This document is an Asbestos Re-Inspection Report for the Biloxi Veterans Administration Medical Center in Biloxi, Mississippi. The report was prepared by MECX, LP in accordance with the Asbestos Hazardous Emergency Response Act (AHERA) to re-inspect asbestos-containing building materials (ACBMs) at the site.
The report identifies several areas with significantly damaged ACBM that require immediate abatement and removal, including floor tiles in Buildings 1, 17, and 50. It also notes materials that were previously identified as asbestos-containing but are no longer present, as well as suspect materials recommended for sampling to determine asbestos content. The report recommends that a supplemental AHERA-compliant asbestos survey be conducted covering all buildings on the site. Until then, AHERA surveys should be performed prior to any renovations or demolition that could disturb potential ACM.
View the file
Other files
Show 40 more
Latest 50 of 64 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS RE-INSPECTION
SURVEY REPORT
Biloxi Veterans Administration Medical Center
400 Veterans Avenue Biloxi, MS 39531
MECX Project No.: 1244.007H.00
Prepared for:
VA Gulf Coast Veterans Health Care System 400 Veterans Avenue
Biloxi, MS 39531
May 6, 2008
Prepared by:
Matthew A. Haak
Asbestos Inspector
Bruce E. Oliver, P.E.
Asbestos Consultant
MECX, LP
3203 Audley Street
Houston, Texas 77098 w w w . m e c x . n e t
BILOXI VA MEDICAL CENTER
PRIVILEGED AND CONFIDENTIAL
TABLE OF CONTENTS
Section Page i
1244 007H ST001RESURVEY REPORT(BEO).DOC
1.0 EXECUTIVE SUMMARY
2.0 EPA’S ASSESSMENT CRITERIA
2.1 ACM APPLICATION TYPES
2.2 EPA ASSESSMENT CRITERIA
3.0 HOMOGENOUS AREAS AND LOCATOIONS OF ACBM RE-INSPECTED
4.0 HIGH PRIORITY RESPONSE ACTION AREAS
5.0 ABATED ACBM MATERIALS / MATERIALS NO LONGER PRESENT
6.0 SUSPECT ACBM RECOMMENDED FOR SAMPLING
LIST OF FIGURES
Figure 1 – Site Plan/Vicinity Map
LIST OF APPENDICES
Appendix A: MECX Re-Inspection Forms Appendix B: MECX Evaluation Team Appendix C: MECX Asbestos Consulting Agency License Appendix D: Site Photographs
LIST OF ACRONYMS
� Asbestos Containing Building Materials (ACBM), 4 � asbestos containing materials (ACM), 3 � Asbestos Hazardous Emergency Response Act (AHERA), 3
� MECX, LP (MECX), 3
� thermal system insulation (TSI), 4
1.0 EXECUTIVE SUMMARY
MECX, LP (MECX) has performed an Asbestos Hazardous Emergency Response Act (AHERA) Three Year Asbestos Re-inspection of Biloxi Veterans Administration Medical Center in Biloxi, Mississippi (the Site) in accordance with the proposal dated January 15, 2008 between MECX and the VA Gulf Coast Veterans Health Care System. The asbestos re-inspection process requires a certified accredited asbestos inspector visually re-inspect and reassess the condition of material know to be asbestos containing materials (ACM).
On March 3, 1992 members of Pickering Environmental Consultants along with members of the HAZCLEAN Corporation performed a comprehensive asbestos survey of the Biloxi VA Medical Center. Subsequent asbestos re-inspections have been performed in September 1998, June 2001 and June 2005. MECX conducted the asbestos re-inspection on March 3 & 4, 2008.
MECX’s asbestos inspector was accompanied by Robert Esher, the VA personnel member with best knowledge of the facility and access to all the buildings on the Biloxi VA campus. A summary of the results of MECX’s survey is presented below.
• Significantly Damaged ACM requiring immediate action:
1. Building #1 – 9”x9” Brown floor Tile and associated mastic located in the first floor computer/communication room is showing signs of wear and is beginning to delaminate.
2. Building #18 – There is no documentation that the soil located in the crawl space was sampled and/or removed during the abatement and removal of the asbestos insulation and debris located on the crawl space floor. The crawl space floor is not encapsulated.
