Drawings - Plumbing - 2.pdf

PDF 12 MB Posted

Attached to
Biloxi Building 1 Renovation - Biloxi, MS -- Y1DA
Solicitation number
QSE--36C10F24R50025
Issued by

About this file

This document appears to be a solicitation for the Biloxi Building 1 Renovation project in Biloxi, MS. The Department of Veterans Affairs Office of Construction and Facilities Management is seeking a contractor to provide all necessary supervision, labor, materials, transportation, and equipment to complete the renovation of Building 1. The project scope includes selective demolition, exterior building envelope alterations, and interior renovation of floors 3, 4, and 5, as well as upgrades to HVAC, plumbing, electrical, telecommunications, chilled water, and fire protection systems. The period of performance is 912 calendar days from the notice to proceed, and the project magnitude is estimated between $50M to $100M. Wage Rate Requirements (Construction) apply. The solicitation number is QSE-36C10F24R50025.

View the file

Other files

File Type Posted
S02_Solicitation Amendment 0003.pdf PDF
C28_02821319 TILE AND MASTIC AND BRICK COATING ABATEMENT.pdf PDF
C28_02833313 LEAD PAINT REMOVAL.pdf PDF
P12_AE Addendum Two.pdf PDF
SolicitationAmendment0004.pdf PDF
P03_Justification and Approval - TekTone Nurse Call System - revised 05.24.24.pdf PDF
P12_Asbestos Report - 01.03.2022.pdf PDF
SolicitationAmendment0003.pdf PDF
52.219-28 Post-Award Small Business Program Rerepresentation.pdf PDF
Wage Determination - Harrison County MS.pdf PDF
QSE 36C10F24R50025.pdf PDF
P12_Asbestos Report - 07.06.2017.pdf PDF
S05_RFI Questions and Answers.pdf PDF
P12_Lead Based Paint Analysis - Bldg 1 - 01.11.2017.pdf PDF
S02_117300 CEILING MOUNTED PATIENT LIFTS - Revised.pdf PDF
P12_Asbestos Report - 05.06.2008.pdf PDF
P12_Addendum 1 - 05.14.2024.pdf PDF
S04_Biloxi Bldg 1 Reno - Pre-Proposal Conference Attendees.pdf PDF
SolicitationAmendment0002.pdf PDF
SolicitationAmendment0001.pdf PDF
QSE 36C10F24R50025.pdf PDF
Wage Determination - Harrison County MS.pdf PDF
52.219-28 Post-Award Small Business Program Rerepresentation.pdf PDF
Drawings - Architectural - 3.pdf PDF
General Contractor Reference Form.docx DOCX document
Drawings - Telecommunication.pdf PDF
Drawings - Architectural - 4.pdf PDF
Drawings - Reference.pdf PDF
VA Biloxi 4th Floor Footwall.pdf PDF
Drawings - Architectural - 1.pdf PDF
Building 1 Inventory - d.pdf PDF
Adec Submittal - VA Biloxi.pdf PDF
Drawings - Electrical - 2.pdf PDF
LOCQ7780-03-SWS-Biloxi VA Dental Lab.pdf PDF
Justification and Approval - Siemens Security and Video Surveillance System.pdf PDF
Past Performance Questionnaire.docx DOCX document
A-dec Floor Plan - VA Biloxi - Elevations.pdf PDF
Drawings - Structural - 2.pdf PDF
Specifications Volume II.pdf PDF
Biloxi VA Reno B1 - Set H.pdf PDF
Drawings - Plumbing - 1.pdf PDF
Drawings - Structural - 1.pdf PDF
VA Biloxi Patient Room Footwall Typical Elevation.pdf PDF
Justification and Approval - Herman Miller Compass Patient Care Modular System.pdf PDF
Solicitation.pdf PDF
000000 Cover Page Appendix.pdf PDF
Justification and Approval - ESTIII Fire Alarm System.pdf PDF
Drawings - General.pdf PDF
A-dec Floor Plan - VA Biloxi - Preliminary.pdf PDF
Drawings - Mechanical - 2.pdf PDF
Show 40 more

Latest 50 of 64 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

G

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

B.8

B.2

10.8 12.2

EXISTING 1-1/4"

OXYGEN RISER UP

WITH SHUT-OFF

VALVE IN RISER.

EXISTING 1/2" OXYGEN UP

TO ZONE VALVE ABOVE.

