Drawings - Electrical - 2.pdf

PDF 5 MB Posted

Attached to
Biloxi Building 1 Renovation - Biloxi, MS -- Y1DA
Solicitation number
QSE--36C10F24R50025
Issued by

About this file

This document contains drawings and schematics related to the fire alarm and electrical systems for the renovation of Building 1 in Biloxi, Mississippi. The drawings provide detailed specifications for the fire alarm system, including the placement of smoke detectors, pull stations, and annunciators. The electrical drawings include power riser diagrams, equipment schedules, and wiring details for the building's electrical distribution system, including panel boards, transformers, and variable frequency drives. The scope of work for the overall renovation project is described in the related federal contract opportunity, which involves selective demolition, exterior building envelope alterations, and interior renovations to the 3rd, 4th, and 5th floors of the building, as well as upgrades to the HVAC, plumbing, electrical, and telecommunications systems. The project has an estimated value between $50 million and $100 million and a period of performance of 912 calendar days.

View the file

Other files

File Type Posted
S02_Solicitation Amendment 0003.pdf PDF
C28_02821319 TILE AND MASTIC AND BRICK COATING ABATEMENT.pdf PDF
C28_02833313 LEAD PAINT REMOVAL.pdf PDF
P12_AE Addendum Two.pdf PDF
SolicitationAmendment0004.pdf PDF
P03_Justification and Approval - TekTone Nurse Call System - revised 05.24.24.pdf PDF
P12_Asbestos Report - 01.03.2022.pdf PDF
SolicitationAmendment0003.pdf PDF
52.219-28 Post-Award Small Business Program Rerepresentation.pdf PDF
Wage Determination - Harrison County MS.pdf PDF
QSE 36C10F24R50025.pdf PDF
P12_Asbestos Report - 07.06.2017.pdf PDF
S05_RFI Questions and Answers.pdf PDF
P12_Lead Based Paint Analysis - Bldg 1 - 01.11.2017.pdf PDF
S02_117300 CEILING MOUNTED PATIENT LIFTS - Revised.pdf PDF
P12_Asbestos Report - 05.06.2008.pdf PDF
P12_Addendum 1 - 05.14.2024.pdf PDF
S04_Biloxi Bldg 1 Reno - Pre-Proposal Conference Attendees.pdf PDF
SolicitationAmendment0002.pdf PDF
SolicitationAmendment0001.pdf PDF
QSE 36C10F24R50025.pdf PDF
Wage Determination - Harrison County MS.pdf PDF
52.219-28 Post-Award Small Business Program Rerepresentation.pdf PDF
Drawings - Architectural - 3.pdf PDF
General Contractor Reference Form.docx DOCX document
Drawings - Telecommunication.pdf PDF
Drawings - Architectural - 4.pdf PDF
Drawings - Reference.pdf PDF
VA Biloxi 4th Floor Footwall.pdf PDF
Drawings - Architectural - 1.pdf PDF
Building 1 Inventory - d.pdf PDF
Adec Submittal - VA Biloxi.pdf PDF
LOCQ7780-03-SWS-Biloxi VA Dental Lab.pdf PDF
Justification and Approval - Siemens Security and Video Surveillance System.pdf PDF
Past Performance Questionnaire.docx DOCX document
A-dec Floor Plan - VA Biloxi - Elevations.pdf PDF
Drawings - Structural - 2.pdf PDF
Specifications Volume II.pdf PDF
Biloxi VA Reno B1 - Set H.pdf PDF
Drawings - Plumbing - 1.pdf PDF
Drawings - Structural - 1.pdf PDF
VA Biloxi Patient Room Footwall Typical Elevation.pdf PDF
Justification and Approval - Herman Miller Compass Patient Care Modular System.pdf PDF
Solicitation.pdf PDF
000000 Cover Page Appendix.pdf PDF
Justification and Approval - ESTIII Fire Alarm System.pdf PDF
Drawings - General.pdf PDF
A-dec Floor Plan - VA Biloxi - Preliminary.pdf PDF
Drawings - Mechanical - 2.pdf PDF
Drawings - Plumbing - 2.pdf PDF
Show 40 more

Latest 50 of 64 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D

D

D

L

F

L

L

L

L

L

L

F

FAPU

FS

D S

D D

S D

C C

FS

DH

DH

F

L L

L

F

L

LL

L

FLTSLFLTSM M

D

L

L

L

FS

FAA

L

L

L

FS

D

MM

FS

FSFS

D

DH

DH

D D

FS

FS FS

FS

FS

FS

FS FS FS FS

FS

FS

FS

FS

FS

L

L

L

L

L

L

FS

FS

FS FS

L

L

L

FS

FS

FS

FS

FS

FS

L

L

L

L

L

L

L

L

FS

L

L

FS

L

L

LOC

C D

S D

C

DSD

L

DSD

DSD

DSD

C

C

C

D

FAA

PATIENT ROOM 1

3B114

PATIENT ROOM 2

3B116

PATIENT ROOM 3

3B118

PATIENT ROOM 4

3B119

CLEAN EQUIPMENT STORAGE

3B121

MD DICTATION

3B122

PATIENT ROOM 5

3B123 PATIENT ROOM 6

3B124

WHEELCHAIR ALCOVE

3B102

ELECTRICAL ROOM

3B101

PATIENT CENTERED CARE

3B103

MEDICAL GAS STORAGE

3B104

CRASH CART

3B105

HAC

3B106

CLEAN UTILITY

3B107

CLEAN LINEN

3B108

KINESIOTHERAPY

3B109

WEST STAIR

3B110

PATIENT ROOM 7 - NEGATIVE

PRESSURE

3B111

UNASSIGNED

3B113

PATIENT BATHROOM

3B111A

ANTE ROOM

3B111B

PATIENT BATHROOM

3B114A

PATIENT BATHROOM

3B118A

PATIENT BATHROOM

3B119A

PATIENT BATHROOM

3B123A

PATIENT BATHROOM

3B124A

CORRIDOR

C3-104

CENTRAL STAIR

3A101

MALE TOILET

3A102

FEMALE TOILET

3A103

FAMILY TOILET

3A104

WAITING / LOUNGE

3A105FAMILY CONSULTATION

3A106

MECHANICAL SHAFT

3A107

SOILED LINEN

3A110

ENGINEERING

3A111

HEAD NURSE / ASSISTANT MANAGER

3A112

MEDICATION ROOM

3A114

NOURISHMENT STATION

3A115

PATIENT ROOM 8

3A117

PATIENT ROOM 9

3A118

MD DICTATION

3A120

IMD SUPPLY STORAGE

3A121

PATIENT ROOM 10

3A122

PATIENT ROOM 11

3A123

BARIATRIC PATIENT ROOM 12

3A125

CONFERENCE / REPORT ROOM

3A128

PATIENT BATHROOM

3A117A PATIENT BATHROOM

3A118A

PATIENT BATHROOM

3A122A PATIENT BATHROOM

3A123A

BARIATRIC PATIENT BATHROOM

3A125A

HAC

3A127

TELEMETRY

3A130

BARIATRIC PATIENT BATHROOM

3A131A

BARIATRIC PATIENT ROOM 13 - NEG.

PRESS.

3A131

ANTE ROOM

3A131B

EAST STAIR

3A133

PHARMACY CUBICLES

3A134

MALE LOCKERS

3A137

STAFF TOILET

3A136

STAFF SHOWER

3A135

CORRIDOR

3A141

STAFF LOUNGE

3A138

FEMALE LOCKERS

3A139

TELECOMM

3A140

SOILED UTILITY

3A142

NURSE STATION

3A109A

CORRIDOR

C3-105

CORRIDOR

C3-103

NURSE SERVER

3A124

CORRIDOR

C3-109

NURSE SERVER

3A132

CORRIDOR

C3-101

NURSE SERVER

3B112

NURSE SERVER

3B125

CORRIDOR

C3-107

NURSE SERVER

3A126NURSE SERVER

3A119

NURSE SERVER

3B120NURSE SERVER

3B117

NURSE SERVER

3B115

NURSE STATION

3A109

PATIENT BATHROOM

3B116A

CORRIDOR

C3-100

CORRIDOR

C3-102

CORRIDOR

C3-102A

CORRIDOR

C3-106

CORRIDOR

C3-107A

CORRIDOR

C3-108

L

(15)(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)(15)

(15)

222019181716151413121110987654321 21

A

B

C

D

E

F

G

(15)

BPS

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)(15)

(15)

(15)

(15)

(15)

(15) (15)

(15)

(15) (15)

(15)

(15)

(15)

1 2 3 4 5 6 7 8 9

11 12

14 15 16 17 18 19 20 21 22

G

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

CENTRAL STAIR

1A101

13121110

A

B

C

D

RM 1A100

FACP

13121110

G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:2

:0

P M

FA101

3RD FLOOR - FIRE ALARM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

218 238

1/8" = 1'-0"FA101

1 3RD FLOOR - FIRE ALARM

1/8" = 1'-0"FA101

2 LEVEL 1 PARTIAL PLAN - FIRE ALARM

1/8" = 1'-0"FA101

EXISTING 1ST FLOOR PARTIAL PLAN - FIRE ALARM -

FAA LOCATION

GENERAL NOTES:

1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,

GENERAL NOTES, RENOVATION NOTES, AND

INSTALLATION NOTES.

DEDUCT ALTERNATE:

1. REFER TO GENERAL CONDITIONS SPECIFICATIONS

FOR REQUIREMENTS OF DEDUCT ALTERNATE.

Revisions: Date:

D D

D

L

F

L

L

L

L

F

FAPU

FS

D S

D D

S D

D S

D C

C C

FS

DH

DH

F

L L

L

F

L

L

LL

L

FLTSL

FLTS

M M

D

L

L

L

FS

FAA

L

L

L

D

MM

FS

FSFS

L

L

FS

L

L

DH

DH

D D

L

D

FS

FS FS

FS

FS FS FS FS

FS FS

FS

FS

L

L

L

L

FS

L

D

D

FS

L

FS

FS

L

FS

L

L

LOC

FS

L

L

L

L

L

FS

FS

L

L

FS

L

FS

FS

FS

FS

CDSD

C

DSD

CDSD

CDSD

DSD

DSD

DSD

DSD

C

C

C

C

PATIENT ROOM 1

4B114

PATIENT ROOM 2

4B116

PATIENT BATHROOM

4B116A

PATIENT BATHROOM

4B114A

PATIENT BATHROOM

4B118A

PATIENT BATHROOM

4B119A

PATIENT ROOM 3

4B118

PATIENT ROOM 4

4B119

CLEAN EQUIPMENT STORAGE

4B121

MD DICTATION

4B122

PATIENT ROOM 5

4B123

PATIENT BATHROOM

4B123A

PATIENT BATHROOM

4B124A

PATIENT ROOM 6

4B124 ENGINEERING

4A111

SOILED LINEN

4A110

STAFF EDUCATION

4A112

MEDICATION ROOM

4A114

NOURISHMENT STATION

4A115

PATIENT ROOM 8

4A117

PATIENT BATHROOM

4A117A

PATIENT BATHROOM

4A118A

PATIENT ROOM 9

4A118

IMD SUPPLY STORAGE

4A121

MD DICTATION

4A120

PATIENT ROOM 10

4A122

PATIENT BATHROOM

4A122A

PATIENT BATHROOM

4A123A

PATIENT ROOM 11

4A123

BARIATRIC PATIENT ROOM 12

4A125

BARIATRIC PATIENT BATHROOM

4A125A

CONFERENCE / REPORT ROOM

4A128

BED STORAGE

4A130BARIATRIC PATIENT BATHROOM

4A131A

BARIATRIC PATIENT ROOM 13 - NEG.

