
7. DATA CENTER FIRE PROTECTION SHALL ADHERE TO NFPA 75. AUTOMATIC DETECTION SHALL BE PROVIDED BY SMOKE DETECTORS (LOCATE AND PROVIDE QUANTITY AS REQUIRED); AUTOMATIC ACTUATION AND NOTIFICATION SHALL BE
PROVIDED BY FIRE ALARM CONTROL PANEL.
- NTS
2 TYPICAL DEVICE MOUNTING HEIGHT DETAIL
DETAIL NOTES(S):
1. THESE TYPICAL MOUNTING HEIGHTS
SHALL BE USED UNLESS OTHERWISE
NOTED.
Revisions: Date:
- NTS
3 DIVERSE ROUTING HORIZONTAL DISTRIBUTION AREA TO MAIN DISTRIBUTION AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:2 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
TN701
TELECOMMUNICATIONS
SCHEDULES -
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
D U
M P
S T
E R
C A
R D
B O
A R
D C
R U
S H
E R
DOCK
LEVELER
DOCK
LEVELER
1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 20
A
B
D
E
F
G
H
I
J
C
EXIST. MECH.
B005
EXIST. MECHANICAL
B006
ELEC.
B004
EXIST. ELEVATOR
EXIST. CUST./RISER
B012
EXIST. MECHANICAL
B010
EXIST. MECHANICAL
2-819
EXIST. TOILET
B011
STAIR B
COOK'S OFFICE
B023
SUBSISTENCE STORAGE
B024
SUPPLY STORAGE
B001
DIETARY OFFICE
B003
ELEC.
B002A
TRAY ASSEMBLY
CART COOLER
B022
COOLER
B021
FREEZER
B020
KITCHEN PREP.
B019
CLO
B014A
DOCK STAGING
B018
CONTAMINATED WASTE
B015
TRASH COLLECTION
B016
CAN WASH
B017
EXIST. SERVICE TUNNEL
B014
NEW SERVICE TOWER
CART STAGING
B007
EXIST CORRIDOR
B013 DISH WASH
B008
TE
B08
1. VA APRROVE TE B008 (24 SQFT).
2. TE IS SHARING SPACE WITH A ROOM WIH ANOTHER PURPOSE, AS
PER DESIGN ALERT 9 IS NOT ALLOWED.
3. HEFP DOES NOT CONSIDER THIS ROOM TO FALL INTO A
CATEGORY OF AN AREA READILY TO GENERAL FOOT TRAFFIC.
TE B001A NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:1
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
02TN800
BLDG 02 - LEVEL 00 - DIAMOND
STUDY PLAN 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1" = 10'-0"
1 BLDG 02 - LEVEL 00 - DIAMOND STUDY PLAN 0 10' 20'
PROJECT
NORTH
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 20
A
B
D
E
F
G
H
I
J
C
WOMEN'S RESTROOM
EXIST. TOILET
EXIST. ADHC OFFICE
EXIST. STAIRS A
EXIST. ADHC/OFFICE
EXIST. CLC NURSING SUPPORT
101 EXIST. OFFICE
102 TR
TC110
ICRA ELEC. CART
104EXIST. VESTIBULE
100C
EXIST MECH. CHASE
122B
JANITOR
EXIST. STORAGE
EXIST. NURSE
EXIST. RESTROOM
EXIST. STAIRS B
119B
POLICE/SECURITY
VENDING AREA
EXIST. ELEVATOR
SEATING AREA
EXIST. VESTIBULE
MEN'S RESTROOM
PSYCHOLOGIST
EXIST. STAIR C
CHAPLAIN OFFICE
EXAM ROOM #2
EXAM ROOM #1
EUCHARISTIC
114A
CLEAN LINEN
SOLID LINEN
MULTI USE
EXIST. LOBBY
100A
CHAPEL
EXIST. CORRIDOR
100B
EXIST. CORRIDOR
CORRIDOR
CHAPLAIN OFFICE
ENCLOSED ELECTRICAL
GENERATOR
OFFICE UNASSIGNED
1. VA APRROVE TR TC110 (110 SQFT).
2. TR MEETS THE MINIMUM 100 SQFT AREA REQUIREMENT FOR TR IN
EXISTING HEALTHCARE BUILDINGS.
3. TR MEETS THE SPACE FORM FACTOR REQUREMENT OF A 10'X10'
FOOTPRINT.
4. TR DOES NOT STACK WITH ABOVE TR.
5. TR IS NEXT TO ICRA ELEC. CART 104 THAT MIGHT CONTAIN
EMF/INTERFERENCE INDUCING EQUIPMENT.
