S02 - Attachment 2 - Butler EHRM IU - Drawing - Civil 1 of 2 R2.pdf

PDF 4 MB Posted

Attached to
EHRM | Butler VA HCS 529-22-700 | Construct Infrastructure Upgrades
Solicitation number
36C77625R0057
Issued by

About this file

This document is a set of detailed technical drawings for communications infrastructure upgrades at the Butler VA Medical Center, focusing on fiber optic cable installation and pathway design. The drawings (CU501-CU505) provide comprehensive specifications for an Air Assisted Fiber (AAF) micro tube cable system, including outdoor and indoor routing details, building entry configurations, and fiber termination procedures. Key technical specifications include:

The design mandates a continuous home run fiber optic cable pathway from the Main Cross-Connect Room (MCR) to Telecommunications Rooms (TR), with strict prohibitions on cross-connects or splicing. The system utilizes FutureFLEX® dielectric tube cables with various tube configurations (1-24 tubes), designed for outside plant environments with temperature ranges from -40°F to +158°F. The installation involves precise conduit pathways, grounding and bonding requirements, and detailed labeling protocols based on ANSI/TIA-606-C standards, ensuring a robust and standardized telecommunications infrastructure upgrade for the VA medical facility.

View the file

Other files

File Type Posted
S06 - Amendment 0005 - Butler EHRM IU - WD - PA20250079 7.18.2025.pdf PDF
S06 - 36C77625R0057 0005.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixE 2of4-Suggeted Boring Locations.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixD Subsurface Utility Locate Campus Exterior Fiber Routes-230818.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixD Subsurface Utility Locate Buidling21-230323.pdf PDF
S06 - Amendment 0004 - RFI Q 25 - Electrical Equipment List - Equipment Evaluation.xlsx XLSX spreadsheet
S06 - 36C77625R0057 0004.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixE 4of4-Summary of Subsurface Explorations.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixE 3of4-Boring Logs.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixC - MCR Topo-Utility Survey.pdf PDF
S06 - Amendment 0004 - Technical Questions and VA Responses - EHRM IU - Butler VAMC.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixE 1of4-Geotech Report.pdf PDF
S06 - Amendment 0004 - RFI Q 35 - AppendixK Drainage Report-231130.pdf PDF
S06 - 36C77625R0057 0003.pdf PDF
S06 - Amendment 0002 - Attachment 1 - Site Visit Sign In - Butler EHRM.pdf PDF
S06 - 36C77625R0057 0002.pdf PDF
S06 - 36C77625R0057 0001.pdf PDF
S06 - Attachment 4 - Butler EHRM IU - Drawing - Telecom 1 of 2 R 1 6-17-2025.pdf PDF
S06 - Attachment 1 - Butler EHRM IU - Specs 6-17-2025.pdf PDF
S02 - Attachment 9 - Butler EHRM IU - Drawing - Structural 1 of 1 R 1.pdf PDF
S02 - Attachment 12 - Butler EHRM IU - Drawing - Electrical 3of 6 R1.pdf PDF
S02 - Attachment 14 - Butler EHRM IU - Drawing - Electrical 5 of 6 R1.pdf PDF
S02 - Attachment 19 - Butler EHRM IU - J and A.pdf PDF
S02 - Attachment 21 - Spec 01 31 00.01 Project Management and Coordination.pdf PDF
S02 - Attachment 23 - Butler Site Visit Map.pdf PDF
S02 - Attachment 6 - Butler EHRM IU - Drawing - Mechanical 1 of 2 R 1.pdf PDF
S02 - Attachment 11 - Butler EHRM IU - Drawing - Electrical 2 of 6 R1.pdf PDF
S02 - 36C77625R0057.pdf PDF
S02 - Attachment 17 - Butler EHRM IU - VA HCS MCP.pdf PDF
S02 - Attachment 4 - Butler EHRM IU - Drawing - Telecom 1 of 2 R 1.pdf PDF
S02 - Attachment 7 - Butler EHRM IU - Drawing - Mechanical 2 of 2 R 1.pdf PDF
S02 - Attachment 5 - Butler EHRM IU - Drawing - Telecom 2 of 2 R 1.pdf PDF
S02- Attachment 1 - Butler EHRM IU - Specs.pdf PDF
S02 - Attachment 3 - Butler EHRM IU - Drawing - Civil 2 of 2 R1.pdf PDF
S02 - Attachment 15 - Butler EHRM IU - Drawing - Electrical 6 of 6 R1.pdf PDF
S02 - Attachment 20 - Butler EHRM IU - PCRA form.pdf PDF
S02 - Attachment 16 - Butler EHRM IU - Asbestos Survey.pdf PDF
S02 - Attachment 22 - Limitations on Subcontracting.pdf PDF
S02 - Attachment 8 - Butler EHRM IU - Drawing - Arch R1.pdf PDF
S02 - Attachment 10 - Butler EHRM IU - Drawing - Electrical 1 of 6 R1.pdf PDF
S02 - Attachment 18 - Butler EHRM IU - WD - PA20250079 3.28.2025.pdf PDF
S02 - Attachment 13 - Butler EHRM IU - Drawing - Electrical 4 of 6 R1.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTE:

