S02 - Attachment 11 - Butler EHRM IU - Drawing - Electrical 2 of 6 R1.pdf
PDF 17 MB Posted
- Attached to
- EHRM | Butler VA HCS 529-22-700 | Construct Infrastructure Upgrades Federal contract opportunity
- Solicitation number
- 36C77625R0057
About this file
This document is an electrical engineering drawing (EP502) for infrastructure upgrades at the VA Butler Healthcare facility, specifically detailing power elevation and schematic configurations for telecommunications rooms (TRs). The drawing provides technical specifications for power distribution, including:
Rack-mounted power infrastructure with detailed electrical configurations such as Uninterruptible Power Supply (UPS) units rated at 5kW, 208V with 16.5-minute runtime at 50% load, and Power Distribution Units (PDUs) with specific voltage and amperage requirements. The design includes redundant power sources (Source A and Source B) for each telecommunications rack, utilizing L21-20R and L21-30R locking receptacles, and specifies equipment like Eaton BladeUPS or approved equivalents. The drawing is part of a comprehensive infrastructure upgrade project for the VA Butler Medical Center, with precise electrical connectivity and power management specifications for telecommunications equipment.
View the file
Other files for this federal contract opportunity
Show all 42
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEG 1 LEG 2 LEG 1 LEG 2
AGROUPA
B
BGROUP AGROUP BGROUP
L21-30P SIDE B
REQUIRES A 208V, 30A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA L21-30R
LOCKING RECEPTACLE.
L21-30P SIDE A
REQUIRES A 208V, 30A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA
L21-30R LOCKING RECEPTACLE.
30A 3-PHASE ZONE PDU BASE
UNIT - REQUIRES TWO 30A 3-
PHASE (WYE) CIRCUITS WITH
L21-30R RECEPTACLES
PHASE Z PHASE Y PHASE X
RACK-MOUNTED UNINTERRUPTIBLE
POWER SUPPLY (UPS), 5KW, 208V WITH
NEMA 20A L21-20P INPUT AND L21-20R
OUTPUT.
SIZE: 6RU, 19" RACK-MOUNTABLE
RUNTIME: 16.5 MINUTES AT 50% LOAD
EATON BLADEUPS OR APPROVED EQUAL.
RACK-MOUNT
UPS
RACKED
EQUIPMENT
RACKED
EQUIPMENT
PDU
A
PDU
B
PDU
A
PDU
BPSA PSB PSA PSB
LEG A LEG B
ZONE PDU
RACK-MOUNT
UPS
RACK/ENCLOSURE RACK/ENCLOSURE
SOURCE A 30A
RECEPTACLE
SOURCE B 30A
RECEPTACLE
REFERENCE
TN DRAWINGS
FOR RACK
MOUNTED
NETWORK
EQUIPMENT
REFERENCE
TN DRAWINGS
FOR RACK
MOUNTED
NETWORK
EQUIPMENT
EP501
EP502
TYP
CB1
CB1
CB2
CB2
CB3
CB3
In lO lO lO
O ut
T em p /H u m id it y
O K
W a rn in g
C ri ti c a l
R e se t
C H
A T
S W
O R
T H
P R
O D
U C
T
O N l
O F
F O
N l
O F
F O
N l
O F
F
CB3
CB3
CB2
CB2
CB1
CB1
CB2
CB2
CB3
CB3
In lO lO lO
O ut
T em p /H u m id it y
O K
W ar ni n g C ri tic al
R e se t
C H
A T
S W
O R
T H
P R
O D
U C
T O
N l
O F
F O
N l
O F
F O
N l
O F
F
CB3
CB3
CB2
CB2
CB1
CB1
CB2
CB2
CB3
CB3
In lO lO lO
O ut
T em p /H u m id it y
O K
W ar ni n g C ri tic al
R e se t
C H
A T
S W
O R
T H
P R
O D
U C
T
O N l
O F
F O
N l
O F
F O
N l
O F
F
CB3
CB3
CB2
CB2
CB1
CB1
CB2
CB2
CB3
CB3
In lO lO lO
O ut
T em p /H u m id it y
O K
W ar ni n g C ri tic al
R e se t
C H
A T
S W
O R
T H
P R
O D
U C
T
O N l
O F
F O
N l
O F
F O
N l
O F
F
CB3
CB3
CB2
CB2
L21-20P SIDE B
REQUIRES A 208V, 20A,
THREE-PHASE CIRCUIT,
TERMINATING IN A NEMA
L21-20R LOCKING
RECEPTACLE.
L21-20P SIDE A
REQUIRES A 208V, 20A,
THREE-PHASE CIRCUIT,
TERMINATING IN A NEMA
L21-20R LOCKING
RECEPTACLE.
RACK-MOUNTED UNINTERRUPTIBLE POWER
SUPPLY (UPS), 5KW, 208V WITH NEMA 20A L21-20P
INPUT AND L21-20R OUTPUT.
SIZE: 6RU, 19" RACK-MOUNTABLE
RUNTIME: 16.5 MINUTES AT 50% LOAD
EATON BLADEUPS OR APPROVED EQUAL.
RACK/ENCLOSURE
RACK-MOUNT
UPS
RACKED
EQUIPMENT
PSA PSB
PDU
A
PDU
B
SOURCE A 20A
RECEPTACLE
SOURCE B 20A
RECEPTACLE
REFERENCE
TN DRAWINGS
FOR RACK
MOUNTED
NETWORK
EQUIPMENT
CB1
CB1
CB2
CB2
CB3
CB3
In lO lO lO
O ut
T em p /H u m id it y
O K
W ar ni n g C ri tic al
R e se t
C H
A T
S W
O R
T H
P R
O D
U C
T
O N l
O F
F O
N l
O F
F O
N l
O F
F
CB3
CB3
CB2
CB2
CB1
CB1
CB2
CB2
CB3
CB3
In lO lO lO
O ut
T em p /H u m id it y
O K
W ar ni n g C ri tic al
R e se t
C H
A T
S W
O R
T H
P R
O D
U C
T
O N l
O F
F O
N l
O F
F O
N l
O F
F
CB3
CB3
CB2
CB2
REQUIRES ONE (1) L21-20R
20A 120/208V 3øY
APC AP8861 RPDU OR EQUIVALENT; RACK
PDU 2G, METERED; L21-20 PLUG; THREE
PHASE; 120/208V INPUT; 20A; ZERO U, 5.7 KW,
208V, (36) C13 & (6) C19 & (2) 5-20 OUTLETS;
FOR USE IN TELECOMMUNICATION ROOMS
AND LOCATIONS WITH LEGACY 110V ONLY
EQUIPMENT
NOTE: USED IN TELECOMMUNICATIONS
ROOMS WHERE 110V DISTRIBUTION
USING NEMA 5-15 OR NEMA 5-20
RECEPTACLES ARE REQUIRED IN
ADDITION TO THE STANDARD 208V
RACK MOUNT PDU. L5- 30 INPUT. NEMA 5-20
OUTPUT. 1 RU. TWO PER ENCLOSURE. ONE ENERGIZED
BY UPS. ONE ENERGIZED BY WALL OUTLET. (SHOWN
HERE FRONT FACING, BUT ARE TO BE INSTALLED ON
THE BACK RAIL.)
RACK MOUNT UPS. L5-30 INPUT.
L5-30 OUTPUT. CAPACITY NTE 2880 VA. 2 RU.
METERED. (APC SMX3000RMLV2U OR EQUIVALENT)
O U
T
IN
O
CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
TELECOMMUNICATIONS
BONDING BUSBAR
QUAD OUTLET (5-20) FOR
BACKBOARD MOUNTED
EQUIPMENT
TE SOURCE A AND B POWER
RECEPTACLES (LOCKING, 120V, 30A,
L5-30) MOUNTED IN JUNCTION BOX SIZED
TO FIT TE POWER CUTOUT LOCATION.
JUNCTION BOX SHALL BE RECESSED IN
WALL BEHIND TE. SOURCE A
RECEPTACLE SHALL FEED TE UPS.
SOURCE B RECEPTACLE SHALL FEED TE
PDU. EACH RECEPTACLE ENERGIZED BY
SEPARATE ONE-POLE 30 AMP
BREAKERS; REFERENCE PLANS FOR
ADDITIONAL CIRCUITING INFORMATION.
<6"
<6"
WALL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:1 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP502
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
3 POWER ELEVATION AND SCHEMATIC FOR A TWO RACK TR
- NTS
1 NOT USED
- NTS
4 POWER ELEVATION AND SCHEMATIC FOR ONE RACK TR
- NTS
2 208V RACK PDU FOR TRs
EP502
TYP
GENERAL NOTES
1. THIS SHEET SHALL BE PRINTED IN COLOR TO
PROVIDE ALL NECESSARY INFORMATION.