NEW 1-1/4" O, RISER UP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL301

EXISTING CRAWL SPACE -MED GAS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 150 238

KEYED NOTES:

1. CONNECT TO EXISTING 2" OXYGEN PIPING.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTORS SHALL REVIEW ROUTING OF PIPING

PRIOR TO BID. ROUTING SHOWN IS ONE POTENTIAL

ROUTE WITH FINAL ROUTE UP TO INSTALLING

CONTRACTOR TO DETERMINE.

3. CONTRACTORS SHALL COORDINATE ROUTING OF PIPING

WITH EXISTING CONDITIONS.

4. REMOVE ALL EXISTING DENTAL VACUUM PIPING

SERVING THE FIRST FLOOR AFTER THE NEW DENTAL LAB

HAS BEEN COMPLETED.

Revisions: Date:

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

B.8

B.2

10.8 12.2

EXISTING 1 1/4"O UP & DN

EXISTING 1 1/4" MA & 1 1/2" MV

UP

PROVIDE SHUT-OFF

VALVES.

UPUP & DN

UP

2" MV CAPPED

FOR FUTURE USE

EXISTING O, MA, MV UP

TO 2ND FLOOR

BIOMEDICAL DEPT.

EXISTING SHUT-OFF VALVES

FOR SERVICES TO 2ND FLOOR

BIOMEDICAL DEPT. EXISTING 0, MA, & MV SERVICES

TO EAST WING

1" O, 1" MA

REMOVE EXISTING DENTAL AIR RISER FROM THE

FIRST FLOOR BACK TO THE DENTAL AIR

COMPRESSORS AFTER THE NEW DENTAL LAB

HAS BEEN COMPLETED AND IS OPERATIONAL.

VERIFY WITH VA PRIOR TO REMOVAL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL302

EXISTING 1ST FLOOR - MED GAS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 151 238

KEYED NOTES:

1. CONNECT TO EXISTING 3/4" O & 3/4" MA

PIPING DOWNSTREAM OF EXISTING SHUT-OFF

VALVES. CAP EXISTING O & MA AT SHUT-OFF VALVES.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. REFER TO PL501 AND PL502 FOR DETAILS.

3. REFER TO PL507 FOR RISER DIAGRAMS.

4. REMOVE ALL EXISTING DENTAL AIR AND DENTAL

VACUUM PIPING ON THE FIRST FLOOR AFTER THE

NEW DENTAL LAB HAS BEEN COMPLETED.

5. REFER TO DRAWING AE102 FOR INFORMATION

REGARDING PHASING OF WORK ON THE SECOND

FLOOR.

1 2 3 4 5 6 7 8 9

11 12

14 15 16 17 18 19 20 21 22

G

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

B.8

B.2

10.8 12.2

PROVIDE SHUT-OFF

VALVES AND CAP

FOR FUTURE USE.

TURN UP/DN..

1"O, 1" MA, 2" MV

CAPPED.

REMOVE EXISTING DENTAL AIR RISER FROM

THE FIRST FLOOR BACK TO THE DENTAL AIR

COMPRESSORS AFTER THE NEW DENTAL LAB

HAS BEEN COMPLETED AND IS OPERATIONAL.

VERIFY WITH VA PRIOR TO REMOVAL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL303

EXISTING 2ND FLOOR - MED GAS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 152 238

KEYED NOTES:

1. EXISTING 1 1/4" OXYGEN PIPING SHALL CONTINUE TO SERVE

THE 1ST & 2ND FLOORS. CAP RISER BELOW 3RD FLOOR & PROVIDE

WITH A SHUT-OFF VALVE.

2. CONNECT TO EXISTING 1 1/2" MA & 1 1/2" MV.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. REFER TO PL501 AND PL502 FOR DETAILS.

3. REFER TO PL507 FOR RISER DIAGRAMS.

4. REFER TO DRAWING AE102 FOR INFORMATION REGARDING

PHASING OF WORK ON THE SECOND FLOOR.

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

B.8

B.2

10.8 12.2

FEC

FEC FEC

ZONE VALVE

MEDICAL GAS

AREA ALARM

PROVIDE

SHUT-OFF VALVES.

ZONE

VALVE

TURN UP/DN..

NEW MA & MV

UP/DN..

