Drawings - Structural - 2.pdf
PDF 4 MB Posted
- Solicitation number
- QSE--36C10F24R50025
About this file
This document contains structural drawings and related information for the renovation of Building 1 in Biloxi, Mississippi. The renovation will include selective demolition, exterior building envelope alterations, and interior renovation of areas within Building 1. Key elements include upgrades to the interior utilities and building systems such as HVAC, plumbing, electrical, telecommunications, and fire protection systems. There will also be limited structural, mechanical, and electrical work related to the underside of the 3rd floor structure within the occupied areas of the 2nd floor. The contractor will be responsible for monitoring the existing Building 1 foundation system throughout the project. The period of performance is 912 calendar days, and the project magnitude is between $50M to $100M. Wage Rate Requirements (Construction) apply.
View the file
Other files
Show 40 more
Latest 50 of 64 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
222019 21
B
C
D
E
F
G
181716151413121110987654321
'-7
'-5
'-1
1/ 2"
'-0
'-1
1/ 2"
'-5
277' - 7"
11' - 9 1/2" 13' - 0" 11' - 9 1/2" 14' - 9 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 14' - 9 1/2" 14' - 3" 13' - 1" 14' - 3" 14' - 9 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 14' - 9 1/2" 11' - 9 1/2" 13' - 0" 11' - 9 1/2"
PHOTO 4-4
PHOTO 4-1
PHOTO 4-5
PHOTO 4-8
PHOTO 4-9
PHOTO 4-7
PHOTO 4-6
PHOTO 4-3PHOTO 4-2
PHOTO 4-10
1/8" = 1'-0"1 FOURTH FLOOR FRAMING CONCRETE REPAIR PLAN
PLAN NORTH
NOTES:
1. REFER TO SHEET S163 FOR PHOTOS REFERENCED IN
THIS PLAN AND ACCOMPANYING REPAIR REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
PHOTO LOCATION PLAN
S160 2210/27/2023
222019181716151413121110 21987654321
C
D
E
F
G
277' - 7"
11' - 9 1/2" 13' - 0" 11' - 9 1/2" 14' - 9 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 14' - 9 1/2" 14' - 3" 13' - 1" 14' - 3" 14' - 9 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 14' - 9 1/2" 11' - 9 1/2" 13' - 0" 11' - 9 1/2"
'-7
'-5
'-1
1/ 2"
'-0
'-1
1/ 2"
'-5
PHOTO 5-2
PHOTO 5-1 PHOTO 5-3
PHOTO 5-4
PHOTO 5-5
PHOTO 5-6
PHOTO 5-7
PHOTO 5-8
PHOTO 5-9
PHOTO 5-10
PHOTO 5-11
1/8" = 1'-0"1 FIFTH FLOOR FRAMING CONCRETE REPAIR PLAN
PLAN NORTH
NOTES:
1. REFER TO SHEET S164 FOR PHOTOS REFERENCED IN
THIS PLAN AND ACCOMPANYING REPAIR REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
PHOTO LOCATION PLAN
S161 2310/27/2023
C
D
E
F
G
222019181716151413121110987654321 21 6" 6"
1/ 2"
1/ 2"
277' - 7"
11' - 9 1/2" 13' - 0" 11' - 9 1/2" 14' - 9 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 14' - 9 1/2" 14' - 3" 13' - 1" 14' - 3" 14' - 9 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 12' - 11 1/2" 14' - 9 1/2" 11' - 9 1/2" 13' - 0" 11' - 9 1/2"
PHOTO A-6
PHOTO A-7
PHOTO A-8
PHOTO A-5
PHOTO A-4
PHOTO A-3
PHOTO A-2
PHOTO A-1
PHOTO A-9 PHOTO A-10
1/8" = 1'-0"1
ATTIC FRAMING CONCRETE REPAIR PLAN
PLAN NORTH
NOTES:
1. REFER TO SHEET S165 FOR PHOTOS REFERENCED IN
THIS PLAN AND ACCOMPANYING REPAIR REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
PHOTO LOCATION PLAN
S162 2410/27/2023
INFILL RECTANGULAR OPENINGS BETWEEN CONCRETE JOISTS PER DETAIL 1 / S142.
PATCH ROUND HOLES IN SLAB UP TO 12" IN DIAMETER PER DETAIL 3 OR 4 / S142.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
1 2PHOTO 4-1
PREPARE THE CONCRETE SLAB BY CHIPPING AWAY ANY DELETERIOUS
MATERIALS AND ROUGHENING THE AREAS THAT WILL RECEIVE SIKATOP 122 PLUS. IF ANY
STEEL REINFORCING IS EXPOSED, CLEAN CORROSION WITH A WIRE BRUSH.
COAT ANY REINFORCING STEEL WITH ARMATEC AND ALLOW TO DRY. APPLY ADDITIONAL
COAT OF ARMATEC AS A BONDING AGENT TO THE ENTIRE REPAIR AREA. REPAIR CONCRETE
USING REPAIR PROCEDURE FOR SIKATOP, ACI RAP BULLETIN 1: FIELD GUIDE TO CONCRETE
REPAIR APPLICATION PROCEDURES, ACI RAP BULLETIN 4, 5 AND 6, AND ACI 546R-14: CONCRETE
REPAIR GUIDE, SEPT. 2014.
KEYNOTES:
= FILL HOLES SOLID WITH NON-SHRINK, NON-METALLIC GROUT. MINIMUM GROUT STRENGTH = 5000 PSI.
FOURTH FLOOR
NOTE:
IF 10% OR MORE SECTION LOSS FOR REINFORCING STEEL IS FOUND,
NOTIFY CONTRACTING OFFICER TO REVIEW AND DETERMINE IF SUPPLEMENTAL
REINFORCING IS REQUIRED.
STRUCTURAL REPAIR PHOTOS
S163
PHOTO 4-2 - & 4 PHOTO 4-3 - 2PHOTO 4-4 -
PHOTO 4-5 - PHOTO 4-6 - 4PHOTO 4-7 - PHOTO 4-8 -
2PHOTO 4-9 -
5 = REPLACE CAPACITY OF PENETRATED CONCRETE JOIST BY INSTALLING NEW STEEL CHANNELS ON
EACH SIDE SIMILAR TO DETAIL 1 / S140. PATCH HOLES IN CONCRETE SLAB PER 4 / S142.
6 = REMOVE UNUSED STEEL RAILS AS REQUIRED AND REPLACE CAPACITY OF CONCRETE JOIST BY INSTALLING NEW STEEL CHANNELS ON EACH SIDE PER DETAIL 1 / S140. PATCH SLAB PER 5 / S142.
7 = PROVIDE ADDITIONAL FRAMING AND PATCH LARGE HOLE IN SLAB PER DETAIL 6 / S140.
6 7 3&1
5&1
8 = PROVIDE STEEL SHIM BETWEEN STEEL AND UNDERSIDE OF SLAB, PER 9 / S142.
8PHOTO 4-10 -
10/27/2023
2PHOTO 5-1
4 PREPARE THE CONCRETE SLAB BY CHIPPING AWAY ANY DELETERIOUS
MATERIALS AND ROUGHENING THE AREAS THAT WILL RECEIVE SIKATOP 122 PLUS. IF ANY
STEEL REINFORCING IS EXPOSED, CLEAN CORROSION WITH A WIRE BRUSH.
COAT ANY REINFORCING STEEL WITH ARMATEC AND ALLOW TO DRY. APPLY ADDITIONAL
COAT OF ARMATEC AS A BONDING AGENT TO THE ENTIRE REPAIR AREA. REPAIR CONCRETE
USING REPAIR PROCEDURE FOR SIKATOP, ACI RAP BULLETIN 1: FIELD GUIDE TO CONCRETE
REPAIR APPLICATION PROCEDURES, ACI RAP BULLETIN 4, 5 AND 6, AND ACI 546R-14:
CONCRETE REPAIR GUIDE, SEPT. 2014.
FIFTH FLOOR
KEYNOTES:
= FILL HOLES SOLID WITH NON-SHRINK, NON-METALLIC GROUT. MINIMUM GROUT STRENGTH = 5000 PSI.
= INFILL RECTANGULAR OPENINGS BETWEEN CONCRETE JOISTS PER DETAIL 1 / S142.
= PATCH ROUND HOLES IN SLAB UP TO 12" IN DIAMETER PER DETAIL 3 OR 4 / S142.