TR TC110 NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:1
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
02TN801
BLDG 02 - LEVEL 01 - DIAMOND
STUDY PLAN 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1" = 10'-0"
1 BLDG 02 - LEVEL 01 - DIAMOND STUDY PLAN 0 10' 20'
PROJECT
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 20
A
B
D
E
F
G
H
I
J
C
NURSE
NURSE
EXIST. TOILET
NURSE
EXIST. STAIR A
TR
STORAGE
RESPIRATORY THERAPY
MULTI PURPOSE
EMS
SPS
PYXIS
NURSE STORAGE
FIRE & ALARM SECURITY
EXIST. STAIR B
EMS/SEWING UNIFORM
EQUIPMENT WASH
KITCHEN SUPERVISOR
210EXIST ELEVATOR
EXIST VESTIBULE
BA-104Y
MECH. EXIST. CHASE
BA-104Z
MIT CART STORAGE
FOOD SERVICE DIRECTOR
SERV. ASSIT.
PORTABLE STOR.
EMS OFFICE
EMS EQUIPMENT
MEN EXIST. R.R.
218 WOMEN EXIST. R.R.
JAN.
WHEELCHAIR REPAIR
EXIST STAIR C
BIOMED
EMS KITCHEN/BREAK
CORRIDOR
1. VA APRROVE TR 204 (176 SQFT).
2. TR MEETS THE MINIMUM 100 SQFT AREA REQUIREMENT FOR TR IN
EXISTING HEALTHCARE BUILDINGS.
3. TR MEETS THE SPACE FORM FACTOR REQUREMENT OF A 10'X10'
FOOTPRINT.
4. TR DOES NOT STACK WITH ABOVE TR.
TR 204 NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:1
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
02TN802
BLDG 02 - LEVEL 02 - DIAMOND
STUDY PLAN 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1" = 10'-0"
1 BLDG 02 - LEVEL 02 - DIAMOND STUDY PLAN 0 10' 20'
PROJECT
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
SUMMARY:
A. VA DIRECTION TO FEED THIS FLOOR TO A TR 204 THAT WILL BE
LOCATED ON LEVEL 02.
1. THERE SHALL BE A MINIMUM OF ONE STANDARDIZED TR PER
FLOOR AS PER TELECOMMUNICATIONS SPACES: 4.1.3
TELECOMMUNICATIONS ROOM.
2. TR MINIMUM AREA REQUIREMENT FOR HEALTHCARE BUILDING IS
100 SQF.
1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 20
A
B
D
E
F
G
H
C
IT ROOM
143 SF
EXIST. ATTIC
5859 SF
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:1
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
02TN803
BLDG 02 - LEVEL 03 - DIAMOND
STUDY PLAN 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1/8" = 1'-0"
1 BLDG 02 - LEVEL 03 - DIAMOND STUDY PLAN 0 10' 20'
PROJECT
UP
UP
ACCESS
DOOR
B C D E F G H I J K LA
MECH RM
B02
CORRIDOR
EMERGENCY
LIGHTING RM
B02A
TRANSFORMER
RM
B01
LAUNDRY
B05
TRUNK STORAGE
(TE)
B03
CRAWL SPACE
B04
STORAGE
B03 A
STAIR - S
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
1. VA APPROVED TE B03B (42 SQFT).
2. TE IS SHARING SPACE WITH A ROOM WITH ANOTHER PURPOSE,
AS PER DESIGN ALERT 9 IS NOT ALLOWED.
3. HEFP DOES NOT CONSIDER THIS ROOM TO FALL INTO A
CATEGORY OF AN AREA READILY TO GENERAL FOOT TRAFFIC.
TE B03B NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:3 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
04TN800
BLDG 04 - LEVEL 00 - DIAMOND
STUDY PLAN 04
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1/4" = 1'-0"
1 BLDG 04 - LEVEL 00 - DIAMOND STUDY PLAN 2'0 4' 8'
PROJECT
B C D E F G H I J K LA
PATIENT BED
ROOM
STAIR A
KITCHEN
LOBBY
TRAINING ROOM
STAIR R
HOUSE MGR
BED RM
CLOSET
GROUP ROOM
DINING ROOM
KITCHEN
LAUNDRY
109BATH ROOM
BATH ROOM
112 - A
PATIENT BED
ROOM
JANITOR
111 - B
Room
B03 R
JANITOR
111 - A
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
A. VA DIRECTION TO FEED THIS FLOOR TO A TE B03B THAT WILL BE
LOCATED ON LEVEL 00.
1. THERE SHALL BE A MINIMUM OF ONE STANDARDIZED TR PER
FLOOR AS PER TELECOMMUNICATIONS SPACE: 4.1.3
TELECOMMUNICATIONS ROOM.
