This document is a set of detailed technical drawings for communications infrastructure upgrades at the Butler VA Medical Center, focusing on fiber optic cable installation and pathway design. The drawings (CU501-CU505) provide comprehensive specifications for an Air Assisted Fiber (AAF) micro tube cable system, including outdoor and indoor routing details, building entry configurations, and fiber termination procedures. Key technical specifications include:
The design mandates a continuous home run fiber optic cable pathway from the Main Cross-Connect Room (MCR) to Telecommunications Rooms (TR), with strict prohibitions on cross-connects or splicing. The system utilizes FutureFLEX® dielectric tube cables with various tube configurations (1-24 tubes), designed for outside plant environments with temperature ranges from -40°F to +158°F. The installation involves precise conduit pathways, grounding and bonding requirements, and detailed labeling protocols based on ANSI/TIA-606-C standards, ensuring a robust and standardized telecommunications infrastructure upgrade for the VA medical facility.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE:
1. THIS DIAGRAMMATICAL RISER OVERVIEW DRAWING SHOWS HOW THE CAMPUS WIDE FIBER OPTIC BACKBONE PATHWAYS CONNECT DIFFERENT LOCATIONS WITHOUT CROSSING OR SHARING ROUTES. EACH
BUILDING HAS ITS OWN ENTRANCE POINTS THAT ARE SEPARATE FROM THE OTHERS.
2. THIS DETAIL TO BE REDLINED BY CONTRACTOR.
MCR
BLDG
A
B
A
B
A
B
A
B
A
B
A B
OUTDOOR FIBER RISER DETAIL (TYP.)C2
CU501 SCALE: NTS
MCR
B
BLDG
(1) TR
BLDG
(1) TR
BLDG
(2) TR'S
C
A27/50
26/38
3/12
1/12
D
23/38
E F H
J K L
2/12
1/1 2 1/12
21/38
3/12 1/ 12 1/12
G18/38 2/12
I
16/38
13/19
2/1 2 5/12
6/12
3/12
1/
2/12
1/
1/12
1/12
2/12
NOTE:
1. THIS DRAWING IS A DIAGRAMMATICAL RISER OVERVIEW OF AN OUTDOOR, AIR ASSISTED FIBER (AAF) TUBE CABLE INSTALLATION. SEE AAF TUBE CABLE DETAIL FOR MORE INFORMATION ABOUT TUBE CABLES. THE NUMBER AND PLACE OF EACH SPLICE ENCLOSURE, AND THE NUMBER OF TUBES INSIDE THE TUBE CABLE, ARE ONLY EXAMPLES.
COORDINATE WITH ALL ACTUAL CONDITIONS AND SPECIFICATIONS BEFORE TUBE CABLE INSTALLATION BEGINS, AND ADJUST THE NUMBER, PLACE, AND ROUTE ACCORDINGLY.
2. THIS DETAIL TO BE REDLINED BY CONTRACTOR.
AB H
H
H
H
H
H H
H
H H H H H H
H
TUBES REQUIRED /
SUPPLIED (TYP.)
HAND HOLE SPLICE
ENCLOSURE (TYP.)
BUILDING SERVING HAND
HOLE ENCLOSURE (TYP.)
