Drawings - Telecommunication.pdf

PDF 4 MB Posted

Attached to
Biloxi Building 1 Renovation - Biloxi, MS -- Y1DA
Solicitation number
QSE--36C10F24R50025
Issued by

About this file

This document appears to be a set of drawings related to the renovation of Building 1 at the Biloxi, MS VA Medical Center. The drawings provide detailed information on the telecommunications, information technology, and security systems that will be installed as part of the renovation project.

The key details include:

  • Renovation of Building 1 at the Biloxi, MS VA Medical Center
  • Scope includes selective demolition, exterior envelope alterations, and interior renovation of floors 3-5
  • Upgrades to HVAC, plumbing, electrical, telecommunications, chilled water, and fire protection systems
  • Structural, mechanical, and electrical work related to the 3rd floor structure within the occupied 2nd floor areas
  • Monitoring of the existing building foundation by a qualified consultant
  • Project duration of 912 calendar days from the Notice to Proceed
  • Estimated project magnitude between $50M to $100M
  • Wage Rate Requirements (Construction) apply

The drawings provide extensive detail on the telecommunications and security infrastructure, including riser diagrams, device locations, conduit routing, and cabling requirements.

View the file

Other files

File Type Posted
S02_Solicitation Amendment 0003.pdf PDF
C28_02821319 TILE AND MASTIC AND BRICK COATING ABATEMENT.pdf PDF
C28_02833313 LEAD PAINT REMOVAL.pdf PDF
P12_AE Addendum Two.pdf PDF
SolicitationAmendment0004.pdf PDF
P03_Justification and Approval - TekTone Nurse Call System - revised 05.24.24.pdf PDF
P12_Asbestos Report - 01.03.2022.pdf PDF
SolicitationAmendment0003.pdf PDF
52.219-28 Post-Award Small Business Program Rerepresentation.pdf PDF
Wage Determination - Harrison County MS.pdf PDF
QSE 36C10F24R50025.pdf PDF
P12_Asbestos Report - 07.06.2017.pdf PDF
S05_RFI Questions and Answers.pdf PDF
P12_Lead Based Paint Analysis - Bldg 1 - 01.11.2017.pdf PDF
S02_117300 CEILING MOUNTED PATIENT LIFTS - Revised.pdf PDF
P12_Asbestos Report - 05.06.2008.pdf PDF
P12_Addendum 1 - 05.14.2024.pdf PDF
S04_Biloxi Bldg 1 Reno - Pre-Proposal Conference Attendees.pdf PDF
SolicitationAmendment0002.pdf PDF
SolicitationAmendment0001.pdf PDF
QSE 36C10F24R50025.pdf PDF
Wage Determination - Harrison County MS.pdf PDF
52.219-28 Post-Award Small Business Program Rerepresentation.pdf PDF
Drawings - Architectural - 3.pdf PDF
General Contractor Reference Form.docx DOCX document
Drawings - Architectural - 4.pdf PDF
Drawings - Reference.pdf PDF
VA Biloxi 4th Floor Footwall.pdf PDF
Drawings - Architectural - 1.pdf PDF
Building 1 Inventory - d.pdf PDF
Adec Submittal - VA Biloxi.pdf PDF
Drawings - Electrical - 2.pdf PDF
LOCQ7780-03-SWS-Biloxi VA Dental Lab.pdf PDF
Justification and Approval - Siemens Security and Video Surveillance System.pdf PDF
Past Performance Questionnaire.docx DOCX document
A-dec Floor Plan - VA Biloxi - Elevations.pdf PDF
Drawings - Structural - 2.pdf PDF
Specifications Volume II.pdf PDF
Biloxi VA Reno B1 - Set H.pdf PDF
Drawings - Plumbing - 1.pdf PDF
Drawings - Structural - 1.pdf PDF
VA Biloxi Patient Room Footwall Typical Elevation.pdf PDF
Justification and Approval - Herman Miller Compass Patient Care Modular System.pdf PDF
Solicitation.pdf PDF
000000 Cover Page Appendix.pdf PDF
Justification and Approval - ESTIII Fire Alarm System.pdf PDF
Drawings - General.pdf PDF
A-dec Floor Plan - VA Biloxi - Preliminary.pdf PDF
Drawings - Mechanical - 2.pdf PDF
Drawings - Plumbing - 2.pdf PDF
Show 40 more

Latest 50 of 64 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T V

T V

C R

C

C

M D

L

P B

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V T

V

CR

C R

CR

C R

CR

M D

L

M D

L

MDL

M D

L

PB

PB

PB

PB

PB

MDL

S

S S

S

S S

S

S S

S

S S SS

S S

S

S

S

S S

S S

S

S S

S S

SS S

S

S S

S

S

SS S

S

S

S

S

S S

S S

S S

S

S

S

S S

S

S S

S

S S

S S

S

S S

S S

S S

S S

S

S

S

S

S

S

S S

S

S S

S S

S S

S

S

S SS

S

S S

S

S

S S

S S

S

S

S

S S

S

S SS S

S S

S

S

S

S

S

S SS S S SS SSS SS

S

S

S SS

S

S

S

S

S

S

S

S S

S

S S S

S

S S

C

PB

CR

M D

L

E

PATIENT ROOM 1

3B114

PATIENT ROOM 2

3B116

PATIENT ROOM 3

3B118

PATIENT ROOM 4

3B119

CLEAN EQUIPMENT STORAGE

3B121

MD DICTATION

3B122

PATIENT ROOM 5

3B123 PATIENT ROOM 6

3B124

WHEELCHAIR ALCOVE

3B102

ELECTRICAL ROOM

3B101

PATIENT CENTERED CARE

3B103

MEDICAL GAS STORAGE

3B104

CRASH CART

3B105

HAC

3B106

CLEAN UTILITY

3B107

CLEAN LINEN

3B108

KINESIOTHERAPY

3B109

WEST STAIR

3B110

PATIENT ROOM 7 - NEGATIVE

PRESSURE

3B111

UNASSIGNED

3B113

PATIENT BATHROOM

3B111A

ANTE ROOM

3B111B

PATIENT BATHROOM

3B114A

PATIENT BATHROOM

3B118A

PATIENT BATHROOM

3B119A

PATIENT BATHROOM

3B123A

PATIENT BATHROOM

3B124A

CORRIDOR

C3-104

CENTRAL STAIR

3A101

MALE TOILET

3A102

FEMALE TOILET

3A103

FAMILY TOILET

3A104

WAITING / LOUNGE

3A105FAMILY CONSULTATION

3A106

MECHANICAL SHAFT

3A107

SOILED LINEN

3A110

ENGINEERING

3A111

HEAD NURSE / ASSISTANT MANAGER

3A112

MEDICATION ROOM

3A114

NOURISHMENT STATION

3A115

PATIENT ROOM 8

3A117

PATIENT ROOM 9

3A118

MD DICTATION

3A120

IMD SUPPLY STORAGE

3A121

PATIENT ROOM 10

3A122

PATIENT ROOM 11

3A123

BARIATRIC PATIENT ROOM 12

3A125

CONFERENCE / REPORT ROOM

3A128

PATIENT BATHROOM

3A117A PATIENT BATHROOM

3A118A

PATIENT BATHROOM

3A122A PATIENT BATHROOM

3A123A

BARIATRIC PATIENT BATHROOM

3A125A

HAC

3A127

TELEMETRY

3A130

BARIATRIC PATIENT BATHROOM

3A131A

BARIATRIC PATIENT ROOM 13 - NEG.