3. Building #17 – 9”x9” Gray floor Tile and associated mastic located behind the stage in the second floor room 209 is showing signs wear and is beginning to delaminate.
This tile will break if walked on.
4. Building #10 – 12”X12” Tan floor tile w/ beige modeling located in the Engineering A/C office area is abrading and showing signs of wear in the area were rolling chair are continuously moving across the floor.
5. Building #50 – 12”X12” Tan floor tile w/ beige modeling located in the Engineering grounds office area is abrading and showing signs of wear in the area were rolling chair are continuously moving across the floor.
• Materials Not Present:
During the MECX asbestos re-inspection previously identified as being asbestos containing in the September 1998, June 2001 and June 2005 re-inspections reports that were not observed during the MECX re-inspection and appeared to have been abated and/or removed. A table detailing the materials is presented in Section 5.0 of this report.
• Materials Recommended For Sampling:
MECX asbestos re-inspection identified suspect materials that were not previously identified as being asbestos containing in the September 1998, June 2001 and June 2005 re-inspections reports. Suspect materials not previously identified and recommended by MECX for sampling are detailed in a table presented in Section 6.0 of this report.
• Regulatory Changes
OSHA regulations have changed since the 1992 survey, adding a requirement that building owners determine the location, amount and condition of ACM in their buildings in accordance with AHERA sampling requirements. The previous asbestos surveys do not conform to AHERA sampling requirements.
MECX recommends that a supplemental asbestos survey be conducted covering all buildings on the Site in accordance with AHERA requirements and to the extent possible taking into account the samples already collected in the previous surveys. Until this supplemental comprehensive survey is completed, AHERA surveys should be conducted in any areas where planned renovations or demolition will potentially disturb possible ACM.
Following this Executive Summary, Section 2.0 provides the USEPA’s assessment criteria.
Section 3.0 presents the homogenous areas and locations re-inspected. Section 4.0 presents a summary of high priority response action areas. Section 5.0 presents a summary of homogenous areas and materials that have been abated and are no longer present and Section
6.0 presents suspect materials recommended for sampling.
2.0 USEPA’S ASSESSMENT CRITERIA
2.1 ACM APPLICATION TYPES
ACBMs are divided into the following application types:
1. Thermal system insulation (TSI): Insulation applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.
2. Surfacing Materials: Material that is sprayed-on, troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
3. Miscellaneous Materials: All other asbestos materials, including floor tiles, ceiling tiles, transite board and cloth materials.
2.2 USEPA AHERA ASSESSMENT CRITERIA
This section presents the seven categories formulated by the USEPA for determining the type and condition of ACBM.
1. Friable & Non-Friable: ACMs are classified as either friable or non-friable. Friable ACMs are those that contain more than one percent asbestos and, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. In contrast, non-friable ACMs cannot be crushed with hand pressure.
2. Damaged ACBM: That material which has deterioration, delamination, water damage, lacks cohesion, is blistered, crumbling, gouged, marred heavily, abraded, or is any way has lost its structural integrity over more than 1% but less than 10% of the surface are if the damage is evenly distributed or less than 25%, if the damage is localized in one area of the homogeneous area. Categorized as fair condition.
3. Significantly Damaged ACBM: That material which has deterioration, delamination, water damage, lacks cohesion, is blistered, crumbling, gouged, marred heavily, abraded, or is any way has lost its structural integrity over at least 10% of the surface area if the damage is evenly distributed or at least 25% of the surface if the damage is localized.
Categorized as poor condition.
4. Good Condition ACBM: ACBM with no visual damage or deterioration in less than one percent of the material and/or covering. All ACBM in good condition is considered to have the potential to become damaged.
5. Potential for contact with ACBM material:
a. High – Work is conducted in the vicinity of the material more than once per week and/or the material is in a public area (e.g., hallway, corridor, auditorium) and accessible to building occupants.
b. Moderate – Work is conducted in the vicinity of the material once per month to once per week and/or the material is located in an area not accessible to building occupants.
c. Low – Work is conducted in the vicinity less than once per month and/or the material is visible but not within reach of building occupants
6. Potential for ACBM to have influence of vibration:
a. High – Loud motors or engines present, intrusive noises or easily sensed vibrations.
b. Moderate – Motors or engines present but not obtrusive, occasional loud sounds.
c. Low – None of the above
7. Potential for air erosion:
a. High – High velocity air (e.g. elevator shafts or fan room)
b. Moderate – Noticeable movement of air(e.g., air shaft, ventilator air stream)
c. Low – None of the above
8. ACBM with potential for damage - Pertains to circumstances which:
a. Friable ACBM is in an area regularly used by building occupants, including maintenance workers, currently intact (good) condition.
b. There are indications that there is a reasonable likelihood that the material or its covering will become damaged, deteriorated or delaminated due to factors such as changed in building use, changes in O&M Practice, and changes in occupancy or recurrent damage.