1. THIS DIAGRAMMATICAL RISER OVERVIEW DRAWING SHOWS HOW THE CAMPUS WIDE FIBER OPTIC BACKBONE PATHWAYS CONNECT DIFFERENT LOCATIONS WITHOUT CROSSING OR SHARING ROUTES. EACH

BUILDING HAS ITS OWN ENTRANCE POINTS THAT ARE SEPARATE FROM THE OTHERS.

2. THIS DETAIL TO BE REDLINED BY CONTRACTOR.

MCR

BLDG

A

B

A

B

A

B

A

B

A

B

A B

OUTDOOR FIBER RISER DETAIL (TYP.)C2

CU501 SCALE: NTS

MCR

B

BLDG

(1) TR

BLDG

(1) TR

BLDG

(2) TR'S

C

A27/50

26/38

3/12

1/12

D

23/38

E F H

J K L

2/12

1/1 2 1/12

21/38

3/12 1/ 12 1/12

G18/38 2/12

I

16/38

13/19

2/1 2 5/12

6/12

3/12

1/

2/12

1/

1/12

1/12

2/12

NOTE:

1. THIS DRAWING IS A DIAGRAMMATICAL RISER OVERVIEW OF AN OUTDOOR, AIR ASSISTED FIBER (AAF) TUBE CABLE INSTALLATION. SEE AAF TUBE CABLE DETAIL FOR MORE INFORMATION ABOUT TUBE CABLES. THE NUMBER AND PLACE OF EACH SPLICE ENCLOSURE, AND THE NUMBER OF TUBES INSIDE THE TUBE CABLE, ARE ONLY EXAMPLES.

COORDINATE WITH ALL ACTUAL CONDITIONS AND SPECIFICATIONS BEFORE TUBE CABLE INSTALLATION BEGINS, AND ADJUST THE NUMBER, PLACE, AND ROUTE ACCORDINGLY.

2. THIS DETAIL TO BE REDLINED BY CONTRACTOR.

AB H

H

H

H

H

H H

H

H H H H H H

H

TUBES REQUIRED /

SUPPLIED (TYP.)

HAND HOLE SPLICE

ENCLOSURE (TYP.)

BUILDING SERVING HAND

HOLE ENCLOSURE (TYP.)

OUTDOOR AAF TUBE RISER DIAGRAM - A ROUTE (TYP.)C6

CU501 SCALE: NTS

BUILDING ENTRY TYPICAL DETAILF2

CU501 SCALE: NTS

CEILING SPACE

INTERIOR SIDE OF

BUILDING WALL

EXTERIOR SIDE OF

BUILDING WALL

BUILDING SLAB

1. (3) SCHEDULE 40 CONCRETE ENCASED 4" CONDUITS

2. BUILDING FEEDING HAND HOLE (MINIMUM 37"X26"X36")

3. SECURE HAND HOLE COVER MARKED “COMMUNICATIONS”

4. (2) GALVANIZED 4" CONDUIT

5. LOCKABLE STAINLESS STEEL NEMA 4X ENCLOSURE (36"X30"X8")

6. INDOOR SECURE ENCLOSURE (20"X20"X7")

7. (2) EMT 2" CONDUITS

8. MINIMUM 40" FACTORY LONG SWEEPS

9. (2) 2" EMT TO TELCOM (TR) ROOMS

EXISTING GROUND LEVEL

2 1

NOTE:

THIS DRAWING IS A DIAGRAMMATICAL OVERVIEW OF THE BUILDING ENTRY TUBE MICRO DISTRIBUTION UNIT (TDU). OUTDOOR, AIR ASSISTED FIBER (AAF) MICRO TUBE CABLES WILL BE “COUPLED” TO INDOOR AAF MICRO TUBE CABLES WITHIN. THE INDOOR TUBE CABLES WILL BE DISTRIBUTED FROM THE BUILDING ENTRY (TDU) ENCLOSURE TO THE TELCOM ROOM (TR/TE) TDU ENCLOSURE LOCATIONS VIA 2" EMT CONDUIT PATHWAYS. ALL TUBE CABLES TO BE FURCATED, PROTECTED, & NEATLY COILED WITH STRAIN RELIEF PROTECTION TO ENSURE THE TUBE CABLE GROUPS ARE SECURED IN SUCH A WAY THAT THEY WILL NOT BE DAMAGED OR DISTURBED DURING ROUTINE MAINTENANCE OR FUTURE WORK PERFORMED INSIDE OF THE TDU. LABELING AND IDENTIFICATION OF EQUIPMENT, COMPONENTS, AND TELECOMMUNICATIONS CABLING SHALL BE BASED ON ANSI/TIA-606-C,NFPA 70, NATIONAL ELECTRICAL CODE, OR AS MODIFIED BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES.