- 1/2" = 1'-0"
5 TELECOMMUNICATIONS ENCLOSURE ELEVATION DETAIL
Revisions: Date:
TE SOURCE A AND B POWER RECEPTACLES
(LOCKING, 120V, 30A, NEMA L5-30) MOUNTED
IN SINGLE GANG JUNCTION BOXES, EACH
SIZED TO FIT TE POWER 6"x6" CUTOUT
LOCATION. JUNCTION BOXES SHALL BE
RECESSED IN WALL BEHIND TE.
SOURCE A RECEPTACLE SHALL FEED TE
UPS. SOURCE B RECEPTACLE SHALL FEED
TE PDU. EACH RECEPTACLE ENERGIZED BY
SEPERATE 1-POLE 30-AMP BREAKERS;
REGERENCE PLANS FOR ADDITIONAL
CIRCUITING INFORMATION.
Load
Blue
Occupancy sensor switch
Black Black
White Bare
Ground
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER
FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
9.52mm (3/8")
MIN GALVANIZED
THREADED ROD,
TYP.
CONDUIT CLAMP.
SIZE AS REQUIRED
LOCKING SQUARE
WASHER &
LOCKNUT
STEEL
EXPANSION
ANCHOR
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL
PREFABRICATED RUBBER BOOT
CAP WITH GRADUATED STEPS &
WEATHER-PROOF PRESSURE SEAL
TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
BY ROOFING CONTRACTOR
MULTIPLE MEMBRANE STRIPPING PLIES
FEATHERED AT FIELD OF ROOF BY
ROOFING CONTRACTOR. PRIME FLANGE
BEFORE STRIPPING.
PREFABRICATED FORMED 1.52mm
(0.06") THICK ALUMINUM FLASHING
ROUND COLLAR WITH MIN. 76mm (3")
WIDE FLANGE. ATTACH TO ROOF PER
MANUFACTURER'S INSTRUCTIONS
CONDUIT CLAMP.
SIZE AS REQUIRED
BATT INSULATION
ROOF MEMBRANE
WATER CUT-OFF MASTIC
COMPATIBLE WITH ROOF
MEMBRANE
STAINLESS
CLAMP, TYP.
SEAL-OFF
FITTING, TYP.
CONCRETE DECKING
STEEL EXPANSION
ANCHOR
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
CONDUIT,
TYP.
FIELD OF VIEW
FOR DETAIL
FINISHED SURFACE
(OR ROOF)
PROVIDE RMC OR
LTFMC AS
REQUIRED TO
CONNECT TO
LOAD
ALL FASTENING
HARDWARE SHALL
BE STAINLESS
STEEL, TYP.
GENERAL DETAIL NOTES:
1. ALL CHANNEL STRUT, POST BASES AND ACCESSORIES SHALL BE HOT-
DIPPED GALVANIZED, UNLESS SPECIFICALLY NOTED OTHERWISE.
2. THIS IS A GENERAL DETAIL INDICATING GENERAL LAYOUT
REQUIREMENTS. CONTRACTOR SHALL SIZE RACK ACCORDINGLY TO
MOUNT ALL REQUIRED EQUIPMENT AS SHOWN ON PLANS; ADDITIONAL
HORIZONTAL AND/OR VERTICAL STRUCTURAL MEMBERS MAY BE
REQUIRED.
ID PLACARD, PROVIDE PER SPECIFICATIONS.
ALL FASTENING
HARDWARE SHALL
BE STAINLESS
STEEL, TYP.
CHANNEL STRUT, 1-5/8" X 1-5/8", LENGTH AS
REQUIRED, TYP.
MYERS HUB, TYP
48" MIN.
ROOF MOUNTED DISCONNECT
FINISHED GROUND/
EARTH
PROVIDE RMC OR
LTFMC AS
REQUIRED TO
CONNECT TO
LOAD
ANCHOR BOLTS,
1/4"-DIA x 12" L (MIN.), STAINLESS STEEL
ID PLACARD, PROVIDE PER SPECIFICATIONS.
ALL FASTENING
HARDWARE SHALL
BE STAINLESS
STEEL, TYP.
CHANNEL STRUT, 1-5/8" X 1-5/8", LENGTH
AS REQUIRED, TYP.
MYERS HUB, TYP
48" MIN.
GROUND MOUNTED DISCONNECT
CONCRETE FOOTING WITH
CHAMFERED EDGE,
3000-PSI,12"-DIA x 30" L (MIN)
CONDUIT STRAP,
TYP.
CONDUIT STRAP,
TYP.
GROUND STRAP, BRAIDED
TINNED COPPER
RMC/IMC CONDUIT, TYP.
EXPANSION COUPLING, EATON
XJG, OR APPROVED EQUAL
U-BOLT WITH FASTENING
HARDWARE, TYP.
FIRE ALARM
CONTROL PANEL
OUTPUTS
INPUTS
DETAIL NOTES
1. DETAIL IS GENERIC IN NATURE AND IS INCLUDED ONLY TO INDICATE HVAC EQUIPMENT SHUNT-TRIP AND SMOKE DAMPER ACTUATOR LOGIC. ALTHOUGH MULTIPLE CIRCUITS MAY BE REQUIRED, ONLY (1) EXAMPLE FOR EACH TYPE OF LOGICAL DIAGRAM IS SHOWN; EACH SETUP SHALL BE PROVIDED WITH THE SAME LOGIC AND MATERIALS. CONTRACTOR SHALL PROVIDE COMPLETE SUBMITTAL INCLUDING, BUT NOT LIMITED TO, FUNCTIONAL NARRATIVE, WIRING DIAGRAMS, SHOP DRAWINGS, BILL OF MATERIALS, AND FLOOR PLANS REDLINING EQUIPMENT INSTALLATION LOCATIONS FOR ENGINEER AND VA
REVIEW AND APPROVAL PRIOR TO COMMENCING WORK.
2. FIRE ALARM CONTROL PANEL SHALL PROVIDE SHUNT TRIP OUTPUT SIGNAL TO CIRCUIT BREAKERS SERVING DATA CENTER HVAC UNITS AND ACTUATE FIRE/SMOKE DAMPERS UPON SMOKE DETECTION VIA SMOKE DETECTORS. PROVIDE ADJACENT JUNCTION BOX TO UTILIZE FOR CONDUIT AND WIRE TERMINATIONS; PROVIDE ADDITIONAL CONTROL HARDWARE AND APPURTENANCES INCLUDING, BUT NOT LIMITED TO, TERMINAL BLOCKS, RELAYS, AND FUSES AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
3. COORDINATE WITH VA, CAMPUS FIRE ALARM CONTRACTOR, AND MECHANICAL CONTRACTOR AS REQUIRED.
4. GROUNDING CONDUCTORS NOT SHOWN FOR CLARITY; PROVIDE GROUNDING CONDUCTORS PER NEC AND AS SPECIFIED.
5. REFERENCE DETAIL '1' ON TELECOMMUNICATIONS SHEET 'TN505' FOR ADDITIONAL FIRE ALARM CONTROL PANEL INFORMATION.
JUNCTION BOX
HVAC SHUTDOWN
PUSHBUTTON
120V
PWR
CR1
TERMINAL BLOCK
CONNECTION, TYP.
ST
CR
PWR
SMOKE
DAMPER
ACTUATOR
(TYPICAL)
CR CR PWR
SHUNT TRIP CIRCUIT
BREAKER (TYPICAL)
HVAC UNIT
(TYPICAL)
CR CR1
(2) SMOKE DETECTORS, NORTH AND SOUTH
(2) SMOKE DETECTORS, MIDDLE AISLE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:1 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP503
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
1 TYPICAL CONDUIT ROOF PENETRATION DETAIL
- 1 1/2" = 1'-0"
2 TYPICAL UNISTRUT RACK MOUNTED DISCONNECT SWITCH
- NTS
3 CONDUIT EXPANSION JOINT DETAIL
- NTS
4 DATA CENTER HVAC SHUTDOWN SWITCH WIRING DIAGRAM
Revisions: Date:
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC) AWG
IRREVERSIBLE CRIMP
CONNECTOR, TYP.
CABLE TRAY BONDING
CONDUCTOR. TYPICAL AT
EACH SECTION
CONNECTION POINT
TO PRIMARY OR SECONDARY
BONDING BUSBAR
IRREVERSIBBLE
COMPRESSION
CONNECTION
RACK BONDING
CONDUCTOR
(6 AWG)
TEBC
(TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR - 4 AWG)
RACK BONDING CONDUCTOR (6 AWG)
UNIT BONDING CONDUCTOR (6 AWG)
TOP-MOUNTED
RACK BONDING
BUSBAR
IRREVERSIBLE CRIMP
CONNECTOR, TYP.
GROUND TO PRIMARY
BONDING BUSBAR.