SHUT-OFF

VALVES

SHUT-OFF

VALVES

SHUT-OFF

VALVES

1 1/4" O, 1 1/2" MA,

2" MV

REMOVE EXISTING DENTAL AIR RISER FROM

THE FIRST FLOOR BACK TO THE DENTAL AIR

COMPRESSORS AFTER THE NEW DENTAL LAB

HAS BEEN COMPLETED AND IS OPERATIONAL.

VERIFY WITH VA PRIOR TO REMOVAL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL304

3RD FLOOR - MED GAS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 153 238

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. REFER TO PL501 AND PL502 FOR DETAILS.

3. REFER TO PL507 FOR RISER DIAGRAMS.

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

B.8

B.2

10.8 12.2

ZONE VALVE

ZONE

VALVE

1 1/2" LA & 1 1/2" DA

UP TO 5TH FLOOR

PROVIDE

SHUT-OFF VALVES.

DENTAL AIR

TURN UP/DN..

NEW MA & MV

UP/DN..

LA

SHUT-OFF VALVE IN

VERTICAL. ( TYP.)

SHUT-OFF

VALVES

1 1/4"O, 1 1/2"

MA, 2"MV

UP TO

WCO

UP TO

WCO

1 1/2" DV UP TO WCO

1 1/2" DV UP TO WCO

2" DV UP

REMOVE EXISTING DENTAL AIR RISER FROM

THE FIRST FLOOR BACK TO THE DENTAL AIR

COMPRESSORS AFTER THE NEW DENTAL LAB

HAS BEEN COMPLETED AND IS OPERATIONAL.

VERIFY WITH VA PRIOR TO REMOVAL.

2" DV FROM

DENTAL INTO TANK

2" DV FROM

PUMP INTO TANK

MEDICAL GAS

AREA ALARM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL305

4TH FLOOR - MED GAS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 154 238

KEYED NOTES:

1. 1/2" DA UP TO DENTAL CHAIR FLOOR BOX.

2. 1/2" LA UP TO DENTAL LAB. COORDINATE

EXACT LOCATION WITH DENTAL LAB

EQUIPMENT LAYOUT, STRUCTURE, AND

RESIDENT ENGINEER.

3. 1-1/2" DV UP TO DENTAL CHAIR FLOOR BOX.

4. 1/2" DA UP TO SIDE ACCESSORY CONSOLE.

5. 1" LA PIPING UP TO DENTAL LAB.

COORDINATE EXACT LOCATION WITH DENTAL

LAB EQUIPMENT LAYOUT, STRUCTURE, AND

RESIDENT ENGINEER.

6. CONTRACTOR TO INSTALL VA PROVIDED

SEPARATOR TANK. CONTRACTOR SHALL

PROVIDE ALL NECESSARY COMPONENTS FOR

COMPLETE INSTALLATION. COORDINATE

REQUIREMENTS WITH VA.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND

NOTES.

2. REFER TO PL501 AND PL502 FOR DETAILS.

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

B.8

B.2

10.8 12.2

ZONE VALVE

1 1/2" LA & 1 1/2" DA

DOWN TO 4TH FLOOR

PROVIDE SHUT-OFF

VALVES.

NEW MA & MV

DN..

NEW MA & MV

UP.

LA

1 1/4" O DN, 1 1/2"MA, 2"

MV UP/DN

UP

UP

UP & DN

WCO

WCO

WCO

WCO

REMOVE EXISTING DENTAL AIR RISER FROM

THE FIRST FLOOR BACK TO THE DENTAL AIR

COMPRESSORS AFTER THE NEW DENTAL LAB

HAS BEEN COMPLETED AND IS OPERATIONAL.

VERIFY WITH VA PRIOR TO REMOVAL.

LOCATE Y-SPLIT OUTLET

AT THESE STATIONS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL306

5TH FLOOR - MED GAS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 155 238

KEYED NOTES:

1. CAP 2" MV & 1 1/2" MA FOR FUTURE USE.

2. 1/2" LA PIPING DOWN TO 4TH FLOOR.

COORDINATE EXACT FLOOR PENETRATION

LOCATION, PIPING TERMINATION, AND OUTLET

TYPE, LOCATION, AND ELEVATION WITH DENTAL

LAB EQUIPMENT/FURNITURE, STRUCTURE, AND

RESIDENT ENGINEER.

3. 1" LA PIPING DOWN TO 4TH FLOOR.