OUTDOOR AAF TUBE RISER DIAGRAM - A ROUTE (TYP.)C6
CU501 SCALE: NTS
BUILDING ENTRY TYPICAL DETAILF2
CU501 SCALE: NTS
CEILING SPACE
INTERIOR SIDE OF
BUILDING WALL
EXTERIOR SIDE OF
BUILDING WALL
BUILDING SLAB
1. (3) SCHEDULE 40 CONCRETE ENCASED 4" CONDUITS
2. BUILDING FEEDING HAND HOLE (MINIMUM 37"X26"X36")
3. SECURE HAND HOLE COVER MARKED “COMMUNICATIONS”
4. (2) GALVANIZED 4" CONDUIT
5. LOCKABLE STAINLESS STEEL NEMA 4X ENCLOSURE (36"X30"X8")
6. INDOOR SECURE ENCLOSURE (20"X20"X7")
7. (2) EMT 2" CONDUITS
8. MINIMUM 40" FACTORY LONG SWEEPS
9. (2) 2" EMT TO TELCOM (TR) ROOMS
EXISTING GROUND LEVEL
2 1
NOTE:
THIS DRAWING IS A DIAGRAMMATICAL OVERVIEW OF THE BUILDING ENTRY TUBE MICRO DISTRIBUTION UNIT (TDU). OUTDOOR, AIR ASSISTED FIBER (AAF) MICRO TUBE CABLES WILL BE “COUPLED” TO INDOOR AAF MICRO TUBE CABLES WITHIN. THE INDOOR TUBE CABLES WILL BE DISTRIBUTED FROM THE BUILDING ENTRY (TDU) ENCLOSURE TO THE TELCOM ROOM (TR/TE) TDU ENCLOSURE LOCATIONS VIA 2" EMT CONDUIT PATHWAYS. ALL TUBE CABLES TO BE FURCATED, PROTECTED, & NEATLY COILED WITH STRAIN RELIEF PROTECTION TO ENSURE THE TUBE CABLE GROUPS ARE SECURED IN SUCH A WAY THAT THEY WILL NOT BE DAMAGED OR DISTURBED DURING ROUTINE MAINTENANCE OR FUTURE WORK PERFORMED INSIDE OF THE TDU. LABELING AND IDENTIFICATION OF EQUIPMENT, COMPONENTS, AND TELECOMMUNICATIONS CABLING SHALL BE BASED ON ANSI/TIA-606-C,NFPA 70, NATIONAL ELECTRICAL CODE, OR AS MODIFIED BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES.
MAINTAIN MICRO TUBE CABLE BEND RADIUS REQUIREMENTS AT ALL TIMES. END TO END PRESSURE TESTING AND CERTIFICATION TO MANUFACTURES SPECIFICATIONS IS REQUIRED FOR ALL MICRO TUBES BEFORE INSTALLATION OF FIBER OPTIC CABLES MAY BEGIN.
SP
AR
E 4"
SPARE 2"
AC
TI
VE
EXTERIOR WALL
GROUND LEVEL
(2) 4" GALVANIZED
CONDUITS (1 ACTIVE /
1 SPARE) TO BUILDING
FEEDING HAND HOLE
LOCKABLE NEMA 4X
STAINLESS STEEL
ENCLOSURE (36"x30"x8")
TRANSITION TO (2) 2" EMT
CONDUITS (1 ACTIVE / 1
SPARE) TO TR ROOMS
BUILDING ENTRY TDU ENCLOSURE LAYOUT TYPICAL DETAILF6
CU501 SCALE: NTS
BLDG
BLDG BLDG BLDG
BLDGBLDGBLDG
BLDG
BLDG BLDG
BLDG BLDG
BLDG
BLDG
(1) TR
BLDG
(1) TR
BLDG
(1) TR
BLDG
(1) TR
BLDG
(1) TR
BLDG
(1) TR
BLDG
(1) TR
BLDG
(2) TR'S
BLDG
(3) TR'S
BLDG
(5) TR'S
BLDG
(6) TR'S
LA
BE
L
LABEL
INDOOR/OUTDOOR
MICRO TUBE CABLES
FIBER OPTIC CABLE IS TO
BE A CONTINUOUS HOME
RUN FROM MCR TO TR/TE.
NO CROSS-CONNECTS
OR SPLICING SHALL BE
PERMITTED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
7 8 9 10321 4 5 6
Revisions: Date:
FULLY SPRINKLERED
A/E:ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HWY S, SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
WSP USA Inc.
33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
PB RDM
COMMUNICATIONS DETAILS
CU501
N/A
100% CONSTRUCTION
DOCUMENTS
BUTLER, PA
EHRM INFRASTRUCTURE
UPGRADES
529-22-700
10/11/2311/30/23
NOTE:
THIS DRAWING IS A LOGICAL RISER OVERVIEW OF THE IN-BUILDING, 2" EMT CONDUIT INFRASTRUCTURE.