NOTE:
IF 10% OR MORE SECTION LOSS FOR REINFORCING STEEL IS FOUND,
NOTIFY CONTRACTING OFFICER TO REVIEW AND DETERMINE IF SUPPLEMENTAL
REINFORCING IS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
STRUCTURAL REPAIR PHOTOS
S164
4PHOTO 5-2 - PHOTO 5-3 - 2PHOTO 5-4 -
2PHOTO 5-5 - PHOTO 5-6 - PHOTO 5-7 - PHOTO 5-8 -
4PHOTO 5-9 - PHOTO 5-10 - PHOTO 5-11 -
6 7 4
5 = REPLACE CAPACITY OF PENETRATED CONCRETE JOIST BY INSTALLING NEW STEEL CHANNELS ON
EACH SIDE SIMILAR TO DETAIL 1 / S140. PATCH HOLES IN CONCRETE SLAB PER 4 / S142.
6 = REMOVE UNUSED STEEL RAILS AS REQUIRED AND REPLACE CAPACITY OF CONCRETE JOIST BY INSTALLING NEW STEEL CHANNELS ON EACH SIDE PER DETAIL 1 / S140. PATCH SLAB PER 5 / S142.
7 = PROVIDE ADDITIONAL FRAMING AND PATCH LARGE HOLE IN SLAB PER DETAIL 6 / S140.
2 5&
5&
13 4&1 5&
PREPARE THE CONCRETE SLAB BY CHIPPING AWAY ANY DELETERIOUS
MATERIALS AND ROUGHENING THE AREAS THAT WILL RECEIVE SIKATOP 122 PLUS. IF ANY
STEEL REINFORCING IS EXPOSED, CLEAN CORROSION WITH A WIRE BRUSH.
COAT ANY REINFORCING STEEL WITH ARMATEC AND ALLOW TO DRY. APPLY ADDITIONAL
COAT OF ARMATEC AS A BONDING AGENT TO THE ENTIRE REPAIR AREA. REPAIR CONCRETE
USING REPAIR PROCEDURE FOR SIKATOP, ACI RAP BULLETIN 1: FIELD GUIDE TO CONCRETE
REPAIR APPLICATION PROCEDURES, ACI RAP BULLETIN 4, 5 AND 6, AND ACI 546R-14:
CONCRETE REPAIR GUIDE, SEPT. 2014.
ATTIC
PHOTO A-1 PHOTO A-2 -
KEYNOTES:
= NOT USED ON THIS SHEET.
= INFILL RECTANGULAR OPENINGS BETWEEN CONCRETE JOISTS PER DETAIL 1 / S142.
= NOT USED ON THIS SHEET.
NOTE:
IF 10% OR MORE SECTION LOSS FOR REINFORCING STEEL IS FOUND,
NOTIFY CONTRACTING OFFICER TO REVIEW AND DETERMINE IF SUPPLEMENTAL
REINFORCING IS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
STRUCTURAL REPAIR PHOTOS
S165
4 PHOTO A-3 - 4 5& PHOTO A-4 - 2
PHOTO A-5 PHOTO A-6
- 4
- 2 - PHOTO A-7 - PHOTO A-8
USE REPAIR DETAIL 2/S142 FOR RESTORATION OF DETERIORATED CONCRETE JOISTS.5 =
6 6
REPLACE CAPACITY OF PENETRATED CONCRETE JOIST BY INSTALLING NEW STEEL CHANNELS ON EACH SIDE PER DETAIL 1 / S140. PATCH HOLES IN CONCRETE SLAB SIM TO DETAIL 1 / S142.
6 =
- 7
FILL HOLE IN ATTIC SLAB PER DETAIL 8 / S140.7 =
PROVIDE ADDITIONAL FRAMING AND PATCH LARGE HOLE IN SLAB SIMILAR TO DETAIL 6 / S140.8 =
PHOTO A-9 - 2 PHOTO A-10 6-
1. THE STRUCTURAL PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE REQUIREMENTS OF THE
INTERNATIONAL BUILDING CODE 2012 EDITION.
2. THE STRUCTURAL DOCUMENTS ARE TO BE USED IN CONJUNCTION WITH THE ARCHITECTURAL DOCUMENTS.
3. USE THESE NOTES IN CONJUNCTION WITH THE SPECIFICATIONS. IF A CONFLICT EXISTS, THE MORE STRINGENT
REQUIREMENT GOVERNS.
4. REVIEW ALL CONTRACT DOCUMENTS, DIMENSIONS AND SITE CONDITIONS AND COORDINATE WITH FIELD DIMENSIONS AND PROJECT SHOP DRAWINGS PRIOR TO CONSTRUCTION. REPORT ANY DISCREPANCIES IN WRITING TO THE RESIDENT ENGINEER. DO NOT CHANGE SIZE OR DIMENSIONS OF STRUCTURAL MEMBERS WITHOUT THE
WRITTEN INSTRUCTION FROM THE RESIDENT ENGINEER.
5. PROTECT EXISTING FACILITIES, STRUCTURES AND UTILITY LINES FROM ALL DAMAGE. EACH CONTRACTOR SHALL PROTECT HIS WORK, ADJACENT PROPERTY AND THE PUBLIC. EACH CONTRACTOR IS SOLELY RESPONSIBLE FOR
DAMAGE OR INJURY DUE TO HIS ACT OR NEGLECT.
6. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR JOB SAFETY AND CONSTRUCTION PROCEDURES.
7. DO NOT SCALE DRAWINGS; USE DIMENSIONS.
8. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF OPENINGS IN STRUCTURE
NOT SHOWN ON STRUCTURAL DRAWINGS.
9. DETAILS LABELED “TYPICAL DETAILS” ON THE DRAWINGS APPLY TO ALL SITUATIONS THAT APPLY WHETHER OR NOT THEY ARE KEYED IN AT EACH LOCATION. QUESTIONS REGARDING APPLICABILITY OF TYPICAL DETAILS SHALL BE
RESOLVED BY THE RESIDENT ENGINEER.
10. DESIGN LOADS AND CRITERIA:
A. WIND DESIGN CRITERIA (ASCE 7-10)
a. WIND SPEED (ULTIMATE) 175 MPH
b. WIND SPEED (NOMINAL) 136 MPH
c. EXPOSURE CATEGORY D
d. RISK CATEGORY IV
e. ENCLOSURE CLASSIFICATION ENCLOSED BUILDING
f. INTERNAL PRESSURE COEFFICIENT ±0.18
B. SEISMIC DESIGN CRITERIA
a. SEISMIC IMPORTANCE FACTOR (I) 1.50
b. RISK CATEGORY IV
c. SITE CLASS D
d. SEISMIC DESIGN CATEGORY C
e. SEISMIC FORCE RESISTING SYTEM ORDINARY CONCRETE FRAME
f. ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
g. MAPPED SPECTRAL RESPONSE ACCELERATIONS
SS 0.160
S1 0.052
h. DESIGN BASE SHEAR 0.085W
i. RESPONSE MODIFICATION COEFFICIENT 3
12. DESIGN IS BASED ON WIND LOADS ONLY. ANTI TERROR / FORCE PROTECTION WAS NOT INCLUDED IN THIS PROJECT.
GENERAL NOTES
1. THIS "STATEMENT OF SPECIAL INSPECTIONS" HAS BEEN PREPARED IN ACCORDANCE WITH IBC 2012, SECTION 1704.
2. CONTRACTOR SHALL EMPLOY ONE OR MORE PRE-COORDINATED AND GOVERNMENT-APPROVED
SPECIAL INSPECTORS TO PROVIDE SPECIAL INSPECTIONS DURING CONSTRUCTION.
3. SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO DEMONSTRATES COMPETENCE, TOTHE
SATISFACTION OF THE CONTRACTING OFFICER'S REPRESENTATIVE, FOR INSPECTION OF THE
PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION.
A. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR THE FOLLOWING SYSTEMS AND
COMPONENTS.
1. ROOF CLADDING
2. WALL CLADDING
4. SPECIAL INSPECTION AGENCY SHALL SUBMIT INSPECTION REPORTS DURING CONSTRUCTION FOR VERIFICATION, INCLUDING FINAL REPORTS IN ACCORDANCE WITH SECTION 1704.2.4 OF IBC 2012.
5. SPECIAL INSPECTOR SHALL USE THE LATEST ISSUE OF THE STRUCTURAL DRAWINGS FOR THE
INSPECTION OF THIS STRUCTURE. SHOP FABRICATION DRAWINGS SHALL NOT BE USED FOR
INSPECTION PURPOSES.