COORDINATE EXACT ROUTE OF LA PIPING WITH

VACUUM TUBING SYSTEM LOCATED WITHIN

ISLAND CABINETRY.COORDINATE EXACT FLOOR

PENETRATION LOCATION, PIPING TERMINATION,

AND OUTLET TYPE, LOCATION, AND ELEVATION

WITH DENTAL LAB EQUIPMENT/FURNITURE AND

VENDOR (LOC), STRUCTURE, AND RESIDENT

ENGINEER.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. REFER TO PL501 AND PL502 FOR DETAILS.

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

B.8

B.2

10.8 12.2

5.1

EXISTING 1-1/2" MEDICAL AIR

EXISTING 2" MEDICAL VACUUM

NEW 1-1/2" DENTAL AIR

NEW 1 1/2"MA, 2"MV, 1 1/2" LA,

& 1 1/2" DA DOWN TO 5TH FLOOR

NEW MA & MV

DN..

NEW 1-1/2" LABORATORY AIR

DN

2" DV EXHAUST TO OUTSIDE WEATHER

CAP. COORDINATE INSTALLATION WITH

MECHANICAL CONTRACTOR. EXHAUST

OUTLET TO BE 25 FEET MINIMUM FROM

HVAC INTAKES.

INSTALL VA PROVIDED PUMP. CONTRACTOR

SHALL PROVIDE ALL NECESSARY

COMPONENTS FOR COMPLETE INSTALLATION.

COORDINATE REQUIREMENTS WITH VA AND

ELECTRICAL.

REMOVE EXISTING DENTAL AIR RISER FROM

THE FIRST FLOOR BACK TO THE DENTAL AIR

COMPRESSORS AFTER THE NEW DENTAL LAB

HAS BEEN COMPLETED AND IS OPERATIONAL.

VERIFY WITH VA PRIOR TO REMOVAL.

REVISE EXISTING PIPING ROUTE FOR NEW

MECHANICAL AND DUCT INSTALLATION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL307

ATTIC - MED GAS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 156 238

KEYED NOTES:

1. 1 1/2" LA CONNECTION TO EXISTING DENTAL

AIR COMPRESSOR. PROVIDE PRESSURE REDUCING VALVE

SET AT 50 PSI.

2. 1 1/2" DA CONNECTION TO EXISTING DENTAL AIR

COMPRESSOR. PROVIDE PRESSURE REDUCING VALVE SET

AT 140 PSI.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

12 13

B

A

B.4

B.2

12.2

UP & DN

4" SAN UP

& DN

4"

VENT

UP

2" CW UP

1 1/2" CW

UP

UP

UP

UP

UP

UP & DN

16 17

D

D.2

4" SAN

UP & DN

3" VENT

UP

UP

UP

UP

UP

UP

UP

UP

12 13

B.4

B.2

12.2

4" SAN

DN

UP1" CW,

1/2" HW,

1/2" HWR

DN

UP

3 4

D

C

D.2

WCO

4" SV UP

4" SS DN

F

E

D.8

1 1/2" CW DN

1" HW DN

1" CW DN

1/2" HWR DN

DN

4" SV

UP

UP & DN

19 20 21 22

C

B

B.4

B.7

B.8

B.2

4" SAN

DN

2" SAN

DN

2" SS DN

WCO

4" SAN

DN

2" CW DN

1 1/2"HW DN

UP

UP

1 1/2"HWR DN

MULTIPLE

TRAP PRIMER

DN

4" SV UP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL401

ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 157 238

KEYED NOTE

1. 1/2" CW BELOW SLAB TO TRAP.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO

0.5GPM UNLESS NOTED OTHERWISE.

10 11 12 13

F

F.8

F.3

10.8 12.2

DN

UP

DN

3" SS

3" SS DN

2" SV UP

WCO

2" SV

4" SS

DN

2" CW DN

1 1/2" HW DN

1 1/2" HWR DN

1" CW UP TO

HOSE BIBBS IN

ATTIC.