COORDINATE WITH VA
FOR EXACT
CONDUCTOR ROUTING
TWO-HOLE COMPRESSION LUGS (RACKS SHALL NOT
BE MODIFIED IF ONLY ONE-HOLE IS PROVIDED; USE
ONE-HOLE COMPRESSION LUGS IN THIS CASE)
TWO-HOLE
COMPRESSION LUGS (RACKS
SHALL NOT BE MODIFIED IF
ONLY ONE-HOLE IS PROVIDED;
USE ONE-HOLE COMPRESSION
LUGS IN THIS CASE)
RACK ISOLATION PADS
BONDING CONDUCTOR TO
PANEL BOARD GROUND LUG (ACEG)
USE TWO-HOLE LUGS FOR
BONDING CONNECTOR
TELECOMMUNICATIONS
BONDING BUSBAR
BOND RBB TO CABINET LUG. AWG #6
BOND RBB TO EACH SWITCH
AND ROUTER CHASIS
BOND RBB TO TELECOMMUNICATIONS BONDING BUSBAR. AWG #6
RACK BONDING BUSBAR (RBB)
OTHER CONNECTIONS
AS REQUIRED
(BONDING CONDUIT,
CABLE TRAYS,
BUILDING STEEL, TO
THE PBB OR SBB,
ETC.)
CHATSWORTH PRODUCTS
#40158-012, OR APPROVED
EQUAL
MOUNTING BRACKETS
1/4" THICK
L= 12"
D
INSULATOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0 /2
:2
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP504
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
2 CABLE TRAY GROUNDING/BONDING REQUIREMENTS
- NTS
1 TELECOMMUNICATION RACK BONDING DETAIL
- NTS
4 TELECOMMUNICATIONS ENCLOSURE GROUNDING DETAIL
- NTS
5 BONDING BUSBAR
- NTS
3 TELECOMMUNICATIONS GROUNDING RISER DETAIL
TELECOMMUNICATIONS
SECONDARY BONDING BUSBAR
ALL CONNECTIONS TO
BUSBAR SHALL BE (2) BOLT
MECHANICAL LUGS, TYP.
BONDING CONDUCTOR TO
BUILDING STEEL, #3/0 AWG
GREEN INSULATION W/YELLOW
TRACER
BONDING CONDUCTOR TO
RACEWAYS, CONDUITS,
WIREWAYS, CABLE TRAYS, #6
AWG GREEN INSULATION W/
YELLOW TRACER
BONDING CONDUCTOR TO
PANELBOARD(S) IN ROOM
PRESENT, #6 AWG GREEN
INSULATION W/ YELLOW TRACER
BONDING CONDUCTOR FROM
TELECOMMUNICATIONS
SECONDARY BONDING
BUSBAR TO
TELECOMMUNICATIONS
BONDING BACKBONE (IF NOT
PRESENT, BOND TO PRIMARY
SERVICE ENTRY MAIN
BUSBAR), #3/0 AWG GREEN
INSULATION W/YELLOW
TRACER
TELECOMMUNICATIONS BONDING
BACKBONE CONDUCTOR. PROVIDE WITH
GREEN INSULATION AND YELLOW
TRACER, SIZE PER TIA/ANSI STANDARDS
AS REQUIRED. WHERE EXISTING, EXTEND
AND REROUTE BACKBONE TO AND FROM
RELOCATED/EXPANDED
TELECOMMUNICATIONS ROOMS. IF NEW,
PROVIDE AS REQUIRED.
IRREVERSIBLE
CRIMP CONNECTOR,
UL LISTED
Revisions: Date:
PROVIDE BOND TO ELECTRO-STATIC
DISCHARGE FLOORING. BONDING
CONDUCTOR SHALL BE 12 AWG MIN'
PROVIDE AND INSTALL PER
MANUFACTURER'S INSTRUCTIONS.
EXOTHERMIC WELD
STRUCTURAL STEEL REINFORCING BAR
BARE COPPER CONDUCTOR
EXOTHERMIC WELD
BARE COPPER CONDUCTOR, TYP.
PRECAST CONCRETE CURB
VALVE BOX - 8 1/2" (212mm) I.D. X 18" (450mm) D. - CHRISTY #F14
BOX OR EQUAL
BURNDY TYPE GK CONNECTOR
REMOVABLE COVER - REINFORCED CONCRETE -
CHRISTY CONCRETE PRODUCTS #F8D OR EQUAL
GRADE
SAND FILL
BARE SOFT-DRAWN COPPER
GROUNDING ELECTRODE
CONDUCTOR, TYP.
GROUND ROD "COPPERWELD" 3/4"
(20mm) DIA. X 10'-0" (3M) LONG
EXOTHERMIC WELD CROSS CONNECTOR
BARE COPPER CONDUCTOR, TYP.
FLEXIBLE COPPER STRAP,
COORDINATE INSTALLATION
WITH ARCHITECTURAL
AIR TERMINAL ROD
(18"L, COPPER)
CLASS I LIGHTNING
CONDUCTOR
STRUCTURE
AIR TERMINAL ROD
(18"L, COPPER)
COPPER CLAD STEEL
BASE PLATE
STRUCTURE
EXOTHERMIC
WELD
STEEL PLATE,
COORDINATE INSTALLATION
WITH ARCHITECTURAL
CLASS I LIGHTING
CONDUCTOR
CLASS 1 LIGHTING
CONDUCTOR, COPPER
TEE CONNECTOR, HANGER
MODEL A207, OR EQUAL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:2 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP505
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
1 TYPICAL BUILDING STRUCTURE EXOTHERMIC CONNECTION DETAIL
- NTS
4 TYPICAL EXOTHERMIC "T" CONNECTION DETAIL
- NTS
2 TYPICAL GROUND ROD WITH TEST WELL INSTALLATION DETAIL
- NTS
5 TYPICAL EXOTHERMIC CROSS CONNECTION DETAIL
DETAIL NOTES:
1. ALL CONDUCTORS SHALL BE SIZED PER PLANS. EXOTHERMIC CONNECTOR
SHALL BE SIZED PER CONDUCTOR AND STRUCTURAL STEEL.
DETAIL NOTES:
1. ALL CONDUCTORS SHALL BE SIZED PER PLANS. EXOTHERMIC CONNECTOR
SHALL BE SIZED PER CONDUCTORS.
DETAIL NOTES:
1. ALL CONDUCTORS SHALL BE SIZED PER PLANS. EXOTHERMIC CONNECTOR
SHALL BE SIZED PER CONDUCTORS.
- NTS
3 PEAK-ROOFED AIR TERMINAL ROD INSTALLATION DETAIL
- NTS
7 NON-PEAKED AIR TERMINAL ROD INSTALLATION DETAIL
- NTS
6 LIGHTNING CONDUCTOR TEE CONNECTOR
PDU
A1
PDU
B1
RACKED EQUIPMENT
PS
PS
BUS A BUS B
L21-20P SIDE B REQUIRES A 208V, 20A,
THREE-PHASE CIRCUIT, TERMINATING
IN A NEMA L21-20R LOCKING
RECEPTACLE.
L21-20P SIDE A REQUIRES A 208V, 20A,
THREE-PHASE CIRCUIT, TERMINATING
IN A NEMA L21-20R LOCKING
RECEPTACLE.
EACH RACK WILL CONTAIN:
1. ONE L21-20C DROP PER BUSWAY.
2. A MINIMUM OF TWO ZERO U VERTICAL RACK PDUs
UTILIZING SEPARATE BUSWAY TAP INPUTS.
3. DIVERSE POWER INPUTS FOR ACTIVE EQUIPMENT
ALLOWING FOR SOURCE POWER TO BE SPLIT ACROSS
THE TWO BUSWAYS.
DETAIL NOTES:
1. UPS A AND UPS B SHALL HAVE A MIRRORED LAYOUT WITH POWER DISTRIBUTION CABINETS CLOSEST TO MAIN
DISTRIBUTION AREA AND BATTERY CABINET FURTHEST AWAY.
2. MAINTENANCE BYPASS SWITCH CAN BE INSTALLED ON THE RIGHT OR LEFT OF UPS CABINET.
3. EACH CABINET DEPTH IS 42"
4. UPS IS TOP AIR EXHAUSTED.
5. UPS SHALL BE ENERGY SAVER SYSTEM (ESS) PROVIDING 99% EFFECIENCY RATING.
CONDUIT TO BUSWAY FEEDER BOXES.
BATTERY
CABINET
120kW FRAME
UPS CABINET
MAINTENANCE
BYPASS SWITCH POWER
DISTRIBUTION
CABINET
COLOR DISPLAY
PERFORATED DOORS FOR
VENTILATION
.74"
FLOOR .34.2"
.34.5"
.31"
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
SOURCE A/B BUSWAY
FEEDER BOX A/B SIDE FIBER OPTIC AND
UTP BACKBONE PATCH
PANEL
L21-20P SIDE A REQUIRES
A 208V, 20A, THREE-PHASE
CIRCUIT, TERMINATING IN
A NEMA L21-20R LOCKING
RECEPTACLE.
