S02 Attachment 12_0124003 Medical Gas Pressure Drop Calcs_6 Pages.pdf

PDF 79 KB Posted

Attached to
Z2DA--FY26: NRM (PROJ: 548-CSI-139) BB Construction Renovate IR Cath Lab
Solicitation number
36C24826Q0453
Issued by

About this file

This document is a Design Brief containing pressure drop calculations for medical gas systems at WPB IR Cath Lab, Project No. 548-CSI-139, dated 5/9/2025 and prepared by AJZ.

The brief includes six separate pressure drop calculator sheets for different medical gases used in an interventional radiology catheterization lab facility. For Oxygen (55 PSIG system, 51 PSI operating), the calculated pressure drop is 0.434 PSI across three main pipe sections (O1 to ZVB, ZVB, and ZVB to Main) with 1/2-inch piping and 100% diversity factor. Vacuum (19 inhg system, 16 inhg operating) shows a calculated total pressure drop of 0.338 inhg with similar piping sections and 1.0-inch piping. Medical Air (55 PSI system, 51 PSI operating) has a calculated pressure drop of 0.386 PSI using 1/2-inch piping. WAGD (12 inhg system, 7 inhg operating) shows 0.118 inhg pressure drop with 0.75-inch piping. Nitrous Oxide (55 PSI system, 51 PSI operating) indicates 0.227 PSI calculated pressure drop with 1/2-inch piping. Nitrogen (185 PSI system, 201 PSI operating) displays 0.665 PSI calculated pressure drop across four pipe sections with mixed 1/2-inch and 3/4-inch piping, and flows of 10.60 CFM per outlet.

All calculations apply a 1.50 fitting factor, maintain 100% diversity factor across active sections, and stay within allowable pressure drop limits specified for each gas type. The design establishes residual pressure requirements at system endpoints and defines outlet configurations for cardiac catheterization room applications.

View the file

Other files

File Type Posted
S06 Attachment_Updated Price Cost Schedule 4-30-2026_1 Page.docx DOCX document
36C24826Q0453 0003.docx DOCX document
S06 Attachment_Updated Statement of Work_BB 548-CSI-139_04-30-2026_22 Pages.pdf PDF
S06 Attachment_Site Visit Sign In Sheet - 548-CSI-139 Renovate IR CathLab Walk-Through_1 Page.pdf PDF
36C24826Q0453 0002.docx DOCX document
S06 Attachment_548-CSI-139 WPB Renovate IR Cath Lab_Addendum 01_2026-04-24_28 Pages.pdf PDF
S06 Attachment_548-CSI-139 RFI_Responses_7 Pages.pdf PDF
S06 Attachment_Pneumatic Tube Stations Transfer Stations_2 Pages.pdf PDF
S06 Attachment_VA WPB Cath Lab 100 DWGS R1 - 11-17-20_17 Pages.pdf PDF
36C24826Q0453 0001.docx DOCX document
S02 Attachment 25_230923 Direct-Digital Control System for HVAC- rev041326_71 Pages.pdf PDF
S02 Attachment 26_BAS Facility Standards_16 Pages.pdf PDF
S02 Attachment 11_EX 1-AHU-25 Ventilation Calc_1 Page.pdf PDF
S02 Attachment 19_WD FL20260220 dated 01-02-2026_5 pages.pdf PDF
S02 Attachment 05_CD Drawings_100 percent_dated 10.01.2025_548-CSI-139 WPB Renovate IR Cath Lab_71 Pages.pdf PDF
S02 Attachment 04_Cx Plan_100 percent - 548-CSI-139 WPB Renovate IR Cath Lab_55 Pages.pdf PDF
S02 Attachment 24_EMR_1 Page.pdf PDF
S02 Attachment 08_1-AHU-60 Load Calc_1 Page.pdf PDF
36C24826Q0453_1.docx DOCX document
S02 Attachment 18_SLD211033-1 West Palm Beach VA Hybrid_LAYOUT_Rev 4_2 Pages.pdf PDF
S02 Attachment 20_PPQ_4 Pages.pdf PDF
S02 Attachment 09_1-AHU-60 Ventilation Calc_1 Page.pdf PDF
S02 Attachment 10_EX 1-AHU-25 Load Calc_1 Page.pdf PDF
S02 Attachment 22_Base Offer Price Breakdown_1 Page_Excel Form.xlsx XLSX spreadsheet
S02 Attachment 23_VA NOTICE OF LIMITATIONS ON SUBCONTRACTING_2 Pages.pdf PDF
S02 Attachment 06_Narrative_100 percent - 548-CSI-139 WPB Renovate IR Cath Lab_57 Pages.pdf PDF
S02 Attachment 03_Cx Procurement_100 percent - 548-CSI-139 WPB Renovate IR Cath Lab_1 Page.pdf PDF
S02 Attachment 14_2410-08-AVIP_6 Pages.pdf PDF
S02 Attachment 02_Asbestos Report - 548-CSI-139 WPB Renovate IR Cath Lab_36 Pages.pdf PDF
S02 Attachment 07_CD Specifications_100 percent_dated 10.01.2025_548-CSI-139 WPB Renovate IR Cath Lab_897 Pages.pdf PDF
S02 Attachment 21_Price Cost Schedule_1 Page.docx DOCX document
S02 Attachment 15_940537-Submittal-04_45 Pages.pdf PDF
S02 Attachment 13_0124003_100 percent CD Structural Calculations_38 Pages.pdf PDF
S02 Attachment 16_940537-Submittal-05_45 Pages.pdf PDF
S02 Attachment 01_Statement of Work_BB 548-CSI-139_03-31-2026_22 Pages.pdf PDF
S02 Attachment 17_N-SOU240607_3 Pages.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN BRIEF

PROJECT:

PROJECT No: 548-CSI-139

DATE: 5/9/2025

PREPARED BY: AJZ

CHECKED BY:

SUBJECT: Oxygen Pressure Drop Calculator

Type of Gas O2 (55 PSIG)

System Pressure 51 PSI

Allowable PD 1 PSI Calculated PD 0.434 PSI

Max. Desired PD/100 Ft 0.71 PSI

Fitting Factor 1.50

O1 TO ZVB 57.5 86.3 51.00 1.00 2.00 2.00 2.56 100% 5.12 5.12 1/2 0.306 0.264 50.736

ZVB 13 19.5 50.74 0.74 - 2.00 - 100% 0.00 5.12 1/2 0.306 0.060 50.676

ZVB TO MAIN 24 36.0 50.68 0.68 - 2.00 - 100% 0.00 5.12 1/2 0.306 0.110 50.566

- 50.57 0.57 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

- - - 2.00 100% 0.00 5.12 - - 50.566

Pipe Section Length

(Ft)

Effective

Length

Initial

Presssure

(PSI)

Allowable

Pressure

Drop

Section

PSI H

i

P D

A la rm Pressure Drop

WPB IR CATH LAB

Outlets

Added

This Leg

Cumulative

Number

Outlets

Design

Flow

(CFM)

Diversity

Factor

Adjusted

Flow

(CFM)

Total

Adjusted

Flow

Pipe

Size

(in)

Residual

Pressure

PD

PSI per

100 Ft

PROJECT No: 548-CSI-139

DATE: 5/9/2025

PREPARED BY: AJZ

SUBJECT: Vacuum Pressure Drop Calculator

Type of Gas Vacuum (19 inhg)

System Pressure 16 inhg Calculated Total PD 0.338 inhg

Allowable PD 1 inhg

Max. Desired PD/100 Ft 0.75

Fitting Factor 1.50

O1 TO O2 17.75 26.6 16.00 1.00 3.00 Cardiac Catherization Room 0.10 0.30 100% 4.00 4.00 1.00 0.251 0.067 0.933

O2 TO ZVB 38 57.0 15.93 0.93 3.00 Cardiac Catherization Room 0.10 0.30 100% 0.30 4.30 1.00 0.251 0.143 0.790

ZVB 13 19.5 15.79 0.79 - - - - 100% - 4.30 1.00 0.251 0.049 0.741

ZVB TO MAIN 21 31.5 15.74 0.74 - - - - 100% - 4.30 1.00 0.251 0.079 0.662

- 15.66 0.66 - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

- - - - - - 100% - 4.30 - - 0.662

Residual

Pressure

PD

Adjusted

Flow

(CFM)

Total

Adjusted

Flow H i rm Pressure Drop

WPB IR CATH LAB

Pipe Section Length

(Ft)

Effective

Length

Initial

Presssure

(inhg)

Service Count Cumulative

CFM

Diversity

Factor

CFM

per

Outlet

Pipe

Size

(in)

Section inhg inhg

/100 Ft

Outlets

Added

This Leg

Allowable

Pressure

Drop

PROJECT No: 548-CSI-139

DATE: 5/9/2025

PREPARED BY: AJZ

SUBJECT: Medical Air Pressure Drop Calculator

Type of Gas MED AIR (55 PSI)

System Pressure 51 PSI

Allowable PD 1 PSI Calculated PD 0.386 PSI

Max. Desired PD/100 Ft 0.71 PSI

Fitting Factor 1.50

O1 TO ZVB 57.5 86.3 51.00 1.00 2.00 2.00 2.56 100% 5.12 5.12 1/2 0.272 0.235 50.765

ZVB 13 19.5 50.77 0.77 - 2.00 100% 0.00 5.12 1/2 0.272 0.053 50.712

ZVB TO MAIN 24 36.0 50.71 0.71 - 2.00 100% 0.00 5.12 1/2 0.272 0.098 50.614

- 50.61 0.61 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

- - - 2.00 100% 0.00 5.12 - - 50.614

Pipe Section Length

(Ft)

Effective

Length

Initial

Presssure

(PSI)

Allowable

Pressure

Drop

Section

PSI H

i rm Pressure Drop

WPB IR CATH LAB

Outlets

Added

This Leg

Cumulative

Number

Outlets

Design

Flow

(CFM)

Diversity

Factor

Adjusted

Flow

(CFM)

Total

Adjusted

Flow

Pipe

Size

(in)

Residual

Pressure

PD

PROJECT No: 548-CSI-139

DATE: 5/9/2025

PREPARED BY: AJZ

SUBJECT: WAGD Pressure Drop Calculator

Type of Gas WAGD (12 inhg)

System Pressure 7 inhg

Allowable PD 1 inhg Calculated PD 0.118 inhg

Max. Desired PD/100 Ft 0.71 ingh

CFM flow per outlet 1.80 CFM

Fitting Factor 1.50

O1 TO ZVB 57.5 86.3 7.00 1.00 1.00 1.00 1.80 100% 1.80 1.80 0.75 0.083 0.072 6.928

ZVB 13 19.5 6.93 0.93 - 1.00 1.80 100% 0.00 1.80 0.75 0.083 0.016 6.912

ZVB TO MAIN 24 36.0 6.91 0.91 - 1.00 1.80 100% 0.00 1.80 0.75 0.083 0.030 6.882

- 6.88 0.88 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

- - - 1.00 1.80 100% 0.00 1.80 - - 6.882

Cumulative

Number

Outlets

Design

Flow

(CFM)

Diversity

Factor

Adjusted

Flow

(CFM)

Total

Adjusted

Flow

Pipe

Size

(in) H i rm Pressure Drop Residual

Pressure

PD

inhg

/100 Ft

Section inhg

WPB IR CATH LAB

Pipe Section Length

(Ft)

Effective

Length

Initial

Presssure

(inhg)

Allowable

Pressure

Drop

Outlets

Added

This Leg

PROJECT No: 548-CSI-139

DATE: 5/9/2025

PREPARED BY: AJZ

SUBJECT: Nitrous Oxide Pressure Drop Calculator

Type of Gas NO (55 PSI)

System Pressure 51 PSI

Allowable PD 1 PSI Calculated PD 0.227 PSI

Max. Desired PD/100 Ft 0.71 PSI

Fitting Factor 1.50

O1 TO ZVB 57.5 86.3 51.00 1.00 1.00 1.00 1.06 100% 1.06 1.06 1/2 0.160 0.138 50.862

ZVB 13 19.5 50.86 0.86 - 1.00 - 100% 0.00 1.06 1/2 0.160 0.031 50.831

ZVB TO MAIN 24 36.0 50.83 0.83 - 1.00 - 100% 0.00 1.06 1/2 0.160 0.058 50.773

- 50.77 0.77 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

- - - 1.00 100% 0.00 1.06 - - 50.773

Pipe Section Length

(Ft)

Effective

Length

Initial

Presssure

(PSI)

Allowable

Pressure

Drop

Section

PSI H

i rm Pressure Drop

WPB IR CATH LAB

Outlets

Added

This Leg

Cumulative

Number

Outlets

Design

Flow

(CFM)

Diversity

Factor

Adjusted

Flow

(CFM)

Total

Adjusted

Flow

Pipe

Size

(in)

Residual

Pressure

PD

PROJECT No: 548-CSI-139

DATE: 5/9/2025

PREPARED BY: AJZ

SUBJECT: Nitrogen Pressure Drop Calculator

Type of Gas N2 (185 PSI)

System Pressure 201 PSI

Allowable PD 1 PSI Calculated PD 0.665 PSI

Max. Desired PD/100 Ft 0.53 PSI

CFM flow per outlet 10.60

Fitting Factor 1.50

O1 TO ZVB 51 76.5 201.00 1.00 1.00 1.00 10.60 100% 10.60 10.60 1/2 0.419 0.321 200.679

ZVB 13 19.5 200.68 0.68 - 1.00 10.60 100% 0.00 10.60 1/2 0.419 0.082 200.598

ZVB TO MAIN 22 33.0 200.60 0.60 - 1.00 10.60 100% 0.00 10.60 1/2 0.419 0.138 200.459

MAIN TO SOURCE 103.75 155.6 200.46 0.46 - 1.00 10.60 100% 0.00 10.60 3/4 0.080 0.125 200.335

- 200.33 0.33 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

- - - 1.00 10.60 100% 0.00 10.60 - - 200.335

Section

PSI H

i rm Pressure Drop

WPB IR CATH LAB

Outlets

Added

This Leg

Cumulative

Number

Outlets

Design

Flow

(CFM)

Diversity

Factor

Adjusted

Flow

(CFM)

Total

Adjusted

Flow

Pipe

Size

(in)

Residual

Pressure

PD

PSI per

100 Ft

Pipe Section Length

(Ft)

Effective

Length

Initial

Presssure

(PSI)

Allowable

Pressure

Drop