PRESS.

3A131

ANTE ROOM

3A131B

EAST STAIR

3A133

PHARMACY CUBICLES

3A134

MALE LOCKERS

3A137

STAFF TOILET

3A136

STAFF SHOWER

3A135

CORRIDOR

3A141

STAFF LOUNGE

3A138

FEMALE LOCKERS

3A139

TELECOMM

3A140

SOILED UTILITY

3A142

NURSE STATION

3A109A

CORRIDOR

C3-105

CORRIDOR

C3-103

NURSE SERVER

3A124

CORRIDOR

C3-109

NURSE SERVER

3A132

CORRIDOR

C3-101

NURSE SERVER

3B112

NURSE SERVER

3B125

CORRIDOR

C3-107

NURSE SERVER

3A126NURSE SERVER

3A119

NURSE SERVER

3B120NURSE SERVER

3B117

NURSE SERVER

3B115

NURSE STATION

3A109

PATIENT BATHROOM

3B116A

TYP

TYP

REV

ALIGN ALIGN

FEC

FEC

FEC

3RD

FLOOR

2ND

FLOOR

1ST

FLOOR

3RD

FLOOR

2ND

FLOOR

1ST

FLOOR

3RD

FLOOR

2ND

FLOOR

1ST

FLOOR

NOTE: SEE SHEET "IN101" FOR INTERIOR ELEVATION REFERENCE

CORRIDOR

C3-100

CORRIDOR

C3-102

CORRIDOR

C3-102A

CORRIDOR

C3-106

CORRIDOR

C3-107A

CORRIDOR

C3-108

222019181716151413121110987654321 21

A

B

C

D

E

F

G

18"x4"

SIGNAGE

72"

TDM

TDMTDM

T T T T T T T T T T T T T T T T T T T T T T

T

+18"

TN101

TN101

WAP

WAP

WAP

WAPWAP

WAP

WAP

72"

72"

72"72" 72" 72"

72"

72" 72"

72" 72"

72" 72" 72" 72"

T

72"

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

N L

N d

N d

N d

N

N

NN

L

N L

N L

N d

N d

N d N c

N z

N z

N d

N s

N a

Na

N2J

NP

NRk

N s

N s N s

N a N a

N s N s

Na Na

N s N s

N a N a

N s N s

Na N a

N a

N L

N s

N s

N a

N d

Ns

Na

N L

N d

N d

N L

N L

N L

N L

N L

N L

N L

N L N

L N

L

W

W

N

N 2J

N a

N c

N ct

N d

N L

N P

N Rk

N s

N z

PULL CORD-EMERGENCY

2-JACK ISOLATED INPUTS FOR AUZILIARY ALARMS THAT ARE

COMPATIBLE WITH VARIOUS 1/4" JACK COMPATIBLE MEDICAL

INSTRUMENTS.

AUDIO EMERGENCY PULL CORD.

NURSE CONSOLE.

NC2828 HEAD END CABINET.

DUTY STATION CONTROLLED BY DOMELESS CONTROLLER ABOVE

CEILING.

CORRIDOR LIGHT VISUAL INDICATOR FOR THE NURSE CALL.

ENHANCED SINGLE PATIENT STATION WITH STAFF ASSIST AND CODE BLUE.

BED RECEPTACLE INDUSTRY STANDARD 37 PIN BED RECEPTACLE KIT.

PULL CORD STATION EMERGENCY PULL CORD STATION(SHOWER).

CORRIDOR LIGHT VISUAL ZONE INDICATOR FOR THE NURSE CALL.

NURSE CALL LEGEND:

WAP

(TYP.)

TN101

TN101

+38"

+83"

+18"

+38" +83"

N 2J

N P

N Rk

+48" +48"

(TYP.)

N2J

NP

NRk N2J

NP

NRk

N 2J

N P

N Rk

N2J

NP

NRk

N 2J

N P

N Rk

N2J

NP

NRk

N 2J

N P

N Rk

N 2J

N P

N Rk N2J

NP

NRk

N 2J N P

N RkN2J

NP

NRk

18"x4" 18"x4"18"x4"18"x4"

"x

N pm ROUGH-IN FOR FUTURE PATIENT MONITORING SYSTEM

N pmN pmN pm N pm

N pm N pm

N pm N pm N pm N pm N pm

N pm N pm

NOTE - ALL NURSE CALL DEVICES SHALL BE TEKTONE TO MATCH EXISTING CAMPUS NURSE CALL SYSTEM.

TCS

T D

M

T D

M T

D M

N c

T D

M

TELECOMM

3A140

D

RACK

RACK

N ct

N ct

4'X8' AC

RATED PLYWOOD

BACKBOARD

TGB

12"x4"

TELECOMM

3A140

D

"x

"x

12"x4"

"x

"1

"x

" 10' AFF

9' AFF

10' AFF

18"x4"

12"x4"

4'X8' AC RATED

PLYWOOD BACK

BOARD

(2) 4" CONDUIT

TGB

12"x4"

"x

9' AFF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

C R e v it L o c a l F ile s \I C

T

B

L D

G

E le c tr ic a l C

D S

M a tt h e w

.L .G rz o v ic

.r v t

/1 /2

:2

:4

P M

TN101

3RD FLOOR - TELECOM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 MATGRZ SIDROY

231 238

1/8" = 1'-0"TN101

1 3RD FLOOR - TELECOM

1/4" = 1'-0"TN101 TN101

2 3RD FLOOR - TELECOM ROOM - LARGE SCALE PLAN

1/4" = 1'-0"TN101 TN101

3RD FLOOR - TELECOM ROOM - LARGE SCALE CEILING

PLAN

KEYED NOTES:

1. ELECTRICAL CONTRACTOR TO SUPPLY

CONDUIT AND BOXES ONLY FOR

SECURITY SYSTEM.

2. PROVIDE 4' X 8' X 3/4" A-C GRADE FIRE-

RATED PLYWOOD BACKBOARD ALL

WALLS IN COMM ROOM. EXPOSED SIDE

SHALL BE SMOOTH. PAINT BLACK

LEAVING FIRE RATING MARKINGS

VISIBLE. VERIFY PAINT COLOR WITH VA

AND REFER TO ARCHITECTURAL FOR

MORE INFORMATION.

3. ROUGH-IN FOR FUTURE PATIENT

MONITORING. PROVIDE ONE (1) 1-1/4"

CONDUIT FROM ACCESSIBLE CEILING

ABOVE HEADWALL TO THE CORRIDOR

CABLE TRAY TERMINATED WITH NYLON

BUSHING. COORDINATE FINAL

LOCATION IN THE FIELD WITH

RESIDENT ENGINEER.

4. OUTLET HEIGHTS INDICATED ARE

TYPICAL FOR ALL PATIENT ROOMS ON

THIS SHEET.

5. PROVIDE HDMI CABLING AND

CONNECTIVITY FROM TV OUTLET TO

PC. COORDINATE PC LOCATION WITH

RESIDENT ENGINEER PRIOR TO

INSTALLATION.