UP

MULTIPLE

TRAP PRIMER

UP

3" SS UP TO EXISTING

FLOOR DRAIN

2 3 4

C

B

B.4

B.7

B.8

B.2

4" VENT

UP

UP & DN

WCO

UP

UP

UP

UP

UP

SERVICES TO

PATIENT

ROOM SINK

CS-2

UP

UP

TP-2

UP

UP

G

F

E

F.8

F.3

D.8

4" SAN

UP & DN

4" VENT

UPUP

UP

UPUP

UP

UP

UP

UP & DN

TP-2

TP-2

BFP

1/2" HWR UP

1/2" HW UP

1/2" CW UP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL402

ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 158 238

KEYED NOTE

1. 1/2" CW BELOW SLAB TO TRAP

2. PROVIDE 3/4" DRAIN WITH SOLENOID VALVE THEN

MANUAL SHUT-OFF VALVE EXTENDED TO FLOOR SINK (OR

MOP SINK) TO "HEAT AND FLUSH" DOMESTIC HOT WATER

LINE. SOLENOID VALVE TO BE WIRED TO BAS FOR REMOTE

OPERATION AND MONITORING. COORDINATE VALVE

SELECTION AND LOCATION WITH OWNER AND

TEMPERATURE CONTROL CONTRACTOR.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO

0.5GPM UNLESS NOTED OTHERWISE.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS

SPECIFICATION SECTION 01 00 00.1.38

ALTERNATE NO.2 FOR REQUIREMENTS OF

DEDUCT ALTERNATE OF THE DIALYSIS

BOXES INDICATED ON THIS SHEET.

1 2 3 4 5 6

F

E

F.8

F.3

D.8

4" SV UP

4" SAN

UP & DN

4" SV UP

4" SAN

UP & DN

4" SAN

UP &

DN

4" SAN

UP & DN

1/2" HWR

UP

WC

UP

UP UP

UP

WCO

UP

UP UP & DN

UP

UP

DN

UPUP

UP

UP & DN

CS-2

CS-2

CS-2

CS-2

UPUP

UP

TP-2

TP-2

TP-2

DNTP-2

1/2" HW

UP

1/2" CW

UP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL403

ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 159 238

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS

SPECIFICATION SECTION 01 00 00.1.38

ALTERNATE NO.2 FOR REQUIREMENTS OF

DEDUCT ALTERNATE OF THE DIALYSIS

BOXES INDICATED ON THIS SHEET.

19 20 21

C

B

B.4

B.7

B.8

B.2

UP

DN

UP & DN

DN

UP

DN

UP

UP

CS-2

TP-2

UP

UP

UP

UP

UP

UP

UP

1 2 3 4

C

B

B.4

B.7

B.8

B.2

DN

BAL V

4" SS DN

4 5

F

F.8

F.3

WCO

87.4

F.8

F.3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL404

ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 160 238

KEYED NOTES:

1. PROVIDE 1/2" CW, 1/2" HW, AND 1 1/2" WASTE

CONNECTIONS FOR SINK LOCATED IN SIDE ACCESSORY

CONSOLE. COORDINATE ROUGH-IN REQUIREMENTS

WITH EQUIPMENT PROVIDER.

2. PROVIDE P-710 HANDHELD EYEWASH STATION WITH

MIXING VALVE MOUNTED BELOW COUNTER.

COORDINATE PIPING, MOUNTING BRACKET, UNIT

LOCATION, AND MIXING VALVE LOCATION WITH SINK

AND EQUIPMENT.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO

0.5GPM UNLESS NOTED OTHERWISE.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS

SPECIFICATION SECTION 01 00 00.1.38

ALTERNATE NO.2 FOR REQUIREMENTS OF

DEDUCT ALTERNATE OF THE DIALYSIS BOXES

INDICATED ON THIS SHEET.

MEDICAL GAS MOUNTING HEIGHT DETAIL

NOT TO SCALE

PIPE PENETRATION THROUGH WALL BELOW GRADE

NOT TO SCALE

(P-809) DIALYSIS BOX DETAIL

NOT TO SCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL501

DETAILS - PLUMBING RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 161 238Revisions: Date:

PORTABLE

WATER

ANALYZER

AUTOMATIC SPRINKLER SYSTEM SECTIONAL

CONTROL VALVE AND INSPECTOR'S TEST

VALVE AND DRAIN ASSEMBLY DETAIL

FLOOR MOUNTED HANDICAPPED, WATER CLOSET DETAIL

WALL HUNG HANDICAPPED, WATER CLOSET DETAIL

MEDICAL GAS PIPING AT OUTLETS 4

5a

3 5WATER MONITORING SYSTEM DETAIL

NOT TO SCALE

5b

NOT TO SCALE

NOT TO SCALE NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL502

DETAILS - PLUMBING RENOVATE BUILDING 1

10/27/2023 SCOPRZ AARMEY 162 238Revisions: Date:

1ST FLOOR 0'-0"