THIS DIAGRAM REPRESENTS ONLY THE “A” SIDE FEED AND DEPICTS ONE POSSIBLE CONDUIT ROUTE BETWEEN THE ENTRY TDU ENCLOSURE AND THE INDIVIDUAL TR ROOMS FOR THE REQUIRED TWO 2" EMT CONDUITS. ALL JUNCTION BOXES, PULL THRU’S, AND 90 DEGREE ELBO’S MUST MEET MIN BEND RATIO REQUIREMENTS, LONG FACTORY SWEEPS (36"- 40") ARE REQUIRED. SEE INDIVIDUAL BUILDING FLOOR PLAN DETAILS FOR MORE SPECIFIC INTERNAL CONDUIT ROUTE INFORMATION. REFER TO THE INDOOR AAF MICRO TUBE COUNT DIAGRAM DETAIL FOR AIR ASSISTED MICRO TUBE CABLE COUNT AND SIZING INFORMATION BETWEEN ENTRY AND TR ROOM SPACES. INDOOR CONDUIT INFRASTRUCTURE ONLY. AIR ASSISTED MICRO TUBE CABLES ARE TO BE PLACED WITHIN (1) OF THE 2" EMT CONDUITS.
TR1 N/A
N/A TR3 TR4
TR6 TR5 N/A
TR7 N/A N/A
LEVEL 00
LEVEL 01
LEVEL 02
LEVEL 03
J
EXAMPLE
BUILDING
ENTRY TDU-A
J
J
J
TR2
(2) 2" EMT
CONDUITS (TYP.)
INDOOR CONDUIT RISER DETAILC2
CU502 SCALE: NTS
NOTE:
THIS DRAWING IS A LOGICAL OVERVIEW OF THE INDOOR AIR ASSISTED FIBER (AAF) MICRO TUBE CABLE REQUIREMENTS FOR THE “A” SIDE FIBER OPTIC BACKBONE ROUTE. THE EXACT COUNT AND ROUTING LOCATION OF EACH INTERNAL MICRO TUBE COUNT SHOWN ARE DIAGRAMMATICAL. COORDINATE EXACT LOCATIONS, AND ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION. ACTIVE MICRO TUBE CABLES ARE TO BE “COUPLED” AT JUNCTION POINTS WITH FACTORY CERTIFIED COUPLERS. MAINTAIN MICRO TUBE CABLE BEND RADIUS REQUIREMENTS AT ALL TIMES. END TO END PRESSURE TESTING AND CERTIFICATION TO MANUFACTURES SPECIFICATIONS IS REQUIRED FOR ALL MICRO TUBES BEFORE INSTALLATION OF FIBER OPTIC CABLES MAY BEGIN. TYPICAL MINIMUM INDOOR MICRO TUBE CABLE SIZING RECOMMENDATION, (1) MICRO TUBE PER TR/TE ROOM SERVED PLUS MIN 50% FUTURE GROWTH.
TR1 TR2 N/A
N/A TR3 TR4
TR6 TR5 N/A
TR7 N/A N/A
LEVEL 00
LEVEL 01
LEVEL 02
LEVEL 03
J
EXAMPLE
BUILDING
ENTRY TDU-A7/19
7/
6/12
5/
1/4
3/
2/7
1/
7/19 (OUTDOOR AAF)
MICRO TUBES REQUIRED
/ SUPPLIED (TYP.)
INDOOR AAF MICRO TUBE COUNT DIAGRAM - A ROUTEC8
CU502 SCALE: NTS
BONDING AND GROUNDING - RISER DETAILF2
CU502 SCALE: NTS
BUILDING
STEEL
BUILDING
STEEL
BUILDING
STEEL
BUILDING
STEEL
LEVEL 0
LEVEL 1
LEVEL 2
1. PRIMARY BONDING BUS BAR (PBB)
2. ELECTRICAL ENTRANCE / GROUNDING ELECTRODE CONDUCTOR (GEC)
3. BUILDING OR STRUCTURAL STEEL
4. ALTERNATING CURRENT EQUIPMENT GROUND (ACEG)
5. EQUIPMENT BONDING CONDUCTOR (6AWG TYP.)
6. IRREVERSIBLE CRIMP CONNECTOR
7. SECONDARY BONDING BUS BAR (SBB)
NOTE:
ALL GROUNDING AND BONDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D
“COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS”, ISO/IEC 30129,NFPA 70, BICSI, AND IN COMPLIANCE WITH
EQUIPMENT MANUFACTURE REQUIREMENTS AND LOCAL CODES. SIZE ALL BONDING
AND GROUNDING CONDUCTORS PER ANSI/TIA 607, ISO/IEC 30129 SPECIFICATIONS.
PRIMARY SECONDARY1
4 5
1. SECONDARY BONDING BUSBAR (SBB)
2. TELECOMMUNICATIONS EQUIPMENT BONDING
CONDUCTOR, (TEBC) MAINTAIN MINIMUM BEND
RADIUS REQUIREMENTS (6AWG TYP.)
3. HORIZONTAL RACK BONDING BUSBAR (RBB)
4. INDIVIDUAL EQUIPMENT BONDING CONDUCTORS
FROM EACH PIECE OF EQUIPMENT. (6AWG TYP.)
5. RACK FLOOR MOUNT ISOLATION PADS (IF REQUIRED)
TO PBB/SBB
NOTE:
ALL GROUNDING AND BONDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D
“COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS”, ISO/IEC 30129,NFPA 70, BICSI, AND IN COMPLIANCE WITH
EQUIPMENT MANUFACTURE REQUIREMENTS AND LOCAL CODES. SIZE ALL BONDING
AND GROUNDING CONDUCTORS PER ANSI/TIA 607, ISO/IEC 30129 SPECIFICATIONS.
BUILDING
STEEL
BONDING AND GROUNDING - TYPICAL RACK / CABINET DETAILF4
CU502 SCALE: NTS
1. SECONDARY BONDING BUSBAR (SBB)
2. TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR, (TEBC)
MAINTAIN MINIMUM BEND RADIUS REQUIREMENTS (6AWG TYP.)
3. IRREVERSIBLE CRIMP CONNECTOR
4. INDIVIDUAL EQUIPMENT BONDING CONDUCTORS. (6AWG TYP.)
TO PBB/SBB
BUILDING
STEEL
NOTE:
ALL GROUNDING AND BONDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D
“COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS”, ISO/IEC 30129,NFPA 70, BICSI, AND IN COMPLIANCE WITH
EQUIPMENT MANUFACTURE REQUIREMENTS AND LOCAL CODES. SIZE ALL BONDING
AND GROUNDING CONDUCTORS PER ANSI/TIA 607, ISO/IEC 30129 SPECIFICATIONS.
TYPICAL COMMUNICATIONS LADDER / CABLE TRAY
BONDING AND GROUNDING - TYPICAL LADDER TRAY DETAILF8
CU502 SCALE: NTS
FIBER OPTIC CABLE IS TO
BE A CONTINUOUS HOME
RUN FROM MCR TO TR/TE.
NO CROSS-CONNECTS
OR SPLICING SHALL BE
PERMITTED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
7 8 9 10321 4 5 6
Revisions: Date:
FULLY SPRINKLERED
A/E:ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HWY S, SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
WSP USA Inc.
33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
PB RDM
COMMUNICATIONS DETAILS
CU502
N/A
100% CONSTRUCTION
DOCUMENTS
BUTLER, PA
EHRM INFRASTRUCTURE
UPGRADES
TR ROOM - BACKBONE FIBER TRAY AND RACK TYPICAL DETAILC1
CU503 SCALE: NTS
1-12 13-24 B A B A B A B A B A B A
25-36 37-48 B A B A B A B A B A B A
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
1. RACK MOUNT FIBER CASSETTE HOLDER
2. 24 FIBER SPLICE CASSETTE
3. RACK MOUNT SPLICE CASSETTE HOLDER
4. (2) 12 STRAND SM CASSETTES (LC FRONT/MPO REAR)
5. (2) 12 FIBER, SM, MPO – FIBER SPLICE PIGTAILS
6. (1) 24 STRAND SM AIR BLOW FIBER (AAF) CABLE (FROM MCR)
7. (1) INDOOR AAF 2 TUBE CABLE
8. INDOOR TUBE DISTRIBUTION UNIT (TDU) ENCLOSURE
9. (2) EMT 2" CONDUITS FROM BLDG ENTRY TDU (1-ACTIVE, 1-SPARE)
10. INDOOR AAF TUBE CABLE FROM BUILDING ENTRY TDU ENCLOSURE
NOTE:
THIS DRAWING IS A HIGH LEVEL OVERVIEW OF A SAMPLE TR ROOM FIBER
TERMINATION DETAIL. RACK MOUNTED ITEMS MAY BE SPACED FOR CLARITY.
FIBER CABLE (#7) TO BE SUPPORTED IN DEDICATED FIBER TRAY FROM TDU
TO RACK. COORDINATE MPO FIBER POLARITY BEFORE INSTALLATION.
TR ROOM - FIBER TERMINATION TYPICAL DETAILC5
CU503 SCALE: NTS
MCR - FIBER TERMINATION TYPICAL DETAIL - A SIDEC8
CU503 SCALE: NTS
NOTE:
THIS DRAWING IS AN OVERVIEW OF THE LABELING REQUIREMENTS FOR THE AIR ASSISTED FIBER
(AAF) TUBE CABLES. LABELING AND IDENTIFICATION OF EQUIPMENT, COMPONENTS, AND
TELECOMMUNICATIONS CABLING SHALL BE BASED ON ANSI/TIA-606-C, ADMINISTRATION
STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE, AND NFPA 70, NATIONAL ELECTRICAL
CODE, OR AS MODIFIED BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR
TELECOMMUNICATIONS SPACES. COORDINATE ALL LABELING SCHEMES PRIOR TO INSTALLATION.
HAND HOLE /
SPLICE ENCLOSURE
(TYP.)
LABEL
LABEL
4" C
O N
D U
IT
4"
C O
N D
U
IT
SP
AR
E
SP
AR
E
METAL CABLE
TIE - 4" LONG
MINIMUM
ROUND EDGES PER
MANUFACTURER
INSTRUCTIONS
SECURE LABELS PER
MANUFACTURER
INSTRUCTIONS
TDU LOCATION
TO BUILDING
FROM TR
FROM BUILDINGTO TR
TO TR
TO TR
TO TR
SAMPLE - TWO
2-TUBE CABLES
B1-FTC19A-056.BB102-057.1B139
C1-FT19.2-056.BB102-57.1B139
C1-FT19.1-056.BB102-057.1B139
C2-FT19.2-056.BB102-057.1B120
C2-FT19.1-056.BB102-057.1B120
LABELING AND DOCUMENTATION DETAIL - TUBE CABLESF1
CU503 SCALE: NTS
NOTE:
THIS DRAWING IS AN OVERVIEW OF THE LABELING REQUIREMENTS FOR THE INDOOR TUBE
DISTRIBUTION UNIT. LABELING AND IDENTIFICATION OF EQUIPMENT, COMPONENTS, AND
TELECOMMUNICATIONS CABLING SHALL BE BASED ON ANSI/TIA-606-C, ADMINISTRATION
STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE, AND NFPA 70, NATIONAL ELECTRICAL
CODE, OR AS MODIFIED BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR
TELECOMMUNICATIONS SPACES. COORDINATE ALL LABELING SCHEMES PRIOR TO INSTALLATION.
LABEL WHERE TUBE
CABLE ENTERS TR ROOM
LABEL AAF INDOOR
TUBE CABLES
LABEL AAF INDOOR
TUBE CABLES
LABEL INDOOR TDU
ENCLOSURE
LABELING AND DOCUMENTATION DETAIL - INDOOR TDUF4
CU503 SCALE: NTS
2 TUBE AAF
MINIMUM ONE
OPEN TUBE IN
EACH TR FOR
FUTURE USE
LABEL WHERE
TUBE ENTERS TR
LABEL CABLE
TUBE PRIOR TO
ENTERING
SPLICE CASE
LABEL EACH
SPLICE CASSETTE
24-STRAND, OS2,
SM FIBER
NOTE:
THIS DRAWING IS AN OVERVIEW OF THE SAMPLE LABELING
REQUIREMENTS. LABELING AND IDENTIFICATION OF
EQUIPMENT, COMPONENTS, AND TELECOMMUNICATIONS
CABLING SHALL BE BASED ON ANSI/TIA-606-C, ADMINISTRATION
STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE,
AND NFPA 70, NATIONAL ELECTRICAL CODE, OR AS MODIFIED
BY GUIDANCE IN THE VA INFRASTRUCTURE STANDARD FOR
TELECOMMUNICATIONS SPACES. COORDINATE ALL LABELING
SCHEMES PRIOR TO INSTALLATION.
LABER EACH MPO CABLE
PRIOR TO CASSETTE/MODULE
FIBER CASSETTE/MODULE WITH
MPO / LC CONNECTION (TYP.),
LABEL PER VA STANDARDS
LABELING AND DOCUMENTATION DETAIL - FINAL TERMINATIONF7
CU503 SCALE: NTS
B A B A B A B A B A B A
B A B A B A B A B A B A
PW
R
D
IS
TR
SW
IT
C
H
IN
G
PA
TC
H
IN
G
#6 AWG
TYP.