MAINTAIN MICRO TUBE CABLE BEND RADIUS REQUIREMENTS AT ALL TIMES. END TO END PRESSURE TESTING AND CERTIFICATION TO MANUFACTURES SPECIFICATIONS IS REQUIRED FOR ALL MICRO TUBES BEFORE INSTALLATION OF FIBER OPTIC CABLES MAY BEGIN.

SP

AR

E 4"

SPARE 2"

AC

TI

VE

EXTERIOR WALL

GROUND LEVEL

(2) 4" GALVANIZED

CONDUITS (1 ACTIVE /

1 SPARE) TO BUILDING

FEEDING HAND HOLE

LOCKABLE NEMA 4X

STAINLESS STEEL

ENCLOSURE (36"x30"x8")

TRANSITION TO (2) 2" EMT

CONDUITS (1 ACTIVE / 1

SPARE) TO TR ROOMS

BUILDING ENTRY TDU ENCLOSURE LAYOUT TYPICAL DETAILF6

CU501 SCALE: NTS

BLDG

BLDG BLDG BLDG

BLDGBLDGBLDG

BLDG

BLDG BLDG

BLDG BLDG

BLDG

BLDG

(1) TR

BLDG

(1) TR

BLDG

(1) TR

BLDG

(1) TR

BLDG

(1) TR

BLDG

(1) TR

BLDG

(1) TR

BLDG

(2) TR'S

BLDG

(3) TR'S

BLDG

(5) TR'S

BLDG

(6) TR'S

LA

BE

L

LABEL

INDOOR/OUTDOOR

MICRO TUBE CABLES

FIBER OPTIC CABLE IS TO

BE A CONTINUOUS HOME

RUN FROM MCR TO TR/TE.

NO CROSS-CONNECTS

OR SPLICING SHALL BE

PERMITTED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

Revisions: Date:

FULLY SPRINKLERED

A/E:ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HWY S, SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

WSP USA Inc.

33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600

TEL: (206) 431-2300

FAX: (206) 431-2250

PB RDM

COMMUNICATIONS DETAILS

CU501

N/A

100% CONSTRUCTION

DOCUMENTS

BUTLER, PA

EHRM INFRASTRUCTURE

UPGRADES

529-22-700

10/11/2311/30/23

NOTE:

THIS DRAWING IS A LOGICAL RISER OVERVIEW OF THE IN-BUILDING, 2" EMT CONDUIT INFRASTRUCTURE.

THIS DIAGRAM REPRESENTS ONLY THE “A” SIDE FEED AND DEPICTS ONE POSSIBLE CONDUIT ROUTE BETWEEN THE ENTRY TDU ENCLOSURE AND THE INDIVIDUAL TR ROOMS FOR THE REQUIRED TWO 2" EMT CONDUITS. ALL JUNCTION BOXES, PULL THRU’S, AND 90 DEGREE ELBO’S MUST MEET MIN BEND RATIO REQUIREMENTS, LONG FACTORY SWEEPS (36"- 40") ARE REQUIRED. SEE INDIVIDUAL BUILDING FLOOR PLAN DETAILS FOR MORE SPECIFIC INTERNAL CONDUIT ROUTE INFORMATION. REFER TO THE INDOOR AAF MICRO TUBE COUNT DIAGRAM DETAIL FOR AIR ASSISTED MICRO TUBE CABLE COUNT AND SIZING INFORMATION BETWEEN ENTRY AND TR ROOM SPACES. INDOOR CONDUIT INFRASTRUCTURE ONLY. AIR ASSISTED MICRO TUBE CABLES ARE TO BE PLACED WITHIN (1) OF THE 2" EMT CONDUITS.

TR1 N/A

N/A TR3 TR4

TR6 TR5 N/A

TR7 N/A N/A

LEVEL 00

LEVEL 01

LEVEL 02

LEVEL 03

J

EXAMPLE

BUILDING

ENTRY TDU-A

J

J

J

TR2

(2) 2" EMT

CONDUITS (TYP.)