PRESS.

4A131

M.O.D. ROOM

4A134

EAST STAIR

4A133

STAFF TOILET

4A136

STAFF SHOWER

4A135

MALE LOCKERS

4A137

STAFF LOUNGE

4A138

FEMALE LOCKERS

4A139

TELECOMM

4A140

SOILED UTILITY

4A142

CORRIDOR

4A141

ANTE ROOM

4A131B

CENTRAL STAIR

4A101

MALE TOILET

4A102

FEMALE TOILET

4A103

FAMILY TOILET

4A104

FAMILY CONSULTATION

4A106

MECHANICAL SHAFT

4A107

CORRIDOR

C4-104

WAITING / LOUNGE

4A105

ELECTRICAL ROOM

4B101

PATIENT CENTERED CARE

4B103

MEDICAL GAS STORAGE

4B104

CRASH CART

4B105

HAC

4B106

CLEAN UTILITY

4B107

CLEAN LINEN

4B108

KINESIOTHERAPY

4B109

WHEELCHAIR ALCOVE

4B102

WEST STAIR

4B110

PATIENT ROOM 7 - NEGATIVE

PRESSURE

4B111

PATIENT BATHROOM

4B111A

UNASSIGNED

4B113

ANTE ROOM

4B111B

CORRIDOR

C4-103

NURSE STATION

4A109A

CORRIDOR

C4-105

CORRIDOR

C4-101

CORRIDOR

C4-107

NURSE SERVER

4B120

NURSE SERVER

4B125

NURSE SERVER

4A119

NURSE SERVER

4A124

NURSE SERVER

4A132

NURSE SERVER

4B112

HAC

4A127

NURSE SERVER

4B115

NURSE SERVER

4B117

NURSE SERVER

4A126

M.O.D. BATHROOM

4A134A

CORRIDOR

C4-109

NURSE STATION

4A109

DENTAL VAC CLOSET

4B100A

SIM

TYP

FEC

FEC FEC

NOTE: SEE SHEET "IN102" FOR INTERIOR ELEVATION REFERENCE

CORRIDOR

C4-100

CORRIDOR

C4-102

CORRIDOR

C4-102A

CORRIDOR

C4-106

CORRIDOR

C4-107A

CORRIDOR

C4-108

222019181716151413121110987654321 21

A

B

C

D

E

F

G

L

(15)(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

BPS

(15)

(15)

(15)

(15)

(15)

(30)

(30)

(30) (30)

(15)

(15)

(15)

(15)

(15)

(15)

SYSTEM

CONNECTED,

SOUNDER BASE

(15)

(15)

(15)

(15) (15)

(15) (15)

(15)

(15)

(15)

(15) (15)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:2

:1

P M

FA102

4TH FLOOR - FIRE ALARM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

219 238

1/8" = 1'-0"FA102

1 4TH FLOOR - FIRE ALARM

GENERAL NOTES:

1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,

GENERAL NOTES, RENOVATION NOTES, AND

INSTALLATION NOTES.

D

D

F

L

L

F

FS

D S

D D

S D

D S

D C

C C

FS

DH

DH

FS

L L

L

F

FLTS

L

L

L

L

L

LFAPU

L

L

L

L

L

L

L

L

L

L L

D D

DH

DH

L

L

L

L

FS

FS

FS

L

FLTS

M M

FS

FS

FS

L

L

L

FS

FS FS

M M

L

L

FS

FS

FS

L

FS

L

FS

FS

DH

DH

D D

FS

FS FS

FS

FS

FS FS FS FS

FS

FS

FS

FS

FS

FS

L

D

FS

FS

FS

FSFS

FS

FS

FS

L

L

L

L

L L

L

L

FS

L

LL

L

FS

FS

L

FSFS

L

L

FS

L

CDSD

CDSD

CDSD

L

L

IMD SUPPLY

5B122 PANORAMIC X-RAY

5B123 STERILE INSTR. STORAGE

5B128

SOILED UTILITY

5B130

EQUIPMENT STORAGE

5B135

UNISEX TOILET

5B136

DENTIST WORKSTATIONS

5B129

OPERATORY TREATMENT GENERAL

AREA

5B131

HAC

5A110

ENGINEERING

5A111

STAFF LOUNGE

5A112

MALE TOILETS / LOCKERS

5A113

FEMALE TOILETS / LOCKERS

5A114SCRUBS DISTRIBUTION

5A108

CRASH CART

5A115

PHYSICIANS CUBICLES

5A117

FILE ROOM

5A118

COPY ROOM

5A119

OFFICE

5A120

SUPPLY STORAGE

5A121

DIRECTORS CONFERENCE ROOM

5A122

MENS TOILET ROOM

5A124

CORRIDOR

C5-109

WOMENS TOILET ROOM

5A126

HAC

5A127EAST STAIR

5A128

STAFF LOUNGE

5A130

OFFICE

5A131

CUBICLES

5A134

OFFICE

5A132

OFFICE

5A133

TELECOMM

5A135

CENTRAL STAIR

5A101

FAMILY TOILET

5A102

MEDICAL CONFERENCE

5A103

DENTAL CONFERENCE

5A105

MECHANICAL SHAFT

5A106

LOBBY / LOUNGE

C5-105

ELECTRICAL ROOM

5B102

WAITING

5B103

RECEPTION / SECRETARY

5B104

COPY ROOM

5B105

DENTAL SERVICE CHIEF OFFICE

5B106

MEDICATION ROOM

5B109

AO OFFICE

5B107

WEST STAIR

5B111

TOILET ROOM

5B112

SOILED UTILITY

5B114

CORRIDOR

C5-104A

CORRIDOR

C5-104

CORRIDOR

C5-107ACORRIDOR

C5-102C

CORRIDOR

C5-106

CORRIDOR

C5-103

OPERATORY TREATMENT GENERAL

AREA

5B115

SHIPPING/ RECEIVING ROOM

5B110

DENTAL TREATMENT ROOM 1

5B116

DENTAL TREATMENT ROOM 2

5B117

DENTAL TREATMENT ROOM 3

5B118

DENTAL TREATMENT ROOM 4

5B119

DENTAL TREATMENT ROOM 6

5B121

DENTAL TREATMENT ROOM 7

5B125

DENTAL TREATMENT ROOM 8

5B126

DENTAL TREATMENT ROOM 10-

SPECIAL NEEDS

5B132

DENTAL TREATMENT ROOM 11

5B133

DENTAL TREATMENT ROOM 12

5B134

DENTAL LAB

5B113

PIPE ACCESS

5A125

DECONTAMINATION AREA

5B115A

TYP TYP

REV

REV

SIM

TYP

TYP

FEC

FEC

SOLID SURFACE

CAP (S-1)

SIM SIM

SIM, REV

NOTE: SEE SHEET "IN103" FOR INTERIOR ELEVATION REFERENCE

CORRIDOR

C5-102A

CORRIDOR

C5-102B

CORRIDOR

C5-102C

DENTAL TREATMENT ROOM 9 -

SPECIAL NEEDS

5B127

DENTAL TREATMENT ROOM 5

5B120

CORRIDOR

C5-102

CORRIDOR

C5-101

CORRIDOR

C5-107

CORRIDOR

C5-108

FEC

L (15)

(15)

(15) (15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

222019181716151413121110987654321 21

A

B

C

D

E

F

G

(30)

(30)

(15)

(15)

(15)

(15)

BPS

(15)

(15)

(15)

(15)

(15) (15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)

(15)(15)

(15)

(15)(15)

(15)

(15)

1 2 3 4 5 6 7 8 9

11 12

14 15 16 17 18 19 20 21 22

G

F

E

D

C

B

A

7.4

F.8

F.3

B.4

B.7

D.8

D.2

(75) (75)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:2

:2

P M

FA103

5TH FLOOR - FIRE ALARM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

220 238

1/8" = 1'-0"FA103

1 5TH FLOOR - FIRE ALARM

GENERAL NOTES:

1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,

GENERAL NOTES, RENOVATION NOTES, AND

L

F

D S

D

D S

D

D S

D

D S

D

D S

D

D S

D

D S

D

DSD

DSD

L

D S

D D

S D

C C

L

L

LL

L

DD

D

FS FS

FS

FS FSFS

FS FS

FS

FSFS

L

LL

C

DSDC

DSDC

DSDC

DSD

C

DSDC

L

L

DSD

DSD

ELEVATOR EQUIP ROOM

6B102

CENTRAL STAIR

6B103

ELECTRICAL ROOM

6B100A

ELECTRICAL ROOM

6B100B

RADIO ROOM

6B104

ALCOVE

6B105

FE

FE

222019181716151413121110987654321 21

A

B

C

D

E

F

G

SV

HD

(15)

(15)

HD

SV

(15)

(30)

(30)

(30)

(15) C

CCCCCC

(15)

(15)(15)

(15)

(15)

C

C

C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:2

:2

P M

FA104

ATTIC PLAN - FIRE ALARM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

221 238

1/8" = 1'-0"FA104

1 ATTIC - FIRE ALARM

GENERAL NOTES:

1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,

GENERAL NOTES, RENOVATION NOTES, AND

FIRE ALARM SYSTEM NOTES

• The location of the branch circuit disconnecting means shall be identified at all fire alarm control equipment.

• Disconnecting means for fire alarm system components shall be identified with a red marking.

• A duct smoke detector shall be provided within five feet of all fire smoke dampers and located per the requirements of the International Building Code.

• Duct smoke detectors shall be provided in all HVAC units greater than 2000 CFM per the International Building Code.

• Contractor shall refer to the mechanical drawings for drawings and details associated with the shutdown of HVAC equipment.

• HVAC units serving egress corridors shall shutdown automatically upon activation of the fire alarm system.

• A connection to the fire pump controller shall be provided for supervision.