2. TR MINIMUM AREA REQUIREMENT FOR HEALTHCARE BUILDING IS
100 SQF.
NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:3 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
04TN801
BLDG 04 - LEVEL 01 - DIAMOND
STUDY PLAN 04
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1/4" = 1'-0"
1 BLDG 04 - LEVEL 01 - DIAMOND STUDY PLAN 2'0 4' 8'
PROJECT
B C D E F G H I J K LA
TV ROOM
238 SF
STAIR S
110 SF PATIENT BED
ROOM
167 SF
PATIENT BED
ROOM
150 SF
PATIENT BED
ROOM
139 SF
STAIR R
111 SF
PATIENT BED
ROOM
162 SF
BATH
32 SF
PATIENT BED
ROOM
165 SF
PATIENT BED
ROOM
162 SF
PATIENT BED
ROOM
142 SF
CLOSET
16 SF
RESTROOM
122 SF
RESTROOM
209 A
126 SF
KITCHEN
95 SF
PATIENT BED
ROOM
158 SF
HSK
16 SF
CORRIDOR
330 SF
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
A. VA DIRECTION TO FEED THIS FLOOR TO A TE B03B THAT WILL BE
LOCATED ON LEVEL 00.
1. THERE SHALL BE A MINIMUM OF ONE STANDARDIZED TR PER
FLOOR AS PER TELECOMMUNICATIONS SPACE: 4.1.3
TELECOMMUNICATIONS ROOM.
2. TR MINIMUM AREA REQUIREMENT FOR HEALTHCARE BUILDING IS
100 SQF.
NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:3 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
04TN802
BLDG 04 - LEVEL 02 - DIAMOND
STUDY PLAN 04
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
2'0 4' 8'
PROJECT
NORTH
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1/4" = 1'-0"
1 BLDG 04 - LEVEL 02 - DIAMOND STUDY PLAN
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
A B C D E F G
ELECTRICAL
CLOSET
B06
B07
STORAGE
B05
STORAGE
B05A
MECHANICAL
ROOM
B04
MECHANICAL
ROOM
B01
TELEPHONE
CLOSET
B03A
STORAGE
B03
TELEPHONE
CLOSET
TC02
11 SF
B100
A. VA DIRECTION TO FEED THIS FLOOR TO TR 102 THAT WILL BE
LOCATED ON LEVEL 01.
1. THERE SHALL BE A MINIMUM OF ONE STANDARDIZED TR PER
FLOOR AS PER TELECOMMUNICATIONS SPACE: 4.1.3
TELECOMMUNICATIONS ROOM.
2. TR MINIMUM AREA REQUIREMENT FOR HEALTHCARE BUILDING IS
100 SQF.
TELEPHONE CLOSET TC02 NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
06TN800
BLDG 06 - LEVEL 00 - DIAMOND
STUDY PLAN 06
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- 1/8" = 1'-0"
1 BLDG 06 - LEVEL 00 - DIAMOND STUDY PLAN 4'0 8' 16'
PROJECT
NORTH
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
A B C D E F G
8.19.1
RESTROOM/SHOWER
108A
LINEN ROOM
LOCKER
ROOM
STORAGE
RESTROOM/SHOWER
ROOM
107A
LOCKER
ROOM
LAUNDRY
OFFICE
105B
CLOSET
105A
MECHANICAL
ROOM
LOUNGE
TR
1. VA APPROVED TR 102 (198 SQFT).
2. TR MEETS THE MINIMUM 100 SQFT AREA REQUIREMENT FOR TR IN
EXISTING HEALTHCARE BUILDINGS.
3. TR MEETS THE SPACE FORM FACTOR REQUIREMENT OF A 10'x'10'
FOOTPRINT.
TR 102 NOTES
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
06TN801
BLDG 06 - LEVEL 01 - DIAMOND
STUDY PLAN 06
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- 1" = 10'-0"
1 BLDG 06 - LEVEL 01 - DIAMOND STUDY PLAN
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
0 10' 20'
PROJECT
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
B C D E F G H
BOILER PLANT
B01
B02
SUMMARY:
A. VA DIRECTION TO FEED THIS FLOOR TO A TE 101A THAT WILL BE
LOCATED ON LEVEL 01.
1. THERE SHALL BE A MINIMUM OF ONE STANDARDERIZED TR PER FLOOR
AS PER TELECOMMUNICATIONS SPACES: 4.1.3 TELECOMMUNICATIONS
ROOM.
2. TR MINIMUM AREA REQUIREMENT FOR ADMIN BUILDING IS 80 SQF.
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B L
D G
.r v t
07TN800
BLDG 07 - LEVEL 00 - DIAMOND
STUDY PLAN 07
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 3/16" = 1'-0"
1 BLDG 07 - LEVEL 00 - DIAMOND STUDY PLAN 4'0 8' 12'
PROJECT
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
B C E F G H
ELECTRICAL
VAULT
EMERGENCY
GENERATOR
TE
101A
BOILER ROOM
OFFICE
102A
SUMMER BOILER
ROOM
103A
STORAGE
LOCKER ROOM
105A
LOCKER ROOM
RESTROOM/SHOWER
ROOM
105AA
DEAERATOR
102B
LOCKSHOP
CORRIDOR
100B
OFFICE
101 58 SF
1. VA APRROVE TE 101A (58 SQFT).
2. TE IS SHARING SPACE WITH A ROOM WITH ANOTHER PURPOSE, AS
PER DESIGN ALERT 9 IS NOT ALLOWED.