INDOOR CONDUIT RISER DETAILC2

CU502 SCALE: NTS

NOTE:

THIS DRAWING IS A LOGICAL OVERVIEW OF THE INDOOR AIR ASSISTED FIBER (AAF) MICRO TUBE CABLE REQUIREMENTS FOR THE “A” SIDE FIBER OPTIC BACKBONE ROUTE. THE EXACT COUNT AND ROUTING LOCATION OF EACH INTERNAL MICRO TUBE COUNT SHOWN ARE DIAGRAMMATICAL. COORDINATE EXACT LOCATIONS, AND ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION. ACTIVE MICRO TUBE CABLES ARE TO BE “COUPLED” AT JUNCTION POINTS WITH FACTORY CERTIFIED COUPLERS. MAINTAIN MICRO TUBE CABLE BEND RADIUS REQUIREMENTS AT ALL TIMES. END TO END PRESSURE TESTING AND CERTIFICATION TO MANUFACTURES SPECIFICATIONS IS REQUIRED FOR ALL MICRO TUBES BEFORE INSTALLATION OF FIBER OPTIC CABLES MAY BEGIN. TYPICAL MINIMUM INDOOR MICRO TUBE CABLE SIZING RECOMMENDATION, (1) MICRO TUBE PER TR/TE ROOM SERVED PLUS MIN 50% FUTURE GROWTH.

TR1 TR2 N/A

N/A TR3 TR4

TR6 TR5 N/A

TR7 N/A N/A

LEVEL 00

LEVEL 01

LEVEL 02

LEVEL 03

J

EXAMPLE

BUILDING

ENTRY TDU-A7/19

7/

6/12

5/

1/4

3/

2/7

1/

7/19 (OUTDOOR AAF)

MICRO TUBES REQUIRED

/ SUPPLIED (TYP.)

INDOOR AAF MICRO TUBE COUNT DIAGRAM - A ROUTEC8

CU502 SCALE: NTS

BONDING AND GROUNDING - RISER DETAILF2

CU502 SCALE: NTS

BUILDING

STEEL

BUILDING

STEEL

BUILDING

STEEL

BUILDING

STEEL

LEVEL 0

LEVEL 1

LEVEL 2

1. PRIMARY BONDING BUS BAR (PBB)

2. ELECTRICAL ENTRANCE / GROUNDING ELECTRODE CONDUCTOR (GEC)

3. BUILDING OR STRUCTURAL STEEL

4. ALTERNATING CURRENT EQUIPMENT GROUND (ACEG)

5. EQUIPMENT BONDING CONDUCTOR (6AWG TYP.)

6. IRREVERSIBLE CRIMP CONNECTOR

7. SECONDARY BONDING BUS BAR (SBB)

NOTE:

ALL GROUNDING AND BONDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D

“COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS”, ISO/IEC 30129,NFPA 70, BICSI, AND IN COMPLIANCE WITH

EQUIPMENT MANUFACTURE REQUIREMENTS AND LOCAL CODES. SIZE ALL BONDING

AND GROUNDING CONDUCTORS PER ANSI/TIA 607, ISO/IEC 30129 SPECIFICATIONS.

PRIMARY SECONDARY1

4 5

1. SECONDARY BONDING BUSBAR (SBB)

2. TELECOMMUNICATIONS EQUIPMENT BONDING

CONDUCTOR, (TEBC) MAINTAIN MINIMUM BEND

RADIUS REQUIREMENTS (6AWG TYP.)

3. HORIZONTAL RACK BONDING BUSBAR (RBB)

4. INDIVIDUAL EQUIPMENT BONDING CONDUCTORS

FROM EACH PIECE OF EQUIPMENT. (6AWG TYP.)

5. RACK FLOOR MOUNT ISOLATION PADS (IF REQUIRED)

TO PBB/SBB

NOTE:

ALL GROUNDING AND BONDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D

“COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS”, ISO/IEC 30129,NFPA 70, BICSI, AND IN COMPLIANCE WITH

EQUIPMENT MANUFACTURE REQUIREMENTS AND LOCAL CODES. SIZE ALL BONDING

AND GROUNDING CONDUCTORS PER ANSI/TIA 607, ISO/IEC 30129 SPECIFICATIONS.

BUILDING

STEEL

BONDING AND GROUNDING - TYPICAL RACK / CABINET DETAILF4

CU502 SCALE: NTS

1. SECONDARY BONDING BUSBAR (SBB)

2. TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR, (TEBC)

MAINTAIN MINIMUM BEND RADIUS REQUIREMENTS (6AWG TYP.)

3. IRREVERSIBLE CRIMP CONNECTOR

4. INDIVIDUAL EQUIPMENT BONDING CONDUCTORS. (6AWG TYP.)

TO PBB/SBB

BUILDING

STEEL

NOTE:

ALL GROUNDING AND BONDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D

“COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS”, ISO/IEC 30129,NFPA 70, BICSI, AND IN COMPLIANCE WITH

EQUIPMENT MANUFACTURE REQUIREMENTS AND LOCAL CODES. SIZE ALL BONDING

AND GROUNDING CONDUCTORS PER ANSI/TIA 607, ISO/IEC 30129 SPECIFICATIONS.