• Contractor shall provide fire alarm connections to all kitchen hoods as required by the hood assembly. All electrical equipment located under the hood shall be shunt trip at the breaker in the panel serving the equipment via the fire alarm system.

• Heat detectors shall be provided with in 24” of each sprinkler located within the elevator hoistways, elevator pits, elevator machine rooms and elevator control rooms for shut down of elevator prior to sprinkler operation. Contractor shall coordinate with sprinkler layout and shop drawings for quantity of heat detectors to be provided. Contractor shall provide the shunt trip breaker(s) in the panel which serves the elevator equipment. The shunt trip operation shall not occur within the elevator machine/control room.

• All electrically locked doors in a required means of egress shall automatically release upon activation of the fire alarm system. Coordinate locations with architectural floor plans and door schedules.

• Emergency communication system circuits shall meet the survivability requirements as indicated in NFPA 72.

• Level 2 or Level 3 pathway survivability is required for in building emergency communications systems employing relocation or partial evacuation.

• Where two-way emergency communications systems are required/specified, fireman’s telephone jacks shall be provided at all locations as indicated in NFPA 72.

• Level 2 or Level 3 pathway survivability is required for two-way in building wired emergency communications systems.

• Level 2 or Level 3 pathway survivability is required for area of refuge wired emergency communications systems.

• A weather-proof fire alarm horn/strobe shall be provided outside of the fire sprinkler room.

• Fire alarm contractor shall provide connection to the overhead paging or voice reinforcement system as required for automatic override of those systems in the event of a fire. Coordinate with appropriate vendor for exact integration requirements.

No Scale

NOTES FOR FIRE ALARM SYSTEM

2. SMOKE DETECTOR IS AN ADDRESSED ZONE ONLY.

NOTES:

5. SOLENOID VALVE KEEPS WATER OUT OF SHAFT AND MACHINE ROOM.

3. LOBBY SMOKE DETECTOR IS ADDRESSED SPECIFICALLY BY ZONE AND INITIATES

ELEVATOR RECALL DIRECTLY (NOT THRU F.A.C.P.).

1. HEAT DETECTOR IN MACHINE ROOM OR SHAFT OR PIT (LESS THAN 2' FROM BOTTOM)

EITHER DIRECTLY OR THRU THE F.A.C.P. UPON DETECTION OF HEAT (135 F):

4. FLOW SWITCH IS A SPECIFIC ADDRESS AND INDICATES AN OPEN SPRINKLER HEAD

IN SHAFT OR MACHINE ROOM.

6. THIS SMOKE DETECTOR IS AN ADDRESSED ZONE AND LIGHTS AN L.E.D. MOUNTED

AT THE FIRE FIGHTERS OPERATION KEY SWITCH TO ALERT FIRE DEPT. PERSONEL OF

SMOKE IN ELEV. SHAFT.

SMOKE DETECTOR

HEAT DETECTOR

SOLENOID VALVE

FLOW SWITCH

TAMPER SWITCH

SPRINKLER HEAD

SD

HD

SV

FS

TS

FIRE ALARM CONTROL PANELFACP

LEGEND

SD

NOTE 1

SD

NOTE 3

SDHD SVFLTS

ELEVATOR

MACHINE

ROOM

NOTE 1

NOTE 6

NOTE 5

NOTE 4

NOTE 1

NOTE 2

A. OPENS ITS ASSOCIATED SOLENOID VALVE

B. KILLS POWER TO ELEVATOR WITH A SHUNT TRIP BREAKER.

C. IS ADDRESSED SPECIFICALLY AT THE F.A.C.P.

D. LOCATE HEAT DETECTOR WITHIN 18" FROM EACH SPRINKLER HEAD.

ALL DETECTION ASSOCIATED WITH ELEVATOR RECALL AND ELEVATOR

SHUTDOWNSHALL BE CONNECTED AND SUPERVISED THROUGH THE BUILDING FIRE

ALARM SYSTEMIN ACCORDANCE WITH NFPA 72, 3-9.3.1. CONTROL CIRCUITS TO SHUT

DOWNELEVATOR POWER SHALL BE MONITORED IN ACCORDANCE WITH NFPA 72, 3-9.4.4.

GENERAL NOTE:

No Scale

ELEVATOR FIRE ALARM SYSTEM

HD

HD

SD

NOTE 3

SD

NOTE 3

SD

NOTE 3

CAB

SD

NOTE 3

SD

NOTE 3

FIRST FLOOR

FACP

NEW

REMOTE

ANNUNCIA

TOR IN

LOBBY.

3. REFER TO MECHANICAL FOR ADDITIONAL NOTES ON SEQUENCE OF OPERATION FOR THE

SHUT DOWN OF AIR HANDLING UNITS.

GENERAL NOTES:

4. ALL MAGNETIC DOOR HOLD OPEN DEVICES ARE TO RELEASE UPON ALARM ACTIVATION.

5. ALL ACCESS CONTROL DEVICES ARE TO "UNLOCK" UPON ALARM.

(TYPICAL INSTALLATION REPRESENTED)

FIRE ALARM RISER DIAGRAM

2. FIRE ALARM SHUTDOWN

A. WHENEVER THE FIRE ALARM SYSTEM SENSES SMOKE/FIRE, THE FIRE

ALARMSYSTEM SHALL SIGNAL THE DDC SYSTEM.

B. THE DDC SYSTEM IS TO DE-ENERGIZE THE UNIT AND SHALL PERFORM

THEFOLLOWING.

1) SHUTDOWN THE SUPPLY AIR FAN

2) SHUTDOWN THE RETURN AIR FAN

3) SHUTDOWN THE ASSOCIATED EXHAUST FANS.

4) CLOSE CHILLED WATER VALVE V-CHW.

5) CLOSE THE OUTSIDE AIR DAMPER (D-OSA).

6) OPEN THE RETURN AIR DAMPER (D-RET).

NOTES:

1. PROVIDE BUILDING MAP AT THE FACP LOCATIONS AND ANNUNCIATOR THAT INDICATES

ZONES AND DEVICES. THE MAP SHALL BE ENGRAVED PHENOLIC WITH 1/4" HIGH HIGH LETTERING, SIZED AS REQUIRED.

2. PROVIDE WEATHERPROOF DEVICES WERE SHOWN OR AS REQUIRED BASED ON THE

LOCATION OF THE DEVICE.

3. RECORD AND SHOP DRAWINGS SHALL INDICATE EXACT ROUTING AND LOCATIONS OF ALL

DEVICES, CONDUITS (TYPES AND SIZES), CONDUCTORS (TYPES AND SIZES) AND ALL PERTINENT

INSTALLATION INFORMATION.

4. USE FINAL ACTUAL ROOMS NAMES AND NUMBERS BASED IN THE INSTALLATION OF

SIGNAGEAND NOT THE ARCHITECTURAL ROOM NAMES WHEN PROGRAMMING THE FINAL

SYSTEM.

1. APPROVED FIRE ALARM SHOP DRAWINGS TO BE SUBMITTED TO THE AUTHORITY

HAVING JURISDICTION.

No Scale

FIRE ALARM RISER DIAGRAM

TYPICAL THIRD THRU 5TH FLOOR

(COMPLY WITH

NFPA 72- 8.5.3.2)

D D

R

L L

D

L

BPS

D D

L

D

LL

PHONE LINES

DEDICATED

REMOTE

ANNUNCIATOR

PANEL

J

(VERIFY QUANTITIES

AND LOCATIONS, ADD

AS REQUIRED)

(VERIFY QUANTITIES

AND LOCATIONS)

TSFL

FIRE ALARM TAMPER

& FLOW SWITCHES FOR THE

BACK FLOW PREVENTER.

COORDINATE THE FINAL

LOCATIONS AND QUANTITIES.

F

INDICATING

DEVICES

INITIATING

DEVICES

INDICATING

DEVICES

INITIATING

DEVICES

CONTROL

DEVICES

ATTIC FLOOR

BPS

J

JUST OUTSIDE

RM 1A100

No Scale

FIRE ALARM RISER DIAGRAM NOTES

D D

R

L L

D

L

D D

L

D

LL

F

INDICATING

DEVICES

INITIATING

DEVICES

INDICATING

DEVICES

INITIATING

DEVICES

CONTROL

DEVICES

REMOTE

ANNUNCIATOR

PANEL

EXTEND EXISTING EDWARDS

FIRE ALARM SYSTEM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:2

:2

P M

FA201

LEGENDS AND RISER - FIRE ALARM RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

222 238

(95)

DH

PS

FS

FL

TS

E

S

DSD

D

SD

SD

HD

L

D

SYSTEM CONNECTED SMOKE DETECTOR FOR FIREMAN'S RECALL

DUCT-SMOKE DETECTOR INDICATOR LIGHT (WALL MOUNTED 10"BELOW CEILING)

HORN/FLASHING LIGHT COMBINATION (CANDELA VALUE AS SPECIFIED)

SMOKE DOOR HOLDER

FIRE SPEAKER CEILING MOUNTED

TAMPER SWITCH

PRESSURE SWITCH

FLOW SWITCH

SYSTEM CONNECTED SMOKE DETECTOR

SYSTEM CONNECTED SMOKE DETECTOR

AUTOMATIC HEAT DETECTOR (RATE OF RISE TYPE)

DUCT-SMOKE DETECTOR (SUPPLY) OR (RETURN)

BELL/FLASHING LIGHT COMBINATION

CHIME/FLASHING LIGHT COMBINATION

MANUAL PULL STATION

6'-0"

CEILING

CEILING

CEILING

80"

46"

80"

80"

NON-SYSTEM CONNECTED SMOKE DETECTOR. CONNECT TO 120V.(WITH BATTERY BACK UP.)

CEILING

WALL @ 7'

L

L

L

F

B

VCP

M

FAA

FAPU

FAST

FACC

FR

E.O.L.

C

FAPC

FACP

SV

SA

GRA

HI

GV

FIRE ALARM MONITOR MODULE, ADDRESSABLE

FIRE ALARM CONTROL MODULE, ADDRESSABLE

SPEAKER STATION WALL MOUNTED SPEAKERS TO BE DUAL CONE, LTS TO BE DUAL WHITE/AMBER

VOICE CONTROL PANEL

END OF LINE DEVICE

COMMAND CENTER

CENTRAL PROCESSING UNIT

REMOTE ANNUNCIATOR

CONTROL PANEL

TRANSPONDER

FIRESTAT

PULL CABINET

7'-0"

SOLENOID VALVE

SMOKE DETECTOR W AUDIBLE ALARM.