6. TWO (2) 4" SLEEVES.

GENERAL NOTES:

1. REFER TO E001 FOR COMMUNICATIONS

SYMBOLS LIST.

2. REFER TO 1/TN202 FOR ACCESS

CONTROL RISER DIAGRAM.

3. REFER TO 2/TN202 FOR VIDEO

SURVEILLANCE RISER DIAGRAM.

4. REFER TO 3/TN202 FOR INFORMATION

OUTLET ROUGH-IN DETAIL.

5. REFER TO 4/TN202 FOR BONDING RISER

DIAGRAM.

6. REFER TO TN202 FOR INFORMATION

OUTLET SCHEDULE.

7. CONTRACTOR SHALL REMOVE ANY AND

ALL ABANDONED CONDUIT BACK TO THE

SOURCE.

8. GC TO PROVIDE

PATHWAY/INFRASTRUCTURE AND

TELEMETRY WIRELESS NETWORK TO

SUPPORT VA PROCUREMENT OF

PATIENT MONITORING EQUIPMENT.

9. ALL CABLE SHALL BE IN CONDUIT.

CONDUITS CONTAINING NETWORK

CABLING SHALL BE CONNECTED TO THE

CABLE TRAY. NO J-HOOKS SHALL BE

ALLOWED.

10. COORDINATE OFCI AND CFCI

TELEPHONE AND DATA EQUIPMENT

WITH VA BILOXI OI&T.

11. COORDINATE OFCI AND CFCI CABLE

TELEVISION DISTRIBUTION EQUIPMENT

WITH VA BILOXI OI&T.

1/4" = 1'-0"TN101 TN101

3RD FLOOR - FMS/SECURITY ROOM - LARGE SCALE

PLAN 1/4" = 1'-0"TN101 TN101

3RD FLOOR - FMS/SECURITY ROOM - LARGE SCALE

CEILING PLAN

Revisions: Date:

C

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V T V

T V

T V

T V

T V

C R

C

M D

L

P B

T V

CR

C R

C R

C R

CR

M D

L

MDL

M D

L

MDL

M D

L

P B

PB

P B

PB

PB

CR

M D

L

C

PB E

PATIENT ROOM 1

4B114

PATIENT ROOM 2

4B116

PATIENT BATHROOM

4B116A

PATIENT BATHROOM

4B114A

PATIENT BATHROOM

4B118A

PATIENT BATHROOM

4B119A

PATIENT ROOM 3

4B118

PATIENT ROOM 4

4B119

CLEAN EQUIPMENT STORAGE

4B121

MD DICTATION

4B122

PATIENT ROOM 5

4B123

PATIENT BATHROOM

4B123A

PATIENT BATHROOM

4B124A

PATIENT ROOM 6

4B124 ENGINEERING

4A111

SOILED LINEN

4A110

STAFF EDUCATION

4A112

MEDICATION ROOM

4A114

NOURISHMENT STATION

4A115

PATIENT ROOM 8

4A117

PATIENT BATHROOM

4A117A

PATIENT BATHROOM

4A118A

PATIENT ROOM 9

4A118

IMD SUPPLY STORAGE

4A121

MD DICTATION

4A120

PATIENT ROOM 10

4A122

PATIENT BATHROOM

4A122A

PATIENT BATHROOM

4A123A

PATIENT ROOM 11

4A123

BARIATRIC PATIENT ROOM 12

4A125

BARIATRIC PATIENT BATHROOM

4A125A

CONFERENCE / REPORT ROOM

4A128

BED STORAGE

4A130BARIATRIC PATIENT BATHROOM

4A131A

BARIATRIC PATIENT ROOM 13 - NEG.

PRESS.

4A131

M.O.D. ROOM

4A134

EAST STAIR

4A133

STAFF TOILET

4A136

STAFF SHOWER

4A135

MALE LOCKERS

4A137

STAFF LOUNGE

4A138

FEMALE LOCKERS

4A139

TELECOMM

4A140

SOILED UTILITY

4A142

CORRIDOR

4A141

ANTE ROOM

4A131B

CENTRAL STAIR

4A101

MALE TOILET

4A102

FEMALE TOILET

4A103

FAMILY TOILET

4A104

FAMILY CONSULTATION

4A106

MECHANICAL SHAFT

4A107

CORRIDOR

C4-104

WAITING / LOUNGE

4A105

ELECTRICAL ROOM

4B101

PATIENT CENTERED CARE

4B103

MEDICAL GAS STORAGE

4B104

CRASH CART

4B105

HAC

4B106

CLEAN UTILITY

4B107

CLEAN LINEN

4B108

KINESIOTHERAPY

4B109

WHEELCHAIR ALCOVE

4B102

WEST STAIR

4B110

PATIENT ROOM 7 - NEGATIVE

PRESSURE

4B111

PATIENT BATHROOM

4B111A

UNASSIGNED

4B113

ANTE ROOM

4B111B

CORRIDOR

C4-103

NURSE STATION

4A109A

CORRIDOR

C4-105

CORRIDOR

C4-101

CORRIDOR

C4-107

NURSE SERVER

4B120

NURSE SERVER

4B125

NURSE SERVER

4A119

NURSE SERVER

4A124

NURSE SERVER

4A132

NURSE SERVER

4B112

HAC

4A127

NURSE SERVER

4B115

NURSE SERVER

4B117

NURSE SERVER

4A126

M.O.D. BATHROOM

4A134A

CORRIDOR

C4-109

NURSE STATION

4A109

DENTAL VAC CLOSET

4B100A

SIM

TYP

FEC

FEC FEC

NOTE: SEE SHEET "IN102" FOR INTERIOR ELEVATION REFERENCE

CORRIDOR

C4-100

CORRIDOR

C4-102

CORRIDOR

C4-102A

CORRIDOR

C4-106

CORRIDOR

C4-107A

CORRIDOR

C4-108

222019181716151413121110987654321 21

A

B

C

D

E

F

G

N L

N d

N d

N d

N d

N

N

N N

L

N L

N L

N d

N d

N d

N c

N z

N z

N

N 2J

N a

N c

N ct

N d

N L

N P

N Rk

N s

N z

PULL CORD-EMERGENCY

2-JACK ISOLATED INPUTS FOR AUZILIARY ALARMS THAT ARE

COMPATIBLE WITH VARIOUS 1/4" JACK COMPATIBLE MEDICAL

INSTRUMENTS.

AUDIO EMERGENCY PULL CORD.

NURSE CONSOLE.

NC2828 HEAD END CABINET.

DUTY STATION CONTROLLED BY DOMELESS CONTROLLER ABOVE

CEILING.

CORRIDOR LIGHT VISUAL INDICATOR FOR THE NURSE CALL.

ENHANCED SINGLE PATIENT STATION WITH STAFF ASSIST AND CODE BLUE.

BED RECEPTACLE INDUSTRY STANDARD 37 PIN BED RECEPTACLE KIT.

PULL CORD STATION EMERGENCY PULL CORD STATION(SHOWER).

CORRIDOR LIGHT VISUAL ZONE INDICATOR FOR THE NURSE CALL.