TYPICAL COMMUNICATIONS LADDER / CABLE TRAY

BONDING AND GROUNDING - TYPICAL LADDER TRAY DETAILF8

CU502 SCALE: NTS

FIBER OPTIC CABLE IS TO

BE A CONTINUOUS HOME

RUN FROM MCR TO TR/TE.

NO CROSS-CONNECTS

OR SPLICING SHALL BE

PERMITTED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

Revisions: Date:

FULLY SPRINKLERED

A/E:ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HWY S, SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

WSP USA Inc.

33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600

TEL: (206) 431-2300

FAX: (206) 431-2250

PB RDM

COMMUNICATIONS DETAILS

CU502

N/A

100% CONSTRUCTION

DOCUMENTS

BUTLER, PA

EHRM INFRASTRUCTURE

UPGRADES

TR ROOM - BACKBONE FIBER TRAY AND RACK TYPICAL DETAILC1

CU503 SCALE: NTS

1-12 13-24 B A B A B A B A B A B A

25-36 37-48 B A B A B A B A B A B A

A B C D

A B C D

A B C D

A B C D

A B C D

A B C D

1. RACK MOUNT FIBER CASSETTE HOLDER

2. 24 FIBER SPLICE CASSETTE

3. RACK MOUNT SPLICE CASSETTE HOLDER

4. (2) 12 STRAND SM CASSETTES (LC FRONT/MPO REAR)

5. (2) 12 FIBER, SM, MPO – FIBER SPLICE PIGTAILS

6. (1) 24 STRAND SM AIR BLOW FIBER (AAF) CABLE (FROM MCR)

7. (1) INDOOR AAF 2 TUBE CABLE

8. INDOOR TUBE DISTRIBUTION UNIT (TDU) ENCLOSURE

9. (2) EMT 2" CONDUITS FROM BLDG ENTRY TDU (1-ACTIVE, 1-SPARE)

10. INDOOR AAF TUBE CABLE FROM BUILDING ENTRY TDU ENCLOSURE

NOTE:

THIS DRAWING IS A HIGH LEVEL OVERVIEW OF A SAMPLE TR ROOM FIBER

TERMINATION DETAIL. RACK MOUNTED ITEMS MAY BE SPACED FOR CLARITY.

FIBER CABLE (#7) TO BE SUPPORTED IN DEDICATED FIBER TRAY FROM TDU

TO RACK. COORDINATE MPO FIBER POLARITY BEFORE INSTALLATION.

TR ROOM - FIBER TERMINATION TYPICAL DETAILC5

CU503 SCALE: NTS

MCR - FIBER TERMINATION TYPICAL DETAIL - A SIDEC8

CU503 SCALE: NTS

NOTE:

THIS DRAWING IS AN OVERVIEW OF THE LABELING REQUIREMENTS FOR THE AIR ASSISTED FIBER

(AAF) TUBE CABLES. LABELING AND IDENTIFICATION OF EQUIPMENT, COMPONENTS, AND

TELECOMMUNICATIONS CABLING SHALL BE BASED ON ANSI/TIA-606-C, ADMINISTRATION

STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE, AND NFPA 70, NATIONAL ELECTRICAL

CODE, OR AS MODIFIED BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR

TELECOMMUNICATIONS SPACES. COORDINATE ALL LABELING SCHEMES PRIOR TO INSTALLATION.

HAND HOLE /

SPLICE ENCLOSURE

(TYP.)

LABEL

LABEL

4" C

O N

D U

IT

4"

C O

N D

U

IT

SP

AR

E

SP

AR

E

METAL CABLE

TIE - 4" LONG

MINIMUM

ROUND EDGES PER

MANUFACTURER

INSTRUCTIONS

SECURE LABELS PER

MANUFACTURER

INSTRUCTIONS

TDU LOCATION

TO BUILDING

FROM TR

FROM BUILDINGTO TR

TO TR

TO TR

TO TR

SAMPLE - TWO

2-TUBE CABLES

B1-FTC19A-056.BB102-057.1B139

C1-FT19.2-056.BB102-57.1B139

C1-FT19.1-056.BB102-057.1B139

C2-FT19.2-056.BB102-057.1B120

C2-FT19.1-056.BB102-057.1B120

LABELING AND DOCUMENTATION DETAIL - TUBE CABLESF1

CU503 SCALE: NTS

NOTE:

THIS DRAWING IS AN OVERVIEW OF THE LABELING REQUIREMENTS FOR THE INDOOR TUBE

DISTRIBUTION UNIT. LABELING AND IDENTIFICATION OF EQUIPMENT, COMPONENTS, AND

TELECOMMUNICATIONS CABLING SHALL BE BASED ON ANSI/TIA-606-C, ADMINISTRATION

STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE, AND NFPA 70, NATIONAL ELECTRICAL

CODE, OR AS MODIFIED BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR

TELECOMMUNICATIONS SPACES. COORDINATE ALL LABELING SCHEMES PRIOR TO INSTALLATION.