3. HEFP DOES NOT CONSIDER THIS ROOM TO FALL INTO A CATEGORY
OF AN AREA READILY TO GENERAL FOOT TRAFFIC.
TE 100CA NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B L
D G
.r v t
07TN801
BLDG 07 - LEVEL 01 - DIAMOND
STUDY PLAN 07
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 3/16" = 1'-0"
1 BLDG 07 - LEVEL 01 - DIAMOND STUDY PLAN 4'0 8' 12'
PROJECT
A B C D
EXISTING SHED
59 SF
COMPRESSOR
111 SF
MAINTENANCE
SHOP
3205 SF
ELECTRICAL
CLOSET
102A
39 SF
FILE STORAGE
101A
101 SF
VALVE ROOM
93 SF
BREAK AREA
344 SF
ENTRY
156 SF
TE
45 SF
LOCKER ROOM
108 SF
MH
65 SF
TOILER ROOM
108A
50 SF
CHANGING AREA
58 SF
PRIVATE OFFICE
102 SF
EXISTING ROOM
EXPANSION
NEW LOCATION
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
LEGENDS
1. VA APRROVE TE 103 (45 SQFT).
2. TE IS SHARING SPACE WITH A ROOM WITH ANOTHER PURPOSE,
AS PER DESIGN ALERT 9 IS NOT ALLOWED.
3. HEFP DOES NOT CONSIDER THIS ROOM TO FALL INTO A
CATEGORY OF AN AREA READILY TO GENERAL FOOT TRAFFIC
TE 103 NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:1 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B L
D G
.r v t
08TN801
BLDG 08 - LEVEL 01 - DIAMOND
STUDY PLAN 08
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 3/16" = 1'-0"
1 BLDG 08 - LEVEL 01 - DIAMOND STUDY PLAN 4'0 8' 12'
PROJECT
A B C D E F G H I J
K
M
N
O
P
STOR.
W129.3
15 SF
SEATING AREA
C-13.1
673 SF
CORR.
C-13
184 SF
SEATING AREA
C-12.1
279 SF
THERAPY
W130
488 SF
VISITOR BEDROOM
W132
257 SF
PRIVATE
TOILET
W132.1
67 SF
DATA
W131
52 SF
FAMILY
LAUNDRY
W132.2
63 SF
PAT. ROOM
W101
217 SFTOILET
W101.1
65 SF
TOILET
W128.1
65 SF
PAT. ROOM
W128
217 SF
SPD
W135
93 SF
EQUIPMENT
STORAGE
W134
93 SF
SPA
W133
339 SF
TOILET
W133.1
52 SF
TOILET
W137
45 SF
CONFERENCE
W138
225 SF
OFFICE
W139
121 SF
CONSULT
W140
123 SF
CLERICAL
W136
240 SF
SUN ROOM
W116
543 SF
ATTIC ACCESS
W112
37 SF
FAMILY DINING
W123
181 SF
WARMING
KITCHEN
W124
125 SF
ELEC.
W125
10 SF
STAFF TLT.
W108
44 SF
STORAGE
W105
17 SF
JAN. CL.
W104
27 SF
SOILED RM.
W103
86 SF
MED./TREAT.
W107
74 SF
CORR
2119 SF
ATRIUM
1512 SF
ELEC.
E114
10 SF
FAMILY DINING
E116
181 SF WARMING
KITCHEN
E115
125 SF
MED./TREAT.
E104
74 SF
SOILED
E108
86 SF
STAFF
TLT.
E105
44 SF
JAN. CL.