9. ACBM with potential for significant damage - Pertains to circumstances which:
a. Friable ACBM is in an area regularly used by building occupants, including maintenance.
b. Indications that there is a reasonable likelihood that the material or its covering will become damaged, deteriorated or delaminated due to factors such as changed in building use, changes in O&M Practice, changes in occupancy or recurrent damage.
c. The material is subject to major or continuing disturbance, due to factors including but not limited to accessibility or under certain circumstances, vibration or air erosion.
3.0 SUMMARY OF ACBM & LOCATIONS RE-INSPECTED
Bldg
Location of Material HA Material Description Notice of Change and/or Damage
Existing Response
Action
1 1st Floor Computer Room New 9”x9” Floor Tile & Mastic Computer Room
No Change Damaged Tile
Starting To Delaminate
Managed In Place
3 Exterior Panel Walls 01 Transite/Aggregate Panels
Painted w/ Encapsulant
Encapsulated
3 Lab New Interior Lining of Fume Hood Transite Panel
None Managed In Place
3 Lab New Lab Bench Tops None Managed In Place
3 Floor Tile Mastic New Black Mastic None Managed In Place
5 Attic Over Temporary Quarters; Mastic On
Metal Duct Work
08 Brown HVAC Duct Mastic
None; HVAC Duct Work Insulated
Managed In Place
6 Under Carpet Enclosed Porch
01 12”X12” Floor Tile and Mastic
None Managed In Place
7 Enclosed Porch 01 Sheet Vinyl Removed (Wood Floors Now
Present) Building Renovated 2007 -
Removed
7 Living/Dining Rooms 03 Spray Applied Ceiling Surfacing
Removed No Texturing Present
Removed Building
Renovated 2007 -2008
9 Warehouse Doors 01 Fire Doors None Managed In Place
9 Vault Door New Vault Door Near Book Keeping Office
None Managed In Place
10 107A Closet Engineering Survey Closet
11 9”X9” Floor Tile & Mastic
None Managed In Place
10 Engineering A/C Shop Area
10 12”X12” Tan Floor Tile w/ Beige Modeling &
Mastic
Floor Tile Wearing Around Table Area From
Rolling Chairs
Managed In Place
17 2nd Floor Projection Room; Room 215
New 1’X1’ White Acoustical Ceiling Tile
None Managed In Place
Bldg
Location of Material HA Material Description Notice of Change and/or Damage
Existing Response
Action
17 2nd Floor Projection Room Room 215
20 9”X9” Brown Floor Tile & Black Mastic
None Managed In Place
17 Fire Curtain 01 Stage Area None Managed In Place
17 Rooms 209 & 214 Behind Stage Located on 2nd
Floor
06 9”X9” Tan & Gray Floor Tile & Black Mastic
RM 214 Floor Tile Removed Mastic Present; RM 209 Floor Tile Present
& Damaged
None
17 Rooms 103, 109 & 205C 09 9”X9” Tan Floor Tile & Black Mastic
Rooms 109 & 205 Carpet Present
Floor Tile Removed w/
Residual Black Mastic Present;
Room 103 Floor
Tile Remains Under Carpet
Room 103 Floor Tile
Covered With Carpet and Managed In
Place
18 Crawl Space 07, 08, &
Pipe Insulation Removed Insulation No
Longer Present
Building Renovated
19 Room 3A105 10 Brown HVAC Duct Mastic
Covered With Insulation
Managed In Place
21 Rooms 100B & 100C Canteen Dining Floors
12 Brown Sheet Vinyl On Top Of Floor Tile
Removed Building Renovated
49 Beneath House 01 Transite Drain Pipe Removed Building Demolished
50 Engineering Grounds Office Room 4A
05 12”X12” Tan Floor Tile w/ Beige Modeling &
Mastic
Floor Tile Wearing Around Table Area From
Rolling Chairs
Managed In Place
51 Kitchen Area 01 12”X12” Beige Floor Tile w/ Brown Modeling
& Mastic
None Managed In Place
52 Warehouse Cooler Room Ceiling
01 Black Mastic Minor Small Hole In Mastic
Managed In Place
52 Warehouse Office 03 9”X9” Orange Floor Tile & Mastic
Covered w/ 12”X12” White & Gray Floor Tile