LABEL WHERE TUBE

CABLE ENTERS TR ROOM

LABEL AAF INDOOR

TUBE CABLES

LABEL AAF INDOOR

TUBE CABLES

LABEL INDOOR TDU

ENCLOSURE

LABELING AND DOCUMENTATION DETAIL - INDOOR TDUF4

CU503 SCALE: NTS

2 TUBE AAF

MINIMUM ONE

OPEN TUBE IN

EACH TR FOR

FUTURE USE

LABEL WHERE

TUBE ENTERS TR

LABEL CABLE

TUBE PRIOR TO

ENTERING

SPLICE CASE

LABEL EACH

SPLICE CASSETTE

24-STRAND, OS2,

SM FIBER

NOTE:

THIS DRAWING IS AN OVERVIEW OF THE SAMPLE LABELING

REQUIREMENTS. LABELING AND IDENTIFICATION OF

EQUIPMENT, COMPONENTS, AND TELECOMMUNICATIONS

CABLING SHALL BE BASED ON ANSI/TIA-606-C, ADMINISTRATION

STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE,

AND NFPA 70, NATIONAL ELECTRICAL CODE, OR AS MODIFIED

BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR

TELECOMMUNICATIONS SPACES. COORDINATE ALL LABELING

SCHEMES PRIOR TO INSTALLATION.

LABER EACH MPO CABLE

PRIOR TO CASSETTE/MODULE

FIBER CASSETTE/MODULE WITH

MPO / LC CONNECTION (TYP.),

LABEL PER VA STANDARDS

LABELING AND DOCUMENTATION DETAIL - FINAL TERMINATIONF7

CU503 SCALE: NTS

B A B A B A B A B A B A

B A B A B A B A B A B A

PW

R

D

IS

TR

SW

IT

C

H

IN

G

PA

TC

H

IN

G

#6 AWG

TYP.

FIBER DUCT

ABOVE CEILING

INDOOR TDU

CABLE TRAY

FRONT SIDE

SECONDARY GBB

FIBER DUCT

CABLE

TRAY

INDOOR TDU

TOP

SECONDARY GBB

SECONDARY GBB

TO PRIMARY GBB

NOTE:

THIS DRAWING IS A HIGH LEVEL OVERVIEW OF A SAMPLE TR ROOM LADDER

TRAY AND EQUIPMENT RACK DETAIL. ITEMS MAY BE SPACED FOR DETAIL AND

CLARITY. FIBER CABLE TO BE SUPPORTED IN DEDICATED FIBER DUCT / TRAY

FROM INDOOR WALL MOUNTED TDU ENCLOSURE TO RACK. COORDINATE

EXACT LOCATIONS AND EQUIPMENT SPACING BEFORE INSTALLATION.

MCR - A

42 42

41 41

40 40

39 39 X4 38 38

37 37

36 36

35 35

34 34

33 33

32 32

31 31

30 30

29 29

28 28

27 27

26 26

25 25

24 24

23 23

22 22

21 21

20 20

19 19

18 18

17 17

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

1. RACK MOUNT FIBER SPLICE & MODULE ENCLOSURE

2. FUSION SPLICE TRAY STORAGE

3. 24 STRAND OS2, SM MODULE (24 LC FRONT/2 MPO REAR)

4. (2) 12 FIBER, SM, MPO – MPO SPLICE PIGTAIL CORD

5. 24 STRAND, OS2, SM FIBER CABLES

6. INDOOR AIR ASSISTED FIBER MICROTUBE CABLES

7. INDOOR TUBE DISTRIBUTION UNIT (TDU) ENCLOSURE (36"X30"X12")

8. (2) EMT 4" CONDUITS FROM BLDG ENTRY TDU (1-ACTIVE, 1-SPARE)

NOTE:

THIS DRAWING IS A HIGH LEVEL OVERVIEW OF A SAMPLE MCR ROOM

FIBER TERMINATION DETAIL. QUANTITIES SHOWN ARE FOR EXAMPLE

ONLY, RACK MOUNTED EQUIPMENT SPACED FOR CLARITY. OUTDOOR AIR

ASSISTED FIBER MICROTUBE CABLES STORED AND COUPLED WITHIN

INDOOR TDU ENCLOSURE. FIBER CABLES (#5) TO BE SUPPORTED IN

DEDICATED FIBER TRAY FROM TDU TO RACK. COORDINATE MPO FIBER

POLARITY AND EXACT EQUIPMENT QUANTITIES BEFORE INSTALLATION.

6 7

3 1 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

Revisions: Date:

FULLY SPRINKLERED

A/E:ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HWY S, SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

WSP USA Inc.

33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600

TEL: (206) 431-2300

FAX: (206) 431-2250

PB RDM

COMMUNICATIONS DETAILS

CU503

N/A

100% CONSTRUCTION

DOCUMENTS

BUTLER, PA

EHRM INFRASTRUCTURE

UPGRADES

AAF MICROTUBE CABLE TYPICAL DETAILF4

CU504 SCALE: NTS

FutureFLEX® TCxxTOX / TCxxTOD DIELECTRIC (OSP) TUBE CABLE SERIES CONSTRUCTION 8mm

6mm

SEL PART NUMBER

TC01TOX

TC07TOX

TC04TOD

TC02TOX

TC12TOX

TC19TOX

TC24TOX

1 - TUBE, WATER BLOCKING TAPE, BLACK POLYETHYLENE OUTER JACKET

2 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE

OUTER JACKET

7 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE

OUTER JACKET

12 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE

OUTER JACKET

19 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE

OUTER JACKET

24 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE

OUTER JACKET

PRODUCT DESCRIPTION

0.53 - (13.5)

0.81 - (20.6)

0.94 - (23.9)

1.14 - (29.0)

01.46 - (37.1)

1.77 - (45.0)

2.0 - (50.8)

MAX. WEIGHT

(LBS./KFT..)

REEL F X W (INCHES)

SEL PART NUMBER

TC01TOX

TC04TOD

TC02TOX

TC07TOX

TC12TOX

TC19TOX

* TC24TOX

1000FT.

54 x 16 54 x 16 54 x 16 54 x 32 60 x 42 60 x 42 72 x 45

3000FT.

60 x 42 60 x 42 60 x 42 60 x 42 72 x 45 72 x 45

* 72 x 45

PERFORMANCE

PROPERTY

OPERATION TEMPERATURE RANGE

REFER SEL SPECIFICATION

SF-F04-005 - (TCXXTOX-TOD)

SPECIFICATION

1000FT.

3000FT.

* 36

TUBE CABLE (1000ft. 3000ft.) REEL LENGTHS

MINIMUM DRUM

DIAMETER (INCHES)

EMPTY REEL

WEIGHT (LBS.)

1000FT.

*543

3000FT.

FULL REEL WEIGHT (LBS.)

1000FT.

* 2493

TC19TOX

TC12TOX

16 17

TC24TOX

TC02TOX

HDPE CENTRAL MEMBER

(NOT FOR PULLING)

TC04TOD

3000FT.

RIPCORD

TC07TOX

TC01TOX

WATER BLOCKING TAPE

BLACK TUBE

RIPCORD

23 24

MAX. TENSILE

LOAD (LBS.)

2 3 4

6 5

BLACK

POLYETHYLENE -

UV RESISTANT

OUTER JACKETWATER

BLOCKING TAPE

BLACK

TUBES

ALL DRAWINGS

NOT TO SCALE

DETAIL TYPICAL

CONSTRUCTION

SCALE: 4:1

TUBE CONSTRUCTION: HIGH-PERFORMANCE BLACK POLYETHYLENE. TUBE DIAMETERS: O.D. 8MM, I.D. 6MM TCXXTOX AND TC04TOD: DESIGNED FOR ALL NORMAL OSP ENVIRONMENTS IN DUCT AND IN DIRECT BURIED APPLICATIONS.

TUBE CABLE ENDS: BOTH ENDS OF THE TUBE CABLE ARE ACCESSIBLE ON THE REEL. EACH TUBE IS SEALED WITH A PLASTIC CAP OR

PLUG. TUBE CABLE ENDS ARE SEALED WITH A HEAT SHRINK END CAP.

REEL MARKINGS: THE OUTSIDE OF EACH FLANGE IS MARKED WITH THE SUMITOMO ELECTRIC LIGHTWAVE CORP. PRODUCT PART NUMBER, THE TUBE CABLE MANUFACTURED LENGTH IN FEET, AND THE TEXT “DO NOT LAY FLAT” AND “FORKLIFT FROM FLANGES ONLY.”

BLACK POLYETHYLENE – UV

RESISTANT OUTER JACKET

ALL DRAWINGS

NOT TO SCALE

MINIMUM BEND RADIUS

DURING / AFTER INSTALLATION

-40°F TO +158°F (-40°C TO +70°C)

[ PER ICEA 640 ]

DURING INSTALLATION – 20 X CABLE O.D.

AFTER INSTALLATION – 10 X CABLE O.D.

* NOTE: TC24TOX: IS ONLY AVAILABLE IN 1000FT. AND 2000FT. REEL SIZES.

TUBE CABLE MARKINGS: THE OUTSIDE SURFACE OF EACH JACKETED CABLE IS MARKED EVERY TWO (2) FEET.

OUTSIDE DIAMETER

INCHES – (mm)

4 - TUBES, HDPE CENTRAL MEMBER, WATER BLOCKING TAPE, RIPCORD,

BLACK POLYETHYLENE OUTER JACKET

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

Revisions: Date:

FULLY SPRINKLERED

A/E:ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HWY S, SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

WSP USA Inc.