GENERATOR ANNUNCIATOR PANEL

LED TEXT DISPLAY FOR HEARING IMPAIRED

GAS VALVE SHUT OFF

FLASHING LIGHT SPEAKER SIGNAL STATION WALL MOUNTEDL

S

FS FLASHING LIGHT FIRE SPEAKER CEILING MOUNTEDL

FLASHING LIGHT 80"LL

FIRE ALARM SYSTEM

FLASHING LIGHT CEILING MOUNTEDL

LOC LOCAL OPERATING CONSOLE

7'-0"

BPS FIRE ALARM BOOSTER POWER SUPPLY

CONDUIT AND WIRE DESIGNATION SCHEDULE

WIRE/BKR D

E

S

IG

WIRE/BKR D

E

S

IG

MAX AMPS # DESCRIPTION MAX AMPS # DESCRIPTION

20 1 2#12, 1/2"C 200 32

20 2 2#12, 1#12G, 1/2"C 200 33 3#3/0, 1#6G, 2"C

20 3 3#12,1#12G, 1/2"C 200 34 4#3/0, 1#6G, 2"C

20 4 4#12, 1#12G, 1/2"C 230 35

30 5 2#10, 1#10G, 3/4"C 230 36 3#4/0, 1#4G, 2"C

30 6 3#10, 1#10G, 3/4"C 230 37 4#4/0, 1#4G,2-1/2"C

30 7 4#10, 1#10G, 3/4"C 255 38

40 8 2#8, 1#10G, 3/4"C 255 39 4#250MCM, 1#4G,2-1/2"C

40 9 3#8, 1#10G, 3/4"C 285 40 3#300MCM, 1#4G,2-1/2"C

40 10 4#8, 1#10G, 3/4"C 285 41 4#300MCM,1#4G,3"C

55 11 2#6, 1#10G, 3/4"C 310 42 3#350MCM,1#3G, 2-1/2"C

55 12 3#6, 1#10G, 3/4"C 310 43 4#350MCM, 1#3G, 3"C

55 13 4#6, 1#10G, 1"C 380 44 3#500MCM, 1#3G, 3"C

70 14 2#4, 1#8G, 1"C 380 45 4#500MCM,1#3G,3-1/2"C

70 15 3#4, 1#8G, 1"C 460 46 2 SETS,EA:4#4/0,1#2G.,2-1/2"C

70 16 4#4, 1#8G, 1-1/4"C 510 47 2 SETS,EA:4#250MCM,1#1G,2-1/2"C

85 17 620 48 2 SETS,EA: 4#350MCM,1#1/0G,3"C

85 18 760 49 2 SETS,EA: 4#500MCM, 1#1/0G,3-1/2"C

85 19 4#3, 1#8G, 1-1/4"C 855 50 3 SETS, EA: 4#300MCM,1#2/0G,3"C

95 20 930 51 3 SETS, EA: 4#350MCM,1#2/0G,3"C

95 21 3#2, 1#8G, 1-1/4"C 1005 52 3 SETS, EA: 4#400MCM,1#3/0G,3"C

95 22 4#2, 1#8G, 1-1/4"C 1140 53 3 SETS,EA:4#500MCM,1#3/0G,3-1/2"C

130 23 2#1, 1#6G, 1-1/4"C 1240 54 4 SETS,EA: 4#350MCM,1#4/0G,3"C

130 24 3#1, 1#6G, 1-1/4"C 1675 55 5 SETS,EA:4#400MCM,1#250MCMG,3"C

130 25 4#1, 1#6G, 1-1/2"C 1900 56 5 SETS,EA:4#500MCM,1#250MCMG,3-1/2"C

150 26 2010 57 6 SETS,EA:4#400MCM,1#350MCMG,3-1/2"C

150 27 3#1/0, 1#6G,1-1/2"C 2280 58 6 SETS,EA:4#500MCM,1#350MCMG,3-1/2"C

150 28 4#1/0, 1#6G, 2"C 2660 59 7 SETS,EA:4#500MCM,1#400MCMG,3-1/2"C

175 29 2#2/0, 1#6G, 1-1/2"C 3040 60 8 SETS, EA:4#500MCM,1#500MCMG,3-1/2"C

175 30 3#2/0, 1#6G,1-1/ 2"C 4180 61

175 31 4#2/0, 1#6G, 2"C

CONDUIT SIZE BASED ON THHN/THWN 40% FILL CALCULATION

WIRE SIZE BASED ON NEC 110-14C WITH 60°C AMPACITY TABLES FOR 20A THRU 100 AMPS

AND 75°C AMPACITY TABLES FOR VALUES > 100 AMPS.

NOTE!

IN GENERAL, THE ACTUAL BREAKER AMPERAGE SHALL BE EQUAL TO OR NEXT STANDARD SIZE

SMALLER THAN THE MAXIMUM WIRE AMPS. EXCEPTIONS SHALL BE MOTOR AND SPECIAL EQUIPMENT

BREAKERS WHICH SHALL BE SIZED PER N.E.C. AND VENDOR REQUIREMENTS. OMIT GROUND CONDUCTORS

UNLESS NOTED OTHERWISE ALL 20A., 1P. BREAKERS TO UTILIZE #12 CONDUCTORS. EXCEPT WHERE

BRANCH CIRCUIT IS IN EXCESS OF 90 LINEAR FEET CONDUCTORS TO BE #10 AND OVER 175 FEET

LINEAR FEET CONDUCTORS TO BE #8.

ON SERVICE ENTRANCE FEEDERS (TYPICAL). USE #12 WIRE U.O.N. PRIOR TO ROUGH-IN, CONTRACTOR

SHALL COORDINATE BREAKER AND WIRING WITH ACTUAL REQUIREMENTS OF EQUIPMENT BEING FURNISHED

FOR THIS SPECIFIC PROJECT.

2#3, 1#8G, 1-1/4"C

3#3, 1#8G, 1-1/4"C

2#2, 1#8G, 1-1/4"C

2#1/0, 1#6G, 1-1/2"C

2#3/0, 1#6G,2"C

2#4/0, 1#4G,2"C

3#250MCM,1#4G, 2-1/2"C

11 SETS, EA:4#500MCM,1#600MCMG,3-1/2"C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:1

:5

P M

E201

RISERS - POWER RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

223 238

BUILDING 1

POWER RISER DIAGRAM

SCALE: NTS

BUILDING 1

ONE LINE

208V, 3200A

GE TIE A

EXISTING

208V, 3200A

GE TIE B

EXISTING

UTILITY

12.4 KV

EXISTING

UTILITY

12.4 KV

EXISTING

DPA

TVSS

THIRD FLOOR

FOURTH FLOOR

FIFTH FLOOR

ATTIC MECHANICAL

208V, 1200A

3PH,4W

5NA

208V, 225A

3PH,4W

4NA

208V, 225A

3PH,4W

3NA

208V, 225A

3PH,4W

LS

ATS

L

N E

CRITICAL

ATS

DPB

TVSS

208V, 1200A

3PH,4W

5NB

208V, 225A

3PH,4W

4NB

208V, 225A

3PH,4W

3NB

208V, 225A

3PH,4W

EQDP

208V, 900A

3PH,4W L

N E

L

N E

LSDP

208V, 100A

3PH,4W

CDP

208V, 600A

3PH,4W

5LS1

208V, 100A

3PH,4W

5C1

208V, 225A

3PH,4W

4C1

208V, 125A

3PH,4W

3C1

208V, 125A

3PH,4W

TVSS TVSS

GRADE

3LS1

208V, 100A

3PH,4W

WEST WING EAST WING

500KW

GENERATOR

208V

EXISTING

208V, 100A 208V, 600A

37 37

37 37

EDP

TVSS

208V, 1200A

3PH,4W

TIE TO

EXISTING

1200AMP

BREAKER AT

GENERATOR.

4EQ1

208V, 100A

3PH,4W

TVSS

TVSS 1 CURRENT TECHNOLOGY

TVSS 2 TG3-125-208-3Y-MDT-M6E

TG3-200-208-3Y-MDT-M6E

CURRENT TECHNOLOGY

TVSS 3 TG3-080-208-3Y-MDT-M6ECURRENT TECHNOLOGY

SPD SCHEDULE

2 3 2

11 1

TVSS3

TVSS3

TVSS3

TVSS3

TVSS3

TVSS3

PROVIDE STRAIN

RELIEF PER NEC 300.19

EQUIP.

ATS

208V, 900A

DPM DPM

DPM DPM DPM

DPM

WIRE DESIGNATION

WIRE DESIGNATION

WIRE DESIGNATION

NOTES:

1. COORDINATE WITH VA FOR EQUIPMENT PURCHASED AND ONSITE.

2. REFER TO SPECIFICATION 26 05 73 FOR SYSTEM STUDY REQUIREMENTS

TYPICAL OCCUPANCY SENSOR AND DAY LIGHTING SENSOR

Pack Power

BZ-

B rn

Y lw

Grey

Purple

Sa

Sb

GRY

VIO

BLU

GRN

YLW

ORN

RED

BRN

Wires

(not used) Light level output capped

Common

+24VDC

Light Level Output 24 VDC Common

Control Output 24VDC

Normally Open Contact Common Normally Closed Contact

Isolated Relay Outputs

Occupancy Sensor

(a,b)

Dim Lighting Pendant Level Sensor

Dimming Light

LS-301

(a,b)

Dim Non-

(c)

CFLSc

Lighting Pendant

Wallwasher

White (Neutral)

Red (Load)

Wht

BlkHot

Neutral

Red (Line)

R e d

B lk

B lu

Wiring Diagram

110 V.

SUPPLY

MED. VACUUM

1. LINE PRESS. HIGH

2. LINE PRESS. LOW

3. RESERVE IN USE

4. GENERAL LOCAL

ALARM

MED. AIR

1. RESERVE IN USE

2. LINE PRESS. HIGH

3. LINE PRESS. LOW

4. DEWPOINT HIGH

5. GENERAL LOCAL

ALARM

OXYGEN:

1. CHANGE OVER

TO RESERVE

2. LIQUID LEVEL

LOW

3. RESERVE IN USE

4. RESERVE LOW

5. LINE PRESS. HIGH

6. LINE PRESS. LOW

NITROGEN

1. RESERVE IN USE

2. LINE PRESS. HIGH

3. LINE PRESS. LOW

4. RESERVE LOW

NITROUS OXIDE

1. RESERVE IN USE

2. LINE PRESS. HIGH

3. LINE PRESS. LOW

4. RESERVE LOW

C02

1. RESERVE IN USE

2. LINE PRESS. HIGH

3. LINE PRESS. LOW

4. RESERVE LOW

MASTER

ALARM PANEL

CEP CONTROL

ROOM

MASTER

ALARM PANEL

PBX

NOTE:

EACH ALARM POINT LISTED REQUIRES A STRANDED 18

GUAGE, SHIELDED TWISTED PAIR CABLE EQUAL TO

BELDEN #8451 OR WEST PENN #452. ALL WIRING IN MIN.