Covered Managed In
Place
53 Fire Hose Closet 05 9”X9” Floor Tile & Mastic
Floor Tile Not Observed In Fire
Closet Near
Removed Mastic Present
Bldg
Location of Material HA Material Description Notice of Change and/or Damage
Existing Response
Action
Room 1A106 Mechanical Room Had Black Mastic
Under Carpet
53 Attic HVAC Ducts 11 Brown HVAC Duct Mastic
Covered With Insulation
Managed In Place
53 Room 1A134 Storage New Floor Tile Not Found N/A
54 Office Area Under Carpet 03 Brown 9”X9” Floor Tile and Mastic
Not Observed In Areas Inspected
Under Carpet Residual Mastic
Observed In Some Locations
Potentially Removed
54 Office Area Under Carpet 04 Blue/Green 9”X9” Floor Tile and Mastic
Not Observed In Areas Inspected
Under Carpet Residual Mastic
Observed In Some Locations
Potentially Removed
4.0 HIGH PRIORITY RESPONSE ACTION AREAS
MECX conducted the asbestos re-inspection on March 3 & 4, 2008. MECX based the re-inspection on a comprehensive asbestos survey of the Biloxi VA Medical Center dated March 3, 1992 performed members of Pickering Environmental Consultants along with members of the HAZCLEAN Corporation. Subsequent asbestos re-inspections have been performed in September 1998, June 2001 and June 2005 by Micro Methods. The materials below were observed during the survey to be significantly damaged and MECX recommends that they be properly removed:
Bldg
Location of
Material Material
Description Condition Comments Recommended
Response Action Taken
01 1st Floor Computer
Room
9”x9” Floor Tile & Black Mastic
Significantly Damaged
Floor tile showing signs of wear and is beginning to delaminate
Remove
10 Engineering A/C Office
Area
12”X12” Tan Floor
Tile w/ Beige
Mottling
Damaged Floor tile abrading and showing signs of wear in the areas were rolling chairs are continuously moving across the floor
Repair and Manage In
Place
17 2nd Floor Behind Stage Rooms 209 &
9”X9” Tan & Gray
Floor Tile & Black Mastic
Significantly Damaged
Floor tile showing signs of wear appears brittle and is beginning to delaminate.
Floor tile will break if walked on.
Remove
18 Crawl Space Soil N/A There is no documentation that the soil located in the crawl space was sampled and/or removed during the abatement and removal of the asbestos insulation and debris located on the crawl space floor. The crawl space floor is not encapsulated.
Sample and Base
Response Upon Data Collected
50 Engineering Grounds
Office
12”X12” Tan Floor
Tile W/ Beige
Mottling
Damaged Floor tile abrading and showing signs of wear in the areas were rolling chairs are continuously moving across the floor
Repair & Manage In
Place
5.0 ABATED/REMOVED ACBM MATERIALS / MATERIALS NO LONGER PRESENT
MECX conducted the asbestos re-inspection on March 3 & 4, 2008. MECX based the re-inspection on a comprehensive asbestos survey of the Biloxi VA Medical Center dated March 3, 1992 performed members of Pickering Environmental Consultants along with members of the HAZCLEAN Corporation. Subsequent asbestos re-inspections have been performed in September 1998, June 2001 and June 2005 by Micro Methods. The following materials were previously identified as contain asbestos were not observed and appeared to be abated and/or removed:
Location of Material Material Description Comments
07 Under Carpet In The Enclosed Porch Area
Tan Sheet Vinyl In 2007 Building #7 was abated and completely renovated and replaced with new building materials.
07 Living/Dining Area Ceilings
Sprayed Applied Ceiling Texture
In 2007 Building #7 was abated and completely renovated and replaced with new building materials.