FIBER DUCT
ABOVE CEILING
INDOOR TDU
CABLE TRAY
FRONT SIDE
SECONDARY GBB
FIBER DUCT
CABLE
TRAY
INDOOR TDU
TOP
SECONDARY GBB
SECONDARY GBB
TO PRIMARY GBB
NOTE:
THIS DRAWING IS A HIGH LEVEL OVERVIEW OF A SAMPLE TR ROOM LADDER
TRAY AND EQUIPMENT RACK DETAIL. ITEMS MAY BE SPACED FOR DETAIL AND
CLARITY. FIBER CABLE TO BE SUPPORTED IN DEDICATED FIBER DUCT / TRAY
FROM INDOOR WALL MOUNTED TDU ENCLOSURE TO RACK. COORDINATE
EXACT LOCATIONS AND EQUIPMENT SPACING BEFORE INSTALLATION.
MCR - A
42 42
41 41
40 40
39 39 X4 38 38
37 37
36 36
35 35
34 34
33 33
32 32
31 31
30 30
29 29
28 28
27 27
26 26
25 25
24 24
23 23
22 22
21 21
20 20
19 19
18 18
17 17
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
1 1
1. RACK MOUNT FIBER SPLICE & MODULE ENCLOSURE
2. FUSION SPLICE TRAY STORAGE
3. 24 STRAND OS2, SM MODULE (24 LC FRONT/2 MPO REAR)
4. (2) 12 FIBER, SM, MPO – MPO SPLICE PIGTAIL CORD
5. 24 STRAND, OS2, SM FIBER CABLES
6. INDOOR AIR ASSISTED FIBER MICROTUBE CABLES
7. INDOOR TUBE DISTRIBUTION UNIT (TDU) ENCLOSURE (36"X30"X12")
8. (2) EMT 4" CONDUITS FROM BLDG ENTRY TDU (1-ACTIVE, 1-SPARE)
NOTE:
THIS DRAWING IS A HIGH LEVEL OVERVIEW OF A SAMPLE MCR ROOM
FIBER TERMINATION DETAIL. QUANTITIES SHOWN ARE FOR EXAMPLE
ONLY, RACK MOUNTED EQUIPMENT SPACED FOR CLARITY. OUTDOOR AIR
ASSISTED FIBER MICROTUBE CABLES STORED AND COUPLED WITHIN
INDOOR TDU ENCLOSURE. FIBER CABLES (#5) TO BE SUPPORTED IN
DEDICATED FIBER TRAY FROM TDU TO RACK. COORDINATE MPO FIBER
POLARITY AND EXACT EQUIPMENT QUANTITIES BEFORE INSTALLATION.
6 7
3 1 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
7 8 9 10321 4 5 6
Revisions: Date:
FULLY SPRINKLERED
A/E:ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HWY S, SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
WSP USA Inc.
33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
PB RDM
COMMUNICATIONS DETAILS
CU503
N/A
100% CONSTRUCTION
DOCUMENTS
BUTLER, PA
EHRM INFRASTRUCTURE
UPGRADES
AAF MICROTUBE CABLE TYPICAL DETAILF4
CU504 SCALE: NTS
FutureFLEX® TCxxTOX / TCxxTOD DIELECTRIC (OSP) TUBE CABLE SERIES CONSTRUCTION 8mm
6mm
SEL PART NUMBER
TC01TOX
TC07TOX
TC04TOD
TC02TOX
TC12TOX
TC19TOX
TC24TOX
1 - TUBE, WATER BLOCKING TAPE, BLACK POLYETHYLENE OUTER JACKET
2 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE
OUTER JACKET
7 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE
OUTER JACKET
12 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE
OUTER JACKET
19 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE
OUTER JACKET
24 - TUBES, WATER BLOCKING TAPE, RIPCORD, BLACK POLYETHYLENE
OUTER JACKET
PRODUCT DESCRIPTION
0.53 - (13.5)
0.81 - (20.6)
0.94 - (23.9)
1.14 - (29.0)
01.46 - (37.1)
1.77 - (45.0)
2.0 - (50.8)
MAX. WEIGHT
(LBS./KFT..)