3/4 " CONDUIT. ALL WIRING AND CONDUIT BETWEEN THE

MASTER ALARM PANELS AND THE SOURCES, AS SHOWN,

SHALL BE PROVIDED BY AND INSTALLED BY THE

ELECTRICAL CONTRACTOR. (REFER TO MEDICAL GAS

DRAWINGS FOR ALL EQUIPMENT CONNECTIONS

REQUIRED).

No Scale

MEDICAL GAS MASTER ALARM

PANEL WIRING SCHEMATIC

HG NCONDUIT

N

H

G

NG H

WIRENUT

WHIP

NOTE:

NO REMOVAL OF ANY DEVICE SHALL INTERRUPT CONTINUITY OF GROUND CONDUCTORS.

GREEN

GROUND

SCREW

FINISHED

WALL

TYPICAL DUPLEX

RECEPTACLE

RECEPTACLE GROUND

No Scale

CONDUIT, TYP MINERAL WOOL

(FIRMLY

PACKED)FIRESTOP SEALANT

PER SECTION 07 84

00, FIRESTOPPING

9.52mm

JUNCTION BOX

(SIZE AS

REQUIRED)

CONDUIT FITTING

SPRING

NUT,

TYP

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL, TYP.FLOOR SLAB,

TYP.

STEEL

EXPANSION

ANCHOR, TYP

(3/8") MAX

FLOOR SLAB PENETRATION DETAIL

No Scale

4GROUNDING BAR DETAIL

No Scale

(2 m m

(4 m m (1")

25mm

(1")

25mm

(1")

25mm

(2")

51mm

(1 1/2") TYP

38mm

(1 m m

(5 /8 m m

6.35mm (1/4") DIA.

MOUNTING

HOLES

TYP. OF (4)

BASE CLAMP/

BRACKET

9.52mm (3/8") DIA.

HOLE TYP. OF (6)

9.52mm (3/8") x 16mm

(5/8") HEX HEAD

BOLT

9.52mm (3/8") LOCK WASHER

9.52mm (3/8") FLAT WASHER 9.52mm (3/8") LOCK WASHER

6.35mm (1/4")

THICK CU BAR

(2'-0") MIN

610mm

6.35mm (1/4") DIA.

HOLE TYP OF (8)

GENERAL NOTES:

1. ALL HARDWARE SHALL BE STAINLESS STEEL.

2. PROVIDE 1 MOUNTING POINT PER 305mm (12") OF BAR LENGTH.

3. HOLES MAY BE ADDED IF REQUIRED.

SECTION

STEEL

EXPANSION

ANCHOR

INSULATOR

9.52mm (3/8") FLAT WASHER

OCCUPANCY SENSOR DETAIL

No Scale

2 LUMINAIRE MOUNTING - LAY IN CEILING DETAIL

No Scale

LUMINAIRE

SUSPENSION

WIRES

REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST

MINIMUM

(TYP)

FIXTURE WHIP

FROM

JUNCTION BOX

(1829mm (6') LONG

MAX.)

LUMINAIRE. REFER TO SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

REFER TO SPECIFICATION

SECTION

26 51 00

ACOUSTICAL

CEILING

TILE (TYP)

ARCHITECTURA

L

CEILING GRID

LUMINAIRE.

REFER TO

SCHEDULE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

GROUND BAR

GENERAL NOTES:

NORMAL

PANEL

CRITICAL

PANEL

FEEDER

CONDUIT

UNBROKEN

GROUND

WIRE

NO. 10

LOOP

NO. 10 - 1/2" CONDUIT

(ALL PANELBOARDS,

SWITCHGEAR, ETC.)

1. IN AREAS FOR PATIENT CARE, PROVIDE GROUNDING IN ACCORDANCE

WITH NEC 517.13 AND 517.14.

2. THE EQUIPMENT GROUNDING TERMINAL BARS OF THE NORMAL AND

ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS SHALL BE BONDED

TOGETHER WITH AN INSULATED CONTINUOUS COPPER CONDUCTOR

NOT SMALLER THAN NO. 10. THIS APPLIES TO ALL PANELS SIZED

PER NEC 250.95 FOR FEEDER OVER 60 AMP. ACCEPTABLE TO

HIGH PRESS IN ORDER TO PROVIDE CONTINUOUS LOOP.

No Scale

TYPICAL EQUIPOTENTAIL GROUND SYSTEM

DIAGRAM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:1

:5

P M

E301

DETAILS - ELECTRICAL RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

224 238Revisions: Date:

CEILING MOUNTED TV OUTLETS DETAIL

No Scale

FINISHED FLOOR

CEILING

CEILING

MOUNTED TV

AND MOUNT

FURNISHED

BY OTHERS.

CAT6

VGA

HDMI

PROVIDE 1" E.C.

BACK TO TELCOM

ROOM.

RECESSED

TYPE

OUTLETS

TO

PANEL.

4"x4"

BOX AA

DETAIL A-A

TO PANEL.

TO TELCOM ROOM.

NOTE: PROVIDE IN ALL CONFERENCE ROOMS:

POWER/VGA/HDMI/DATA AT MONITOR AND PC WORKSTATION SITE .

VGA AND HDMI SHOULD BE FEMALE JACKS AT BOTH MONITOR AND

PC LOCATIONS. COORDINATE MOUNTING LOCATIONS WITH

ARCHITECT/OWNER.

RG6

POWER J-

BOX

WALL MOUNTED TV DATA/VIDEO/POWER

OUTLETS DETAIL

No Scale

A .F

.F

U O

N

ABOVE FINISHED FLOOR

L C

INSTALL 4"x4"

JUNCTION BOX

TYPICAL

PROVIDE 1" E.C.

STUB-UP ABOVE

THE ACCESSIBLE

CEILING FOR

DATA/VIDEO.

CAT6

RG6 XLR

HDMI

CEILING

A/V PULLBOX

TV BY OTHERS

ALL A/V

CABLING BACK

TO RACK

LOCATION AS

SHOWN ON

TELCOM PLAN.

RECESSED TYPE

OUTLETS TYPICAL

TO

PANEL

NOTE: PROVIDE IN AUDITORUM: POWER/VGA/HDMI/DATA/XLR/RG6

AT EACH MONITOR AND PC WORKSTATION SITE . ALL SHOULD BE

FEMALE JACKS AT BOTH MONITOR AND PC LOCATIONS.

COORDINATE MOUNTING LOCATIONS WITH ARCHITECT/OWNER.

VGAHDMI

PATIENT ROOM SENSOR SINK OUTLET

DETAIL

TYPICAL RECEPTACLE FOR

PATIENT ROOM SINK

CONTROLLER.

COORDINATE INSTALLATION

TO BE READILY ACCESSIBLE.

FAUCET

SENSOR

CONTROLLER

SINK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:1

:5

P M

E302

DETAILS - ELECTRICAL RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

225 238Revisions: Date:

T

VARIABLE FREQUENCY DRIVE SCHEDULE

STARTER TYPE: REMARKS:

PWM - PULSE WIDTH MODULATED SA - STANDARD ACCESSORIES TA - TWO CONVERTIBLE AUXILIARY CONTACTS

12PWM- 12 PULSE PWM (INCLUDES * ITEMS) ISO - ISOLATION TRANSFORMER

18PWM- 18 PULSE PWM *MA - MANUAL SPEED ADJUSTMENT *SHZ - SKIP FREQUENCY CAPABILITY

LINE DISCONNECT *ET - ELECTRONIC THERMAL OVERLOADS RSS - REMOTE START-STOP

DS - DISCONNECT SWITCH *CT - CONTROL TRANSFORMER, FUSED,

120V

RDR - REMOTE DRIVE RUN

FDS - FUSIBLE DISCONNECT SWITCH RFT - REMOTE FAULT TRIP

CB - CIRCUIT BREAKER *HA - HAND-OFF-AUTO DOOR SWITCH LR - INPUT LINE REACTOR

CONTROL: TO - MELTING THERMAL OVERLOADS HAR - PASSIVE HARMONIC FILTER

PN - 3-15 PSI PRESSURE TRANSDUCER MOL - MULTIPLE MOTOR OVERLOADS

420 - 4-20mA FOLLOWER

INPUT VOLTAGE DRIVE

ITEM

LINE

DISC.

DRIVE

BYPASS CONTROL INPUT OUTPUT PH.

H.P.

RATING TYPE

NEMA

ENCLOSURE REMARKS APPROVED MANUFACTURERS

VFD-2

EF-1

EF-2

EF-3

DS 3

CONTACT

PN

208 208 3 2 PWM 1 SA' 'LR'

VARIABLE

TORQUE

WITH BYPASS

TOSHIBA Q9 SERIES

ABB ACH 550 SERIES

YASKAWA Z1000 SERIES

VFD-3

EF-4

DS 3

CONTACT

PN

208 208 3 3 PWM 1 SA' 'LR'

VARIABLE

TORQUE

WITH BYPASS

TOSHIBA Q9 SERIES

ABB ACH 550 SERIES

YASKAWA Z1000 SERIES

VFD-15

AHU-

RETURN

DS 3

CONTACT

PN

208 208 3 15 PWM 1 SA' 'LR'

VARIABLE

TORQUE

WITH BYPASS

TOSHIBA Q9 SERIES

ABB ACH 550 SERIES

YASKAWA Z1000 SERIES

VFD-20

AHU-

5,6

RETURN

DS 3

CONTACT

PN

208 208 3 20 PWM 1 SA' 'LR'

VARIABLE

TORQUE

WITH BYPASS

TOSHIBA Q9 SERIES

ABB ACH 550 SERIES

YASKAWA Z1000 SERIES

VFD-25

AHU-

SUPPLY

DS 3

CONTACT

PN

208 208 3 25 PWM 1 SA' 'LR'

VARIABLE

TORQUE

WITH BYPASS

TOSHIBA Q9 SERIES

ABB ACH 550 SERIES

YASKAWA Z1000 SERIES

VFD-40

AHU-

5,6

SUPPLY

SCHWP-1,2

DS 3

CONTACT

PN

208 208 3 40 PWM 1 SA' 'LR'

VARIABLE

TORQUE

WITH BYPASS

TOSHIBA Q9 SERIES

ABB ACH 550 SERIES

YASKAWA Z1000 SERIES

ID ROOM NAME/DESCRIPTION V/PH KW HP FLA WIRE, CONDUIT SIZE REMARKSDISC./FUSE

POWER CONNECTION SCHEDULE

REMARKS:

1. CIRCUIT TO INCLUDE ONE (1) GREEN GROUNDING CONDUCTOR SIZED PER BRANCH CIRCUIT SIZE UNLESS SHOWN

TO BE SIZED DIFFERENTLY. ALL CONDUCTORS TYPE THW.

2. DUAL ELEMENT TYPE FUSE AND SWITCH OF PROPER VOLTAGE. IF FUSE SIZE NOT SHOWN, UNIT TO BE UNFUSED.

3. FINAL CONNECTION USING LIQUID TIGHT FLEXIBLE CONDUIT.

4. FINAL CONNECTION USING FLEXIBLE CONDUIT.

5. MOUNT ABOVE CEILING.

6. WALL MOUNTED.

7. VERIFY ALL ELECTRICAL REQUIREMENTS WITH MANUFACTURER'S SHOP DRAWINGS

8. DISCONNECT SWITCH INTEGRAL WITH UNIT.

9. EACH FAN TO BE PROTECTED SEPARATELY.

10. USE RECEPTACLE IN ACCORDANCE WITH NEC TO INSTALL THIS DEVICE.

11. MOUNT DISCONNECT ON SIDE OF UNIT.

12. VSMC/VARIABLE FREQUENCY DRIVE SCHEDULE AND SPECIFICATION SECTION 26 29 11 FOR MORE INFORMATION.

13. PROVIDE FULLY RATED MANUAL MOTOR STARTER FOR EACH FAN MOTOR IN THE SUPPLY/RETURN ARRAY FOR

OVERLOAD PROTECTION.

ATTIC AHU-5,6 SUPPLY 208/3 - 2@15 97.7 3#2/0;1#6G;1 1/2"C. 1,4,7,12,13

ATTIC EF-1,2 208/3 - 2 7.8 3#12;1#12G;3/4"C. 1,3,7,12

ATTIC EF-3 208/3 - 2 7.8 3#12;1#12G;3/4"C. 1,3,7,12

- FCU-1 THRU 5 120/1 - <1 2#12;1#12G;3/4"C. BY DIV 15 1,4,7

BLDG 53

ATTIC AHU-5,6 RETURN 208/3 - 2@7.5 50.4 3#2;1#8G;1 1/4"C. 1,4,7,12,13

RP-2 120/1 - 13.8 2#12;1#12G;3/4"C. BY DIV 15 1,4,7.75

RM6B102 EXIST. 30 ELEVATOR 208/3 - 30 92 3#1;1#6G;1-1/4"C. EXISTING 1,3,7

EXIST. 40 ELEVATOR 208/3 - 40 120 3#1/0MCM;1#6G;1-1/2"C. EXISTING 1,3,7RM6B102

EXIST. EF-7 ELEV VENT 208/3 - 1/4 1.5 3#12;1#12G;3/4"C. EXISTING 1,3,7RM6B102

EXIST. DENTAL AIR COMP. 208/3 - 2@10 62.1 3#2;1#8G;1 1/4"C. EXISTING 1,3,7ATTIC

EXIST. MED. AIR COMP. 208/3 - 2@7.5 48.3 3#2;1#8G;1 1/4"C. EXISTING 1,3,7ATTIC

EXIST. MED. VACUUM 208/3 - 2@5 32.2 3#4;1#10G;1"C. EXISTING 1,3,7ATTIC

EXIST. AIR DRYER 208/3 - 1/2 2.5 3#12;1#12G;3/4"C. EXISTING 1,3,7ATTIC

EXIST. AIR DRYER 120/1 - 1/3 7.2 2#10;1#10G;3/4"C. EXISTING 1,3,7ATTIC

EXIST. EF-1 AND 3 208/3 - 3 11 3#12;1#12G;3/4"C. EXISTING 1,3,7ATTIC

EF-4 208/3 - 3 10.6 3#12;1#12G;3/4"C. VFD BY E.C. 1,3,7,12ATTIC

SCHWP-1 AND 2 208/3 - 40 114 3#3/0;1#6G;2"C. VFD BY E.C. 1,3,7,12

PANORAMIC XRAY 120/1 - 16 2#10;1#10G;3/4"C. 5-20R RECEPTACLE 1,4,7-XRAY

BCU-1,2,3 208/3 - 1 4.6 BY DIV 15 1,3,7ATTIC 3#12;1#12G;3/4"C.

VFD BY E.C.

VFD BY E.C.

VFD BY E.C.

VFD BY E.C.

AHU-10 SUPPLY 208/3 - 66.4 VFD BY E.C. 1,4,7,12,13ATTIC 3#2;1#8G;1 1/4"C.21

AHU-10 RETURN 208/3 - 40.5 VFD BY E.C.ATTIC 3#2;1#8G;1 1/4"C.22

2@10

2@5 1,4,7,12,13

EF-5 208/3 0.5 2.4 3#12;1#12G;3/4"C. BY DIV 15 1,3,7ATTIC

DW

PW

W2

DW2

LS

ELC

H

P

P2

DUAL TECHNOLOGY WALL SWITCH/SENSOR

DUAL TECHNOLOGY WALL SWITCH/SENSOR DUAL RELAY

46"46"

46"

PASSIVE INFRARED WALL SWITCH/SENSOR

PASSIVE INFRARED WALL SWITCH/SENSOR DUAL RELAY

46"46"

46"

CEILING MOUNTED ULTRASONIC SENSOR. 2200 SF W/RELAY CEILING

CEILING MOUNTED HALLWAY SENSOR W/RELAY

DUAL VOLTAGE POWER PACK.

CEILING

ABV.CEILING

DUAL TECHNOLOGY SENSOR WALL/CORNER MOUNT 7'-6"

WALL MOUNT DIGITAL TIME SWITCH 46"

CEILING MOUNT DIMMING DAYLIGHTING PHOTOSENSOR-REQUIRES OCC-RJ45 CEILING

MANUFACTURER

SIEMENS

PASSIVE INFRARED SENSOR CEILING/WALL MOUNT

PASSIVE INFRARED CEILING SENSOR

CEILING MOUNTED ULTRASONIC SENSOR. 500SF CEILING

EMERGENCY LIGHTING CONTROL UNIT.

DUAL V. POWER PACK W/ HOLD ON & MANUAL ON DIP SW.(BI-LEVEL SWITCHING) ABV.CEILING

CEILING MOUNTED ULTRASONIC SENSOR. 1000SF CEILING

7'-6"

LIGHTING CONTROLS LEGEND

0-10v DIMMER FOR LED, VERIFY COMPATABILITY WITH LIGHT FIXTURE

DRIVER MANF'R.

46"

DC

DIMMING DAYLIGHTING CONTROLLER-THREE RELAYS, THREE

DIMMERS AND ONE EMERGENCY UL924 RELAY

REMOTE-

ACCESSIBLE

0-10v THREE WAY DIMMER FOR LED, VERIFY COMPATABILITY WITH LIGHT

FIXTURE DRIVER MANF'R.

D3 or Sd103

46"

CEILING

NOTES:

1. ULTRASONIC SENSORS SHOULD BE KEPT MINIMUM 6'

AWAY FROM

HVAC SUPPLY REGISTERS.

2. * = SEE SPECS FOR DEVICE COLOR.

DESCRIPTIONSYMBOL MOUNTING

D or Sd10

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

NOTES:

1. ALL LINEAR FIXTURES SHALL BE MINIMUM 48,000 HOURS AVERAGE LIFE.

2. SUFFIX "D" BESIDE FIXTURE ON PLANS NOTES TO SUPPLY A 0-10V DIMMING DRIVER FOR THE FIXTURE.

3. COORDINATE WITH VA FOR EQUIPMENT PURCHASED AND ONSITE.

DR COOPER METALUX 24GR-LD5-64-A125-L850

2X SEDRWEI

1X DUAL-LITE SESRWEI

11W G LIGHTING SHEFFIELD GL-4580-LED-S-NSN MODIFIED TO LED

49LED 6400 LUMEN/50K

LED 3

LED 3

LED

XR2 NEWSTAR DLM6 A L2 40 F D B 1 UN DM 29 120LED 1.3KLUM/3500K CRI 80

UC4 1SF4 L24/35 AF12125 DIM 21LED 2400 LUMEN/35K 120

5S ZL1D L48 7000LM 35K 90CRI

41R 2RTL4 48L LP835

34R SPECTRUM SGE8LEDGV-55L-35K GS

31R22 2GTL2 33L A12125 LP835

31R LITHONIA 2GTL4 40L A12125 LP835

28R ACUITY-GOTHAM EVO6WW 35/15 AR MD LSS

27R LED6WDDLM15 35K UNV 6LEDWDCLATLANTIC LIGHTING

LED 4000 LUMEN/3500K 30

41R22 2RTL2 20L LP835 21

LED 1100 LUMEN/3500K

LED 3300 LUMEN/3500K

LED 1500 LUMEN/3500K 15

LED 5500 LUMEN/3500K

LED 4800 LUMEN/3500K

LED 2000 LUMEN/3500K

LED 7000 LUMEN/3500K

UC2 H.E. WILLIAMS 1SF2 L12/35 AF12125 DIM 12LED 1200 LUMEN/35K 120

2W WL2 08L LP840 8LED 800 LUMEN/4000K 120

UC3 1SF3 L18/35 AF12125 DIM 16LED 1800 LUMEN/35K 120

1C4'

1C2' VISIONEERING LCOM24 LED 840K 023LUNV

LCOM48 LED 840K 042LUNV

TYPE MANUFACTURER MODEL NUMBER LAMP WATTS

NLT NEWSTAR SNL2 OF L 32 12 AM LED/3500K 3

LIGHTING FIXTURE SCHEDULE

LED 2300 LUMEN/4,000K 26

LED 4200 LUMEN/4,000K 42

VOLTS

E17 HUBBELL SAE105-S4-8-35K-105 38LED 1050 LUMEN/3500K 120

32R 2GTL4 60L A12125 LP835 LED 6000 LUMEN/3500K 49 120

32R22 2GTL2 40L A12125 LP835 34LED 4000 LUMEN/3500K 120

1H PRESCOLITE LBSLEDA10L30K9 WH LED 12016

LITHONIA

LITHONIA

LITHONIA

VISIONEERING

LITHONIA

LITHONIA

LITHONIA

LITHONIA

H.E. WILLIAMS

H.E. WILLIAMS

DUAL-LITE

C1 LUMENWREX POROR 12 ULO FH SW 80 1100 35 UNV LED 1100 LUMEN/3500K 11 120

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:1

:5

P M

E401

SCHEDULES - ELECTRICAL RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

226 238Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:1

:5

P M

E402

PANEL SCHEDULES - ELECTRICAL RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

227 238

[Key*:] *G = GFCI BREAKER

Total Amps: 115.9 123.5 124.11

Total Load: 13.91 kVA 14.7 kVA 14.77 kVA

-- 3C1-83 -- -- -- 0 0 1 20 A SPARE 3C1-84

-- 3C1-81 -- -- -- 0 0 1 20 A SPARE 3C1-82

3C1-79 TVSS 60 A 3 0 0 1 20 A SPARE 3C1-80

3C1-77 SPARE 20 A 1 0 0 1 20 A SPARE 3C1-78

3C1-75 SPARE 20 A 1 0 0 1 20 A SPARE 3C1-76

3C1-73 SPARE 20 A 1 0 0 1 20 A SPARE 3C1-74

3C1-71 SPARE 20 A 1 0 0 1 20 A SPARE 3C1-72

3C1-69 COPIER-3A114 20 A 1 1.2 0 1 20 A SPARE 3C1-70

3C1-67 REC-3A111 20 A 1 0.72 0.5 1 20 A DOOR ROOM 3A140 3C1-68

3C1-65 3B108 DISPEN 20 A 1 0.5 0.18 1 20 A CRASH CART C3-7 3C1-66

3C1-63 3B108 DISPEN 20 A 1 1 0.3 1 20 A REC SENSORS 114-124 3C1-64

3C1-61 RACK RM 3A140 20 A 1 1 0.3 1 20 A REC-SENSORS 114-124 3C1-62

3C1-59 RACK RM 3A140 20 A 1 1 0.9 1 20 A REC-C CONNX 117-128 3C1-60

3C1-57 PARALLEL BAR 3A131 20 A 1 0.36 1.08 1 20 A REC-C CONNX 114-124 3C1-58

3C1-55 LTS-3B114, 115 20 A 1 0.43 0.36 1 20 A PARALLEL BAR 3A125 3C1-56

3C1-53 LTS-3A134 20 A 1 0.23 0.51 1 20 A LTS-TELCOMM/SHWRS 3C1-54

3C1-51 LTS-3A128 20 A 1 0.3 0.36 1 20 A LTS -3A131 3C1-52

3C1-49 LTS-3B118, 117 20 A 1 0.37 0.51 1 20 A LTS-3A121 3C1-50

3C1-47 LTS-3A109 20 A 1 0.72 0.4 1 20 A LTS-3A111 3C1-48

3C1-45 LTS-3B118, 119 20 A 1 0.37 0.51 1 20 A LTS-3B1121 3C1-46

3C1-43 LTS-3A111 20 A 1 0.22 0.37 1 20 A LTS 3C1-44

3C1-41 LTS-3B101-107 20 A 1 0.65 0.48 1 20 A LTS-3B108, 109 3C1-42

*G 3C1-39 REC PAT LIFT 3B1114A 20 A 1 0.69 1.03 1 20 A REC PAT LIFT 3C1-40 *G

*G 3C1-37 REC PAT LIFT 3B1114 20 A 1 0.34 0.34 1 20 A REC PAT LIFT 3A131 3C1-38 *G

*G 3C1-35 REC PAT LIFT 3B1114 20 A 1 1.03 1.03 1 20 A REC PAT LIFT 3C1-36 *G

3C1-33 HEADWALL-3B111 20 A 1 0.5 0.54 1 20 A REC-3B105, 107 3C1-34

3C1-31 HEADWALL-3B119 20 A 1 0.5 0.59 1 20 A REC-3B111 3C1-32

3C1-29 HEADWALL-3B123 20 A 1 0.5 1.08 1 20 A REC-3B123, 124 3C1-30

3C1-27 REC-OMNICELL 3A1114 20 A 1 0.18 0.5 1 20 A HEADWALL-3B124 3C1-28

*G 3C1-25 REFRIG-3B115 20 A 1 1 1.08 1 20 A REC-3A109, 112 3C1-26

3C1-23 HEADWALL-3B117 20 A 1 0.5 0.72 1 20 A REC-3A113, 114 3C1-24

3C1-21 HEADWALL-3B122 20 A 1 0.5 0.5 1 20 A HEADWALL-3A118 3C1-22

3C1-19 HEADWALL-3B125 20 A 1 0.5 0.5 1 20 A HEADWALL-3A123 3C1-20

3C1-17 REC-DICTATION 20 A 1 0.72 0.54 1 20 A REC-3A117, 118 3C1-18

3C1-15 REC-3B130 20 A 1 0.9 0.9 1 20 A REC-3A122, 123 3C1-16

3C1-13 REC-3B134 20 A 1 0.72 0.9 1 20 A REC-3A130 3C1-14

3C1-11 REC-3B134 20 A 1 0.72 0.72 1 20 A REC-3A134 3C1-12

3C1-9 HEADWALL-3B114 20 A 1 0.5 0.72 1 20 A REC-3A140 TELCOMM 3C1-10

3C1-7 REC 3B140 TELCOMM 20 A 1 1.08 0.72 1 20 A REC-3A140 TELCOMM 3C1-8

3C1-5 REC 3B140 TELCOMM 20 A 1 1.26 0.5 1 20 A HEADWALL-3B131 3C1-6

3C1-3 REC-3B118, 119 20 A 1 1.26 0.59 1 20 A REC 3C1-4

3C1-1 REC 20 A 1 0.5 0.5 1 20 A HEADWALL-3B117 3C1-2

CKT NO. LOAD DESCRIPTION

OVERCURREN

T PROTECTION

AMPS P

A B C

OVERCURREN

T PROTECTION

P AMPS LOAD DESCRIPTION CKT NO.

Panel Notes:

LOCATION: ELECTRICAL ROOM 3B101 DEMAND: 20.35 kVA

SCCR: 22,000 WIRE: 4

FED FROM: PANEL CDP GROUND BUS PHASE: 3

MOUNTING: Surface SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 125 A/MCB

PANEL NAME: 3C1 CONNECTED 43.4 kVA

[Key*:]

Total Amps: 32.88 20.13 12.61

Total Load: 3.83 kVA 2.3 kVA 1.51 kVA

-- 3LS1-29 -- -- -- 0 0 1 20 A SPARE 3LS1-30

-- 3LS1-27 -- -- -- 0 0 1 20 A SPARE 3LS1-28

3LS1-25 TVSS 60 A 3 0 0 1 20 A SPARE 3LS1-26

3LS1-23 SPARE 20 A 1 0 0 1 20 A SPARE 3LS1-24

3LS1-21 SPARE 20 A 1 0 0 1 20 A SPARE 3LS1-22

3LS1-19 SPARE 20 A 1 0 0 1 20 A SPARE 3LS1-20

3LS1-17 SPARE 20 A 1 0 0 1 20 A SPARE 3LS1-18

3LS1-15 LTS CORR 4B100 20 A 1 0.3 0.42 1 20 A LTS 4A139, 102, 103&4 3LS1-16

3LS1-13 LTS LOBBY 4A100 20 A 1 0.13 0.31 1 20 A LTS 4A116 3LS1-14

3LS1-11 LTS CORR 3A116 20 A 1 0.24 0.29 1 20 A LTS CORR 3B100 3LS1-12

3LS1-9 LTS LOBBY 3A100 20 A 1 0.13 0.48 1 20 A LTS TLT LOCKERS 3A141 3LS1-10

3LS1-7 FIRE ALARM BOOSTER 20 A 1 1.2 1.2 1 20 A FIRE ALARM BOOSTER 3LS1-8

3LS1-5 FIRE ALARM PANEL 20 A 1 0.5 0.5 1 20 A MED GAS ALARM 3LS1-6

3LS1-3 DOOR HOLDER 20 A 1 0.5 0.5 1 20 A MED GAS ALARM 3LS1-4

3LS1-1 DOOR HOLDER 20 A 1 0.5 0.5 1 20 A MED GAS ALARM 3LS1-2

CKT NO. LOAD DESCRIPTION

OVERCURREN

T PROTECTION

AMPS P

A B C

OVERCURREN

T PROTECTION

P AMPS LOAD DESCRIPTION CKT NO.

Panel Notes:

LOCATION: ELECTRICAL ROOM 3B101 DEMAND: 5.18 kVA

SCCR: 22,000 WIRE: 4

FED FROM: PANEL LSDP GROUND BUS PHASE: 3

MOUNTING: Surface SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 60 A/MCB