33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600

TEL: (206) 431-2300

FAX: (206) 431-2250

PB RDM

COMMUNICATIONS DETAILS

CU504

N/A

100% CONSTRUCTION

DOCUMENTS

BUTLER, PA

EHRM INFRASTRUCTURE

UPGRADES

NOTES:

THIS DIAGRAMMATICAL RISER OVERVIEW DRAWING DEPICTS THE INSTALLATION OF MICRO

TUBE CABLES IN CONDUIT PATHWAYS. ONCE THE MICRO TUBE CABLES ARE INSTALLED,

INDIVIDUAL FIBER CABLES ARE BLOWN OR “JETTED” INTO AN INDIVIDUAL MICRO TUBE, TUBES

ARE COUPLED ALONG THE ROUTE AS REQUIRED, THUS PROVIDING A SINGLE, DEDICATED

PATHWAY FOR END TO END FIBER INSTALLATION FROM MCR TO TR. (NO-SPLICES)

J

J

CEILING SPACE

BUILDING SLAB

INTERIOR SIDE OF

BUILDING WALL

LEVEL 1

(2) 2" EMT

CONDUIT

J

J

CEILING SPACE

CEILING SPACE

LEVEL 2

LEVEL 3

J

J

J

TR ROOM

EXTERIOR SIDE OF

BUILDING WALL

(2) 2" EMT CONDUIT (TYP.)

TO OTHER TR’S

TYP.

TYP.

INTERIOR SIDE OF

BUILDING WALL

BUILDING SLAB

MCR

(2) 4"

GALVANIZED

CONDUIT

4" PVC

CONCRETE

ENCASED

4" PVC

CONCRETE

ENCASED

H HS (2) 4"

GALVANIZED

CONDUIT

BUILDING

GROUND LEVEL

MICRO TUBE (12)

OUTDOOR

TDU

INDOOR TDU

MICRO TUBES ARE “COUPLED” TO COMPLETE

PATHWAYS

MICRO TUBE SPLICE ENCLOSURE

OUTDOOR MICRO TUBE PATHWAY DETAIL (TYP.)D2

CU505 SCALE: NTS

MICRO TUBES

FROM MCR

A ROUTE

1 2

9 10

12 1112 TUBE

4" CONDUIT1

1 2

9 10

12 1112 TUBE

4" CONDUIT

19 TUBE 19 TUBE

x24

INSIDE WALL OF

UNDERGROUND ENCLOSURE

x12

GROUND LEVEL

NOTE:

THIS DRAWING IS A DIAGRAMMATICAL OVERVIEW DEPICTING THE “COUPLING” OF AIR ASSISTED

MICROTUBE CABLES LOCATED IN AN UNDERGROUND ENCLOSURE (HANDHOLE). A CAP IS ALSO

SHOWN FOR PRESERVATION OF SPARE MICROTUBES. THE COUPLING OF MICROTUBES CREATES A

DEDICATED AIRTIGHT, AND WATERTIGHT PATHWAY FROM THE MCR TO THE TR IN TURN ALLOWING

THE SINGLE MODE FIBER OPTIC CABLES TO BE HOMERUN, WITHOUT ANY SPLICE POINTS.

CROSS SECTION VIEW OF

UNDERGROUND ENCLOSURE

x12

FIBER OPTIC CABLE IS TO

BE A CONTINUOUS HOME

RUN FROM MCR TO TR/TE.

NO CROSS-CONNECTS

OR SPLICING SHALL BE

PERMITTED.

1 4 INCH CONDUIT - FROM MCR (TYP)

MICROTUBE CABLE (TYP)

INDIVIDUAL MICROTUBES (AIR & WATER TIGHT)

INDIVIDUAL MICROTUBE COUPLER (AIR & WATER TIGHT)

MICROTUBE MOUNT

4 INCH CONDUIT – TO NEXT ENCLOSURE (TYP)

MINIMUM 4" LIGHT AGGREGATE BOTTOM (TYP)

48" X 60" X 48" UNDERGROUND ENCLOSURE (TYP)

MICROTUBE SPLICE ENCLOSURE (AIR & WATER TIGHT)

MICROTUBE CAP (AIR & WATER TIGHT)

SPARE

SPARE

MICROTUBE COUPLING DETAIL (TYP.)D8

CU505 SCALE: NTS

SEE DETAIL THIS SHEET

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

Revisions: Date:

FULLY SPRINKLERED

A/E:ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HWY S, SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

WSP USA Inc.

33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600

TEL: (206) 431-2300

FAX: (206) 431-2250

PB RDM

COMMUNICATIONS DETAILS

CU505

N/A

100% CONSTRUCTION

DOCUMENTS

BUTLER, PA

EHRM INFRASTRUCTURE

UPGRADES

File details come from the government source that posted it. Updated .