E107
27 SF
STORAGE
E106
17 SF
WASHINGTON
COURTYARD
2554 SF
CLEAN
SUPPLY
W142
84 SF
SUN ROOM
E123
544 SF
ATTIC ACCESS
E127
37 SF BARIATRIC
TOILET
E128.1
86 SF
BARIATRIC PAT. ROOM
E128
335 SF
PAT. ROOM
E126
219 SF
TOILET
E126.1
67 SF
TOILET
E125.1
66 SF
PAT. ROOM
E125
219 SF
PAT. ROOM
E113
220 SF
TOILET
E113.1
68 SF
PAT. ROOM
E117
224 SF
TOILET
E117.1
70 SF
PAT. ROOM
E118
221 SF
TOILET
E118.1
68 SF
PAT. ROOM
E119
220 SF
TOILET
E119.1
68 SF
TOILET
E121.1
68 SF
PAT. ROOM
E121
231 SF
PAT. ROOM
E120
233 SF
TOILET
E120.1
68 SF
PAT. ROOM
E102
264 SF
TOILET
E102.1
68 SF
TOILET
E109.1
68 SF
PAT. ROOM
E109
220 SF
TOILET
E111.1
68 SFPAT. ROOM
E111
222 SF
PAT. ROOM
E110
221 SF
TOILET
E110.1
68 SF
TOILET
E112.1
68 SFPAT. ROOM
E112
222 SF
BARIATRIC PAT. ROOM
E101
309 SF
BARIATRIC
TOILET
E101.1
87 SF
STAFF BREAK
W141
214 SF
PAT. ROOM
W127
222 SF TOILET
W127.1
68 SF
PAT. ROOM
W126
221 SF
TOILET
W126.1
68 SF
PAT. ROOM
W114
219 SF
TOILET
W114.1
67 SF
PAT. ROOM
W113
219 SF
TOILET
W113.1
66 SF
TOILET
W122.1
70 SF
PAT. ROOM
W122
224 SF
TOILET
W121.1
67 SF
PAT. ROOM
W121
220 SF
TOILET
W120.1
68 SF
ATTIC
ACCESS
W129.1
47 SF
PAT. ROOM
W120
218 SF
TOILET
W118.1
67 SF PAT. ROOM
W118
231 SF
PAT. ROOM
W119
233 SF
TOILET
W119.1
67 SF
PAT. ROOM
W109
264 SF
TOILET
W109.1
68 SF
PAT. ROOM
W102
221 SF
TOILET
W102.1
68 SF
CORR.
C-15
2116 SF
BARIATRIC PAT. ROOM
W111
341 SF
BARIATRIC
TOILET
W111.1
89 SF
BARIATRIC PAT. ROOM
W110
309 SF
BARIATRIC
TOILET
W110.1
89 SF
NURSE
E103
136 SF
DINING
E122
299 SF
LIVING
E124
248 SF
NURSE
W106
136 SF
DINING
W117
299 SF
LIVING
W115
248 SF
CORR.
C-12
318 SF
PAT. RM.
N123
233 SF
PAT. RM.
N124
221 SF
TLT.
N124.1
66 SF
TLT
N125.1
66 SF
PAT. RM.
N125
220 SF
PAT. RM.
N126
224 SF
TLT.
N126.1
68 SF
TLT.
N123.1
66 SF
TLT.
N122.1
66 SF
PAT. RM.
N122
231 SF
FAMILY DINING
N119
182 SF
WARMING
KITCHEN
N118
127 SF
PAT. RM.
N116
218 SF
TLT.
N116.1
66 SF
ELEC.
N117
10 SF
PAT. RM.
N115
219 SF
TLT.
N115.1
66 SF
PAT. RM.
N114
219 SF
TLT.
N114.1
65 SF
TLT.
N113.1
65 SF
PAT. RM.
N113
218 SF
PAT. RM.
N112
218 SFTLT.
N112.1
66 SF
SOILED
N111
68 SF
ATTIC
ACCESS
N110.1
15 SF
MED./ TREAT
N107
74 SF
STAFF RM.
N109
45 SF
JAN. CL.
N110
26 SF
STORAGE
N108
17 SF
PAT. RM.
N104
220 SF
TLT.
N104.1
67 SF
PAT. RM.
N102
234 SF
TLT.
N102.1
76 SF
PUBLIC TLT.
W176
65 SF
PUBLIC TLT.
W177
64 SF
VEST.
W100
110 SF
CONFERENCE
W178
212 SFPAT. RM.
N105
221 SF
TLT.
N105.1
66 SF
PAT. RM.
N103
222 SF
TLT.
N103.1
66 SF
PAT. RM.
N101
237 SF
TLT.
N101.1
75 SF
SPA
W179
324 SF
STAFF TLT.
W180
60 SF
NURSE MGR.
W181
120 SF
CONSULT/FILES
W182
114 SF
STOR
10 SF
STAFF
W183
189 SFSPA TLT.
W112.1
56 SF
BLDG. STOR
W184
126 SF
ELEC.
W185
54 SF
EQUIP. STOR.
W186
70 SF
DATA
W187
56 SF
SPD STOR.
W188
89 SF
CLEAN
W189
117 SF
MECH/ELEC
W190
490 SF
JAN. CL.
W191
42 SF
MULTI-PURPOSE
W192
361 SF
STORAGE
W193
39 SF
ELEC.
W194
27 SF
STORAGE
W195
40 SF
ATTIC
ACCESS
W129.2
21 SF
TLT.
W196
58 SF
STORAGE
W197
51 SF
STOR
W198
66 SF
CORR.
C-3
261 SF
CLERICAL
W199
287 SF
RECEPTION
W200
103 SF
WAIT
W201
187 SF
CORR.
C-1
549 SF
ATRIUM COURTYARD
ATRIUM
1469 SF
ATRIUM ENCLOSED
AREA
1443 SF
CORR.
C-10
548 SF
NURSE
N106
141 SF
SEATING AREA
C-5.1
745 SF
CORR.
C-5
222 SF
CORR.