17 Rooms # 214 9”X9” Floor Tile Floor tile has been removed;
however, residual mastic is still present.
17 Rooms # 109 & 205 9”X9” Floor Tile Floor tile has been removed;
however, residual mastic is still present.
21 Dining Room Floor Brown Sheet Vinyl Flooring On Top Of
Green Floor Tile
Building #21 has been completely renovated and all ACM have been abated and replaced with new building materials.
49 Drain Pipe Transite Drain Pipe Building #49 has been demolished.
53 Fire Closet 9”X9” Floor Tile The floor tile located in the fire closet was not observed and appears to have been removed.
However, black mastic was observed beneath the carpet in the office areas and 12”x12” floor tile. In September 2007, the black mastic located beneath the carpet and floor tile throughout Building #3 was sampled by Micro- Methods and determined to be asbestos containing. The floor tile mastic in Building #3 was previously thought to be negative.
Bldg
Location of Material Material Description Comments
54 Beneath Carpet Brown 9”X9” Floor Tile & Mastic
9”X9” floor tile and mastic was not observed in the areas inspected beneath the carpet. Residual mastic was observed in various locations beneath the carpet.
54 Beneath Carpet Blue/Green 9”X9” Floor Tile & Mastic
9”X9” floor tile and mastic was not observed in the areas inspected beneath the carpet. Residual mastic was observed in various locations beneath the carpet.
6.0 SUSPECT ACBM RECOMMENDED FOR SAMPLING
MECX conducted the asbestos re-inspection on March 3 & 4, 2008. The following materials were not previously identified as containing asbestos in the September 1998, June 2001 and June 2005 re-inspections reports. MECX observed the following suspect materials not previously identified and recommends sampling the following materials:
Location of Material Material Description Comments
01 Beneath Carpeting & Floor Tile Throughout
Building #1
Black Mastic Black floor tile mastic was observed beneath the carpeting and floor tile throughout Building #1. In September 2007, the black mastic located beneath the carpet and floor tile throughout Building #3 was sampled by Micro- Methods and determined to be asbestos containing. The floor tile mastic in Building #3 was previously thought to be negative. MECX recommends sampling the floor tile & mastic in this building do determine if the building materials are asbestos containing.
07 Exterior Siding Un-Known What’s Under Vinyl Siding
MECX recommends investigating the siding material located beneath the vinyl siding.
08 Exterior Siding Un-Known What’s Under Vinyl Siding
MECX recommends investigating the siding material located beneath the vinyl siding.
17 1st Floor Lobby & Hallway
2nd Floor Hallway
9”x9” Green & Lime Floor Tile (1st floor lobby/hallway) & 9”x9” Tan Floor Tile (2nd floor hallway)
9”x9” green and lime floor tile was observed in the 1st floor lobby/hallway and 9”x9” tan floor tile located in the 2nd floor hallway that was not identified in the previous re-inspection reports.
MECX recommends sampling the floor tile & mastic in these areas to determine if the building materials are asbestos containing.
Bldg
Location of Material Material Description Comments
18 Crawl Space Soil There is no documentation that the soil located in the crawl space was sampled and/or removed during the abatement and removal of the asbestos insulation and debris located on the crawl space floor. The crawl space floor is not encapsulated. MECX recommends sampling located in the crawl space to determine if it was impacted by the historic ACM debris.
53 Beneath The Carpeting & Floor Tile Throughout
Building #53
Black Mastic Black floor tile mastic was observed beneath the carpeting and floor tile throughout Building #53. In September 2007, the black mastic located beneath the carpet and floor tile throughout Building #3 was sampled by Micro- Methods and determined to be asbestos containing. The floor tile mastic in Building #3 was previously thought to be negative. MECX recommends sampling the floor tile & mastic in this building to determine if the building materials are asbestos containing.
53 Break Area Near Director’s & Assistant
Director’s Office
Yellow/Beige 12”X12 Floor Tile
MECX observed Yellow/Beige 12”X12” floor tile in a break area near the Directors and Assistant Directors offices that was not previously identified in the earlier re-inspection reports. MECX recommends sampling the floor tile & mastic in this area to determine if the building materials are asbestos containing.
57 Connecting Hallway Between Canteen and
Building #57
Yellow 12”X12” Floor Tile
MECX did not re-inspect Building #57 and the connecting hallway between the Canteen and Building #57 as part of this re-inspection. MECX recommends re-inspecting this building and connecting hallway for suspect ACM.