L21-20P SIDE B REQUIRES
A 208V, 20A, THREE-PHASE
CIRCUIT, TERMINATING IN
A NEMA L21-20R LOCKING
RECEPTACLE.
VERTICAL PDU
SOURCE A/B BUSWAY
DETAIL NOTES:
1. MDA A AND B WILL HAVE A MIRRORED LAYOUT, WITH THE OUTER MOST CABINETS BEING THE TR DISTRIBUTION CABINETS.
2. EACH CABINET HAS A DEPTH OF 43.3".
3. BUSWAY 'A' AND 'B' ARE PHYSICALLY SEPARATE BY AT LEAST 1' BUT ARE AT THE SAME ELEVATION WITH 'A' IN FRONT OF 'B'.
RESERVED FOR
DISTRIBUTION TO
TR'S
RESERVED FOR
CORE, SECURITY
AND WAN
ELEMENTS
RESERVED FOR
SPINE,
AGGREGATION AND
OOB SWITCHES AND
LAN ELEMENTS.
7'
3' 4"
10'
EP506
TYP
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB2
CB3
CB3
CB2
CB1
CB1
CB1
CB1
CB1
CB1
CB1
CB1
CB1
CB1
CB1
CB1
CB2
CB3
CB3
CB2
CB2
CB3
CB3
CB2
CB2
CB3
CB3
CB2
CB2
CB3
CB3
CB2
CB2
CB3
CB3
CB2
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0 /2
:4
:3 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP506
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
1 POWER SCHEMATIC FOR STANDARD DENSITY DATA CENTER ENCLOSURE DETAIL
- NTS
2 TYPICAL UPS ELEVATION.
- NTS
3 MDA POWER ELEVATION, TYPICAL
GENERAL NOTES
THIS SHEET SHALL BE PRINTED IN COLOR TO
PROVIDE ALL NECESSARY INFORMATION.
1.
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
FLOOR
CHATSWORTH eCONNECT PDU
OR EQUIVALENT
(2) 208V, 3-PHASE
A/B BUSWAY RAILS
L21-20P SIDE B REQUIRES A 208V, 20A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA L21-20R LOCKING
RECEPTACLE.
L21-20P SIDE A REQUIRES A 208V, 20A,
THREE-PHASE CIRCUIT, TERMINATING IN A
NEMA L21-20R LOCKING RECEPTACLE.
STANDARD DENSITY
IT ENCLOSURE, TYPICAL
SOURCE A BUSWAY
FEEDER BOX,
PHYSICALLY SEPARATE
FROM SOURCE B
BUSWAY
HORIZONTOL
DISTRIBUTION AREA
ENCLOSURE, TYPICAL
.3' 4" .
30' 3"
C B
C
B
C B
C B
C
B
C B
SOURCE B BUSWAY
FEEDER BOX,
PHYSICALLY SEPARATE
FROM SOURCE A
BUSWAY
.7'
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
C B
C
B
C B
.2'
A SIDE BUSWAY B SIDE BUSWAY
BEHIND A SIDE
EP506
TYP.
EP506
TYP.
TO UPS B POWER
DISTRIBUTION
PANEL
TO UPS A POWER
DISTRIBUTION
PANEL
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
CB1
CB2
CB1
CB2
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
CB1
CB1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0 /2
:1
:4 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP507
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
NTS137EP101
1 SERVER CABINET ROW POWER ELEVATION
- NTS
2 NOT USED
- NTS
3 NOT USED
GENERAL NOTES
1. THIS SHEET SHALL BE PRINTED IN COLOR TO
PROVIDE ALL NECESSARY INFORMATION.
CB1
CB1
BLUE
BLACKBLACK
BARE
OCCUPANCY
SENSOR SWITCH
LOAD
WHITE
GROUND
HOT/LIVE
120 V~ 50/60 Hz
NEUTRAL
WHEN USING CONTROLS IN
SINGLE LOCATION
INSTALLATIONS, TIGHTEN THE
BLUE TERMINAL OR CAP BLUE
WIRE. DO NOT CONNECT THE
BLUE TERMINAL/WIRE TO ANY
OTHER WIRE OR TO GROUND.
BARE
BLACK
BLUE
WHITE WIRE WITH
GREEN SLEEVE
TYPICAL
DATA
RACK
FIN. FLOOR
HORIZONTAL CAT6A
DISTRIBUTION AND
FIBER-OPTIC BACKBONE
CABLE TRAY, TYPICAL.
F L O
O R
T O
U N
D E
R S
ID
E
S T
R U
C T
U R
E
84"
6" MIN
BOTTOM OF FLOOR OR ROOF ABOVE
LIGHT FIXTURE: REFERENCE TR ROOM
LUMINAIRE MOUNTING SCHEDULE. LIGHT
MOUNTING LOCATION IS DIAGRAMMATIC;
CONTRACTOR SHALL COORDINATE EXACT
MOUNTING HEIGHT AND PLACEMENT WITH ALL
OBSTRUCTIONS INCLUDING CABLE TRAY, RACKS
AND ARCHITECTURAL FEATURES.
POWER PACK(S)
(QUANTITY AS REQUIRED)
LIGHTING
LOAD
DAYLIGHT / OCCUPANCY SENSOR(S)
(QUANTITY AS REQUIRED; WHERE
INDICATED ON PLANS)
OCCUPANCY SENSOR(S)
(QUANTITY AS REQUIRED;
WHERE INDICATED ON PLANS)
LOW VOLTAGE SWITCH(ES)
(QUANTITY AS REQUIRED;
WHERE INDICATED ON PLANS)
N
L
120VAC
24V CONTROL
DS
OS
PP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:0 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP508
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
1 TYPICAL WALL SWITCH OCCUPANCY SENSOR
- 3/4" = 1'-0"
2 TYPICAL TELECOMMUNICATIONS ROOM ELEVATION
- NTS
3 TYPICAL CEILING MOUNTED SENSOR LIGHTING WIRING DIAGRAM
- NTS
4 TYPICAL RECESSED LIGHTING INSTALLATION
- NTS
5 TYPICAL EXIT SIGN INSTALLATION DETAIL
FUEL TANK GENERATOR CONTROL PANEL
OVERFILL FLOAT SWITCH
"FLT-OF"
LOW FLOAT SWITCH
"FLT-LO"
LD
COMM
MODULE
AUTOMATIC
TRANSFER SWITCH
"137-ATS-A"
GENERATOR
CALL TO RUN
GENERATOR
CALL TO RUN
AUTOMATIC
TRANSFER SWITCH
"137-ATS-B"
FUEL POLISHING SYSTEM
GENERAL ALARM
GENERATOR
START
BMS JACE PANEL
COMM
BACNET
COMM
MODULE
DPM
SWITCHBOARD
"137-SWBD-B"
BACNET
COMM
DPM
SWITCHBOARD
"137-SWBD-N"
BACNET
COMM
COMM
MODULE
UPS
"137-UPS-A1"
BACNET
COMM
COMM
MODULE
UPS
"137-UPS-B1"
BACNET
COMM
BACNET
COMM 2
PANEL "137-106A"
BACNET
COMMDPM
PANEL "137-108A"
BACNET
COMMDPM
PANEL "137-105A"
BACNET
COMMDPM
BACNET
COMMDPM
SWITCHBOARD
"137-SWBD-A"
COMM
MODULE BACNET
COMMDPM
SWITCHBOARD
"137-SWBD-E"
BACNET
COMMDPM
PANEL "137-106B"
COMM 3
BACNET
COMMDPM
PANEL "137-108B"
BACNET
COMMDPM
PANEL "137-105B"
LEAK DETECTION
BACNET
EXISTING STRUCTURE
EXISTING CEILING JOIST, TYPICAL
ELECTRICAL CONDUITCONDUIT STRAP
WITH GALVANIZED
FASTENING
HARDWARE
DETAIL NOTES:
1. UTILIZE GALVANIZED STEEL HARDWARE
TO SUPPORT CONDUIT AS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:5
:0 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP509
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
1 DATA CENTER EQUIPMENT CONTROL AND STATUS WIRING DIAGRAM
- NTS
3 NOT USED
- NTS
2 JOIST CONDUIT MOUNTING DETAIL
DETAIL NOTES:
1. DETAIL IS GENERIC IN NATURE. PROVIDE
STATUSES INDICATED PER MANUFACTURER'S
REQUIREMENTS. PROVIDE ALL TERMINATIONS,
CABLING, RACEWAYS,PROGRAMMING AND
APPURTENANCES AS REQUIRED.