W202
333 SF
DINING
N121
270 SF
LIVING
N120
292 SF
CORR.
C-9
802 SF
CORR.
C-2
400 SF
GAME ROOM
W126
466 SF
ELEC.
S117
10 SF
WARMING
KITCHEN
S118
127 SF
FAMILY DINING
S119
182 SF
MED./TREAT
S107
74 SF
STORAGE
W129.4
13 SF
PAT. RM.
S102
229 SF
TLT.
S102.1
72 SF
PAT. RM.
S104
220 SF
TLT.
S104.1
67 SF
TLT.
S101.1
75 SF
PAT. RM.
S101
237 SF
PAT. RM.
S103
222 SF
TLT.
S103.1
66 SF
PAT. RM.
S112
218 SF
TLT.
S112.1
66 SF
ATTIC
ACCESS
S110.1
15 SF
SOILED
S111
68 SF
STAFF TLT.
321A
45 SF
STORAGE
17 SF
TLT.
S115.1
66 SF
PAT. RM.
S115
219 SF
PAT. RM.
S114
221 SF
TLT.
S114.1
66 SF
TLT.
S113.1
66 SF
PAT. RM.
S113
220 SF
PAT. RM.
S116
218 SF
TLT.
S116.1
66 SF
PAT. RM.
S126
224 SF
TLT.
S126.1
68 SF
PAT. RM.
S125
220 SF
TLT.
S125.1
66 SF
PAT. RM.
S124
221 SF
TLT.
S124.1
66 SF
PAT. RM.
S123
233 SF
TLT.
S123.1
66 SF
TLT.
S122.1
66 SF
PAT. RM.
S122
231 SF
TLT.
S105.1
66 SF
NURSE
S106
141 SF
JAN. CL.
28 SF
LIVING
S120
328 SF
DINING
S121
239 SF
Room
C-11
748 SF
MECH./ ELEC.
W123
551 SF
STUDY
W128
374 SF
MULTIPURPOSE
W129
845 SF
CORR
C-4
420 SF
CORR.
C-11
286 SF
STORAGE
W129.1
13 SF
TR
220A
100 SF
TR
417A
106 SF
CORRIDOR
C-8
1205 SF
CORRIDOR
C-6
335 SF
CORRIDOR
C-7
549 SF
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
1. VA APPROVED TR 417A (101 SQFT).
2. TR MEETS EXISTING HEALTHCARE BUILDING MINIMUM AREA
REQUIREMENT OF 100 SQFT FOR TR.
3. TR DOES NOT MEET FORM FACTOR REQUIREMENT OF A
10' X 10' FOOTPRINT.
TR 417A NOTES
1. VA APPROVED TR 220A (99 SQFT).
2. TR DOES NOT MEET EXISTING HEALTHCARE BUILDING MINIMUM
AREA REQUIREMENT OF 100 SQFT FOR TR.
3. TR DOES NOT MEET FORM FACTOR REQUIREMENT OF A
10' X 10' FOOTPRINT.
TR 220A NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:0
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
20TN801
BLDG 20 - LEVEL 01 - DIAMOND
STUDY PLAN 20
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
0 20' 40'10'
PROJECT
NORTH
- 1" = 20'-0"
1 BLDG 20 - LEVEL 01 - DIAMOND STUDY PLAN
A
B
C
D
E
F
G
H
I
J
K
L
M
N
1 2 3 4 5 6 7 8 9 10 11 12 13 15 1613'
VESTIBULE
D-100
128 SF
LOBBY
D-101
286 SF
CLERICAL
D-102
249 SF
DIRECTOR'S OFFICE
D-103
146 SF
STORAGE
D-104
23 SF
STAFF
D-105
78 SF
CORRIDOR
D-106
94 SF
GROUP THERAPY
D-107
314 SF
STOR
D-108
58 SF
STUDENT OFFICE
D-109
112 SF
PROG. COORD. OFFICE
D-110
115 SF
OFFICE
D-111
114 SF
OFFICE
D-112
114 SF
OFFICE
D-113
114 SF
OFFICE
D-114
114 SF
OFFICE
D-115
114 SF
OFFICE
D-116
114 SF
OFFICE
D-117
114 SF
CORR.
D-118
406 SF
GROUP THERAPY
D-119
440 SF
GROUP THERAPY
D-120
269 SF
VESTIBULE
D-121
117 SF
CORRIDOR
D-122
516 SF
GROUP THERAPY
D-123
195 SF
WOMEN
D-124
143 SF
DINING
D-125
941 SF
CORRIDOR
D-126
767 SF
WARMING KITCHEN
D-127
336 SF
PHONE
D-128
14 SF
PHONE
D-129
18 SF
CUST. COORD
D-130
122 SF
STOR.
D-131
28 SF
STAFF TLT.
D-132
53 SF
STAFF TLT.