FIGURE
3203 Audley Street Houston, TX 77098 www.mecx.net
SITE MAP
Biloxi, VA
VA Gulf Coast Veterans Health Care System
400 Veterans Avenue Biloxi, MS 39531 Project Number
1244.007H.00
APPENDIX A
MECX RE-INSPECTION FORMS
Asbestos Re-Inspection Biloxi/Gulfport VA Medical Center
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
250 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Discription of ACBM: Building #1 Computer/Communication Room Brown 9"x9"
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
9"X9" Brown Floor Tile
Building/Unit/Room # Building #1 First Floor
Computer/Communication Room New
X Suspect ACM floor tile. The floor tile appears worn and is delaminating.
Non-Friable
Monitor Regulary Abate & Remove
Air Erosion
Good
Limit access to room until material can be removed.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
X
Low Medium High
X X
Significantly Damaged
X
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
MECX recomends sampling the floor tile and mastic
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High throughout Building #1.
Suspect ACM Non-Friable
X Monitor Regulary Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Black Floor Tile Mastic
Building/Unit/Room # Floors Throughout NA
Location/Discription of ACBM: Suspect black floor tile mastic located throughout builidng.
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material
X X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
N/A
Potential For Damage From:
(check box/boxes that apply)
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
142,609 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Discription of ACBM: Transite aggregate exterior panel walls. Exterior walls were
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Transite Exterior Wall Panels
Building/Unit/Room # Building #3 Exterior Panels 1
X Suspect ACM just recently encapsulated with thick white paint/sealer.
Non-Friable
X Monitor Regulary Abate & Remove
Air Erosion
Good
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
X Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
100,000 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Black floor tile mastic located throughout building.
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Black Floor Tile Mastic
Building/Unit/Room # Building #3 Entire Building NA
X Suspect ACM Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good carpet and floor tile throughout Building #3 was sampled by Micro-Methods and determined to be asbestos containing. The floor tile mastic in Building #3 was previously thought to be negative. The floor tile and associated mastic needs to be added to the O&M and 3-year re-inspection list.
In September 2007, the black mastic located beneath the
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
36 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Transite panel located inside the chemical fume hood in the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Transite Panel
Building/Unit/Room # Building #3/Lab Hood New
X Suspect ACM lab.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM of Building #3.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Lab Bench Tops
Building/Unit/Room # Building #3/Lab
X
Location/Description of ACBM: Black asbestos containing lab bench tops located in the lab
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
N/A
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
None
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM attic. The HVAC ducts are insulated with fiberglass TSI.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Brown HVAC Duct Mastic
Building/Unit/Room # Building #5 8
X
Location/Description of ACBM: Brown mastic located on the HVAC metal duct work in the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
N/A
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
None
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #6 1
X
Location/Description of ACBM: Beneath carpet on the floor of the enclosed porch
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
250 ft2
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. N/A
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
mastic has been abated and removed. The enclosed porch in now covered with wood flooring, (check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
N/A
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: The floor tile and mastic was historically located on the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material N/A
Low Medium High
Re-Inspected ACBM:
Floor Tile and Mastic
Building/Unit/Room # Building #7 1
N/A Suspect ACM enclosed porch. Building #6 has been completely renovated and the asbestos floor tile and
Non-Friable
N/A Monitor Regularly Abate & Remove
Air Erosion
Good present.
Floor tile and mastic have been abated and are no longer
N/A
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
N/A N/A
Significantly Damaged
N/A
N/A Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc.
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
containing materials have been abated and removed. The ceilings in the living/dining rooms are smooth with no texturing and appear to be new sheetrock materials.
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
5000 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: The spray applied ceiling material was historically located on
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material N/A
Low Medium High
Re-Inspected ACBM:
Spray Applied Ceiling Material
Building/Unit/Room # Building #7 3
N/A N/A
Suspect ACM the living/dining room ceilings. Building #7 has been completely renovated; all asbestos
Non-Friable
N/A Monitor Regularly Abate & Remove
Air Erosion
Good removed.
Spray applied ceiling materials have been abated and
N/A
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
N/A N/A
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Fire Doors
Building/Unit/Room # Building #9 New
X
Location/Description of ACBM: Building #9 warehouse fire doors.