2ND FLOOR 13'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

CS-2

CS-2

EXISTING FLOOR

DRAIN

EXISTING

4" VTR

EXISTING

4" VTR

EXISTING

4" VTR

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

4" VTR

4" VTR

4" VTR

CONNECT TO

EXISTING 4" VTR

EXISTING 4" VTR

CS-2

EXISTING VENT PIPING IN

ATTIC WHICH IS TO BE

REMOVED AS EXISTING

RISERS ARE REMOVED FROM

SERVICE. (TYPICAL)

REMOVE EXISTING

4" VTR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL505

OVERALL SANITARY RISER RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 163 238

KEYED NOTES:

1. PROVIDE 1/2" CW, 1/2" HW, AND 1 1/2" WASTE

CONNECTIONS FOR SINK LOCATED IN SIDE ACCESSORY

CONSOLE. COORDINATE ROUGH-IN REQUIREMENTS

WITH EQUIPMENT PROVIDER.

GENERAL SHEET NOTES:

1. REFER TO FLOOR PLANS FOR SIZES.

2. REFER TO PL601 FOR SYMBOLS AND NOTES.

3. REFER TO PL508, PL509, PL510, AND PL511 FOR

ENLARGED RISER DIAGRAMS.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS

SPECIFICATION SECTION 01 00 00.1.38

ALTERNATE NO.2 FOR REQUIREMENTS OF

DEDUCT ALTERNATE OF THE DIALYSIS BOXES

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

CS-2

CS-2

CS-2

CS-2

CS-2

CS-2

CS-2

CS-2

CS-2

CS-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

TP-2

CS-2

CS-2

CS-2

CS-2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL506

OVERALL WATER RISER RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 164 238

KEYED NOTES:

1. PROVIDE 1/2" CW, 1/2" HW, AND 1 1/2" WASTE

CONNECTIONS FOR SINK LOCATED IN SIDE

ACCESSORY CONSOLE. COORDINATE ROUGH-

IN REQUIREMENTS WITH EQUIPMENT

PROVIDER.

2. PROVIDE P-710 HANDHELD EYEWASH STATION

WITH MIXING VALVE MOUNTED BELOW

COUNTER. COORDINATE PIPING, MOUNTING

BRACKET, UNIT LOCATION, AND MIXING VALVE

LOCATION WITH SINK AND EQUIPMENT.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. REFER TO FLOOR PLANS FOR SIZES.

3. REFER TO PL508, PL509, PL510, AND PL511 FOR

ENLARGED RISER DIAGRAMS.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS

SPECIFICATION SECTION 01 00 00.1.38

ALTERNATE NO.2 FOR REQUIREMENTS OF

DEDUCT ALTERNATE OF THE DIALYSIS BOXES

ATTIC 66'-0"

5TH FLOOR 52'-0"

4TH FLOOR 39'-0"

3RD FLOOR 26'-0"

2ND FLOOR 13'-0"

1ST FLOOR 0'-0"

EXISTING

EXISTING

EXISTING

EXISTING

VA PROVIDED,

CONTRACTOR INSTALLED

SEPARATOR TANK

EXISTING

VA PROVIDED,

CONTRACTOR INSTALLED

VACUUM PUMP

MEDICAL GAS

AREA ALARM

MEDICAL GAS

AREA ALARM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL507

OVERALL MED GAS RISER RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 165 238

GENERAL NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. REFER TO FLOOR PLANS FOR SIZES NOT SHOWN.

3. REFER TO FLOOR PLANS PL301, PL302, AND PL307 FOR SYSTEM CONNECTIONS.

4. PROVIDE MEDICAL GAS RISER DIAGRAM IN SHOP DRAWING SUBMITTAL FOR REVIEW. VERIFY ROUTING IN FIELD PRIOR TO SUBMITTING DRAWINGS.

WCO

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

TO EXISTING VTR

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

TP-2

TP-2

CS-2

WCO

WCO

WCO

WCO

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

FD-M

FD-M

2" VTR

TP-2

TP-2

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR

39'-0"

5TH FLOOR 52'-0"

TP-2

TP-2

TP-2

TP-2

WCO

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

3/4" HW DRAIN LINES WITH

SOLENOID VALVE THEN MANUAL

SHUT-OFF VALVE EXTENDED TO

FLOOR SINK (OR MOP SINK) TO

"HEAT AND FLUSH" DOMESTIC HOT

WATER LINE.

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

3/4" HW DRAIN LINES WITH

SOLENOID VALVE THEN MANUAL

SHUT-OFF VALVE EXTENDED TO

FLOOR SINK (OR MOP SINK) TO

"HEAT AND FLUSH" DOMESTIC

HOT WATER LINE.

TP-2

TP-2

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

BFP

BFP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL508

PLUMBING RISERS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 166 238

SIMILAR RISERS:

P/3, P/4, P/7, P/8, P/9

SIMILAR RISERS:

P/3, P/4, P/7, P/8, P/9

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO

0.5GPM UNLESS NOTED OTHERWISE.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS

SPECIFICATION SECTION 01 00 00.1.38 ALTERNATE

NO.2 FOR REQUIREMENTS OF DEDUCT ALTERNATE

OF THE DIALYSIS BOXES INDICATED ON THIS SHEET.

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

WCO

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

3/4" HW DRAIN LINES WITH SOLENOID

VALVE THEN MANUAL SHUT-OFF VALVE

EXTENDED TO FLOOR SINK (OR MOP

SINK) TO "HEAT AND FLUSH" DOMESTIC

HOT WATER LINE.

WCO

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL509

PLUMBING RISERS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 167 238

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO

0.5GPM UNLESS NOTED OTHERWISE.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS

SPECIFICATION SECTION 01 00 00.1.38 ALTERNATE

NO.2 FOR REQUIREMENTS OF DEDUCT ALTERNATE

OF THE DIALYSIS BOXES INDICATED ON THIS SHEET.

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

FLOOR 3 26'-0"

FLOOR 4 39'-0"

FLOOR 5 52'-0"

WCO

2ND FLOOR 13'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

2ND FLOOR 13'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL510

PLUMBING RISERS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 168 238

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO

0.5GPM UNLESS NOTED OTHERWISE.

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

CS-2

TP-2

TP-2

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

6TH FLOOR 66'-0"

3/4" HW DRAIN LINES WITH SOLENOID

VALVE THEN MANUAL SHUT-OFF VALVE

EXTENDED TO FLOOR SINK (OR MOP

SINK) TO "HEAT AND FLUSH" DOMESTIC

HOT WATER LINE.

CS-2

TP-2

TP-2

FILTER

BFP

2ND FLOOR 13'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

CS-2

CS-2

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

CS-2

CS-2

3RD FLOOR 26'-0"

PATIENT ROOMS

3&4, 5&6, 8&9 10&11

ARE SIMILAR

3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

CS-2

CS-2

CS-2

CS-2

PATIENT ROOMS

3&4, 5&6, 8&9, 10 &11

ARE SIMILAR 3RD FLOOR 26'-0"

4TH FLOOR 39'-0"

5TH FLOOR 52'-0"

CS-2

CS-2

CS-2

CS-2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL511

PLUMBING RISERS RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 169 238

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO

0.5GPM UNLESS NOTED OTHERWISE.

DEDUCT ALTERNATE:

1. REFER TO GENERAL REQUIREMENTS SPECIFICATION

SECTION 01 00 00.1.38 ALTERNATE NO.2 FOR

REQUIREMENTS OF DEDUCT ALTERNATE OF THE

DIALYSIS BOXES INDICATED ON THIS SHEET.

PACKAGE BOOSTER PUMP SCHEDULE

MARK LOCATION AREA AND/OR

BLDG SERVED

SYSTEM

AND/OR

SERVICE

TYPE

CIRCULATING FLUID

PRESSURE

TRANSMITTER

SETPOINT

OUTLET BUFFER

TANK ACCEPTANCE

VOLUME

(MINIMUM)

ELECTRICAL MOTOR

FLUID NO

PUMPS

FLOW EA. PUMP HEAD EA. PUMP MIN

NPSH

AVAIL

TEMPERATURE

SP GR % EFF

NOMINAL POWER,

EA. PHASE VOLT MAX RPM SPEED

CONTROL REMARKS

GPM [L/s] FT [M] °F [°C] PSIG [kPa] GAL [L] HP [kW]

1-BP1

BLDG 1

BASEMENT

MECH ROOM BC

HOSPITAL

PRESSURE

FLOORS 3, 4,

AND 5

DOMESTIC

BOOSTER PUMP

VERTICAL

MULTISTAGE

DOMESTIC COLD

WATER 3 75 [ 5 ] 173.3 [ 52 ] N/A 50 [ 10 ] 1 68 75 [ 520 ] 30 [ 110 ] 3.0 [ 2 ] 3 208 3600 VARIABLE -----

NOTES:

1. UNIT INCOMING PRESSURE 50PSI, OUTLET PRESSURE TO BE 75 PSI. REFER TO SPECIFICATIONS FOR OPERATION.

2. PROVIDE UNIT WITH CAPABILITY TO INTERFACE WITH BAS. REFER TO DRAWINGS AND SPECIFICATIONS FOR MORE INFORMATION.

3. SYSTEM CONTROLLER SHALL ALTERNATE PUMPS TO EQUAL RUNTIME ON THE PUMPS. REFER TO SPECIFICATIONS FOR MORE INFORMATION.

4. PROVIDE SEPARATE PRESSURE SWITCHES FOR THE HIGH PRESSURE CUT OFF AND NOT FLOW CUT OFF SAFETIES. EACH DEVICE SHALL BE WIRED SEPARATELY TO THE BOOSTER PUMP CONTROL. THE USE OF A SINGLE DEVICE FOR VFD/SYSTEM PRESSURE CONTROL

AND MULTIPLE SAFETIES IS NOT ACCEPTABLE.

5. BASIS OF DESIGN UNIT ARMSTRONG DESIGN ENVELOPE 6800 BOOSTER SYSTEM MODEL N290102-3. CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES REQUIRED DUE TO DIFFERENCES FROM BASIS OF DESIGN MODEL INCLUDING COORDINATION WITH ELECTRICAL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PL601

SCHEDULES - PLUMBING RENOVATE BUILDING 1

10/27/2023 SCOPRZ AARMEY 170 238Revisions: Date:

PROVIDE TWO 6" LOW PRESSURE DROP RPZ STYLE BACK FLOW

PREVENTORS ARRANGED IN PARALLEL CONFIGURATION ON 8" WATER LINE

SERVING BUILDING 1. UNITS SHALL BE INSTALLED ABOVE GRADE WITH

PIPING CONNECTION TO EXISTING MAINS LOCATED BELOW GRADE.

CONTRACTOR SHALL FIELD VERIFY EXISTING PIPING LOCATIONS PRIOR TO

EXCAVATING. CONTRACTOR SHALL COORDINATE TIE IN LOCATIONS AND

NEW BACKFLOW PREVENTOR LOCATION WITH THE RESIDENT ENGINEER.

CONNECT TO EXISTING 4" CW MAIN. ROUTE NEW 4" CW LINE THROUGH

BASEMENT WINDOW BOX AT BUILDING 53. CONTRACTOR SHALL VERIFY

EXISTING PIPE MATERIAL AT TIE-IN LOCATIONS. CONTRACTOR SHALL FIELD

VERIFY EXISTING PIPING LOCATIONS PRIOR TO EXCAVATING.

CONTRACTOR SHALL COORDINATE TIE IN LOCATION WITH THE RESIDENT

ENGINEER.

8" CW

8" CW

PRIMARY PUMP LOCATION

IN ROOM BC 109

ALTERNATE PUMP

LOCATION IN ROOM BC 109

APPROXIMATE LOCATION

OF ROOM BC 109

PROVIDE DOMESTIC WATER

BOOSTER PUMP SYSTEM IN

BASEMENT ROOM BC 109.

UNIT SHALL BE NO LARGER

THAN 72"W X 88" H X 60"D.

4" CW

CONTRACTOR TO TIE INTO VA FURNISHED 4"

COPPER PIPING WITH BACKFLOW PREVENTOR

IN MECHANICAL SPACE BELOW BUILDING 53.

REFER TO PL101 FOR MORE INFORMATION.

EXISTING 4" WATER

MAIN FOR BUILDING 53

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of

PS101

SITE PLAN - PLUMBING RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 SCOPRZ AARMEY 136 238

KEYED NOTES:

1. CONNECT TO EXISTING LIFT STATION.

2. REFER TO PL101 FOR CONTINUATION.

GENERAL SHEET NOTES:

1. REFER TO PL601 FOR SYMBOLS AND NOTES.

2. CONTRACTORS SHALL REVIEW ROUTING OF PIPING

PRIOR TO BID. ROUTING SHOWN IS ONE POTENTIAL ROUTE

WITH FINAL ROUTE UP TO INSTALLING CONTRACTOR TO

DETERMINE.

3. CONTRACTORS SHALL COORDINATE ROUTING OF PIPING

WITH EXISTING CONDITIONS.