D-133
53 SF
ART
D-134
128 SF OCC. THER. KITCHEN
D-135
145 SF
RECREATION
D-136
809 SF
REC. THER. OFFICE
D-137
106 SF
COMP
D-138
179 SF
RESOURCE LIBRARY
D-139
113 SF
STOR.
D-140
56 SF
SPD STOR.
D-141
85 SF
PHYS. THER
D-142
219 SF
STOR.
D-143
77 SF
CORRIDOR
D-144
151 SF
DOCK
D-145
295 SF
LINEN HOLD
D-146
57 SF
DATA
D-147
66 SF
SWITCHGEAR
D-148
86 SF
ELEC.
D-149
18 SF
STOR.
D-150
17 SF
MECHANICAL EQUIPMENT
D-151
261 SF
P/ FP
D-152
48 SF
VENDING
D-153
24 SF
SPECIMEN TOILET
D-154
68 SF NURSE PRACTITIONER
D-155
131 SF
PHONE
D-156
15 SF
EXAM
D-157
155 SF NURSE
D-158
140 SF
JAN. CL.
D-159
34 SF
MEDS
D-160
100 SF
DOM. ASSIST
D-161
245 SF
MEN
D-162
141 SF
TR
D-119A
113 SF
EXISTING ROOM
EXPANSION
NEW LOCATION
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
LEGENDS
1. VA APRROVE TR D-119A (120 SQFT).
2. TR MEET THE EXISTING HEALTHCARE BUILDING MINIMUM
AREA REQUIREMENT OF 100 SQFT FOR TR
3. TR MEET THE FORM FACTOR REQUIREMENT OF A 10' X 10'
FOOTPRINT.
TR D-119A NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:1
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
21TN801
BLDG 21 - LEVEL 01 - DIAMOND
STUDY PLAN 21
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 1/8" = 1'-0"
1 BLDG 21 - LEVEL 01 - DIAMOND STUDY PLAN 4'0 8' 16'
PROJECT
1A 1 2 3 4 5
B
C
SWITCHGEAR
355 SF
EMERGENCY
GENERATOR
422 SF
CONTROL ROOM
210 SF
TE
105A
58 SF
TOILET ROOM
58 SF
SHOWER ROOM
44 SF
BREAK ROOM
297 SF
WORKSHOP
439 SF
PARTS STORAGE
293 SF
EQUIPMENT
ROOM
3985 SF
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
1. VA APRROVE TE 105A (58 SQFT).
2. TE IS SHARING SPACE ROOM WITH ANOTHER PURPOSE,
AS PER DESIGN ALERT 9 IS NOT ALLOWED.
3. HEFP DOES NOT CONSIDER THIS ROOM TO FALL INTO A
CATEGORY OF AN AREA READILY TO GENERAL FOOT TRAFFIC.
TE 105A NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:3
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B L D
G
.r v t
30TN801
BLDG 30 - LEVEL 01 - DIAMOND
STUDY PLAN 30
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- 3/16" = 1'-0"
1 BLDG 30 - LEVEL 01 - DIAMOND STUDY PLAN
KEY NOTES
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
4'0 8' 12'
PROJECT
1A 1 2 3 4 5
B
C
EXISTING ROOM
EXPANSION
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
1. THERE SHALL BE A MINIMUM OF ONE STANDARDIZED TR PER
FLOOR AS PER TELECOMMUNICATIONS SPACES: 4.1.3
TELECOMMUNICATIONS ROOM.
2. TR MINIMUM ARE REQUIREMENT FOR HEALTHCARE BUILDING
IS 100 SQF.
SUMMARY:
A. VA DIRECTION TO FEED THIS FLOOR TO A TE 105A THAT WILL
BE LOCATED ON LEVEL 01.
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:3
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B L D
G
.r v t
30TN802
BLDG 30 - LEVEL 02 - DIAMOND
STUDY PLAN 30
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
- 3/16" = 1'-0"
1 BLDG 30 - LEVEL 02 - DIAMOND STUDY PLAN 4'0 8' 12'
PROJECT
B C E F H I J K
A D G L NM
CARPENTER'S SHOP
1478 SF
STORAGE
123A
214 SF
122A
605 SF
STORAGE
939 SFSTORAGE
120A
359 SF
PAINT SHOP
119B
127 SF
PAINT SHOP
558 SF
STORAGE
92 SF
MECHANICAL ROOM
119A
34 SF
STORAGE
118A
16 SF
LOUNGE/LUNCH ROOM
649 SF
100SA
70 SF
MAINTENANCE LEADER
131 SF
SUPERVISORY PROGRAM
SPECIALIST
98 SF
BUDGET ANALYST
162 SF
100S
398 SF
UTILITIES SYSTEM/ OPERATIONS
SUPERVISOR
232 SF
KITCHEN
108 SF
MALE RESTROOM
160 SF
COPY ROOM
89 SF
BENEFICIARY TRAVEL/ASST.