GENERAL NOTES (FOR THIS SHEET ONLY)
GENERATOR POINTS TO BE MONITORED, AT MINIMUM, SHALL BE AS FOLLOWS:
- GENERATOR RUNNING "137-GEN-RUN"
- GENERATOR TROUBLE "137-GEN-TRB"
- GENERATOR FAIL "137-GEN-FL"
- GENERATOR LOW FUEL "137-GEN-LOF"
- GENERATOR START "137-GEN-STR"
ATS "A" POINTS TO BE MONITORED, AT MINIMUM, SHALL BE AS FOLLOWS:
- ATS IN NORMAL POSITION "137-ATS-A-NPS"
- ATS IN EMERGENCY POSITION "137-ATS-A-EPS"
- ATS NORMAL POWER AVAILABLE "137-ATS-A-NPA"
- ATS EMERGENCY POWER AVAILABLE "137-ATS-A-EPA"
- ATS FAIL "137-ATS-A-FAL"
ATS "B" POINTS TO BE MONITORED, AT MINIMUM, SHALL BE AS FOLLOWS:
- ATS IN NORMAL POSITION "137-ATS-B-NPS"
- ATS IN EMERGENCY POSITION "137-ATS-B-EPS"
- ATS NORMAL POWER AVAILABLE "137-ATS-B-NPA"
- ATS EMERGENCY POWER AVAILABLE "137-ATS-B-EPA"
- ATS FAIL "137-ATS-B-FAL"
BMS PANEL SHALL BE ACCOMPANIED BY I/O EXPANSION MODULES AS REQUIRED
FOR ALL ELECTRICAL AND MECHANICAL EQUIPMENT CONTROL AND STATUS.
PROVIDE ALL TERMINATIONS, CABLING, RACEWAYS, PROGRAMMING AND
APPURTENANCES AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL
SYSTEM. REFERENCE MECHANICAL DRAWINGS AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
KEY NOTES (FOR THIS SHEET ONLY)
LEVEL 01
TR-D-119A TE-105A TR-101D TE-105H TE-100CA
PBB PBB PBB PBB
BUILDING 21 BUILDING 30 BUILDING 46 BUILDING 47 BUILDING 48
LEVEL 01
ER-105 TR-106 ER-108
PBB
BUILDING 137
RM D-148 RM 101 RM 119
RM 102 RM 100CA
LEVEL 02
TYP.
TR-204
LEVEL 01
TR-TC110
TE-B08
TYP.
LEVEL 00
PBB
TE-B03
PBB PBB PBB
TR-102 TE-101A TE-103 TR-220A TR-417A
PBB
TYP.
BUILDING 2
PBB
BUILDING 4 BUILDING 6 BUILDING 7 BUILDING 8 BUILDING 20
TYP.
2 4
TYP.
TYP.
RM W123RM 102ARM 106
RM 2-B19
21-BUS-MDP 30-BUS-MDP
FUSED
DISCONNECT
46-01-DC
47-BUS-MDP NE
TYP.
GENERATOR ROOM 116 DATA CENTER 114
RM 110
SWITCHBOARD N
TYP.
47-BUS-MDP
2-BUS-MDPC 4-BUS-M
RM B02A
RM 104
6-BUS-MDP PP-7 PANEL LS 20-BUS-SWBD1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0 /2
:1
:0 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
EP510
ELECTRICAL DETAILS
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
- NTS
1 TELECOMMUNICATIONS BONDING RISER DIAGRAM
GENERAL NOTES (FOR THIS SHEET ONLY)
PROVIDE PRIMARY BONDING BUSBAR (PBB). WHERE EXISTING PBB EXISTS,
CONTRACTOR SHALL REPLACE; CONTRACTOR TO FIELD VERIFY EXISTING
LOCATION. PROVIDE ALL BONDING CONNECTIONS AS REQUIRED.
PROVIDE TELECOMMUNICATIONS BONDING BACKBONE (TBB) CONDUCTOR AS
INDICATED. CONTRACTOR SHALL ROUTE AND PROVIDE ALL REQUIRED PATHWAYS
FOR TBB AS REQUIRED. EXISTING TBB SHALL BE DEMOLISHED AND REMOVED;
PROVIDE ALL PATCHING, REPAIR AND FIREPROOF SEALING AS REQUIRED.
PROVIDE IRREVERSIBLE CRIMP CONNECTOR, UL LISTED.
TELECOMMUNICATIONS ROOM. REFER TO ENLARGED FLOOR PLANS FOR
ADDITIONAL INFORMATION.
PROVIDE TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR (TEBC) TO
CONNECT TBB TO SBB. MINIMUM SIZE SHALL BE 6 AWG.
PROVIDE SECONDARY BONDING BUSBAR (SBB). PROVIDE TELECOMMUNICATIONS
EQUIPMENT BONDING CONDUCTOR TO BOND SBB TO THE FOLLOWING EQUIPMENT:
DATA RACK, CABLE TRAY, TR CONDUITS, ELECTRICAL PANEL, ETC. REFERENCE
SHEET EP504 FOR ADDITIONAL BONDING INFORMATION.
PROVIDE TELECOMMUNICATIONS BONDING CONDUCTOR (TBC) TO BOND TO
BUILDING ELECTRICAL SERVICE EQUIPMENT GROUNDING BUSBAR. MINIMUM
CONDUCTOR SIZE SHALL BE 3 AWG.
PROVIDE (1) 1" CONDUIT WITH 1 AWG GND (MINIMUM) FROM SBB TO PBB AS
INDICATED.
1. ALL BONDING CONDUCTORS, INCLUDING TBB, SHALL FOLLOW SIZING
REQUIREMENTS SPECIFIED IN ANSI/TIA-607-D.
2. CONTRACTOR SHALL PROVIDE ALL REQUIRED BONDING, CONDUCTORS, AND
PATHWAYS AS REQUIRED. PROVIDE ALL PATCHING, REPAIR AND FIREPROOFING
FOR REMOVAL OF ALL EXISTING EQUIPMENT AND CONDUCTORS AS REQUIRED .
KEY NOTES (FOR THIS SHEET ONLY)
Revisions: Date:
PBB
P
RM 105H
CONTRACTOR SHALL PROVIDE ALL REQUIRED BONDING, CONDUCTORS, AND
PATHWAYS REQUIRED FOR THE TELECOMMUNICATIONS SYSTEM BONDING. ALL
EXISTING TELECOMMINCATIONS BONDING FOR EQUIPMENT BEING REMOVED SHALL
BE DEMOLISHED. PROVIDE ALL PATCHING, REPAIR AND FIREPROOFING
FOR REMOVAL OF ALL EXISTING EQUIPMENT AND CONDUCTORS AND NEW
INSTALLATIONS AS REQUIRED .