PANEL NAME: 3LS1 CONNECTED 7.1 kVA

[Key*:] *G = GFCI BREAKER

Total Amps: 123.75 110.03 98.91

Total Load: 14.67 kVA 13.03 kVA 11.87 kVA

-- 4C1-83 -- -- -- 0 0 1 20 A SPARE 4C1-84

-- 4C1-81 -- -- -- 0 0 1 20 A SPARE 4C1-82

4C1-79 TVSS 60 A 3 0 0 1 20 A SPARE 4C1-80

4C1-77 SPARE 20 A 1 0 0 1 20 A SPARE 4C1-78

4C1-75 SPARE 20 A 1 0 0 1 20 A SPARE 4C1-76

4C1-73 SPARE 20 A 1 0 0 1 20 A SPARE 4C1-74

4C1-71 SPARE 20 A 1 0 0 1 20 A SPARE 4C1-72

4C1-69 SPARE 20 A 1 0 0 1 20 A SPARE 4C1-70

4C1-67 REC-COPIER 4A114 20 A 1 1.2 0 1 20 A SPARE 4C1-68

4C1-65 REC-4A111 20 A 1 0.72 0.5 1 20 A DOOR ROOM 4A140 4C1-66

4C1-63 4B108 DISPEN 20 A 1 0.5 0.18 1 20 A CRASH CART C3-7 4C1-64

4C1-61 4B108 DISPEN 20 A 1 1 1 1 20 A RACK RM 4A140 4C1-62

4C1-59 REC SENSOR SINKS 20 A 1 0.3 1 1 20 A RACK RM 4A140 4C1-60

*G 4C1-57 REC PAT LIFT 7 20 A 1 0.34 0.3 1 20 A REC SENSOR SINKS 4C1-58

*G 4C1-55 REC PAT LIFT 4,5,6 20 A 1 1.03 1.03 1 20 A REC PAT LIFT 1,2,3 4C1-56 *G

*G 4C1-53 REC PAT LIFT 11,12 20 A 1 0.69 0.34 1 20 A REC PAT LIFT 13 4C1-54 *G

*G 4C1-51 REC PAT LIFT 8,9,10 20 A 1 1.03 0.9 1 20 A REC C CONX 117-125 4C1-52

4C1-49 REC-MOT PARALLEL BAR 4A131 20 A 1 0.36 1.08 1 20 A REC C CONX 114-124 4C1-50

4C1-47 HEADWALL-4B114 20 A 1 0.5 0.05 1 20 A VAV BOX MED GAS STO 4C1-48

4C1-45 LTS-4B123, 124 20 A 1 0.51 0.36 1 20 A REC-MOTORIZED PARALLEL BAR 4C1-46

4C1-43 LTS-4B118, 119 20 A 1 0.37 0.37 1 20 A LTS-4B118, 119 4C1-44

4C1-41 LTS-4B106-4B109 20 A 1 0.69 0.2 1 20 A LTS-4B111 4C1-42

4C1-39 LTS-4A140, 142 20 A 1 0.56 0.59 1 20 A LTS-4B103, 104, 105 4C1-40

4C1-37 LTS-4A131 20 A 1 0.18 0.12 1 20 A LTS-4A134 4C1-38

4C1-35 LTS-4A121 20 A 1 0.51 0.3 1 20 A LTS-4A125, 128 4C1-36

4C1-33 LTS-NURSE STATION 20 A 1 0.72 0.37 1 20 A LTS-4A117, 118 4C1-34

4C1-31 LTS-4A110, 111, 112 20 A 1 0.4 0.44 1 20 A LTS-4A114, 115 4C1-32

4C1-29 REC-4B111 20 A 1 0.5 0.36 1 20 A REC-4B107 4C1-30

4C1-27 REC-OMNICELL 20 A 1 0.18 1 1 20 A REFRIG-4A115 4C1-28

4C1-25 REC-4B111 20 A 1 0.59 0.18 1 20 A REC-4B105 CRASH CART 4C1-26

4C1-23 REC-4B114, 116 20 A 1 0.54 0.72 1 20 A REC-4B114, 116 4C1-24

4C1-21 HEADWALL-4B118 20 A 1 0.5 0.5 1 20 A HEADWALL-4B116 4C1-22

4C1-19 HEADWALL-4B123 20 A 1 0.5 0.5 1 20 A HEADWALL-4B119 4C1-20

4C1-17 HEADWALL-4B124 20 A 1 0.5 1.08 1 20 A REC-4B123, 124 4C1-18

4C1-15 REC-4A114 20 A 1 0.72 1.08 1 20 A REC-4A112 4C1-16

4C1-13 HEADWALL-4A117 20 A 1 0.5 0.54 1 20 A REC-4A117, 118 4C1-14

4C1-11 REC-4A120 20 A 1 0.72 0.5 1 20 A HEADWALL-4A118 4C1-12

4C1-9 HEADWALL-4A123 20 A 1 0.5 0.5 1 20 A HEADWALL-4A122 4C1-10

4C1-7 HEADWALL-4A125 20 A 1 0.5 0.9 1 20 A REC-4A122, 123, 125 4C1-8

4C1-5 REC-4A130 20 A 1 0.77 0.5 1 20 A HEADWALL-4A130 4C1-6

4C1-3 REC-TELCOMM 4A139 20 A 1 1.08 0.72 1 20 A REC-TELCOMM 4A139 4C1-4

4C1-1 REC-TELCOMM 4A139 20 A 1 1.08 0.9 1 20 A REC-TELCOMM 4A139 4C1-2

CKT NO. LOAD DESCRIPTION

OVERCURREN

T PROTECTION

AMPS P

A B C

OVERCURREN

T PROTECTION

P AMPS LOAD DESCRIPTION CKT NO.

Panel Notes:

LOCATION: ELECTRICAL ROOM 4B101 DEMAND: 19.4 kVA

SCCR: 22,000 WIRE: 4

FED FROM: PANEL CDP GROUND BUS PHASE: 3

MOUNTING: Surface SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 125 A/MCB

PANEL NAME: 4C1 CONNECTED 39.6 kVA

[Key*:] *G = GFCI BREAKER

Total Amps: 100.43 100.21 66.01

Total Load: 11.51 kVA 11.48 kVA 7.92 kVA

3NA-83 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-84

3NA-81 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-82

3NA-79 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-80

3NA-77 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-78

3NA-75 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-76

3NA-73 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-74

3NA-71 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-72

3NA-69 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-70

3NA-67 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-68

3NA-65 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-66

3NA-63 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-64

3NA-61 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-62

3NA-59 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-60

3NA-57 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-58

3NA-55 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-56

3NA-53 SPARE 20 A 1 0 0 1 20 A SPARE 3NA-54

3NA-51 VAV BOXES CORR 20 A 1 0.4 0 1 20 A SPARE 3NA-52

3NA-49 LTS-CORR 3A116 20 A 1 0.5 0.25 1 20 A VAV BOXES LOCKERS 3NA-50

3NA-47 LTS-CORRIDOR C3-107, 108, 109 20 A 1 0.15 0 1 20 A SPARE 3NA-48

3NA-45 LTS-3A125, 127, 128 20 A 1 0.34 0.11 1 20 A LTS -3A131 3NA-46

3NA-43 LTS-3A117, 3A118 20 A 1 0.2 0.29 1 20 A LTS-3A121, 122, 123 3NA-44

3NA-41 LTS LOCKERS, LOUNGE 20 A 1 0.38 0.16 1 20 A LTS-CORRIDOR 3C-106 3NA-42

3NA-39 LTS 3A105, 3A106 20 A 1 0.63 0.6 1 20 A LTS SCONCES 3A100 3NA-40

3NA-37 HEADWALL 3A117 20 A 1 0.5 0.88 1 20 A REC - 3A117 BATH 3NA-38

3NA-35 HEADWALL 3A118 20 A 1 0.5 0.88 1 20 A REC - 3A118 BATH 3NA-36

3NA-33 HEADWALL 3A122 20 A 1 0.5 0.88 1 20 A REC - 3A122 BATH 3NA-34

3NA-31 HEADWALL 3A123 20 A 1 0.5 0.88 1 20 A REC - 3A123 BATH 3NA-32

3NA-29 HEADWALL 3A125 20 A 1 0.5 0.88 1 20 A REC - 3A125 BATH 3NA-30

*G 3NA-27 REC - 3A115 20 A 1 0.18 1 1 20 A WATER COOLERS 3NA-28 *G

3NA-25 REC - 3A121 20 A 1 0.54 0.8 1 20 A MICROWAVE 3A115 3NA-26 *G

3NA-23 MONITOR 3A128 20 A 1 0.18 0 1 20 A SPARE 3NA-24

3NA-21 REC - 3A128 20 A 1 0.72 0.9 1 20 A REC-3A128 3NA-22

3NA-19 REC - 3A136 20 A 1 0.18 0.72 1 20 A REC-3A134 3NA-20

*G 3NA-17 MICROWAVE 3A138 20 A 1 0.8 0.18 1 20 A REC-3A135 3NA-18

*G 3NA-15 REC - 3A138 20 A 1 1.3 0.72 1 20 A REC-3A138 3NA-16

3NA-13 REC - 3A114, 3A115 20 A 1 0.72 0.9 1 20 A REC-3A141, 137, 138 3NA-14

3NA-11 COPIER-3A113 20 A 1 1.2 0 1 20 A SPARE 3NA-12

3NA-9 REC - 3A116 20 A 1 1.08 1.2 1 20 A COPIER-3A112 3NA-10

3NA-7 REC - 3A108, 3A113 20 A 1 0.9 0.9 1 20 A REC-3A109, 114, 115 3NA-8

3NA-5 REC - 3A105 20 A 1 1.08 1.08 1 20 A REC-3A102,103,104&5 3NA-6

3NA-3 REC- VENDING 3A100 20 A 1 0.5 0.5 1 20 A REC - VENDING 3A100 3NA-4

3NA-1 HEADWALL 3A131 20 A 1 0.5 1.41 1 20 A REC-3A131 ANTE BATH 3NA-2

CKT NO. LOAD DESCRIPTION

OVERCURREN

T PROTECTION

AMPS P

A B C

OVERCURREN

T PROTECTION

P AMPS LOAD DESCRIPTION CKT NO.

Panel Notes:

LOCATION: ELECTRICAL ROOM 3B101 DEMAND: 18.32 kVA

SCCR: 22,000 WIRE: 4

FED FROM: PANEL DPA GROUND BUS PHASE: 3

MOUNTING: Surface SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 225 A/MCB

PANEL NAME: 3NA CONNECTED 30.9 kVA

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

520-317X

Dwg. of fi le s \C o rp o ra te \T e a m s \C

S L

E G

\B

IM

D o c u m e n ts \1

.0

\R e v it \I C

T

B

L D

G

E le c tr ic a l C

D S

.r v t

/1 /2

:1

:5

P M

E403

PANEL SCHEDULES - ELECTRICAL RENOVATE BUILDING 1

BILOXI, MISSISSIPPI

10/27/2023 IMEG STEWIE

228 238

[Key*:]

Total Amps: 8.08 8.08 3.75

Total Load: 0.9 kVA 0.9 kVA 0.45 kVA

-- 4EQ1-29 -- -- -- 0 0 1 20 A SPARE 4EQ1-30

-- 4EQ1-27 -- -- -- 0 0 1 20 A SPARE 4EQ1-28

4EQ1-25 TVSS 60 A 3 0 0 1 20 A SPARE 4EQ1-26

4EQ1-23 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-24

4EQ1-21 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-22

4EQ1-19 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-20

4EQ1-17 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-18

4EQ1-15 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-16

4EQ1-13 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-14

4EQ1-11 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-12

4EQ1-9 SPARE 20 A 1 0 0 1 20 A SPARE 4EQ1-10

4EQ1-7 ROOM PRESSURE MONITORING 20 A 1 0.35 0 1 20 A SPARE 4EQ1-8

4EQ1-5 VAV BOX PATIENT 20 A 1 0.45 0 1 20 A SPARE 4EQ1-6

4EQ1-3 VAV BOX NURSE, 8 - 12 20 A 1 0.45 0.45 1 20 A VAV BOX NURSE, 1-7 4EQ1-4

4EQ1-1 VAV BOX PAT 13 20 A 1 0.15 0.4 1 20 A VAV BOX NURSE, 8 - 13 4EQ1-2

CKT NO. LOAD DESCRIPTION

OVERCURREN

T PROTECTION

AMPS P

A B C

OVERCURREN

T PROTECTION

P AMPS LOAD DESCRIPTION CKT NO.

Panel Notes:

LOCATION: ELECTRICAL ROOM 4B101 DEMAND: 2.25 kVA

SCCR: 22,000 WIRE: 4

FED FROM: PANEL EQDP GROUND BUS PHASE: 3

MOUNTING: Surface SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 100 A/MCB

PANEL NAME: 4EQ1 CONNECTED 2.3 kVA

[Key*:] *G = GFCI BREAKER

Total Amps: 148.08 98.31 128.47

Total Load: 17.29 kVA 11.8 kVA 14.93 kVA

5NA-83 SPARE 20 A 1 0 0 1 20 A SPARE 5NA-84

5NA-81 SPARE 20 A 1 0 0 1 20 A SPARE 5NA-82

5NA-79 SPARE 20 A 1 0 0 1 20 A SPARE 5NA-80

5NA-77 SPARE 20 A 1 0 0 1 20 A SPARE 5NA-78

5NA-75 SPARE 20 A 1 0 0 1 20 A SPARE 5NA-76

5NA-73 SPARE 20 A 1 0 0 1 20 A SPARE 5NA-74

5NA-71 SPARE 20 A 1 0 0 1 20 A SPARE 5NA-72

5NA-69…