This is a technical HVAC design document containing outside air calculations for a construction project. The document pertains to VA Project Number 548-CSI-139 (Above Group Project Number 0124003) for the VAMC WPB Renovate IR Cath Lab located in West Palm Beach, currently in the 100% Construction Documents phase. The exhibit, designated EX 1-AHU-25, provides HVAC specifications for room 2B-223 TRANSITION AREA, classified as a Semi-Restricted Corridor.
The room specifications are as follows: the space measures 160 square feet with a 9-foot ceiling height and accommodates zero occupants. The minimum outside air requirements are 2 air changes per hour (ACH), translating to 115 CFM of minimum outside air. The design supply CFM is specified at 200 CFM. This data sheet is based on the VA HVAC Design Manual Room Data Sheet standards for room type and name classifications and is served by air handling unit EX 1-AHU-25.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC Outside Air Calculations
VA Project Number: 548-CSI-139
Above Group Project Number: 0124003
Project Name: VAMC WPB Renovate IR Cath Lab
Location: West Palm Beach
Current Phase: 100% Construction Documents
EX 1-AHU-25
Room Name VA HVAC Design Manual Room Data
Sheet: Room Type and Name
Served by
Space
Area (sq.
ft.)
Number of People
Ceiling
Height
(ft)
Min. OA
ACH
Min.
Outside
CFM
Design
Supply
CFM
2B-223 TRANSITION AREA Semi-Restricted Corridor
EX 1-
AHU-25
160 0 9 2 115 200