TRANSPORTATION
177 SF
CONFERENCE ROOM
249 SF
100E
384 SF
CHIEF ENGINEER
223 SF
TELEPHONE CLOSET
7 SF
FEMALE RESTROOM
44 SF
ENVIRO. PROTECTION SPEC.
118 SF
ENGINEERING TECH./AUTOCAD
115 SF
100C
189 SF
ENGINEER TECH.
130 SF
100W
156 SF
ENGINEER
161 SF
CONFERENCE ROOM
294 SF
SAFETY OFFICER
101B
120 SF
OFFICE
101C
77 SF
PLOTTER/FILES ROOM
101A
224 SF
TR
101D
90 SF
EXISTING ROOM
EXPANSION
NEW LOCATION
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
LEGENDS
1. VA APRROVE TR 101D (90 SQFT).
2. TR DOES NOT MEET THE EXISTING HEALTHCARE BUILDING
MINIMUM AREA REQUIREMENT OF 100 SQFT FOR TR
3. TR DOES NOT MEET THE FORM FACTOR REQUIREMENT OF
A 10' X 10' FOOTPRINT.
TR 101D NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:1
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
46TN801
BLDG 46 - LEVEL 01 - DIAMOND
STUDY PLAN 46
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
- 1" = 10'-0"
1 BLDG 46 - LEVEL 01 - DIAMOND STUDY PLAN 0 10' 20'
PROJECT
NORTH
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
A B C D E F G H I J K L M N O P
PESTICIDE STORAGE
102A
178 SF
EQUIPMENT STORAGE
102D
890 SF
LOUNGE/BREAK
102B
251 SF
STOARGE
102C
580 SF
STORAGE
105CA
100 SF
STORAGE
105B
2715 SF
EQUIPMENT STORAGE
6389 SF
OFFICE
103A
128 SF
FOYER
43 SF
MECHANICAL ROOM
341 SF
DRUG VAULT
105C
1186 SF
BREAK ROOM
195 SF
PURCHASING AGENT
105EB
107 SF
INVENTORY MANAGER
105EA
103 SF
PURCHASING AGENT
105E
119 SF
SUPERVISOR OFFICE
105D
150 SF
TELEPHONE CLOSET
105A
9 SF
LOADING DOCK
254 SF
ENGINEERING PRIMARY
GIP STORAGE
848 SF
IT STORAGE
105G
269 SF
HOUSE KEEPING
INVENTORY
270 SF
LOADING DOCK
101A
72 SF
RECEIVING AREA
7974 SF
OFFICE STORAGE
105GA
225 SF
MALE RESTROOM
105FA
84 SF
FOYER
105F
45 SF
105FB
11 SF
RESTROOM/SHOWER
105FC
40 SF
TE
105H
24 SF
9 SF
1. VA APRROVE TE 105H (24 SQFT).
2. COMPLIANCE WITH DESIGN ALERT 9.
TE 100CA NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:2
:0 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B ld g
.r v t
47TN801
BLDG 47 - LEVEL 01 - DIAMOND
STUDY PLAN 47
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- 1" = 10'-0"
1 BLDG 47 - LEVEL 01 - DIAMOND STUDY PLAN
GENERAL NOTES
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
ASSOCIATED TELECOMMUNICATIONS PLANS FOR ADDITIONAL INFORMATION.
0 10' 20'
PROJECT
NEW LOCATION
LEGENDS
NOTE: ALL DIAMONDS ARE 80 METERS FROM CENTER
PER VA STANDARDS.
A B C D E F G H
I
10 11
CHIEF SLEEPING
124 SF
SLEEPING
81 SF
SLEEPING
81 SF
MECH
188 SF
DAYROOM
284 SF
SLEEPING
79 SF
SLEEPING
79 SF
CAPTAIN SLEEPING
105 SF
BATHROOM
53 SF
BATHROOM
54 SF
TE
100CA
62 SF
CLOSET
111A
20 SF
KITCHEN
82 SF
CORRIDOR
120 SF
DAYROOM
624 SF
OFFICE
130 SF
OFFICE
104 SF
TOILET
47 SF
LOBBY
291 SF
TRUCK GARAGE
2335 SF
LOCKERS
123 SF
UTLITY
91 SF
1. VA APRROVE TE 100CA (64 SQFT).
2. COMPLIANCE WITH DESIGN ALERT 9.
TE 100CA NOTES
PLAN INCLUDED FOR
INFORMATIONAL PURPOSES
ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:1
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ E
E
B L D
G
.r v t
48TN801
BLDG 48 - LEVEL 01 - DIAMOND
STUDY PLAN 48
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
KEY NOTES
GENERAL NOTES
- 1/8" = 1'-0"
1 BLDG 48 - LEVEL 01 - DIAMOND STUDY PLAN
PROJECT
NORTH
4'0 8' 16'
1. PLAN INCLUDED TO SHOW HORIZONTAL CABLING COVERAGE. REFERENCE
File details come from the government source that posted it. Updated .