SIGNAGE

72"

TDM

TDMTDM

T T T T T T T T T T T T T T T T T T T T T T

T

N d

TN102

TN102

WAP

WAP

WAP

WAPWAP

WAP

N s

N a

N a

N s

72"

72"

N s N s

N a N a

72" 72"

N s N s

N a N a

72" 72"

N s N s

N a N a

72"72"

N s N s

N a N a

72" 72"

N a

N L

72"

N s

N s

N a

N d

72"

Ns

Na

N L

N d

72"

72"

72"

N d

T

WAP WAP

WAPWAP

WAP

WAP

WAP

WAP

WAP WAP

WAP

WAP

WAP

WAP

WAP

72"

N L

N L N

L N

L N

L N

L N

L N

L N

L N

L

W W

(TYP.)

TN102

TN102

+18" N2J

NP

NRk

+38"

+83"

+18" +38"

+83" +48" +48"

(TYP.)

N2J

NP

NRk N 2J

N P

N Rk

N2J

NP

NRk

N 2J

N P

N Rk

N2J

NP

NRk

N 2J

N P

N Rk

N2J

NP

NRk

N 2J

N P

N Rk

N2J

NP

NRk

N 2J

N P

N Rk

N 2J

N P

N RkN2J

NP

NRk

"x

12"x4" 12"x4"

"x

12"x4" 12"x4" 12"x4"

"x

12"x4" 12"x4"

N pm

N pm N pm

N pm N pm N pm N pm

N pm N pm N pm N pm

N pm

N pm

N pm ROUGH-IN FOR FUTURE PATIENT MONITORING SYSTEM.

NURSE CALL LEGEND:

NOTE - ALL NURSE CALL DEVICES SHALL BE TEKTONE TO MATCH EXISTING CAMPUS NURSE CALL SYSTEM.

TELECOMM

4A140

4A

SIM

"x

12"x4"

12"x4"

"x

"x

"x

12"x4"

"x

'A

F F9

'A F

F

9'AFF

10'AFF

'A

F F

'A

F F

TELECOMM

4A140

4A

SIM

RACK

RACK 12"x4"

TGB

(2) 4" CONDUIT

4'X8' AC RATED

PLYWOOD BACK

BOARD

TGB

12"x4"

"x

"x

9' AFF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

C R e v it L o c a l F ile s \I C

T

B

L D

G

E le c tr ic a l C

D S

M a tt h e w

.L .G rz o v ic

.r v t

/1 /2

:2

:5

P M

TN102

4TH FLOOR - TELECOM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 MATGRZ SIDROY

232 238

1/8" = 1'-0"TN102

1 4TH FLOOR - TELECOM

1/4" = 1'-0"TN102 TN102

2 4TH FLOOR - TELECOM - LARGE SCALE CEILING PLAN

1/4" = 1'-0"TN102 TN102

3 4TH FLOOR - TELECOM - LARGE SCALE PLAN

KEYED NOTES:

1. ELECTRICAL CONTRACTOR TO SUPPLY

CONDUIT AND BOXES ONLY FOR

SECURITY SYSTEM.

2. PROVIDE 4' X 8' X 3/4" A-C GRADE FIRE-

RATED PLYWOOD BACKBOARD ALL

WALLS IN COMM ROOM. EXPOSED SIDE

SHALL BE SMOOTH. PAINT BLACK

LEAVING FIRE RATING MARKINGS

VISIBLE. VERIFY PAINT COLOR WITH VA

AND REFER TO ARCHITECTURAL FOR

MORE INFORMATION.

3. ROUGH-IN FOR FUTURE PATIENT

MONITORING. PROVIDE ONE (1) 1-1/4"

CONDUIT FROM ACCESSIBLE CEILING

ABOVE HEADWALL TO THE CORRIDOR

CABLE TRAY TERMINATED WITH NYLON

BUSHING. COORDINATE FINAL

LOCATION IN THE FIELD WITH

RESIDENT ENGINEER.

4. OUTLET HEIGHTS INDICATED ARE

TYPICAL FOR ALL PATIENT ROOMS ON

THIS SHEET.

5. PROVIDE HDMI CABLING AND

CONNECTIVITY FROM TV OUTLET TO

PC. COORDINATE PC LOCATION WITH

RESIDENT ENGINEER PRIOR TO

INSTALLATION.

6. TWO (2) 4" SLEEVES.

GENERAL NOTES:

1. REFER TO E001 FOR COMMUNICATIONS

SYMBOLS LIST.

2. REFER TO 1/TN202 FOR ACCESS

CONTROL RISER DIAGRAM.

3. REFER TO 2/TN202 FOR VIDEO

SURVEILLANCE RISER DIAGRAM.

4. REFER TO 3/TN202 FOR INFORMATION

OUTLET ROUGH-IN DETAIL.

5. REFER TO 4/TN202 FOR BONDING RISER

DIAGRAM.

6. REFER TO TN202 FOR INFORMATION

OUTLET SCHEDULE.

7. CONTRACTOR SHALL REMOVE ANY AND

ALL ABANDONED CONDUIT BACK TO THE

SOURCE.

8. GC TO PROVIDE

PATHWAY/INFRASTRUCTURE AND

TELEMETRY WIRELESS NETWORK TO

SUPPORT VA PROCUREMENT OF

PATIENT MONITORING EQUIPMENT.

9. ALL CABLE SHALL BE IN CONDUIT.

CONDUITS CONTAINING NETWORK

CABLING SHALL BE CONNECTED TO THE

CABLE TRAY. NO J-HOOKS SHALL BE

ALLOWED.

10. COORDINATE OFCI AND CFCI

TELEPHONE AND DATA EQUIPMENT

WITH VA BILOXI OI&T.

11. COORDINATE OFCI AND CFCI CABLE

TELEVISION DISTRIBUTION EQUIPMENT

WITH VA BILOXI OI&T.

1/4" = 1'-0"TN102 TN102

4TH FLOOR - FMS/SECURITY ROOM - LARGE SCALE

PLAN

1/4" = 1'-0"TN102 TN102

4TH FLOOR - FMS/SECURITY ROOM - LARGE SCALE

CEILING PLAN

T V

T V

C

CR

C

M D

L

PB

TV

SS

SS

T V

M D

L

CRCR

PBPB

MDL

PB C

R

C R

T V T V

S SS

S S

S

SS S

S S

S

S SS S

S

S S

S S

S

S

S

S

S S

S

S S

S

S

S S

S

SS

SS

S S

S S

S S

S

S

S

S

S S

S

S

S S

S

SS S

SS S

S S

S

S S

S S

S SS

S SS

J

C

FS

CR

M D

L

C

PB

S S

S

S

S

S

S

ES

S

S

S

S

S

S

IMD SUPPLY

5B122 PANORAMIC X-RAY

5B123 STERILE INSTR. STORAGE

5B128

SOILED UTILITY

5B130

EQUIPMENT STORAGE

5B135

UNISEX TOILET

5B136

DENTIST WORKSTATIONS

5B129

OPERATORY TREATMENT GENERAL

AREA

5B131

HAC

5A110

ENGINEERING

5A111

STAFF LOUNGE

5A112

MALE TOILETS / LOCKERS

5A113

FEMALE TOILETS / LOCKERS

5A114SCRUBS DISTRIBUTION

5A108

CRASH CART

5A115

PHYSICIANS CUBICLES

5A117

FILE ROOM

5A118

COPY ROOM

5A119

OFFICE

5A120

SUPPLY STORAGE

5A121

DIRECTORS CONFERENCE ROOM

5A122

MENS TOILET ROOM

5A124

CORRIDOR

C5-109

WOMENS TOILET ROOM

5A126

HAC

5A127EAST STAIR

5A128

STAFF LOUNGE

5A130

OFFICE

5A131

CUBICLES

5A134

OFFICE

5A132

OFFICE

5A133

TELECOMM

5A135

CENTRAL STAIR

5A101

FAMILY TOILET

5A102

MEDICAL CONFERENCE

5A103

DENTAL CONFERENCE

5A105

MECHANICAL SHAFT

5A106

LOBBY / LOUNGE

C5-105

ELECTRICAL ROOM

5B102

WAITING

5B103

RECEPTION / SECRETARY

5B104

COPY ROOM

5B105

DENTAL SERVICE CHIEF OFFICE

5B106

MEDICATION ROOM

5B109

AO OFFICE

5B107

WEST STAIR

5B111

TOILET ROOM

5B112

SOILED UTILITY

5B114

CORRIDOR

C5-104A

CORRIDOR

C5-104

CORRIDOR

C5-107ACORRIDOR

C5-102C

CORRIDOR

C5-106

CORRIDOR

C5-103

OPERATORY TREATMENT GENERAL

AREA

5B115

SHIPPING/ RECEIVING ROOM

5B110

DENTAL TREATMENT ROOM 1

5B116

DENTAL TREATMENT ROOM 2

5B117

DENTAL TREATMENT ROOM 3

5B118

DENTAL TREATMENT ROOM 4

5B119

DENTAL TREATMENT ROOM 6

5B121

DENTAL TREATMENT ROOM 7

5B125

DENTAL TREATMENT ROOM 8

5B126

DENTAL TREATMENT ROOM 10-

SPECIAL NEEDS

5B132

DENTAL TREATMENT ROOM 11

5B133

DENTAL TREATMENT ROOM 12

5B134

DENTAL LAB

5B113

PIPE ACCESS

5A125

DECONTAMINATION AREA

5B115A

TYP TYP

REV

REV

SIM

TYP

TYP

FEC

FEC

SOLID SURFACE

CAP (S-1)

SIM SIM

SIM, REV

NOTE: SEE SHEET "IN103" FOR INTERIOR ELEVATION REFERENCE

CORRIDOR

C5-102A

CORRIDOR

C5-102B

CORRIDOR

C5-102C

DENTAL TREATMENT ROOM 9 -

SPECIAL NEEDS

5B127

DENTAL TREATMENT ROOM 5

5B120

CORRIDOR

C5-102

CORRIDOR

C5-101

CORRIDOR

C5-107

CORRIDOR

C5-108

FEC

222019181716151413121110987654321 21

A

B

C

D

E

F

G

SIGNAGE

72"

T T T T T T T T T T T

T T T T T T T T T T

T

T

TN103

TN103

WAP WAP

WAP

WAP

WAP

WAP

WAP

72"

72"

72"

N

N

N c

72"

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP WAP

WAP

WAPWAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

12"x4" 12"x4" 12"x4"

TV

EP202

N

N 2J

N a

N c

N ct

N d

N L

N P

N Rk

N s

N z

PULL CORD-EMERGENCY

2-JACK ISOLATED INPUTS FOR AUZILIARY ALARMS THAT ARE

COMPATIBLE WITH VARIOUS 1/4" JACK COMPATIBLE MEDICAL

INSTRUMENTS.

AUDIO EMERGENCY PULL CORD.

NURSE CONSOLE.

NC2828 HEAD END CABINET.

DUTY STATION CONTROLLED BY DOMELESS CONTROLLER ABOVE

CEILING.

CORRIDOR LIGHT VISUAL INDICATOR FOR THE NURSE CALL.

ENHANCED SINGLE PATIENT STATION WITH STAFF ASSIST AND CODE BLUE.

BED RECEPTACLE INDUSTRY STANDARD 37 PIN BED RECEPTACLE KIT.

PULL CORD STATION EMERGENCY PULL CORD STATION(SHOWER).

CORRIDOR LIGHT VISUAL ZONE INDICATOR FOR THE NURSE CALL.

N

TN103

TN103

"x

T

N pm ROUGH-IN FOR FUTURE PATIENT MONITORING SYSTEM.

AV AV

AV

AV

AV

+72"

+72"

+44"

+84"

12"x4" 12"x4"

N L

N L

J J J J J

J J

10 10 10 10 10

10 10

NURSE CALL LEGEND:

NOTE - ALL NURSE CALL DEVICES SHALL BE TEKTONE TO MATCH EXISTING CAMPUS NURSE CALL SYSTEM.

+81"

WWW

W

W

W

W

W

W

+72" 9 +72"

TELECOMM

5A135

5A

"x

"x

"x

12"x4"

"x

12"x4"

12"x4"

' A

F F

' A

F F

9' AFF

10' AFF 1

' A

F F

' A

F F

TELECOMM

5A135

5A

RACKRACK

1TGB12

ENGINEERING

5A111

CORRIDOR

C5-104A

(2) 4" CONDUIT

4'X8' AC RATED

PLYWOOD BACK

BOARD

PERSONNEL

DURESS SYS.

NETWORK

SWITCH

SECURITY

CONTROL PANEL

TGB

ENGINEERING

5A111

CORRIDOR

C5-104A

"x

"x

"12"x4" 9' AFF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

C R e v it L o c a l F ile s \I C

T

B

L D

G

E le c tr ic a l C

D S

M a tt h e w

.L .G rz o v ic

.r v t

/1 /2

:2

:0

P M

TN103

5TH FLOOR - TELECOM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 MATGRZ SIDROY

233 238

1/8" = 1'-0"TN103

1 5TH FLOOR - TELECOM

1/4" = 1'-0"TN103 TN103

2 5TH FLOOR - TELECOM - LARGE SCALE CEILING PLAN

1/4" = 1'-0"TN103 TN103

3 5TH FLOOR - TELECOM - LARGE SCALE PLAN

KEYED NOTES:

1. ELECTRICAL CONTRACTOR TO SUPPLY

CONDUIT AND BOXES ONLY FOR

SECURITY SYSTEM.

2. PROVIDE 4' X 8' X 3/4" A-C GRADE FIRE-

RATED PLYWOOD BACKBOARD ALL

WALLS IN COMM ROOM. EXPOSED SIDE

SHALL BE SMOOTH. PAINT BLACK

LEAVING FIRE RATING MARKINGS

VISIBLE. VERIFY PAINT COLOR WITH VA

AND REFER TO ARCHITECTURAL FOR

MORE INFORMATION.

3. INSTALL 2"X4" J-BOX AND ROUTE ONE

1" CONDUIT BACK TO A 2"X4" J-BOX AT

PANORAMIC X-RAY MACHINE.

4. ROUGH-IN FOR AV CONTROL PANEL.

PROVIDE JUNCTION BOX (10"H X 10"W X

4.00"D) WITH THE FOLLOWING AV

CONNECTIVITY: SIX (6) FEMALE HDMI

BULKHEAD; SEVEN (7) FEMALE RCA

BULKHEAD AUDIO PAIRS (RED AND

WHITE); SIX (6) FEMALE XLR

BULKHEADS; AND FOUR (4) FEMALE 15-

PIN HD SUB D FOR VGA. INSTALL BOX

AT +40" AFF. COORDINATE BULKHEAD

LAYOUT WITH RESIDENT ENGINEER

PRIOR TO INSTALLATION.

5. AV CONNECTIVITY FOR VTEL. PROVIDE

DEEP 2-GANG BACKBOX (4.21"H X

4.06"W X 4.00"D) WITH (1) 1", 1-1/4",

1-1/2", 2" KNOCKOUT, (2) 1/2"

KNOCKOUTS AND (4) 1/2"-3/4"

KNOCKOUTS. PROVIDE FOUR (4)

NETWORK DROPS; TWO (2) FEMALE

HDMI BULK HEAD CONNECTORS; AND

TWO (2) FEMALE RCA BULK HEAD

CONNECTORS (ONE RED, ONE WHITE).

PROVIDE AND ROUTE AV CABLING TO

AV CONTROL PANEL LOCATION.

COORDINATE WITH RESIDENT

ENGINEER PRIOR TO INSTALLATION.

INSTALL AT +18 AFF.

GENERAL NOTES:

1. REFER TO E001 FOR COMMUNICATIONS

SYMBOLS LIST.

2. REFER TO 1/TN202 FOR ACCESS

CONTROL RISER DIAGRAM.

3. REFER TO 2/TN202 FOR VIDEO

SURVEILLANCE RISER DIAGRAM.

4. REFER TO 3/TN202 FOR INFORMATION

OUTLET ROUGH-IN DETAIL.

5. REFER TO 4/TN202 FOR BONDING RISER

DIAGRAM.

6. REFER TO TN202 FOR INFORMATION

OUTLET SCHEDULE.

7. REFER TO ARCHITECTURAL DRAWINGS

FOR ELEVATIONS.

8. CONTRACTOR SHALL REMOVE ANY AND

ALL ABANDONED CONDUIT BACK TO THE

SOURCE.

9. ALL CABLE SHALL BE IN CONDUIT.

CONDUITS CONTAINING NETWORK

CABLING SHALL BE CONNECTED TO THE

CABLE TRAY. NO J-HOOKS SHALL BE

ALLOWED.

10. COORDINATE OFCI AND CFCI

TELEPHONE AND DATA EQUIPMENT

WITH VA BILOXI OI&T.

11. COORDINATE OFCI AND CFCI CABLE

TELEVISION DISTRIBUTION EQUIPMENT

WITH VA BILOXI OI&T.

1/4" = 1'-0"TN103 TN103

4 5TH FLOOR - FMS/SECURITY - LARGE SCALE PLAN

1/4" = 1'-0"TN103 TN103

5TH FLOOR - FMS/SECURITY - LARGE SCALE CEILING

PLAN

KEYED NOTES:

6. AV CONNECTIVITY FOR VTEL CAMERA.

PROVIDE DEEP 2-GANG BACKBOX

(4.21"H X 4.06"W X 4.00"D) WITH (1) 1",

1-1/4", 1-1/2", 2" KNOCKOUT, (2) 1/2"

KNOCKOUTS AND (4) 1/2"-3/4"

KNOCKOUTS. COORDINATE WITH

RESIDENT ENGINEER PRIOR TO

INSTALLATION. INSTALL AT +84 AFF.

7. AV WALL PLATE. PROVIDE DEEP 2-

GANG BACKBOX (4.21"H X 4.06"W X

4.00"D) WITH (1) 1", 1-1/4", 1-1/2", 2"

KNOCKOUT, (2) 1/2" KNOCKOUTS AND

(4) 1/2"-3/4" KNOCKOUTS. PROVIDE

FOUR (4) NETWORK DROPS; TWO (2)

FEMALE HDMI BULK HEAD

CONNECTORS; TWO (2) FEMALE XLR

BULK HEAD CONNECTORS; ONE (1)

FEMALE 14-PIN HD SUB D CONNECTOR

FOR VGA; AND TWO (2) FEMALE RCA

BULK HEAD CONNECTORS (ONE RED,

ONE WHITE). PROVIDE AND ROUTE AV

CABLING TO AV CONTROL PANEL

LOCATION. COORDINATE WITH

RESIDENT ENGINEER PRIOR TO

INSTALLATION. INSTALL AT +18" AFF.

8. FURNITURE FEED FOR NETWORK

CABLING INTO DENTAL EQUIPMENT.

COORDINATE WITH FURNITURE

PROVIDER PRIOR TO INSTALLATION.

KEYED NOTES:

9. AV CONNECTIVITY FOR TV. PROVIDE

DEEP 2-GANG BACKBOX (4.21"H X

4.06"W X 4.00"D) WITH (1) 1", 1-1/4",

1-1/2", 2" KNOCKOUT, (2) 1/2"

KNOCKOUTS AND (4) 1/2"-3/4"

KNOCKOUTS. PROVIDE ONE (1)

FEMALE HDMI BULK HEAD

CONNECTOR; ONE (1) FEMALE 14-PIN

HD SUB D CONNECTOR FOR VGA; AND

TWO (2) FEMALE RCA BULK HEAD

CONNECTORS (ONE RED, ONE WHITE).

PROVIDE AND ROUTE AV CABLING TO

AV CONTROL PANEL LOCATION.

COORDINATE WITH RESIDENT

ENGINEER PRIOR TO INSTALLATION.

INSTALL AT +72 AFF.

10. INSTALL JBOX FOR CUBICLE

NETWORK SPACES ABOVE CEILING,

ROUTE CONDUIT AND CABLING DOWN

COLUMNS. CONCEALED. CONFIRM

WHIP WITH FURNITURE INSTALLER.

PROVIDE AN ADDITIONAL 45' SLACK

COIL OF NETWORK CABLING FOR EACH

NETWORK DROP AT EACH LOCATION.

11. TWO (2) 4" SLEEVES.

12. ONE (1) 1" CONDUIT TO PENTHOUSE

RADIO ROOM.

(2

C o n d u it s f o r O

IT

(2

C o n d u it s f o r

F M

S /S e c

(2

C o n d u it s f o r

F M

S /S e c

(2

C o n d u it s f o r

F M

S /S e c

(1

C o n d u it fo r

O

IT

(2

C o n d u it s f o r O

IT

(2

C o n d u it s f o r O

IT

1st Floor Telecom

Room

1A129

3rd Floor Telecom

Room

3A140

4th Floor Telecom

Room

4A140

5th Floor Telecom

Room

5A135

OIT Riser FMS/Security

Riser

1st Floor FMS/Security

1C118

3rd Floor FMS/Security

3A111

4th Floor FMS/Security

4A111

5th Floor FMS/Security

5A111

Penthouse Radio

Room

Conduit Riser

Riser Diagram for FMS/Security & OIT Conduit

Renovation of Building 1 and Building 2

Biloxi VA Complex

Building 1

1st Floor Telecom Room

1A134

-P a ir T e le p h o n e C a b le n e w

-P a ir T e le p h o n e C a b le n e w

-P a ir T e le p h o n e C a b le n e w

-P a ir T e le p h o n e C a b le n e w

1st Floor Telecom

Room 1A129

3rd Floor Telecom Room

3A140

4th Floor Telecom

Room 4A140

5th Floor Telecom

Room

5A135

Penthouse Radio

Room

-S tr a n d M

M

.5

/1

(n e w

-S tr a n d S

M

.3 /1 n e w

-S tr a n d S

M

.3 /1 n e w

-S tr a n d S

M

.3 /1 n e w

-S tr a n d M

M

.5

/1

(n e w

-S tr a n d M

M

.5

/1

(n e w

-S tr a n d M

M

.5

/1

(n e w

Fiber & Copper Riser for OIT

Riser Diagram for OIT

Renovation of Building 1

Biloxi VA Complex

Building 1

TV

TV

TV

FMS/Security

Cabling Homerun

(by Siemens)

FMS/Security

Cabling Homerun

(by Siemens)

FMS/Security

Cabling Homerun

(by Siemens) Siemens

FMS/

Security

Devices

Siemens

FMS/

Security Devices

Siemens

FMS/

Security Devices

R G

C o a x R is e r

(n e w

Cable One Television Feed (existing)

R G

C o a x R is e r

(n e w

R G

C o a x R is e r

(n e w

4' x 4' Plywood

Backboard w/ Splitters

4' x 4' Plywood

Backboard w/ Splitters

4' x 4' Plywood

Backboard w/ Splitters

RG6 Coax Homerun (new)

RG6 Coax Homerun (new)

RG6 Coax Homerun (new)

1st Floor FMS/Security

1C118

3rd Floor FMS/Security 3A111

4th Floor FMS/Security 4A111

5th Floor FMS/Security

5A111

Penthouse Radio

Room

FMS Fiber Connection to Campus Network (existing)

-S tr a n d S

M

.3 /1 n e w

-S tr a n d M

M

.5

/1

(n e w

Fiber & Copper Riser for FMS/Security

Building 1

Riser Diagram for FMS/Security

Renovation of Building 1

Biloxi VA Complex

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

C R e v it L o c a l F ile s \I C

T

B

L D

G

E le c tr ic a l C

D S

M a tt h e w

.L .G rz o v ic

.r v t

/1 /2

:2

:0

P M

TN201

RISER - TELECOM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 MATGRZ SIDROY

234 238Revisions: Date:

OWNER

PROVIDED

NETWORK

EQUIPMENT

MODULAR

PATCH PANEL

SERVER

RECORDER

EXISTING TGB EXISTING TGB

TGB TGB

TGB TGB

TGB TGB

NOTES:

1. THIS RISER IS DIGRAMMATIC AND MAY NOT SHOW ACTUAL DEVICE QUANTITIES OR LOCATIONS. ALL DEVICES SHOWN ARE TYPICAL AND MAY NOT REFLECT EVERY WIRE OR CONNECTION THAT MUST BE MADE. WIRING SHOWN ON THIS DIAGRAM REFLECTS THE REQUIREMENTS FOR THE BASIS OF DESIGN

MANUFACTURER. ANY CHANGES REQUIRED DUE TO THE T.C.'S SELECTION OF AN ALTERNATE

MANUFACTURER, INCLUDING ANY POWER REQUIRED FOR FIELD LOCATED SECURITY CONTROLLERS, SHALL

BE INCLUDED IN THE T.C.'S BID.

2. REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS OF CAMERAS.

3. REFER TO T-500 FOR TECHNOLOGY EQUIPMENT SCHEDULE.

4. ALL CABLE SHALL BE IN CONDUIT. CONDUIT SHALL RUN FROM DEVICE LOCATION TO NEAREST TELECOM

ROOM.

TYPICAL TELECOM

ROOM

KEYNOTES:

1. 23 GAUGE, 4-PAIR, ,CATEGORY 6, UNSHIELDED TWISTED PAIR CABLE, BY LOW VOLTAGE

CONTRACTOR. CONTRACTOR SHALL PROVIDE 20' SLACK AT BOTH ENDS.

2. CATEGORY 6 RJ-45 TO RJ-45 PATCH CABLE. REFER TO SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

C

DOOR CONTACT

ETHERNET

ELECTRIC DOOR

LOCKING

HARDWARE (TYP.)

+120V

TYPICAL TELECOM

ROOM

6/C #18 AWG SH

2/C #18 AWG USH

2/C #18 AWG USH

4/C #18 AWG USH

(TYP.)

SECURITY

CONTROL

PANEL

1. THIS DIAGRAM IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL DEVICE QUANTITIES OR LOCATIONS. ALL DEVICES SHOWN ARE TYPICAL AND MAY NOT REFLECT EVERY WIRE OR CONNECTION THAT MUST BE MADE. WIRING SHOWN ON THIS DIAGRAM REFLECTS THE REQUIREMENTS FOR THE BASIS OF DESIGN

MANUFACTURER. ANY CHANGES REQUIRED DUE TO THE T.C.'S SELECTION OF AN ALTERNATE

MANUFACTURER, INCLUDING ANY POWER REQUIRED FOR FIELD LOCATED SECURITY CONTROLLERS, SHALL BE INCLUDED IN THE T.C.'S BID.

2. ALL WORKSTATIONS AND SERVERS REQUIRE A KEYBOARD AND MOUSE.

3. ALL CABLE SHALL BE IN CONDUIT. CONDUIT SHALL RUN FROM DEVICE LOCATION TO NEAREST TELECOM

ROOM.

NOTES:

KEYNOTES:

1. CATEGORY 6 RJ-45 TO RJ-45 PATCH CABLE. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. WORKSTATIONS AND SERVER ARE EXISTING. VERIFY FUNCTIONALITY AFTER INSTALLATION.

3. 16 AWG 2 CONDUCTOR CABLE TO NORMALLY CLOSED CONTACTS OF FIRE ALARM SYSTEM.

2/C #18 AWG USH

MDL

CR

PB

MS

6/C #18 AWG SH

REFER TO SPECIFICATIONS FOR

IDENTIFICATION REQUIREMENTS (TYP.)

NUMBER INDICATES

FACEPLATE POSITION

(TYP.)

PAIR 3

PAIR 1PAIR 2 PAIR 4

WO WGO BL WBL G WBR BR

1 32 4 5 6 7 8

ANSI/TIA/EIA T568B

PIN/PAIR

ASSIGNMENT

2. REFER TO SPECIFICAITONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS.

VOICE CAT 6A RJ-45

1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS.