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Vault door located adjacent to the book keeping office.
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Vault Door
Building/Unit/Room # Building #9 New
X Suspect ACM Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
Manage in place
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM
Survey closet, Room 107A.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #10/Room 107A 11
X
Location/Description of ACBM: Beige 9"X9" floor tile and mastic located in the Engineering
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
200 ft2
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
the tile. The chair appear to be abrading the floor tile.
X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: 12"X12" Tan/Brown floor tile and mastic located in the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #10/Engineering Shop 10
X Suspect ACM
Engineering A/C shop. The floor tile is showing signs wear of rolling chairs rolling on top of
Non-Friable
Monitor Regularly Abate & Remove
X
Air Erosion
Good degrading the integrity of the tile. The tile needs to be resealed with a good wax on a regular schedule or a protective mat needs to be placed in areas of rolling chair. Abatement of the floor tile is an more costly option.
The rolling chairs are wearing the floor tile down and
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly
Damaged X
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
The ceiling tiles did not appear to be transite as described in
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High the previous re-inspection report. MECX recommends re-sampling the ceiling tiles to determine if the ceiling tile are asbestos containing.
Suspect ACM projection room, Room #215.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Ceiling Tile
Building/Unit/Room # Building #17/Room #215 New
X X
Location/Description of ACBM: White 1'X1' acoustical ceiling tile located in the second floor
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
240 ft2
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
250 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Gray/Tan 9"X9" floor tile and mastic located in the second
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #17/Room #215 20
X Suspect ACM floor projection room, Room #215.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM
The floor tile and mastic appears to have been abated, removed and replaced with new carpet.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #17/Rooms 103, 109 & 205 9
X
Location/Description of ACBM: Rooms 109 & 205 no floor tile and/or black mastic present.
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Room #103 tan 9"x9"and associated mastic remains beneath the carpet.
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
Room #103 (500 ft2)
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
500 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: MECX observed tan/beige 9"X9" floor tile and associated
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material
X X
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #17/Second Floor Hallway N/A
Suspect ACM mastic in the Building #17 second floor hallway that was not identified in the previous reports.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good the floor tile and mastic is asbestos containing. If the floor tile and mastic are found to contain asbestos the floor tile and mastic should be added to the O&M and asbestos materials to be re-inspected every three years.
MECX recommends sampling the floor tile to determine if
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
MECX recommends sampling the floor tile to determine if
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High the floor tile and mastic is asbestos containing. If the floor tile and mastic are found to contain asbestos the floor tile and mastic should be added to the O&M and asbestos materials to be re-inspected every three years.
Suspect ACM mastic in the Building #17 first floor hallway that was not identified in the previous reports.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #17/Second Floor Hallway N/A
Location/Description of ACBM: MECX observed green/lime 9"X9" floor tile and associated
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material
X X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
500 ft2
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc.
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
Damaged
X X
Abate and remove damaged floor tile and associated
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
X
Low Medium High mastic.
Suspect ACM the stage on the second floor on each side of the stage. Room #214 the floor tile has been
Non-Friable
Monitor Regularly Abate & Remove
X
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #17/Rooms 209 & 214 6
Location/Description of ACBM: Gray 9"X9" floor tile and associated mastic located behind
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material removed, however, the mastic remains. Room #209 the floor tile is present and showing signs of wear and the tile is delaminating and becoming brittle.
X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
200 ft2
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
200 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Fire Curtain
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Fire Curtain
Building/Unit/Room # Building #17/Auditorium/Stage 1
X Suspect ACM Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc.
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
MECX recommends sampling the soil in the crawl space to
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High determine the impact if any from the friable TSI & debris that was located in the crawl space.
If maintenance work is required in the crawl space, maintenance worker should wear proper PPE, until sampling has indicated that the soil is not impacted with ACM. If the soil is impacted with ACM, approximately 8"-12" of soil should be removed from the crawl space and the remaining soil should be encapsulated with concrete.
Suspect ACM
Building 18. The asbestos insulation has been abated and removed along with any debris
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
TSI
Building/Unit/Room # Building #18/Crawl Space 7,8,9
X X
Location/Description of ACBM: TSI/pipe insulation located in the crawl space beneath
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing MaterialX located on the dirt floor of the crawl space. TSI was observed on some piping in the crawl space, however, it appear to be new TSI.