REEL F X W (INCHES)
SEL PART NUMBER
TC01TOX
TC04TOD
TC02TOX
TC07TOX
TC12TOX
TC19TOX
* TC24TOX
1000FT.
54 x 16 54 x 16 54 x 16 54 x 32 60 x 42 60 x 42 72 x 45
3000FT.
60 x 42 60 x 42 60 x 42 60 x 42 72 x 45 72 x 45
* 72 x 45
PERFORMANCE
PROPERTY
OPERATION TEMPERATURE RANGE
REFER SEL SPECIFICATION
SF-F04-005 - (TCXXTOX-TOD)
SPECIFICATION
1000FT.
3000FT.
* 36
TUBE CABLE (1000ft. 3000ft.) REEL LENGTHS
MINIMUM DRUM
DIAMETER (INCHES)
EMPTY REEL
WEIGHT (LBS.)
1000FT.
*543
3000FT.
FULL REEL WEIGHT (LBS.)
1000FT.
* 2493
TC19TOX
TC12TOX
16 17
TC24TOX
TC02TOX
HDPE CENTRAL MEMBER
(NOT FOR PULLING)
TC04TOD
3000FT.
RIPCORD
TC07TOX
TC01TOX
WATER BLOCKING TAPE
BLACK TUBE
RIPCORD
23 24
MAX. TENSILE
LOAD (LBS.)
2 3 4
6 5
BLACK
POLYETHYLENE -
UV RESISTANT
OUTER JACKETWATER
BLOCKING TAPE
BLACK
TUBES
ALL DRAWINGS
NOT TO SCALE
DETAIL TYPICAL
CONSTRUCTION
SCALE: 4:1
TUBE CONSTRUCTION: HIGH-PERFORMANCE BLACK POLYETHYLENE. TUBE DIAMETERS: O.D. 8MM, I.D. 6MM TCXXTOX AND TC04TOD: DESIGNED FOR ALL NORMAL OSP ENVIRONMENTS IN DUCT AND IN DIRECT BURIED APPLICATIONS.
TUBE CABLE ENDS: BOTH ENDS OF THE TUBE CABLE ARE ACCESSIBLE ON THE REEL. EACH TUBE IS SEALED WITH A PLASTIC CAP OR
PLUG. TUBE CABLE ENDS ARE SEALED WITH A HEAT SHRINK END CAP.
REEL MARKINGS: THE OUTSIDE OF EACH FLANGE IS MARKED WITH THE SUMITOMO ELECTRIC LIGHTWAVE CORP. PRODUCT PART NUMBER, THE TUBE CABLE MANUFACTURED LENGTH IN FEET, AND THE TEXT “DO NOT LAY FLAT” AND “FORKLIFT FROM FLANGES ONLY.”
BLACK POLYETHYLENE – UV
RESISTANT OUTER JACKET
ALL DRAWINGS
NOT TO SCALE
MINIMUM BEND RADIUS
DURING / AFTER INSTALLATION
-40°F TO +158°F (-40°C TO +70°C)
[ PER ICEA 640 ]
DURING INSTALLATION – 20 X CABLE O.D.
AFTER INSTALLATION – 10 X CABLE O.D.
* NOTE: TC24TOX: IS ONLY AVAILABLE IN 1000FT. AND 2000FT. REEL SIZES.
TUBE CABLE MARKINGS: THE OUTSIDE SURFACE OF EACH JACKETED CABLE IS MARKED EVERY TWO (2) FEET.
OUTSIDE DIAMETER
INCHES – (mm)
4 - TUBES, HDPE CENTRAL MEMBER, WATER BLOCKING TAPE, RIPCORD,
BLACK POLYETHYLENE OUTER JACKET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
7 8 9 10321 4 5 6
Revisions: Date:
FULLY SPRINKLERED
A/E:ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HWY S, SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
WSP USA Inc.