XF T12-SEC
208V, 0A Isc 3P: 9357 A
2-CBL-MDP
Length: 70 ft
(1) 500 kcmil
2-BUS-MAIN TAP
208V, 0A Isc 3P: 7588 A
2-CBL-ATS MDP-ECB (N)
(1) 500 kcmil Length: 5 ft
2-CB-ATS MDP-ECB (N)
GE
Model: TJD Trip: 300 A
2-BUS-ATS MDP-ECB (N)
208V, 300A Isc 3P: 7461 A
2-CBL-ATS ELEV-ECB (N)
(1) 500 kcmil Length: 5 ft
2-CB-ATS ELEV-ECB (N)
GE
Model: TJD Trip: 300 A
2-BUS-ATS ELEV-ECB (N)
208V, 300A Isc 3P: 7489 A
2-CBL-ATS LS-ECB (N)
(1) 2 AWG
Length: 5 ft
2-CBL-ATS MDP (N)
(1) 500 kcmil Length: 20 ft
2-CBL-ATS ELEV (N)
(1) 500 kcmil Length: 25 ft
2-BUS-ATS MDP (N)
208V, 0A Isc 3P: 6992 A
2-BUS-ATS ELEV (N)
208V, 0A Isc 3P: 7036 A
2-CBL-ATS MDP-ECB (E)
(1) 500 kcmil Length: 5 ft
2-CB-ATS MDP-ECB (E)
SIEMENS
Model: JXD6-A Trip: 300 A
2-BUS-ATS MDP-ECB (E)
208V, 300A Isc 3P: 7555 A
2-CBL-ATS MDP (E)
(1) 500 kcmil Length: 25 ft
2-BUS-ATS MDP (E)
208V, 0A Isc 3P: 6992 A
E N
2-ATS-ELEV
300 A
E N
2-CBL-ATS ELEV-ECB (E)
(1) 500 kcmil Length: 5 ft
2-CB-ATS ELEV-ECB (E)
SIEMENS
Model: JXD6-A Trip: 300 A
2-BUS-ATS ELEV-ECB (E)
208V, 300A Isc 3P: 7555 A
2-CBL-ATS ELEV (E)
(1) 500 kcmil Length: 20 ft
2-BUS-ATS ELEV (E)
208V, 0A Isc 3P: 7098 A
2-BUS-GEN TAP
208V, 0A Isc 3P: 7678 A
2-CBL-ATS LS-ECB (E)
(1) 2 AWG
Length: 5 ft
2-CB-ATS LS-ECB (E)
SIEMENS
Model: ED2 Trip: 100 A
2-BUS-ATS LS-ECB (E)
208V, 100A Isc 3P: 7449 A
2-CBL-ATS LS (E)
(1) 2 AWG
Length: 25 ft
2-BUS-ATS LS (E)
208V, 0A Isc 3P: 6248 A
2-BUS-ATS ELEV (L)
208V, 0A Isc 3P: 7036 A
2-CB-ELEV
GE
Model: TFJ Trip: 200 A
2-CBL-ELEV DISC
(1) 3/0 AWG
Length: 100 ft
2-CB-ELEV DISC
GE
Model: SFHA Trip: 175 A
2-BUS-ELEV DISC
208V, 175A Isc 3P: 5191 A
2-CBL-ELEV
(1) 2/0 AWG
Length: 25 ft
2-BUS-ELEV P4
208V, 0A Isc 3P: 4824 A
2-ELEV P4
50 hp
46.6 kW
2-CB-ATS LS-ECB (N)
SIEMENS
Model: ED2 Trip: 100 A
2-BUS-ATS LS-ECB (N)
208V, 100A Isc 3P: 7293 A
2-CBL-ATS LS (N)
(1) 2 AWG
Length: 30 ft
2-BUS-ATS LS (N)
208V, 0A Isc 3P: 5717 A
2-ATS-LS
150 A
2-BUS-ATS LS (L)
208V, 0A Isc 3P: 5717 A
2-CBL-LS B2
(1) 2 AWG
Length: 8 ft
2-CB-LS B2-MAIN
SIEMENS
Model: BLH Trip: 100 A
2-BUS-LS B2
208V, 250A Isc 3P: 5370 A
2-CB-LS B2-1
SIEMENS
Model: HBL Trip: 60 A
2-CBL-LS B2-1
(1) 3 AWG
Length: 70 ft
2-CB-G2-MAIN
SQUARE D
Model: QO-VH Trip: 100 A
2-BUS-G2
208V, 100A Isc 3P: 3126 A
TO 2-ATS-MDP
(02EP602)
TO 2-ATS-MDP
(02EP602)
100A 3P
LS
ENCLOSED CB
G
600A 3P
1200A 3P
TO BLDG 20
20-CB-EDP-MAIN
(20EP601)
XF T12
150kVA, Z% 4.43 Pri: 4160V Sec: 208V Isc 3P: 8517 A
GEN 2/20
400KW
208V
3PH
TO FU-XF T12
(02EP604)
1 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
02EP601
BLDG 02 - ONE-LINE DIAGRAM -
EXISTING - PART 1 OF 4 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
- NTS
1 BLDG 02 - ONE-LINE DIAGRAM - EXISTING - PART 1 OF 4
METERING NOTES
1 METERING POINT: EXISTING ATS "2-ATS-ELEV". REFERENCE "METERING AND LOAD
INFORMATION SCHEDULE" ON SHEET EP701 FOR ADDITIONAL INFORMATION.
METERING POINT: EXISTING ATS "2-ATS-LS". REFERENCE "METERING AND LOAD
INFORMATION SCHEDULE" ON SHEET EP701 FOR ADDITIONAL INFORMATION.
2-CB-ATS EDP-ECB (N)
SQUARE D
Model: MG Trip: 800 A
2-BUS-ATS EDP-ECB (N)
208V, 800A Isc 3P: 18418 A
2-CBL-ATS EDP (N)
(2) 600 kcmil Length: 10 ft
E N
2-ATS-EDP
800 A
Open
2-BUS-AHU 2
208V, 0A Isc 3P: 5770 A
2-BUS-EDP
208V, 1200A Isc 3P: 15857 A
E N
2-ATS-MDP
300 A
S
P
2-BUS-PICNIC
208V, 100A Isc 3P: 1078 A
2-BUS-ATS EDP (N)
208V, 0A Isc 3P: 17704 A
2-BUS-ATS EDP (L)
208V, 0A Isc 3P: 17704 A
2-CBL-EDP
(2) 600 kcmil Length: 30 ft
TO BLDG 20
20-CBL-SWBD1-3
(20EP601)
2-CB-EDP-2
SQUARE D
Model: MG Trip: 600 A
2-CB-EDP-1
SQUARE D
Model: QJ Trip: 175 A
2-CBL-EDP-1
(1) 2/0 AWG
Length: 125 ft
2-CBL-EDP-2
(2) 350 kcmil Length: 8 ft
2-CB-KPA1-MAIN
SQUARE D
Model: LD Trip: 600 A
2-BUS-KPA1
208V, 600A Isc 3P: 15370 A
2-CBL-KPA2
(2) 350 kcmil Length: 5 ft
2-BUS-KPA2
208V, 600A Isc 3P: 15079 A
2-CBL-KPA3
(2) 350 kcmil Length: 5 ft
2-BUS-KPA3
208V, 600A Isc 3P: 14799 A
2-BUS-ATS MDP (L)
208V, 0A Isc 3P: 6992 A
2-CBL-MDPC
(1) 500 kcmil Length: 50 ft
2-CBL-MDPA
(1) 500 kcmil Length: 10 ft
2-CB-MDPA-MAIN
SIEMENS
Model: JXD6-A Trip: 400 A
2-BUS-MDPA
208V, 400A Isc 3P: 6779 A
2-CB-MDPA-3
SIEMENS
Model: HBL Trip: 70 A
2-CB-MDPA-2
SIEMENS
Model: QJH2 Trip: 200 A
2-CB-MDPA-1
SIEMENS
Model: BLH Trip: 100 A
2-CBL-MDPA-3
(1) 3 AWG
Length: 75 ft
2-CBL-MDPA-2
(1) 4/0 AWG
Length: 8 ft
2-CBL-MDPA-1
(1) 2 AWG
Length: 200 ft
CONTINUE TO BLDG 132
132-CB-SMOKE-MAIN
CONTINUE TO BLDG 31
31-BUS-GEN EYE WASH
2-CB-MDPA-MAIN
SIEMENS
Model: QJH2 Trip: 225 A 2-CB-MDPC-MAIN
CUTLER-HAMMER
Model: HKD Trip: 400 A
2-BUS-MDPB
208V, 250A Isc 3P: 6572 A
2-CB-MDPB-1
SIEMENS
Model: BL Trip: 30 A
2-CB-MDPB-2
SIEMENS
Model: BL Trip: 60 A
2-CBL-MDPB-1
(1) 8 AWG
Length: 125 ft
2-CBL-MDPB-2
(1) 6 AWG
Length: 100 ft
2-CB-EV A-MAIN
GE
Model: THQB Trip: 60 A
2-BUS-EV A
208V, 60A Isc 3P: 1919 A
2-CB-MDPC-1
CUTLER-HAMMER
Model: HFD Trip: 225 A
2-CB-MDPC-2
CUTLER-HAMMER
Model: HFD Trip: 225 A
2-CB-MDPC-3
CUTLER-HAMMER
Model: HFD Trip: 225 A
2-BUS-MDPC
208V, 400A Isc 3P: 6040 A
2-CB-MDPC-4
CUTLER-HAMMER
Model: HFD Trip: 225 A
2-CBL-MDPC-1
(1) 4/0 AWG
Length: 60 ft
2-CBL-MDPC-2
(1) 4/0 AWG
Length: 100 ft
2-CBL-MDPC-3