6. THESE INSPECTIONS DO NOT RELAX THE REQUIREMENTS OF IBC 2012 AND OTHER REQUIREMENTS
INCLUDED IN DIVISION 1 SPECIFICATIONS AND GENERAL CONDITIONS.
7. THE CONTRACTOR SHALL PROVIDE A STATEMENT OF RESPONSIBILITY PER IBC 2012 SECTION1704.4.
STATEMENT OF SPECIAL INSPECTIONS
8. REFER TO SCHEDULE OF SPECIAL INSPECTIONS, SPECIFICATION SECTION 01 45 29.02, FOR ADDITIONAL
INFORMATION.
2. FOLLOW MANUFACTURER'S SPECIFICATIONS FOR USE AND
INSTALLATION.
3. INSTALL AND MAINTAIN A MINIMUM EMBEDMENT IN ACCORDANCE WITH
MANUFACTURER'S SPECIFICATIONS, OR AS SPECIFIED ON DRAWINGS.
4. DIAMETER OF HOLE SHALL BE AS RECOMMENDED BY MANUFACTURER FOR
THE PARTICULAR PRODUCT SPECIFIED ON DRAWINGS.
5. UNLESS NOTED, ANCHOR SPACING AND ANCHOR EDGE DISTANCE SHALL
BE ACCORDING TO THE MANUFACTURER'S MOST CURRENT PUBLICATION IN
ORDER TO DEVELOP MAXIMUM WORKING LOADS. IF NOTED DIMENSIONS ARE
LESS THAN THE MANUFACTURER'S RECOMMENDATIONS, THE RESIDENT ENGINEER
SHALL BE CONTACTED FOR CLARIFICATION.
1. USE EPOXY OR POLYESTER RESIN ADHESIVE ANCHORS AS INDICATED ON THE
DRAWINGS. FOR INSTALLATION IN CONCRETE, USE HILTI HIT-HY 200 ANCHORS, OR
APPROVED EQUIVALENT. FOR INSTALLATION IN GROUT OR MASONRY, USE HILTI
HIT-HY 70 ANCHORS, OR APPROVED EQUIVALENT.
6. DO NOT EXCEED MANUFACTURER'S MAX. RECOMMENDED TIGHTENING
TORQUE.
7. ALL ANCHORS SHALL BE INSTALLED AS PER MANUFACTURER'S
RECOMMENDATIONS AND IN ORDER TO DEVELOP THE MOST
CURRENT PUBLISHED WORKING LOADS.
8. ALL EPOXIED ANCHORING SHALL BE TESTED AFTER INSTALLATION AT
CONTRACTOR'S EXPENSE. TWO INITIAL TESTS OF TWO TIMES THE SPECIFIED
WORKING CAPACITY FOR THE ANCHORS IN EACH TYPE OF MATERIAL
(BRICK, CMU, GROUT, LAY TILE, CONCRETE) WILL BE REQUIRED.
ADHESIVE ANCHORING SYSTEMS
1. POST INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION
DOCUMENTS.
2. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE RESIDENT ENGINEER PRIOR TO INSTALLING
POST-INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS.
3. CARE SHALL BE TAKEN IN PLACING POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING
REINFORCING. DO NOT CUT EXISTING REINFORCING.
4. THE FOLLOWING MANUFACTURER’S HAVE BEEN PREAPPROVED FOR SUBMITTAL.
POWERS FASTENERS
HILTI
SIMPSON
5. SUBMITTAL OF ALL PROPOSED PRODUCTS, WITH TECHNICAL DATA AND CURRENT ICC-ERS REPORTS IS REQUIRED FOR REVIEW AND APPROVAL BY THE RESIDENT ENGINEER. ADDITIONAL APPLICATION
CALCULATIONS MAY BE REQUIRED BY THE RESIDENT ENGINEER.
6. HOLES SHALL BE DRILLED AND CLEANED IN STRICT ACCORDANCE WITH THE CURRENT
MANUFACTURER’S PUBLISHED INSTALLATION INSTRUCTIONS (MPII).
7. MANUFACTURER’S FIELD REPRESENTATIVE SHALL PROVIDE INSTALLATION TRAINING FOR ALL PRODUCTS TO BE USED, PRIOR TO COMMENCEMENT OF WORK. ONLY TRAINED INSTALLERS SHALL PERFORM POST INSTALLED ANCHOR INSTALLATION. A RECORD OF TRAINING SHALL BE KEPT ON
SITE AND BE MADE AVAILABLE TO THE RESIDENT ENGINEER AS REQUESTED.
8. PROVIDE SPECIAL INSPECTION FOR ALL MECHANICAL AND ADHESIVE ANCHORS PER THE
APPLICABLE BUILDING CODE AND PER THE CURRENT ICC-ES REPORT FOR THE ANCHOR.
9. PROVIDE PULLOUT AND SHEAR TESTING TO ENSURE MANUFACTURER'S SPECIFIED VALUES ARE
ACHIEVED. SEE TABLE ON SHEET S406 FOR ANCHOR TYPES.
POST-INSTALLED ANCHORING SYSTEMS
10. WHEN DRILLING FOR NEW ANCHORS, DO NOT CUT EXISTING REINFORCEMENT. EXISTING
REINFORCEMENT MAY BE LOCATED USING ONE OF THE FOLLOWING METHODS:
A. XRAY SCANS.
B. DRILL SMALL PILOT HOLES NO LARGER THAN 1/8"Ø.
11. IF EXISTING REINFORCEMENT IS ENCOUNTERED, CEASE DRILLING IMMEDIATELY. FILL HOLE
WITH EPOXY GROUT AND SHIFT DRILL BIT AWAY FROM REINFORCEMENT A MINIMUM OF 2".
MODIFY THE CONNECTING STEEL PLATE OR MEMBER AS REQUIRED FOR THE RELOCATED
HOLE.
1. BOLTS AND ANCHOR BOLTS SHALL BE GALVANIZED OR STAINLESS STEEL.
2. ALL EXPOSED TIMBER OR TIMBER IN CONTACT WITH MASONRY OR
CONCRETE SHALL BE PRESSURE TREATED IN CONFORMANCE WITH AWPA
STANDARDS.
3. ALL PLYWOOD SHEATHING SHALL BE GLUED WITH LIQUID ADHESIVE
APPLIED IN A 1/4" BEAD IN A ZIGZAG PATTERN TO COMPLY WITH THE
MANUFACTURER'S INSTRUCTIONS AND NAILED AS SPECIFIED.
WOOD
1. THE FOLLOWING REQUIREMENTS IN NO WAY REDUCE OR LIMIT ANY ADDITIONAL
REQUIREMENTS OF SPECIFICATIONS.
2. REVIEW OF SUBMITTALS BY THE RESIDENT ENGINEER IS FOR GENERAL CONFORMANCE WITH
THE DESIGN CONCEPT AS PRESENTED BY THE CONTRACT DOCUMENTS. NO DETAILED CHECK
OF QUANTITIES OR DIMENSIONS WILL BE MADE. ONLY THOSE SHOP DRAWINGS REQUIRED BY
THE CONTRACT DOCUMENTS TO BE SUBMITTED WILL BE REVIEWED. ALL OTHERS WILL BE
RETURNED WITHOUT COMMENT.
3. IN ACCORDANCE WITH THE SPECIFICATIONS SUBMIT A COPY OF THE SHOP DRAWING
SUBMITTAL REGISTER TO THE RESIDENT ENGINEER, SHOWING DATES OF SUBMITTAL FOR
EACH SPECIFIC STRUCTURAL SECTION OF THE WORK, CONSISTENT WITH THE FOLLOWING
CRITERIA:
A. ALLOW ADEQUATE TIME FOR TRANSIT AND PROCESSING BEFORE FABRICATION. THE
RESIDENT ENGINEER WILL REVIEW AN AVERAGE SUBMITTAL WITHIN 10 WORKING DAYS OF
RECEIPT.
B. SCHEDULE AND SUBMIT SHOP DRAWINGS FOR SPECIFIC COMPONENTS SUCH AS FRP AND
STRUCTURAL STEEL.
C. SUBMIT SHOP DRAWINGS IN A TIMELY MANNER, CONSISTENT WITH THE ABOVE
REQUIREMENTS.
4. ALL CHANGES AND ADDITIONS MADE ON RESUBMITTALS MUST BE CLEARLY FLAGGED AND
NOTED. THE PURPOSE OF THE RESUBMITTALS MUST BE CLEARLY NOTED ON THE LETTER OF
TRANSMITTAL. ARCHITECT/ENGINEER REVIEW WILL BE LIMITED TO THE ITEMS CAUSING THE
RESUBMITTAL.
