This is a HVAC Outside Air Calculations document prepared by Above Group for a VA medical facility renovation project. The document details HVAC design specifications for the Interventional Radiology Catheterization Lab renovation at the VA Medical Center in West Palm Beach, currently in the 100% Construction Documents phase (VA Project Number 548-CSI-139, Above Group Project Number 0124003).
The document presents outside air and supply air requirements for five spaces served by Air Handling Unit 1-AHU-60: the Semi-Restricted Area (Room 2B-235) requiring 160 CFM outside air and 200 CFM design supply; the Hybrid Operating Room (Room 2B-237, listed twice) requiring 1,795 CFM outside air and 2,800 CFM design supply; the Transition Area (Room 2B-236) requiring 170 CFM outside air and 225 CFM design supply; and the Hybrid OR Control Room (Room 2B-238) requiring 295 CFM outside air and 375 CFM design supply. Each space designation includes room type classifications per the VA HVAC Design Manual, occupancy parameters, ceiling heights ranging from 9 to 9.5 feet, and minimum outside air changes per hour (ACH) ranging from 2 to 4 based on room function and occupancy. Total minimum outside CFM requirements for the AHU-60 system total 4,215 CFM across all spaces.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC Outside Air Calculations
VA Project Number: 548-CSI-139
Above Group Project Number: 0124003
Project Name: VAMC WPB Renovate IR Cath Lab
Location: West Palm Beach
Current Phase: 100% Construction Documents
1-AHU-60
Room Name VA HVAC Design Manual Room Data
Sheet: Room Type and Name
Served by
Space
Area (sq.
ft.)
Number of People
Ceiling
Height
(ft)
Min. OA
ACH
Min.
Outside
CFM
Design
Supply
CFM
2B-235 SEMI-RESTRICTED
AREA
Semi-Restricted Corridor 1-AHU-60 158 1 9 2 160 200
2B-237 HYBRID OR
ORHY1: Monoplane Hybrid Operating
Room
1-AHU-60 848 3 9.5 4 1795 2800
2B-236 TRANSITION AREA Semi-Restricted Corridor 1-AHU-60 168 2 9 2 170 225
2B-237 HYBRID OR
ORHY1: Monoplane Hybrid Operating
Room
1-AHU-60 848 0 9.5 4 1795 2800
2B-238 CONTROL ROOM ORHC1: Hybrid OR Control Room 1-AHU-60 294 0 9 2 295 375