(1) 4/0 AWG
Length: 75 ft
2-CBL-MDPC-4
(1) 4/0 AWG
Length: 15 ft
2-CB-PP B-MAIN
CUTLER-HAMMER
Model: EDB Trip: 225 A
2-XF HUMID-PRI
208V, 0A Isc 3P: 5734 A
2-BUS-PP B
208V, 225A Isc 3P: 4740 A
2-XF-HUMID
75kVA, Z% 5.06 Pri: 208V Sec: 480V
Isc 3P: 5734 A
2-XF HUMID-SEC
208V, 0A Isc 3P: 1040 A
2-CBL-HUMID DISC
(1) 1 AWG
Length: 8 ft
2-FU-HUMID DISC
GOULD SHAWMUT
Model: TRS Trip: 125 A
2-BUS HUMID-DISC
480V, 125A Isc 3P: 1036 A
2-CBL-HUMID
(1) 1 AWG
Length: 200 ft
2-BUS HUMID
480V, 0A Isc 3P: 954 A
2-CBL-MDPC-2 TAP
208V, 0A Isc 3P: 4413 A
2-CBL-PP 2A
(1) 4/0 AWG
Length: 20 ft
2-CBL-PP 1A
(1) 4/0 AWG
Length: 5 ft
2-CB-PP 2A-MAIN
CUTLER-HAMMER
Model: EDB Trip: 225 A
2-CB-PP 1A-MAIN
CUTLER-HAMMER
Model: EDB Trip: 225 A
2-BUS-PP 2A
208V, 225A Isc 3P: 4181 A
2-BUS-PP 1A
208V, 225A Isc 3P: 4353 A
2-CB-PP 2A-1
CUTLER-HAMMER
Model: QBHW Trip: 100 A
2-CB-PP 1A-1
CUTLER-HAMMER
Model: QBHW Trip: 100 A
2-CBL-PP 2A-1
(1) 2 AWG
Length: 5 ft
2-CBL-PP 1A-1
(1) 2 AWG
Length: 5 ft
2-CB-PP 2B-MAIN
CUTLER-HAMMER
Model: QBHW Trip: 100 A
2-CB-PP 1B-MAIN
CUTLER-HAMMER
Model: QBHW Trip: 100 A
2-BUS-PP 2B
208V, 100A Isc 3P: 4068 A
2-BUS-PP 1B
208V, 100A Isc 3P: 4233 A
2-CBL-ATS EDP (E)
(2) 600 kcmil Length: 175 ft
2-BUS-ATS EDP (E)
208V, 0A Isc 3P: 6106 A
TO BLDG 20
20-BUS-BLDG 2 DISC
(20EP601)
CONTINUE TO SHEET 02-BUS-ATS MDP (N)
(02EP602)
2-CBL-MDPC-1 TAP
208V, 0A Isc 3P: 4958 A
2-CBL-MP A
(1) 4/0 AWG
Length: 225 ft
2-CBL-MP B
(1) 4/0 AWG
Length: 5 ft
2-CB-MP A-MAIN
CUTLER-HAMMER
Model: EDB Trip: 225 A
2-CB-MP B-MAIN
CUTLER-HAMMER
Model: EDB Trip: 225 A
2-BUS-MP A
208V, 225A Isc 3P: 2891 A
2-BUS-MP B
208V, 225A Isc 3P: 4884 A
SPACE (3P)
(X6)
TO BUS-ATS MDP (E)
(02EP601)
SPACE
(X6)
2-BUS-KPA4
208V, 100A
2-CB-EDP-3
Trip: 100 A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:5 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
02EP602
BLDG 02 - ONE-LINE DIAGRAM -
EXISTING - PART 2 OF 4 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
- NTS
1 BLDG 02 - ONE-LINE DIAGRAM - EXISTING - PART 2 OF 4
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE DIAGRAM ON SHEET
02EP612 FOR ADDITIONAL INFORMATION .
METERING NOTES
3 METERING POINT: EXISTING ATS "2-ATS-MDP". REFERENCE "METERING AND LOAD
INFORMATION SCHEDULE" ON SHEET EP701 FOR ADDITIONAL INFORMATION.
METERING POINT: EXISTING ATS "2-BUS-EDP" MAIN. REFERENCE "METERING AND
LOAD INFORMATION SCHEDULE" ON SHEET EP701 FOR ADDITIONAL INFORMATION.
METERING POINT: EXISTING PANEL "2-BUS-MDPC" MAIN. REFERENCE "METERING
AND LOAD INFORMATION SCHEDULE" ON SHEET EP701 FOR ADDITIONAL
INFORMATION.
MV-CBL-FEEDER 2-4
(1) 4/0 AWG
Length: 450 ft
MV-CBL-FEEDER 2-2
(1) 4/0 AWG
Length: 100 ft
MV-CBL-FEEDER 2-1
(1) 4/0 AWG
Length: 100 ft
RLY-FEEDER 2
BASLER
Model: BE1-851
CB-FEEDER 2
SQUARE D
Model: VR-05025-12
CB-FEEDER 5
SQUARE D
Model: VR-05025-12
CB-FEEDER 1
SQUARE D
Model: VR-05025-12
RLY-FEEDER 5
BASLER
Model: BE1-851
RLY-FEEDER 1
BASLER
Model: BE1-851
MV-CBL-FEEDER1-1
(1) 4/0 AWG
Length: 1150 ft
TO 99-BUS-
MSC 1
CB-MV NORMAL
SQUARE D
Model: VR-05025-12
RLY-MV NORMAL-GF
BASLER
Model: BE1-951
RLY-MV NORMAL
BASLER
Model: BE1-951
CBL-UTILITY 1
(1) 500 kcmil Length: 75 ft
XF T1-SEC
4160V, 0A Isc 3P: 5940 A
XF-T1
2500 kVA, Z% 5.75 Pri: 25000V
Sec: 4160V Isc 3P: 4948 A
FU-XF-T1
COOPER
Model: NX, 80C
Trip: 80 A
XF T1-PRI
25000V, 0A Isc 3P: 2707 A
UTIL-PREFERRED
25000 V SC Contribution SLG 1446.0 A
SC Contribution 3P 2626.0 A
CB-MV ALTERNATE
SQUARE D
Model: VR-05025-12
RLY-MV ALTERNATE-GF
BASLER
Model: BE1-951
RLY-MV ALTERNATE
BASLER
Model: BE1-951
CBL-UTILITY 2
(1) 500 kcmil Length: 75 ft
XF T2-SEC
4160V, 0A Isc 3P: 3252 A
XF-T2
2500 kVA, Z% 5.75 Pri: 12470V
Sec: 4160V Isc 3P: 3252 A
FU-XF-T2
S&C Model: Positrol, 100T
Trip: 100 A
XF T2-PRI
12470V, 0A Isc 3P: 2283 A
UTIL-ALTERNATE
12470 V SC Contribution SLG 1795.0 A
SC Contribution 3P 2283.0 A
Open
P
S
P
S
TO BLDG 6
XF-T5
(06EP601)
FU-XF-T5
COOPER
Model: 108C12
Trip: 50 A
XF T5-PRI
4160V, 0A Isc 3P: 5710 A
MV-CBL-FEEDER 2-5
(1) 4/0 AWG
Length: 25 ft
6-MV SPLICE
4160V, 0A Isc 3P: 5730 A
TO BLDG 7
7-XF-TX1
(07EP601)
7-XF TX1-PRI
4160V, 0A Isc 3P: 5787 A
7-BUS-PP 7 MV
4160V, 600A Isc 3P: 5792 A
7-CBL-XF PP7
(1) 4/0 AWG
Length: 5 ft
7-FU-MV MAIN
SQUARE D
Model: GDM, 125E
Trip: 125 A
MV-CBL-FEEDER 2-3
(1) 4/0 AWG
Length: 25 ft
7-MV SPLICE
4160V, 0A Isc 3P: 5813 A
TO BLDG 30
XF-T7
(30EP601)
XF T7-PRI
4160V, 0A Isc 3P: 5638 A
MV-CBL-FEEDER 6-1
(1) 500 kcmil Length: 575 ft
RLY-FEEDER 6
BASLER
Model: BE1-851
CB-FEEDER 6
SQUARE D
Model: VR-05025-12
MV-CBL-FEEDER 3-1
(1) 4/0 AWG
Length: 800 ft
RLY-FEEDER 3
BASLER
Model: BE1-851
CB-FEEDER 3
SQUARE D
Model: VR-05025-12
7-BUS-MV SWGR
4160V, 1200A Isc 3P: 5896 A
MV-CBL-FEEDER 3-2
(1) 4/0 AWG
Length: 400 ft
MV-CBL-FEEDER 3-4
(1) 4/0 AWG
Length: 275 ft
TO BLDG 21
XF-T6
(21EP601)
TO BLDG 47
XF-T8
(47EP601)
FU-XF T6(2)
COOPER
Model: ELSP
Trip: 160 A
FU-XF T6(1)
COOPER
Model: 353C17
Trip: 140 A
XF T6-PRI
4160V, 0A Isc 3P: 4986 A
MV-CBL-FEEDER 3-5
(1) 4/0 AWG
Length: 25 ft
BUS-MSC 3B
4160V, 0A Isc 3P: 5002 A
BUS-MSC 3A
4160V, 0A Isc 3P: 5275 A
XF T8-PRI
4160V, 0A Isc 3P: 5239 A