5. RESPONSIBILITIES OF DETAILERS AND FABRICATORS AND VENDORS:
A. GENERAL- SUBMIT SHOP DRAWINGS AND ANY OTHER SPECIAL INFORMATION NECESSARY
FOR PROPER FABRICATION, ERECTION, AND PLACEMENT OF STRUCTURAL FABRICATIONS.
INCLUDE PLANS, ELEVATIONS, AND SECTIONS. CLEARLY SHOW ANCHORAGES,
CONNECTIONS, AND ACCESSORY ITEMS. THE DETAILER MUST INTERPRET THE CONTRACT
DOCUMENTS AND CLEARLY CONVEY THIS INTERPRETATION TO THE FIELD IN THE FORM OF
PLACING OR ERECTION DRAWINGS
6. SEE SECTION TITLED "SHOP DRAWINGS REQUIRING INPUT BY A SPECIALTY ENGINEER" FOR
ADDITIONAL CRITERIA APPLICABLE TO SHOP DRAWINGS.
SHOP DRAWING SUBMITTALS
1. ALL STEEL WORK (INCLUDING FABRICATION AND ERECTION) SHALL CONFORM TO
THE AISC MANUAL OF STEEL CONSTRUCTION 13TH EDITION AND PROJECT
SPECIFICATIONS, USE THE FOLLOWING:
- ROLLED SHAPES, ASTM A992, GRADE 50.
- PLATES BARS A36.
- COLD-FORMED STEEL TUBING: ASTM A500, GRADE B.
- HOT-FORMED STEEL TUBING: ASTM A501.
- STEEL PIPE: ASTM A53, TYPE E OR S, GRADE B.
2. USE STRUCTURAL STEEL THAT IS FULLY WELDABLE OF SIMILAR GRADES AND
FROM ANY GRADE TO ANY OTHER GRADE. WELD ALL SHOP CONNECTIONS, U.N.O.
3. ALL SHOP AND FIELD WELDING SHALL CONFORM TO THE STRUCTURAL WELDING
CODE AWS D1.1, LATEST EDITION, PUBLISHED BY THE AMERICAN WELDING
SOCIETY (AWS). USE ELECTRODES CONFORMING TO AWS D1.1, E70 SERIES,
U.N.O. SHOW ALL SHOP WELDS ON THE FABRICATION DRAWINGS AND ALL FIELD
WELDS ON THE ERECTION DRAWINGS.
4. ALL SHOP AND FIELD WELDERS, WELDING OPERATORS, AND TACKERS SHALL BE
CERTIFIED ACCORDING TO AWS PROCEDURES FOR THE WELDING PROCESS AND
WELDING POSITION USED.
5. ALL JOINT WELDING PROCEDURES TO BE USED SHALL BE PREPARED BY THE
FABRICATOR OR CONTRACTOR AS WRITTEN PROCEDURE SPECIFICATIONS AND
SUBMITTED TO THE ARCHITECT/ENGINEER FOR THEIR RECORD. ALL JOINT
WELDING PROCEDURES SHALL BE QUALIFIED PRIOR TO USE ACCORDING TO AWS
PROCEDURES.
6. A325 BOLTS:
- A325 BOLTS SHALL CONFORM TO ASTM A325 TYPE 1, HIGH STRENGTH BOLTS FOR
STRUCTURAL STEEL JOINTS. DO NOT USE TYPE 2 BOLTS.
- PROVIDE HARDENED WASHERS CONFORMING TO ASTM F436. PLACE HARDENED
WASHERS UNDER PART BEING TURNED.
- LOAD INDICATOR WASHERS SHALL BE USED ON ALL A325 BOLTS.
- ALL BOLTS SHALL BE NEW AND DOMESTICALLY MANUFACTURED. DO NOT REUSE
BOLTS. USE ONLY NON-GALVANIZED NUTS AND BOLTS THAT ARE CLEAN,
RUST-FREE, AND WELL LUBRICATED, U.N.O..
7. USE F1554 BOLTS FOR ANCHOR BOLTS OR WHEN SPECIFICALLY CALLED FOR ON
THE DRAWINGS.
8. CUT, DRILL, OR PUNCH HOLES PERPENDICULAR TO METAL SURFACES. DO NOT
FLAME CUT HOLES OR ENLARGE HOLES BY BURNING.
9. SPLICING OF STRUCTURAL STEEL MEMBERS IN THE FIELD OR IN THE SHOP IS
PROHIBITED EXCEPT WHERE INDICATED ON THE DRAWINGS.
10. DO NOT PAINT STEEL SURFACES IN CONTACT WITH CONCRETE. DO NOT APPLY
FINISH COAT AND LIMIT PRIME COAT TO 2 MILS AT FAYING SURFACES OF SLIP
CRITICAL BOLTED CONNECTIONS, SURFACES TO BE WELDED AND TOP
SURFACES OF BEAMS AND TRUSSES TO RECEIVE STEEL STUDS AND/OR
SUPPORTING METAL FLOOR AND ROOF DECKING. USE PRIMER WHICH HAS A MIN.
CLASS A SLIP COEFFICIENT (0.33).
11. REFER TO ARCHITECTURAL PLANS FOR FIREPROOFING OF STRUCTURAL STEEL
MEMBERS, REFER TO SPECIFICATIONS FOR PAINTING OF STRUCTURAL STEEL.
12. SUBMIT STRUCTURAL STEEL SHOP DRAWINGS TO ARCHITECT/ENGINEER FOR
REVIEW BEFORE FABRICATION.
13. PROVIDE TEMPORARY BRACING AS NECESSARY TO ENSURE A STABLE
STRUCTURE DURING CONSTRUCTION.
14. DO NOT REPRODUCE THE STRUCTURAL DRAWINGS FOR USE AS SHOP
DRAWINGS.
15. NO CUTTING OF SECTIONS, FLANGES, WEBS OR ANGLES SHALL BE ALLOWED
WITHOUT WRITTEN APPROVAL FROM THE RESIDENT ENGINEER.
16. ALL EXPOSED STEEL MEMBERS & CONNECTIONS SHALL BE HOT DIP GALVANIZED
PRIOR TO FABRICATION. ALL CONNECTIONS SHALL BE PRE DRILLED AND/OR
WELDED PRIOR TO GALVANIZING.
17. PAINT ALL STEEL PERMANENT EXPOSED TO EARTH WITH 2 COATS OF COAL TAR
EPOXY INCLUDING BOTTOM OF BASEPLATES.
18. NON-SHRINK GROUT IS DEFINED AS A NON-METALLIC GROUT WITH A 28 DAYS
STRENGTH OF 10,000 PSI AND SHALL CONFORM TO THE CORPS OF ENGINEERS
CRD-C621, FACTORY PREMIX GROUT.
19. THE RESIDENT ENGINEER SHALL BE CONTACTED FOR APPROVAL OF ANY FIELD
MODIFICATIONS OF ANCHOR BOLTS/RODS AND COLUMN BASE PLATES (PER
OSHA).
20. ALL STEEL LINTELS AND SHELF ANGLES SHALL BE HOT DIP GALVANIZED.
21. ALL EXTERIOR ELEMENTS, AND THOSE ELEMENTS NOTED TO BE GALVANIZED,
SHALL BE HOT DIP GALVANIZED IN ACCORDANCE WITH ASTM A123 AFTER
SANDBLAST CLEANING PER SSPC-SPIO. USE ASTM A325 BOLTS HOT DIP
GALVANIZED, GALVANIZED HARDENED WASHERS, AND GALVANIZED HEAVY HEX
NUTS FOR BOLTING OF GALVANIZED ITEMS.
STRUCTURAL STEEL
1. EXTERIOR METAL STUDS AND ATTACHMENTS SHALL BE DESIGNED BY A SPECIALTY
ENGINEER AND CALCULATIONS SHALL BE PROVIDED WITH SUBMITTAL. SUBMITTAL
SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE
OF MISSISSIPPI.
2. THE SPECIALTY ENGINEER OR MANUFACTURER SHALL DESIGN, PROVIDE, AND INSTALL
THEIR COMPONENTS, IT IS THE RESPONSIBILITY OF THE SPECIALTY ENGINEER TO
ENSURE ALL COMPONENTS ARE INSTALLED ACCORDING TO THE APPROVED SHOP
DRAWINGS. THE SPECIALTY ENGINEER SHALL SUBMIT A LETTER TO THE ARCHITECT /
ENGINEER STATING THAT THE SYSTEM HAS BEEN INSTALLED ACCORDING TO THE
APPROVED SHOP DRAWINGS.
3. DESIGN METAL STUDS SYSTEM TO SUPPORT TRIBUTARY WIND FORCES FROM OTHER
ELEMENTS CONNECTED TO THE METAL STUDS. METAL STUD ENGINEER SHALL REVIEW
& COORDINATE METAL PANELS ATTACHMENTS PRIOR TO SHOP DRAWING SUBMITTAL.
4. COORDINATE, PROVIDE, AND INSTALL DOUBLE STUDS WITH METAL PANEL JOINTS,
ATTACHMENT REQUIREMENTS, AND SPACING.
5. COORDINATE UNBRACED FLANGE WITH SHEATHING LOCATIONS. WHERE NO SHEATHING
EXISTS PROVIDE STRAPPING OR BRACING OF UNSUPPORTED FLANGES AS REQUIRED
TO RESIST GRAVITY AND WIND LOADS.
6. DESIGN SHALL BE IN ACCORDANCE WITH AISI "SPECIFICATION FOR THE DESIGN OF
COLD FORMED STRUCTURAL MEMBERS".
7. JOINTS AND CONNECTIONS SHALL BE MADE WITH SCREWS OR BOLTS. PROVIDE A
MINIMUM TWO (2) SCREWS PER CONNECTION.
8. ALL COLD-FORMED STEEL FRAMING, CONNECTORS SHALL RECEIVE A G-90 GALVANIZED
COATING.
9. NO WELDING OF COLD-FORMED MEMBERS IS ALLOWED.
10. SAW CUT STUDS SQUARE AND SET WITH FIRM BEARING AGAINST THE CONNECTING
MEMBER.
11. INSTALL FASTENERS FROM THINNER MATERIAL TO THICKER MATERIAL.
12. ALL STUDS AND CONNECTORS SHALL BE 16 GAUGE OR GREATER IN THICKNESS SHALL
HAVE A MINIMUM YIELD STRENGTH (Fy) OF 50 KSI.
13. PROVIDE MECHANICAL BRIDGING AT INTERVALS NOT EXCEEDING 4'-0" O.C. FOR ALL
STRUCTURAL STUD WALLS.
14. STUD MATERIAL SHALL HAVE A MINIMUM OF 1-5/8" FLANGES AND 1/2" STIFFENING
RETURN LIPS. TRACK MATERIAL SHALL HAVE A MINIMUM OF 1-1/4" FLANGES (NO
STIFFENING RETURN LIP).
COLD - FORMED METAL STUDS
1. SPECIALTY ENGINEER:
A. DEFINITION - A REGISTERED PROFESSIONAL ENGINEER WHO SPECIALIZES IN AND WHO UNDERTAKES
THE DESIGN OF STRUCTURAL COMPONENTS OR STRUCTURAL SYSTEMS INCLUDED IN A SPECIFIC
SUBMITTAL PREPARED FOR THIS PROJECT.
B. SHALL BE:
- AN EMPLOYEE OR OFFICER OF A FABRICATOR VENDOR.
- AN EMPLOYEE OR OFFICER OF AN ENTITY SUPPLYING COMPONENTS TO A VENDOR.
- AN INDEPENDENT CONSULTANT RETAINED BY THE FABRICATOR OR HIS SUPPLIER.
2. THE FOLLOWING SYSTEMS AND COMPONENTS AS A MINIMUM REQUIRE FABRICATION AND
INSTALLATION DRAWINGS WITH INPUT BY A SPECIALTY ENGINEER INCLUDE, BUT ARE NOT LIMITED
TO: WINDOW SYSTEMS, CURTAINWALL SYSTEMS, ROOF SYSTEMS, LOUVERS, DOORS AND ANY
EXTERIOR ANCILLARY STRUCTURES.
3. THE SPECIALTY ENGINEER OR MANUFACTURER SHALL DESIGN, PROVIDE, AND INSTALL THEIR
COMPONENTS AND THE COMPONENT CONNECTIONS TO THE PRIMARY STRUCTURE PER THE LOAD
CRITERIA STATED IN THESE NOTES OR THE CURRENT GOVERNING BUILDING CODES, WHICHEVER IS
MORE STRINGENT.
4. SUBMITTALS SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECT AND APPLICABLE CODES, LIST THE DESIGN CRITERIA, AND SHOW ALL DETAILS AND PLANS NECESSARY FOR PROPER FABRICATION AND INSTALLATION. CALCULATIONS AND SHOP DRAWINGS SHALL IDENTIFY SPECIFIC PRODUCT UTILIZED.
GENERIC PRODUCTS WILL NOT BE ACCEPTED.
5. SHOP DRAWINGS AND CALCULATIONS MUST BE PREPARED UNDER THE DIRECT SUPERVISION AND
CONTROL OF THE SPECIALTY ENGINEER.
6. SHOP DRAWINGS AND CALCULATIONS REQUIRE THE SEAL, DATE AND SIGNATURE OF THE SPECIALTY ENGINEER. COMPUTER PRINTOUTS ARE AN ACCEPTABLE SUBSTITUTE FOR MANUAL COMPUTATIONS PROVIDED THEY ARE ACCOMPANIED BY SUFFICIENT DESCRIPTIVE INFORMATION TO PERMIT THEIR PROPER EVALUATION. SUCH DESCRIPTIVE INFORMATION SHALL BEAR THE SEAL AND SIGNATURE OF THE SPECIALTY ENGINEER AS AN INDICATION THAT HE HAS ACCEPTED RESPONSIBILITY FOR THE
RESULTS.
7. REVIEW OF SUBMITTALS LIMITED TO VERIFYING THE FOLLOWING:
A. THAT THE SPECIALTY ENGINEER HAS UNDERSTOOD THE DESIGN INTENT AND HAS USED THE
SPECIFIED STRUCTURAL CRITERIA. (NO DETAILED CHECK OF CALCULATIONS WILL BE MADE.)
B. THAT THE CONFIGURATION SET FORTH IN THE STRUCTURAL SUBMITTALS IS CONSISTENT WITH THE
CONTRACT DOCUMENTS. (NO DETAILED CHECK OF DIMENSIONS OR QUANTITIES WILL BE MADE.)
SHOP DRAWINGS REQUIRING
INPUT BY A SPECIALTY ENGINEER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
STRUCTURAL NOTES -
WATER INTRUSION
S401 2810/27/2023
12345678910111213141516171819202122
W1
W#
LEGEND:
= WINDOW OPENING TYPES, SEE SHEETS
S404 AND S405, AND COORDINATE WITH
ARCHITECTURAL DRAWINGS. SEE
ARCHITECTURAL DRAWINGS FOR
GLAZING TYPES. GLAZING TYPES VARY
AND DO NOT CORRESPOND DIRECTLY TO
WINDOW OPENING TYPES.
S407
W1 W1
W1 W1 W1
W1W1 W1
W1W1W1
W1 W1 W1
W1W1W1
W1 W1 W1
W1 W1 W1
W1 W1 W1
W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2
W3 W3 W3 W3 W3 W3
W3 W3 W3 W3 W3 W3
W3 W3 W3 W3 W3 W3
W3W3W3W3W3W3
W5 W5
W6
W7 W7 W7 W7
REFER TO DETAIL 2/S404 FOR BRICK
ATTACHMENT WHERE REQUIRED.
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
ATTIC
ATTIC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
S407
W1 W1 W1
W1 W1 W1
W1 W1 W1
W1 W1 W1
W1 W1 W1
W1 W1 W1
W1 W1 W1
W1 W1 W1
W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2
W3 W3 W3 W3 W3 W3
W3 W3 W3 W3 W3
W3 W3 W3 W3 W3 W3
W3W3W3W3W3 W4 W4
W5 W5
W6
W7 W7 W7 W7
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
3/32" = 1'-0"1 NORTH ELEVATION
3/32" = 1'-0"2 SOUTH ELEVATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
BUILDING ELEVATIONS
S402 2910/27/2023
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
ATTIC
W#
LEGEND:
= WINDOW OPENING TYPES, SEE SHEETS
S404 AND S405, AND COORDINATE WITH
ARCHITECTURAL DRAWINGS.
GFEDCBA
W1W1
W1 W1
W1 W1
W2 W2
W3 W3
W3 W3
REFER TO DETAIL 2/S404 FOR BRICK
ATTACHMENT WHERE REQUIRED.
W1
W1
W1
W1
W1
W1
SIM SIM SIM
G F E D C B A
W1 W1
W1 W1
W1 W1W1 W1
W1 W1
W1 W1 W2 W2 W2
W3 W3 W3
W3 W3 W3
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
ATTIC
W1 W1
W1 W1
W1 W1
3/32" = 1'-0"1 EAST ELEVATION
3/32" = 1'-0"2 WEST ELEVATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
BUILDING ELEVATIONS
S403 3010/27/2023
W1
PUNCHED WINDOW OPENING
PUNCHED WINDOW OPENING,
SEE WALL TYPES ON SHEET S406,
COORDINATE ATTACHMENT
WITH WALL TYPE.
5TH FLOOR OPENING
OPEN
CURTAINWALL ATTACHMENTS
TO CONCRETE STRUCTURE
OPEN
NOTES:
1. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WINDOW
TYPES AND DIMENSIONS.
2. CURTAINWALL SYSTEMS SHALL SPAN VERTICALLY
3. CUT & REMOVE EXISTING WOOD BLOCKING, INSTALL NEW
CONCRETE CURB TO MATCH EXISTING.
VERIFY IN FIELD EXISTING CURB DIMENSIONS.
4. REFERENCE S407 AND S408 FOR BUILDING SECTION
DETAILS.
5. WINDOW ATTACHMENT TO FRAMING SHALL BE DESIGNED
BY WINDOW / CURTAINWALL MANUFACTURER.
6. BOTTOM OF CHANNEL FRAMING IS CURRENTLY ANCHORED
TO EXISTING TIMBER CURB. CHANNEL IS TO BE RE-
ANCHORED TO CONCRETE CURB AS NOTED.
VERTICAL MULLIONS
5TH FLOOR OPENING
@ COLUMN
EXISTING CONCRETE
BEAM
CURTAINWALL
ATTACHMENTS
TO CONCRETE
SLAB / BEAM
OPEN
VERTICAL MULLIONS
EXAMPLE PHOTOS FOR REPLACING WOOD CURB WITH CONCRETE CURB:
OPEN
#3 BARS SET WITH EPOXY INTO
EXISTING CONCRETE STRUCTURE AT
EACH MULLION, SEPARATED BY 4" OC,
4" EMBEDMENT. FOR BALANCE OF
DETAIL, PROVIDE #3 @ 16" OC, 4"
EMBEDMENT
2 #4X4'-0"
EXISTING COLUMN
TO REMAIN
EXISTING
CHANNELS
TO REMAIN
#3 BARS SET WITH EPOXY INTO
EXISTING CONCRETE STRUCTURE AT
EACH MULLION, SEPARATED BY 4" OC,
4" EMBEDMENT. FOR BALANCE OF
DETAIL, PROVIDE #3 @ 16" OC, 4"
EMBEDMENT
(2) #4 CONT. ACROSS
BOTTOM OF CURTAINWALL
3RD & 4TH FLOOR OPENING
EXISTING CONCRETE
BEAM
CURTAINWALL
ATTACHMENTS
TO HSS TUBE
CURTAINWALL ATTACHMENTS
TO CONCRETE SLAB / BEAM
OPEN
VERTICAL MULLIONS
SEE WALL SECTIONS
FOR ATTACHMENT
3RD & 4TH FLOOR OPENING
@ COLUMN
EXISTING CONCRETE
BEAM
CURTAINWALL
ATTACHMENTS
TO HSS TUBE
CURTAINWALL
ATTACHMENTS
TO CONCRETE
SLAB / BEAM
OPEN
VERTICAL MULLIONS
OPEN
(2) #4 CONT. ACROSS
BOTTOM OF CURTAINWALL
(2) #4 CONT. ACROSS
BOTTOM OF CURTAINWALL
SEE WALL SECTIONS
FOR ATTACHMENT
EXIST. CONCRETE
COLUMN TO REMAIN
OPEN
EXISTING CONCRETE
BEAM
VERIFY IN FIELD
2' - 11"
EXISTING
COLUMN
BREAK FACE OF
CLAY TILE SHELL
& REPLACE W/
4000 PSI GROUT
FOR SMOOTH
SURFACE
SEE ARCH. FOR
WINDOW SYSTEM
CMU INFILL W/ FULLY GROUTED
CELLS W/ #5 @ 16" O.C., VERTICAL, TYP.
EM
BE
D M
EN
T
1/
2"
1/
2"
EM
BE
D
M
EN
T
(2) #5 IN FILLED CELLS,
4000 PSI GROUT
EXISTING
BRICK / TILE
3RD FLOOR WINDOW
@ LOWER ROOF
(2) #4 CONT. ACROSS
BOTTOM OF CURTAINWALL
REMOVE EXISTING WOOD
SILL REPLACE W/ POURED
CONCRETE CURB
REPLACE BOLTS FOR EXISTING
CHANNEL CONNECTION W/ 5/8"Ø
THREADED RODS W/ NUT & WASHER,
TOP & BOTTOM, 4" EMBEDMENT
EXISTING CONCRETE
BEAM
CONNECTION TO EXIST.
CONCRETE BY WINDOW /
CURTAINWALL MANUFACTURER
CONNECTION TO EXIST.
CONCRETE BY WINDOW /
CURTAINWALL MANUFACTURER
EXISTING CHANNEL
EXISTING WOOD CURB
TO BE REMOVED
W2 W2
W3 W3 W4
APPLY CONCRETE
BONDING AGENT
APPLY CONCRETE
BONDING AGENT
APPLY CONCRETE
BONDING AGENT
(2) #3 BARS SET WITH EPOXY INTO
EXISTING CONCRETE STRUCTURE AT
EACH MULLION, SEPARATED BY 4" OC,
4" EMBEDMENT. FOR BALANCE OF
DETAIL, PROVIDE #3 @ 16" OC, 4"
EMBEDMENT
APPLY CONCRETE
BONDING AGENT
(2) #3 BARS SET WITH EPOXY INTO
EXISTING CONCRETE STRUCTURE AT
EACH MULLION, SEPARATED BY 4" OC,
4" EMBEDMENT. FOR BALANCE OF
DETAIL, PROVIDE #3 @ 16" OC, 4"
EMBEDMENT
" L
AP
1'-2" TYPICAL, COORD
EXTENTS WITH ARCH
1'-2" TYPICAL, COORD
EXTENTS WITH ARCH
8" TYPICAL, COORD
EXTENTS WITH ARCH
8" TYPICAL, COORD
EXTENTS WITH ARCH
DRILL AND ANCHOR BARS
INTO (E) CONC WITH HILTI
HIT-HY 200 ADHESIVE, TOP
AND BOTTOM
PROVIDE HORIZONTAL
LADDER-TYPE JOINT
REINF @ 16" O.C.
PROVIDE CONT HORIZ BOND
BEAMS REINF WITH (2) #5 BARS
AS FOLLOWS:
1. AT BOTTOM OF WALL
2. WITHIN 16" OF TOP OF WALL
3. ABOVE AND BELOW OPENINGS
4. BALANCE AT 48" O.C. MAX
PROVIDE ADDITIONAL
CONTINUOUS #5 BAR IN
SOLID GROUTED CELL AT
OPENING JAMB (TYP)
2' -8
EXAMPLE FOR ADJUSTABLE HECKMANN ANCHOR:
BRICK
CMU
HECKMANN TRIANGLE
ADJUSTABLE ANCHOR
W/ 12 GAGE SCREW - ON
ANCHOR STRAP @ 16" O.C.
VERT. & 16" O.C. HORIZ.
(2) - 1/4"Ø SCREWS,
1-1/2" MIN. EMBEDMENT
IN CMU, PRE - DRILL
AS REQ'D
(PHOTO IS SHOWN FOR INFORMATIONAL PURPOSES, ONLY)
4"
EM
BE
DM
EN
T
(E) FLOOR
#3 BARS
8"
COORDINATE HEIGHT OF CURB WITH
ARCHITECTURAL CURTAINWALL
REQUIREMENTS, UP TO A MAXIMUM
HEIGHT OF 9"
NTS2 BRICK ANCHOR DETAIL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
WINDOW OPENING TYPES
S404
NTS
TYPICAL CURB DETAIL
3110/27/2023
W5
MAIN ENTRY GABLEWING GABLES ROOF DORMER LOUVERS
PROCEDURE CASE 1:
REMOVE WINDOW AND FRAMING IN ITS ENTIRETY.
CHIP AWAY ANY LOOSE, DAMAGED AND OTHER DELETERIOUS
MATERIAL AND REPLACE WITH 4000 PSI GROUT TO FORM A SMOOTH
EDGE FOR ATTACHMENTS. REATTACH WITH 3/8"Ø THREADED RODS
IN EPOXY SCREEN TUBES, SPACED NO GREATER THAN 24" OC,
ALONG SIDES, TOP, AND BOTTOM; 3 1/2" MINIMUM EMBEDMENT
2 - 2X6 FRAMING, EACH
SIDE OF WINDOW
OPEN OPEN
2 - 2X6 FRAMING
EXISTING BRICK
2X4 FRAMING
PROCEDURE CASE 2:
REMOVE WINDOW AND FRAMING IN ITS ENTIRETY.
INSTALL 2"X4" STUD AND ANCHOR TO EXISTING
BRICK WITH 3/8"Ø THREADED RODS IN EPOXY @ 8" MAX.,
SCREEN TUBES, EACH STUD, 3 1/2" EMBEDMENT, MIN.
COORDINATE PLACEMENT OF 2X4 STUDS WITH CONFIGURATION
AND ATTACHMENT REQUIREMENTS OF NEW WINDOW.
OPEN
PROCEDURE:
FRAME ALL SIDES WITH 2X4 FRAMING WITH
(2) 16d NAILS @ 12" OC (MINIMUM OF 4 NAILS ON
EACH SIDE, TOP AND BOTTOM).
PROCEDURE:
USE 3/8"Ø THREADED RODS @ 8" OC MAX IN EPOXY
SCREEN TUBES, 3 1/2" MIN EMBEDMENT, AROUND
FULL PERIMETER OF OPENING.
5/8" PLYWOOD
2X4 FRAMING @ 16" O.C. NAIL
SHEATHING W/ 10d NAILS @ 6" O.C.
WINDOW FRAME
WINDOW FRAME
WINDOW FRAME WINDOW FRAME
W6 W7
WINDOW OPENING TYPES
S405
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
3210/27/2023
HOLLOW CMU
2 - 2X6 FRAMING,
SURROUND, TYP.
OPEN
FILL CELLS SURROUNDING
WINDOW SOLID WITH
GROUT, 8" MIN.
4 4
2X6 FRAMING
EXIST. LINTEL
IF THERE IS NO SOLID MASONRY SURFACE
FOR ANCHOR ATTACHMENT AT BOTTOM OF
WALL, REMOVE ONE COURSE OF BLOCK AND
REPLACE WITH SOLID GROUTED COURSE
EXISTING LINTEL IS ASSUMED TO
PROVIDE A SOLID SURFACE FOR
ANCHOR ATTACHMENT; IF NO SOLID
SURFACE IS PRESENT, INSTALL NEW
STEEL ANGLE LINTEL PER MASONRY
LINTELS GENERAL NOTES, S001
NOTE: THE EXACT LOCATIONS WHERE THIS
DETAIL MAY BE REQUIRED ARE NOT KNOWN.
THE CONTRACTOR SHALL VERIFY EXISTING
CONDITIONS AND APPLY THIS DETAIL IF A
CONDITION IS DISCOVERED IN A HOLLOW CMU
WALL WITH NO EXISTING LINTEL PRESENT.
BRICK
2 - 2X6 FRAMING,
SURROUND, TYP.
OPEN
SMOOTH EDGES W/
GROUT, FILL VOIDS
SOLID WITH GROUT,
ONE FULL CELL
MINIMUM
3 3
2X6 FRAMING
EXIST. LINTEL
FILL W/ 4000 PSI GROUT
ALL VOIDS SURROUNDING
WINDOW, 1'-0" MIN., TYP.
HOLLOW CLAY TILE
OPEN
2 - 2X6 FRAMING,
SURROUND, TYP.
1 1
SAWCUT & REMOVE TOP
FACE OF CLAY TILE SHELL
TO ENSURE PROPER KEYING
OF NEW GROUT
2X6 FRAMING
EXIST. LINTEL
SMOOTH SURFACE W/
4000 PSI GROUT
EXIST. GROUTED
MASONRY
OPEN
2 - 2X6 FRAMING,
SURROUND, TYP.
2 2
2X6 FRAMING
EXIST. LINTEL
FILL W/ 4000 PSI GROUT
2 - 2X6 FRAMING,
SURROUND, TYP.
OPEN
EXISTING SUBSTRATE
FILL W/ CMU, UNGROUTED, V.I.F.
EXISTING STEEL LINTEL
EXAMPLE PHOTO FOR CMU INFILL:
1X6 FRAMING
EXIST. LINTEL
PUNCHED WINDOW ATTACHMENT
SCHEDULE
HOLLOW /
GROUTED CMU
GROUTED
MASONRY2
CLAY TILE
BRICK
NOTE:
1. MAINTAIN AN EDGE DISTANCE OF 2" MIN., AND END
DISTANCE OF 3" MIN. FOR ALL CONNECTIONS INTO WOOD.
2. SCREWS SHALL HAVE A MINIMUM EMBEDMENT OF 1"
INTO THEIR RESPECTIVE SUBSTRATE.
3. MOST PUNCHED WINDOWS ARE SURROUNDED BY A
COMBINATION OF TWO OR MORE SUBSTRATE TYPES.
USE APPLICABLE ATTACHMENT SCHEDULE.
5. DESIGN VALUES ARE FOR 4'-0" WIDE WINDOW, MAX.
6. MIN. THREE FASTENERS PER WINDOW SIDE.
7. ANCHOR SPACING CAN BE ADJUSTED ± 4" TO ACCOMMODATE
ANY UNFORESEEN CONDITIONS.
MARK CONDITION FASTENER MAX. SPACING
1/2"Ø THREADED
ROD IN EPOXY
SCREEN TUBE
@ 4-1/2" EMBED.
1/2"Ø THREADED
ROD IN EPOXY
SCREEN TUBE
@ 4-1/2" EMBED.
3/16"Ø TITEN
SCREW
3/16"Ø TITEN
SCREW
14"
7"
14"
7"
4. WHERE DIFFERENT SUBSTRATE MATERIALS OCCUR AT THE
SAME WINDOW, UTILIZE THE FASTENER AND SPACING
APPROPRIATE FOR EACH MATERIAL.
8. FOR ANCHORS IN BRICK AND CMU, MAINTAIN AN EDGE
DISTANCE FROM VERTICAL MORTAR JOINTS OF 2" MIN.
5" 5"EQ EQ
5"
EQ
EQ
EQ
2"
ELEVATION SECTION VIEW
NOTE: THE DESIGNED CONNECTIONS ARE FOR
THE WOOD STUD FRAMING TO SURROUNDING
SUBSTRATE. WINDOW HEAD CONNECTION THROUGH
(1) 1X6 AND EXIST. STEEL ANGLE BY WINDOW MANUFACTURER.
ALL OTHER SIDES SHALL BE ATTACHED TO (2) 2X6.
COUNTERSINK
ALL WINDOW ANCHORAGE
OPEN
NTS4 HOLLOW CMUNTS3 BRICK
NTS1 HOLLOW CLAY TILE
NTS2 GROUTED MASONRY
NTS6 CMU INFILL
GENERAL NOTES:
1. CHIP AWAY ANY EXISTING, LOOSE, DAMAGED
OR DELETERIOUS MATERIAL & REPLACE WITH
4000 PSI GROUT.
2. GROUT IS TO BE USED TO FLUSH OUT
SURROUNDING WALLS WITH WINDOW STUD
FRAMING.
3. WHERE GROUT IS USED IN HOLLOW
CLAY TILE OR CMU, PROVIDE A MINIMUM
LAYER OF 2" THICK BETWEEN SUBSTRATE
AND WOOD STUDS.
4. ALL WOOD BUCKS SHALL BE PRESSURE TREATED.
5. ALL FASTENERS IN CONTACT WITH PRESSURE
TREATED LUMBER SHALL BE APPROVED AS SUCH.
EXAMPLE PHOTO FOR CLAY TILE ALL AROUND:
EXAMPLE PHOTO FOR CMU TO GROUT
SILL W/ CLAY TILE ON ALL SIDES: EXAMPLE PHOTO FOR BRICK SILL: EXAMPLE PHOTO FOR BRICK AND CMU SILLS:
NTS5 TYPICAL WINDOW BUCK CONNECTION DETAIL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
PUNCHED WINDOW ATTACHMENTS
S406
1 1
1 1
2 2
S4
S4
AT
TI
C
4T H
FL
OO
R
3R D
FL
OO
R
2N D
FL
OO
R
1S T
FL
OO
R
S4
S4
5T H
FL
OO
R
3/ 8"
1'
-0
TY
PI
CA
L C
UR
TA
IN
W
AL
L S
EC
TI
ON
OV
ER
AL
L
WALL SECTIONS
S407
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
N O
TE
S:
1.
R
EF
ER
T O
IN
D
IV
ID
U
AL
S
EC
TI
O
N D
ET
AI
LS
F
O R
N
EW
C O
N
ST
R U
C
TI
O N
3410/27/2023
CURTAINWALL SYSTEM
EXISTING CONCRETE
STRUCTURE, V.I.F.
CONNECTION TO EXIST.
CONCRETE BY WINDOW /
CURTAINWALL MANUFACTURER
(NOTE 2)
4" MINIMUM EDGE
DISTANCE, EACH SIDE
ATTIC
8"
4"
5TH FLOOR
CURTAINWALL SYSTEM
EXISTING CONCRETE
STRUCTURE
EXISTING TOPPING
CURTAINWALL SYSTEM
4"EDGE
DISTANCE
NEW CONCRETE CURB (NOTE 1)
(4) #4 BARS
#3 @ MULLIONS INTO EXISTING
CONCRETE STRUCTURE, 4"
EMBEDMENT, SET W/ EPOXY,
2 @ EACH MULLION 16" SPACING,
MAX. BETWEEN
ATTACHMENT PER WINDOW /
CURTAINWALL MANUFACTURER
1' -2
HSS8x2x1/4, COORDINATE
PLACEMENT WITH WINDOW
FLASHING REQUIREMENTS
1/2"Ø EPOXY ANCHORS, 6"
EMBEDMENT, @ 16" OC MAX
CURTAINWALL SYSTEM
EXISTING CONCRETE
STRUCTURE
(2) - 1/2"Ø EPOXY ANCHORS,
4" EMBEDMENT, 3" GAGE
EXISTING TOPPING
4"
EM
BE
DM
EN
T
HSS8X2X1/4, COORDINATE ELEVATION
WITH ARCH DRAWINGS
WT4X12X0'-8" LONG, SPACED AT 32" OC
MAX, TRIM AS REQ'D
3/16
4TH FLOOR
4"EDGE
DISTANCE
NEW CONCRETE CURB (NOTE 1)
FOR CURB HEIGHTS UP TO 6":
USE (2) #4 x CONT
FOR CURB HEIGHTS BETWEEN
6" AND 9": USE (4) #4 x CONT
#3 @ MULLIONS INTO EXISTING
CONCRETE STRUCTURE, 4"
EMBEDMENT, SET W/ EPOXY,
2 @ EACH MULLION 16" SPACING,
MAX. BETWEEN
ATTACHMENT PER WINDOW /
CURTAINWALL MANUFACTURER
PLATE 3/8"X6"X0'-6" LONG
TR
IM
W T
TO
L
EN
G
TH 3/16
8"
SMOOTH EXISTING CONCRETE
SURFACE WITH 4000 PSI GROUT
CURTAINWALL SYSTEM -
REF ARCHITECTURAL
COORDINATE HEIGHT OF CURB WITH
ARCHITECTURAL CURTAINWALL
REQUIREMENTS, UP TO A MAXIMUM
HEIGHT OF 9"
3/16
3/16
COORDINATE PLACEMENT OF HSS WITH
WINDOW FLASHING REQUIREMENTS
CURTAINWALL SYSTEM
EXISTING CONCRETE
STRUCTURE
EXISTING TOPPING
4"
EM
BE
DM
EN
T
NEW CONCRETE CURB (NOTE 1)
#3 @ MULLIONS INTO EXISTING
CONCRETE STRUCTURE, 4"
EMBEDMENT, SET W/ EPOXY,
2 @ EACH MULLION 16" SPACING,
MAX. BETWEEN
ATTACHMENT PER WINDOW /
CURTAINWALL MANUFACTURER
8"
FOR CURB HEIGHTS UP TO 6":
USE (2) #4 x CONT
FOR CURB HEIGHTS BETWEEN
6" AND 9": USE (4) #4 x CONT
COORDINATE HEIGHT OF CURB WITH
ARCHITECTURAL CURTAINWALL
REQUIREMENTS, UP TO A MAXIMUM
HEIGHT OF 9"
3RD FLOOR
ANCHORAGE PROCEDURES:
1. LAYOUT MULLION ANCHOR LOCATIONS.
2. DRILL 1/4"Ø PILOT HOLES TO CONFIRM NO EXISTING
REINFORCING CONFLICTS.
3. IF CONFLICTS WITH EXISTING REINFORCING, MODIFY
ANCHOR PLATE AS REQ'D FOR ANCHORAGE TO MISS
REINFORCING
1 1/2" = 1'-0"1
TYPICAL WALL SECTION @ CURTAINWALL -
ENLARGED DETAIL 1
1 1/2" = 1'-0"2
TYPICAL WALL SECTION @ CURTAINWALL -
ENLARGED DETAIL 2
1 1/2" = 1'-0"3
TYPICAL WALL SECTION @ CURTAINWALL -
ENLARGED DETAIL 3
1 1/2" = 1'-0"4
TYPICAL WALL SECTION @ CURTAINWALL -
ENLARGED DETAIL 4
ENLARGED WALL SECTIONS -
CURTAINWALL
S408
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RENOVATE BUILDING 1
03/10/2023 MLA WHLRevisions: Date:
BID DOCUMENTS
520-317X
Dwg. of
BILOXI, MISSISSIPPI
15090
NOTES:
1. DO NOT CUT EXISTING REINFORCEMENT WHEN INSTALLING ANCHORS.
REFER TO S401 FOR ADDITIONAL INFORMATION.
2. FOR ANCHORAGE DESIGN, ASSUME 2000 PSI CONCRETE. ANCHOR SPACING
SHALL NOT BE LESS THAN 16" OC. MAXIMUM FORCE PER ANCHOR SHALL
NOT EXCEED 1200 LBS.
NOTES:
1. COORDINATE NEW CURB DIMENSIONS WITH EXISTING CONDITIONS. IF CURB
CANNOT BE INSTALLED AS SHOWN, CONTACT STRUCTURAL ENGINEER
BEFORE PROCEEDING WITH NEW CONSTRUCTION.
2. DO NOT CUT EXISTING REINFORCEMENT WHEN INSTALLING ANCHORS.
REFER TO S401 FOR ADDITIONAL INFORMATION.
3. CURTAINWALL HEAD TO BE DESIGNED BY CONTRACTOR TO PERMIT A
STRUCTURAL DEFLECTION OF UP TO 0.5 INCHES WITHOUT DAMAGE TO
CURTAINWALL SYSTEM.
NOTES:
1. COORDINATE NEW CURB DIMENSIONS WITH EXISTING CONDITIONS. IF CURB
CANNOT BE INSTALLED AS SHOWN, CONTACT STRUCTURAL ENGINEER
BEFORE PROCEEDING WITH NEW CONSTRUCTION.
2. ANCHOR EMBEDMENT SHALL BE MEASURED FROM FACE OF EXISTING
CONCRETE BEAM.
3. DO NOT CUT EXISTING REINFORCEMENT WHEN INSTALLING ANCHORS.
REFER TO S401, MECHANICAL ANCHORING SYSTEMS NOTES, FOR
ADDITIONAL INFORMATION.
4. CURTAINWALL HEAD TO BE DESIGNED BY CONTRACTOR TO PERMIT A
STRUCTURAL DEFLECTION OF UP TO 0.5 INCHES WITHOUT DAMAGE TO
CURTAINWALL SYSTEM.
NOTES:
1. COORDINATE NEW CURB DIMENSIONS WITH EXISTING CONDITIONS. IF CURB
CANNOT BE INSTALLED AS SHOWN, CONTACT STRUCTURAL ENGINEER
BEFORE PROCEEDING WITH NEW CONSTRUCTION.
2. DO NOT CUT EXISTING REINFORCEMENT WHEN INSTALLING ANCHORS.
REFER TO S401 FOR ADDITIONAL INFORMATION.
3. CURTAINWALL HEAD TO BE DESIGNED BY CONTRACTOR TO PERMIT A
STRUCTURAL DEFLECTION OF UP TO 0.5 INCHES WITHOUT DAMAGE TO
CURTAINWALL SYSTEM.
File details come from the government source that posted it. Updated .