33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
PB RDM
COMMUNICATIONS DETAILS
CU504
N/A
100% CONSTRUCTION
DOCUMENTS
BUTLER, PA
EHRM INFRASTRUCTURE
UPGRADES
NOTES:
THIS DIAGRAMMATICAL RISER OVERVIEW DRAWING DEPICTS THE INSTALLATION OF MICRO
TUBE CABLES IN CONDUIT PATHWAYS. ONCE THE MICRO TUBE CABLES ARE INSTALLED,
INDIVIDUAL FIBER CABLES ARE BLOWN OR “JETTED” INTO AN INDIVIDUAL MICRO TUBE, TUBES
ARE COUPLED ALONG THE ROUTE AS REQUIRED, THUS PROVIDING A SINGLE, DEDICATED
PATHWAY FOR END TO END FIBER INSTALLATION FROM MCR TO TR. (NO-SPLICES)
J
J
CEILING SPACE
BUILDING SLAB
INTERIOR SIDE OF
BUILDING WALL
LEVEL 1
(2) 2" EMT
CONDUIT
J
J
CEILING SPACE
CEILING SPACE
LEVEL 2
LEVEL 3
J
J
J
TR ROOM
EXTERIOR SIDE OF
BUILDING WALL
(2) 2" EMT CONDUIT (TYP.)
TO OTHER TR’S
TYP.
TYP.
INTERIOR SIDE OF
BUILDING WALL
BUILDING SLAB
MCR
(2) 4"
GALVANIZED
CONDUIT
4" PVC
CONCRETE
ENCASED
4" PVC
CONCRETE
ENCASED
H HS (2) 4"
GALVANIZED
CONDUIT
BUILDING
GROUND LEVEL
MICRO TUBE (12)
OUTDOOR
TDU
INDOOR TDU
MICRO TUBES ARE “COUPLED” TO COMPLETE
PATHWAYS
MICRO TUBE SPLICE ENCLOSURE
OUTDOOR MICRO TUBE PATHWAY DETAIL (TYP.)D2
CU505 SCALE: NTS
MICRO TUBES
FROM MCR
A ROUTE
1 2
9 10
12 1112 TUBE
4" CONDUIT1
1 2
9 10
12 1112 TUBE
4" CONDUIT
19 TUBE 19 TUBE
x24
INSIDE WALL OF
UNDERGROUND ENCLOSURE
x12
GROUND LEVEL
NOTE:
THIS DRAWING IS A DIAGRAMMATICAL OVERVIEW DEPICTING THE “COUPLING” OF AIR ASSISTED
MICROTUBE CABLES LOCATED IN AN UNDERGROUND ENCLOSURE (HANDHOLE). A CAP IS ALSO
SHOWN FOR PRESERVATION OF SPARE MICROTUBES. THE COUPLING OF MICROTUBES CREATES A
DEDICATED AIRTIGHT, AND WATERTIGHT PATHWAY FROM THE MCR TO THE TR IN TURN ALLOWING
THE SINGLE MODE FIBER OPTIC CABLES TO BE HOMERUN, WITHOUT ANY SPLICE POINTS.
CROSS SECTION VIEW OF
UNDERGROUND ENCLOSURE
x12
FIBER OPTIC CABLE IS TO
BE A CONTINUOUS HOME
RUN FROM MCR TO TR/TE.
NO CROSS-CONNECTS
OR SPLICING SHALL BE
PERMITTED.
1 4 INCH CONDUIT - FROM MCR (TYP)
MICROTUBE CABLE (TYP)
INDIVIDUAL MICROTUBES (AIR & WATER TIGHT)
INDIVIDUAL MICROTUBE COUPLER (AIR & WATER TIGHT)
MICROTUBE MOUNT
4 INCH CONDUIT – TO NEXT ENCLOSURE (TYP)
MINIMUM 4" LIGHT AGGREGATE BOTTOM (TYP)
48" X 60" X 48" UNDERGROUND ENCLOSURE (TYP)
MICROTUBE SPLICE ENCLOSURE (AIR & WATER TIGHT)
MICROTUBE CAP (AIR & WATER TIGHT)
SPARE
SPARE
MICROTUBE COUPLING DETAIL (TYP.)D8
CU505 SCALE: NTS
SEE DETAIL THIS SHEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD STAMPCONSULTANT
7 8 9 10321 4 5 6
Revisions: Date:
FULLY SPRINKLERED
A/E:ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HWY S, SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
WSP USA Inc.
33301 9th Avenue South Suite 300 Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
PB RDM
COMMUNICATIONS DETAILS
CU505
N/A
100% CONSTRUCTION
DOCUMENTS
BUTLER, PA
EHRM INFRASTRUCTURE
UPGRADES