DATA CAT 6A RJ-45

NOTES:

LEGEND

SINGLE GANG WALLPLATES

INFORMATION OUTLET SCHEDULE

CONFIGURATION F

A

C E

P L

A T

E P

O R

T S

FACEPLATE PORT IDENTIFICATION

NOTES

P O

S

IT

IO

N

J

A C

K

Y

P E

P O

S

IT

IO

N

J

A

P E

IDENTIFICATION

IDENTIFICATION

2-Port Faceplate

S

0 W

WAP

DATA

2 DATA

2 VOICE VOICE

2 VOICE VOICE

DATA2 DATA

2 VOICE VOICE

DATA2 DATA

2 VOICE VOICE

DATA DATA

P O

S

IT

IO

N

J

A

P E

P O

S

IT

IO

N

J

A

P E

VOICE VOICEDATA DATA

VOICE VOICEDATA DATA

VOICE VOICEDATA DATA

IDENTIFICATION

IDENTIFICATION

4-Port Faceplate

CONDUCTOR

LENGTH IN FEET

BONDING CONDUCTOR SIZING SCHEDULE

MINIMUM ACCEPTABLE

SIZE - AWG

LESS THAN 13' 6

14' - 20' 4

21' - 26' 3

27' - 33' 2

34' - 41' 1

42' - 52' 1/0

53' - 66' 2/0

GREATER THAN 66' 3/0

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF

MATERIALS. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND

CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT

REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES. REFER TO FLOOR PLANS AND ENLARGED

FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND MORE SPECIFIC

ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

2. ALL CONDUCTORS IN THE TECHNOLOGY BONDING SYSTEM SHALL BE MINIMUM SIZE OF 3/0 AWG

[PLENUM RATED] COPPER (GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR) UNLESS

CONDUCTOR LENGTH IS LESS THAN 66 FEET. REFER TO BONDING CONDUCTOR SIZING SCHEDULE

FOR SIZING CRITERIA FOR CONDUCTORS LESS THAN 66 FEET IN LENGTH. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

3. ALL BONDING CONDUCTORS AND BONDING JUMPERS SHALL BE CONNECTED BY COMPRESSION

LUGS, EXOTHERMIC WELDING, OR IRREVERSIBLE COMPRESSION CONNECTORS. SOLDER IS NOT

AN ACCEPTABLE MEANS OF CONNECTION. SHEET METAL SCREWS SHALL NOT BE USED TO

CONNECT COMMUNICATIONS BONDING CONDUCTORS TO EQUIPMENT. WHERE NECESSARY,

REMOVE PAINT AND/OR USE PAINT-PIERCING WASHERS TO PROVIDE PROPER ELECTRICAL BOND

AT ALL CONNECTIONS.

KEYNOTES:

1. BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT). BCT SHALL BE THE SAME SIZE AS THE

TBB OR LARGER. REFER TO BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING

REQUIREMENTS.

FIRST

FLOOR

EXISTING ELECTRICAL

ENTRANCE INTERSYSTEM

BONDING TERMINATION

GROUNDING

ELECTRODE

CONDUCTOR BY

OTHERS

[EXISTING] ELECTRICAL

GROUNDING ELECTRODE SYSTEM

TELECOMMUNICATION

S

BONDING BACKBONE

(TBB) (TYP)

THIRD

FLOOR

FOURTH

FLOOR

FIFTH

FLOOR

BONDING EQUALIZER (BE)

TELECOM ROOM BONDING EQUALIZER (BE)

FMS/SECURITY ROOM

5A135

4A140

3A140

1C1181A129

3A111

4A111

5A111

TELECOM ROOM FMS/SECURITY ROOM

TELECOM ROOM FMS/SECURITY ROOM

TELECOM ROOM FMS/SECURITY ROOM

1-1/4" EMT CONDUIT, UNLESS

OTHERWISE NOTED

TYPICAL OF ALL

CABLE TRAY

NOTES:

1. THE INTENT OF THE DETAIL IS TO ALIGN AND GROUP DEVICE ROUGH-INS FOR POWER AND LOW VOLTAGE TECHNOLOGY SYSTEMS. SOLIDLY MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE MOUNTED IN A MANNER THAT IS SIMILAR TO THE

SYSTEM NOTED ABOVE OR ACHIEVES THE SAME RESULTS.

2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE WALL. PLASTER RING SHALL BE 3/4" FOR

USE WITH 5/8" GYP BOARD.

3. METAL STUD-TO-STUD MOUNTING BRACKETS FOR MULTIPLE BOXES BETWEEN STUD. ERICO CADDY RBS## SERIES, EATON B-

LINE BB SERIES, OR EQUAL.

4. MOUNTING SUPPORT BRACKETS SIZES FOR SINGLE BOXES IN A STUD CAVITY SHALL MATCH THE STUD DEPTH. ERICO CADDY

H## SERIES, EATON B-LINE BB## SERIES, OR EQUAL.

5. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE DEVICES SHALL BE INSTALLED IN THE SAME STUD CAVITY WITH MOUNTING

BRACKETS OR ALIGNED ON OPPOSITE SIDES OF A COMMON STUD WITH SEPARATE SUPPORT.

6. TERMINATE CONDUIT STUB ORIENTED HORIZONTALLY AT THE HEIGHT OF THE ASSOCIATED CABLE TRAY OR J-HOOK ROUTE.

CONDUIT RUN SHALL NOT CONTAIN MORE THAN 180 DEGREES OF BEND BETWEEN ACCESSIBLE JUNCTION BOXES OR

BETWEEN JUNCTION BOX AND END OF CONDUIT.

7. WHERE CONDUIT STUB IS LOCATED IN A ROOM WITH AN ACCESSIBLE CEILING AND IS NOT REQUIRED TO RUN TO CABLE ROUTE LOCATED OUTSIDE THE ROOM, STUB MUST TERMINATE ABOVE THE ACCESSIBLE CEILING WITH A 90-DEGREE BEND AT THE TOP ORIENTED IN TO THE ROOM AT THE HEIGHT OF THE ASSOCIATED CABLE TRAY OR J-HOOK ROUTE IN THE ROOM.

8. ALL STUBS MUST BE FITTED WITH A NYLON BUSHING ON EACH END OF THE CONDUIT.

9. FURNISH AND INSTALL FIRESTOP MATERIALS FOR TECHNOLOGY ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO

SPECIFICATIONS FOR FIRESTOP REQUIREMENTS.

GROUNDING BUSHING

STUB ROUGH-IN CONDUIT TO

CABLE TRAY

#12 BONDING CONDUCTOR TO

CABLE TRAY AND GROUNDING

BUSHING

REFER TO ARCHITECTURAL

PLANS FOR WALL CONSTRUCTION

PLASTER RING TO COME

WITHIN 1/8" OF FINAL SURFACE

STUD

MOUNTING BRACKET SHALL PROVIDE

SUPPORT FROM STUD AND BACK OF

WALL OR TWO STUDS

ALIGNED AND GROUPED

POWER AND LOW

VOLTAGE ROUGH-INS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

C R e v it L o c a l F ile s \I C

T

B

L D

G

E le c tr ic a l C

D S

M a tt h e w

.L .G rz o v ic

.r v t

/1 /2

:2

:0

P M

TN202

RISER - TELECOM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 MATGRZ SIDROY

235 238

2. VIDEO SURVEILLANCE RISER DIAGRAM

NO SCALE

1. ACCESS CONTROL RISER DIAGRAM

NO SCALE

4. TECHNOLOGY BONDING RISER DIAGRAM

NO SCALE

3. INFORMATION OUTLET ROUGH-IN DETAIL

NO SCALE

Sheets
E001 - LEGENDS - ELECTRICAL
TN101 - 3RD FLOOR - TELECOM
TN102 - 4TH FLOOR - TELECOM
TN103 - 5TH FLOOR - TELECOM
TN201 - RISER - TELECOM
TN202 - RISER - TELECOM

File details come from the government source that posted it. Updated .