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
700 ln/ft
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
120 ln/ft
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Brown HVAC mastic located on the metal duct work in
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
HVAC Duct Mastic
Building/Unit/Room # Building #19/ Room 3A105 Attic 19
X Suspect ACM the attic Room 3A105of Building #19. The duct work was insulated with fiberglass insulation.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. N/A
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
N/A
N/A Damaged
N/A N/A
ACM have been abated and removed.
N/A
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM
The brown sheet vinyl on top of green floor tile has been abated, removed and replaced with
Non-Friable
N/A Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic, Sheet Vinyl
Building/Unit/Room # Building #21/Canteen Dining Room
Rooms #100B & 100C
N/A
Location/Description of ACBM: The Canteen dining room has been completely renovated
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material N/A new 12"X12" floor tile.
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
N/A
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. N/A
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Building #49 has been demolished and removed.
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material N/A
Low Medium High
Re-Inspected ACBM:
Transite Drain Pipe
Building/Unit/Room # Building #49/Beneath House 1
N/A Suspect ACM Non-Friable
N/A Monitor Regularly Abate & Remove
Air Erosion
Good
Site.
Building #49 has been demolished and removed from the
N/A
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
N/A N/A
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
Damaged X
X X
The rolling chairs are wearing the floor tile down and
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High degrading the integrity of the tile. The tile needs to be resealed with a good wax on a regular schedule or a protective mat needs to be placed in areas of rolling chair. Abatement of the floor tile is an more costly option.
Suspect ACM
Engineering Building #50, Grounds Shop Office, Room 4A showed signs of wear and
Non-Friable
Monitor Regularly Abate & Remove
X
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #50/Engineering/Room
4A/Grounds Shop Office
X
Location/Description of ACBM: Tan 12"X12" floor tile with brown modeling located in the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X determination from rolling chairs abrading the surface of the tile.
X
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
100 ft2
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
150 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Tan 12"X12" floor tile with brown modeling located in the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #51/Kitchen 1
X Suspect ACM kitchen area of Building 51.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
500 ft2
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: Black tar mastic located on the ceiling and cooler lining in the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Low Medium High
Re-Inspected ACBM:
Black Tar Mastic
Building/Unit/Room # Building #52/Former Cooler Area Ceiling
& Cooler Lining
X Suspect ACM former cooler room in Bulding#52. Some small holes were observed in the ceiling mastic.
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
X X
Significantly Damaged
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
Significantly Damaged
X
X Damaged
X X
Manage in place.
X
Action Recommended For ACBM: (check box/boxes that apply)
Manage In Place
Low Medium High
Suspect ACM office area of Building #52. The orange floor tile has been covered with new 12"X12" floor
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #52/Office Area 3
X
Location/Description of ACBM: Orange 9"X9" floor tile and associated mastic located in the
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material X
Tile.
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
150 ft2
Inspector: Matthew Haak Date: 2-26-08 - 2-27-08
HA
1. ACM
2. Friable
3. TSI Misc. X
ACBM Condition Assessment : (check box/boxes that apply)
Additional Recommendations:
beneath the new 12"X12" floor tile throughout the building.
(check box/boxes that apply)
Contact Vibration
Total Disturbance Potential:
N/A
Potential For Damage From:
(check box/boxes that apply)
Location/Description of ACBM: MECX did not observe 9"X9" floor tile in the fire hose closets
Define Material Observed: (check box/boxes that apply)
4. Approximant Quantified Amount of ACBM: (ft 2 , ln/ft, ft 3 )
Surfacing Material
X X
Low Medium High
Re-Inspected ACBM:
Floor Tile & Mastic
Building/Unit/Room # Building #53/Fire Hose Closet 5
X Suspect ACM inspected. MECX did observe black mastic in the fire hose closets, beneath the carpets and
Non-Friable
X Monitor Regularly Abate & Remove
Air Erosion
Good hose closet. MECX did observe black mastic in the fire hose closets, beneath the new carpets and new 12"x12" floor tile. MECX recommends sampling the black mastic to if it is asbestos containing. If the mastic is found to be ACM, the mastic needs to be added to the O&M and 3 year re-inspection list.
MECX was unable to locate the 9"X9" floor tile in the fire
X
Action…