FU-XF T8(2)
COOPER
Model: ELSP
Trip: 80 A
FU-XF T8(1)
COOPER
Model: 108C11
Trip: 40 A
MV-CBL-FEEDER 3-3
(1) 2 AWG
Length: 25 ft
TO XF T4-PRI
(02EP604)
TO BUS-MSC 3C
(02EP604)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:0 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
02EP603
BLDG 02 - ONE-LINE DIAGRAM -
EXISTING - PART 3 OF 4 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
- NTS
1 BLDG 02 - ONE-LINE DIAGRAM - EXISTING - PART 3 OF 4
Open
FU-XF T14-PRI (A)
COOPER
Model: NX, 200C
Trip: 200 A
XF T14-PRI
4160V, 0A Isc 3P: 4391 A
FU-XF T14-PRI (B)
COOPER
Model: NX, 200C
Trip: 200 A
TO BLDG 20
XF-T14
(20EP601)
TO BLDG 2
XF-T12
(02EP601)
MV-CBL-FEEDER 2-7
(1) 4/0 AWG
Length: 275 ft
FU-XF T12
COOPER
Model: ELX, 30C
Trip: 30 A
XF T12-PRI
4160V, 0A Isc 3P: 4433 A
MV-CBL-FEEDER 2-8
(1) 4/0 AWG
Length: 200 ft
99-CBL-MSC 2C-4
(1) 4/0 AWG
Length: 400 ft
99-BUS-MSC 2C
4160V, 0A Isc 3P: 4776 A
TO 99-BUS-MSC 2C
MV-CBL-FEEDER 2-6
(1) 4/0 AWG
Length: 900 ft
TO BLDG 5
5-CBL-MDP
(2) 500 kcmil Length: 25 ft
XF T4-SEC
208V, 0A Isc 3P: 21732 A
XF-T4
225 kVA, Z% 2.30 Pri: 4160V
Sec: 208V Isc 3P: 21732 A
P
S
FU-XF-T4
COOPER
Model: 358C14
Trip: 65 A
XF T4-PRI
4160V, 0A Isc 3P: 5381 A
MV-CBL-FEEDER 3-6
(1) 4/0 AWG
Length: 350 ft
MV-CBL-FEEDER 3-8
(1) 4/0 AWG
Length: 275 ft
MV-CBL-FEEDER 3-9
(1) 4/0 AWG
Length: 700 ft
BUS-MSC 3D
4160V, 0A Isc 3P: 4618 A
XF T13-PRI
4160V, 0A Isc 3P: 4244 A
FU-XF T13(1)
COOPER
Model: 361C04CB
Trip: 100 A
FU-XF T13(2)
COOPER
Model: ELSP
Trip: 160 A
TO BLDG 33
TO BLDG 4
XF-T3
(04EP601)
MV-CBL-FEEDER 3-7
(1) 4/0 AWG
Length: 50 ft
BUS-MSC 3C
4160V, 0A Isc 3P: 4827 A
XF T3-PRI
4160V, 0A Isc 3P: 4796 A
FU-XF T3(1)
COOPER
Model: 108C12
Trip: 50 A
FU-XF T3(2)
COOPER
Model: ELSP
Trip: 100 A
TO 6-MV SPLICE
(02EP603)
TO BUS-MSC 3B
(02EP603)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:0 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
02EP604
BLDG 02 - ONE-LINE DIAGRAM -
EXISTING - PART 4 OF 4 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
- NTS
1 BLDG 02 - ONE-LINE DIAGRAM - EXISTING - PART 4 OF 4
XF T12-SEC
Isc 3P: 9357 A
2-CBL-MDP
Length: 70 ft
(1) 500 kcmil
2-BUS-MAIN TAP
208V, 0A Isc 3P: 7588 A
2-CBL-ATS MDP-ECB (N)
(1) 500 kcmil Length: 5 ft
2-CB-ATS MDP-ECB (N)
GE
Model: TJD Trip: 300 A
2-BUS-ATS MDP-ECB (N)
208V, 300A Isc 3P: 7461 A
2-CBL-ATS ELEV-ECB (N)
(1) 500 kcmil Length: 5 ft
2-CB-ATS ELEV-ECB (N)
GE
Model: TJD Trip: 300 A
2-BUS-ATS ELEV-ECB (N)
208V, 300A Isc 3P: 7489 A
2-CBL-ATS LS-ECB (N)
(1) 2 AWG
Length: 5 ft
2-CBL-ATS MDP (N)
(1) 500 kcmil Length: 20 ft
2-CBL-ATS ELEV (N)
(1) 500 kcmil Length: 25 ft
2-BUS-ATS MDP (N)
208V, 0A Isc 3P: 6992 A
2-BUS-ATS ELEV (N)
208V, 0A Isc 3P: 7036 A
2-CBL-ATS MDP-ECB (E)
(1) 500 kcmil Length: 5 ft
2-CB-ATS MDP-ECB (E)
SIEMENS
Model: JXD6-A Trip: 300 A
2-BUS-ATS MDP-ECB (E)
208V, 300A Isc 3P: 7555 A
2-CBL-ATS MDP (E)
(1) 500 kcmil Length: 25 ft
2-BUS-ATS MDP (E)
208V, 0A Isc 3P: 6992 A
E N
2-ATS-ELEV
300 A
E N
2-CBL-ATS ELEV-ECB (E)
(1) 500 kcmil Length: 5 ft
2-CB-ATS ELEV-ECB (E)
SIEMENS
Model: JXD6-A Trip: 300 A
2-BUS-ATS ELEV-ECB (E)
208V, 300A Isc 3P: 7555 A
2-CBL-ATS ELEV (E)
(1) 500 kcmil Length: 20 ft
2-BUS-ATS ELEV (E)
208V, 0A Isc 3P: 7098 A
2-BUS-GEN TAP
208V, 0A Isc 3P: 7678 A
2-CBL-ATS LS-ECB (E)
(1) 2 AWG
Length: 5 ft
2-CB-ATS LS-ECB (E)
SIEMENS
Model: ED2 Trip: 100 A
2-BUS-ATS LS-ECB (E)
208V, 100A Isc 3P: 7449 A
2-CBL-ATS LS (E)
(1) 2 AWG
Length: 25 ft
2-BUS-ATS LS (E)
208V, 0A Isc 3P: 6248 A
2-BUS-ATS ELEV (L)
208V, 0A Isc 3P: 7036 A
2-CB-ELEV
GE
Model: TFJ Trip: 200 A
2-CBL-ELEV DISC
(1) 3/0 AWG
Length: 100 ft
2-CB-ELEV DISC
GE
Model: SFHA Trip: 175 A
2-BUS-ELEV DISC
208V, 175A Isc 3P: 5191 A
2-CBL-ELEV
(1) 2/0 AWG
Length: 25 ft
2-BUS-ELEV P4
208V, 0A Isc 3P: 4824 A
2-ELEV P4
50 hp
46.6 kW
2-CB-ATS LS-ECB (N)
SIEMENS
Model: ED2 Trip: 100 A
2-BUS-ATS LS-ECB (N)
208V, 100A Isc 3P: 7293 A
2-CBL-ATS LS (N)
(1) 2 AWG
Length: 30 ft
2-BUS-ATS LS (N)
208V, 0A Isc 3P: 5717 A
2-ATS-LS
150 A
2-BUS-ATS LS (L)
208V, 0A Isc 3P: 5717 A
2-CBL-LS B2
(1) 2 AWG
Length: 8 ft
2-CB-LS B2-MAIN
SIEMENS
Model: BLH Trip: 100 A
2-BUS-LS B2
208V, 250A Isc 3P: 5370 A
2-CB-LS B2-1
SIEMENS
Model: HBL Trip: 60 A
2-CBL-LS B2-1
(1) 3 AWG
Length: 70 ft
2-CB-G2-MAIN
SQUARE D
Model: QO-VH Trip: 100 A
2-BUS-G2
208V, 100A Isc 3P: 3126 A
TO 2-ATS-MDP
(02EP612)
TO 2-ATS-MDP
(02EP612)
100A 3P
LS
ENCLOSED CB
G
600A 3P
1200A 3P
TO BLDG 20
20-CB-EDP-MAIN
20EP611
XF T12
150 KVA, Z% 4.43
Pri: 4160V Sec: 208V lsc 3P: 8517 A
TO FU-XF T12
(02EP614)
GEN 2/20
400KW
208V
3PH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:1 a m
B
IM
/5
-2
-7
V A
P A
E H
R M
I n fr a U p g ra d e D e s ig n B u tl e r/ V
A B
U T
L E
R
G E
N E
R A
L S
H E
E T
S .r v t
02EP611
BLDG 02 - ONE-LINE DIAGRAM -
REVISED - PART 1 OF 4 02
DCW/LRL JFO/JGD
100% CONSTRUCTION
DOCUMENTS
11/30/2023
529-22-700EHRM INFRASTRUCTURE
UPGRADES - BUTLER
VA Butler Healthcare, 325 New Castle Road, Butler, Pa.
16001
GENERAL NOTES
KEY NOTES
- NTS
1 BLDG 02 - ONE-LINE DIAGRAM - REVISED - PART 1 OF 4
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING…