Attachment-O2__Museum_Drawings_Pt2.pdf

PDF 40 MB Posted

Attached to
Arch Museum Exhibits (JEFF 199869B) Federal contract opportunity
Solicitation number
P16PS00660
Issued by
Department of the Interior National Park Service National Office

About this file

Contract 1 - Museum Drawings Part 2 of 3

View the file

Other files for this federal contract opportunity

Other files attached to Arch Museum Exhibits (JEFF 199869B), newest first.
File Type Posted
SF30_Amendment_0011.pdf PDF
Q_and_A_Amendment_0011.pdf PDF
SF30_Amendment_0010.pdf PDF
Q_and_A_Amendment_0010.pdf PDF
SF30_Amendment_0009.pdf PDF
Q_and_A_Amendment_0009.pdf PDF
Attachment_O_UPDATE-2_Amendment_0008.pdf PDF
Amendment_0008_to_P16PS00660.pdf PDF
Attachment-H_Graphic_Communication_Amendment_0008.pdf PDF
Q_and_A_Amendment_0007.pdf PDF
SF30_Amendment_0007.pdf PDF
Attachment_O_UPDATE_Amendment_0006.pdf PDF
Q_and_A_Amendment_0005.pdf PDF
SF30_Amend_0005.pdf PDF
Attachment_W_SCA_Wage_Rates.pdf PDF
9489_(F)_MWE_502_-_Proposed_Flooring_Layout_Central_Exhibit_Space_Museum_And_The_Hubs-Arch_D .pdf PDF
Attachment_E_Supplementary_Specifications_Amendment_0004.pdf PDF
9489_(Z)_MWE_1530-Arch_D .pdf PDF
9489_(Z)_MWE_1525-Arch_D .pdf PDF
Q_and_A_Amendment_0004.pdf PDF
9489_(-)_MWE_000_-_Drawing_Issue_Register-Arch_D _(1).pdf PDF
Attachment-O3__Museum_Drawings_Pt3.pdf PDF
Attachment-O5_Museum_Specification_Vol_2.pdf PDF
Attachment-O6_Museum_Specification_Vol3.pdf PDF
Q_and_A_Amendment_0003.pdf PDF
Amendment_0003_to_P16PS00660.pdf PDF
Attachment-O4_Museum_Specification_Vol_1.pdf PDF
Revised_RFP_Amendment_0003.pdf PDF
Attachment-O1_Museum_Drawings_Pt1.pdf PDF
Amendment_0002_P16PS00660.pdf PDF
JEFF_Exhibits_Site_Visit_Presentation.pptx PPTX presentation
Final_Amendment_0001_to_P16PS00660.pdf PDF
Revised_Vol_II_Submission_Package_P16PS00660_Amendment_0001.pdf PDF
Attachment-V_NPS_map-standards.pdf PDF
Attachment-D4_JEFF_199869B_Exhibit_Fabrication_Drawings_pg_151-195.pdf PDF
Attachment-M_NPS_Standards_for_Museum_Exhibit_Display_Conditions.pdf PDF
Attachment-P_ADA_ABA_Access_Guidelines.pdf PDF
Attachment-D1_JEFF_199869B_Exhibit_Fabrication_Drawings_pg_1-50.pdf PDF
Attachment-C_1_JEFF_MWE_Database_overview_Report.pdf PDF
Attachment-Q_FMSS_ComponentInventoryForm.xlsm XLSM spreadsheet
Solicitation_P16PS00660_JEFF_Museum_Exhibits.pdf PDF
Attachment-C_3_Custom_Elements_Detail_Report.pdf PDF
Attachment-D5_JEFF_199869B_Exhibit_Fabrication_Drawings_pg_196-245.pdf PDF
Attachment-N_NPS_Ex_Conserv_Guidelines.pdf PDF
Attachment-U_NPS_EditStyleGuide2015.pdf PDF
Attachment-T_NPS_AVEquipSpecs_12-2013.pdf PDF
Attachment-L_Gov_Furnished_Mtls.pdf PDF
Vol_II_Submission_Package_P16PS00660 .pdf PDF
Attachment-G_Accessioned_Object Layouts.pdf PDF
Attachment-S_FMSS_Inspect_Guide_6-26-09.pdf PDF
Show all 50

Arch Museum Exhibits (JEFF 199869B) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F4

FIRE / SMOKE BARRIER DESIGNATIONS

MECHANICAL COVER SHEET

NO SCALE

08.31.15 RFP 005

ENLARGED MAIN FLOOR

MECHANICAL ROOM PLANS

ENLARGED MECHANICAL ROOM 121 PLAN

M-200

ENLARGED MECHANICAL ROOM 110 PLAN - PIPING

M-200

ENLARGED MECHANICAL ROOM 110 PLAN - VENTILATION

M-200

MP-135, MV-135

MP-134 MV-134

01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS

MECHANICAL ISOMETRIC VIEWS

MECHANICAL ROOM 121 ISOMETRIC VIEW

M-201

MECHANICAL ROOM 110 ISOMETRIC VIEW - PIPING

M-201

MECHANICAL ROOM 110 ISOMETRIC VIEW - VENTILATION

M-201

MP-135, MV-135

MP-134 MV-134

MECHANICAL TUNNEL ISOMETRIC VIEW

M-201

MP-145, MV-145

MECHANICAL SECTIONS

EAST WEST PARTIAL SECTION AT CENTERLINE LOOKING NORTH

M-202

EAST WEST PARTIAL SECTION AT GRIDLINE 7B LOOKING NORTH

NORTH SOUTH PARTIAL SECTION AT GRIDLINE F LOOKING WEST

M-202

M-202

NO SCALE

MP-144, MV-144

MP-137, MV-137

MP-135, MV-135

EAST WEST PARTIAL SECTION AT GRIDLINE 11 LOOKING SOUTH

M-202

MP-145, MV-145

LONGITUDINAL SEAMS - REC. DUCT

TRAPEZE HANGER DUCT

WRAP VAPOR SEAL

RECTANGULAR

MITERED ELBOW

WITH VANES

TYPE RE2

RECTANGULAR

MITERED ELBOW

TYPE RE6

RECTANGULAR

RADIUS ELBOW

TYPE RE1

RECTANGULAR

RADIUS ELBOW WITH VANES

TYPE RE3

ELBOW CONSTRUCTION

RECTANGULAR

RADIUS ELBOW WITH

SQUARE THROAT

NOT ALLOWED

RECTANGULAR / OVAL / ROUND

MITERED ELBOW

WITHOUT VANES

TYPE RE4 NOT ALLOWED

OVAL / ROUND

RADIUS ELBOW

SMOOTH OR 5 GORE (MINIMUM)

BRANCH CONNECTIONS

DUCT REINFORCEMENT DETAIL

CENTRIFUGAL FAN INLET BOX

M-203

M-203

M-203

M-203

M-203

M-203

MECHANICAL DETAILS

DIFFUSER CONNECTION DETAIL

M-204

FLEX DUCT CONNECTION W/ BALANCING DAMPER ROUND DUCT TAP CONNECTION FLEX DUCT CONNECTION

DIFFUSER INSTALLATION

SUPPLY REGISTER DETAIL

M-204

M-204

M-204

M-204

M-204

COMBINATION FIRE/SMOKE DAMPER - FRONT ACCESSFIRE DAMPER THRU WALL DETAIL

M-205

M-205

ACCESS DOOR DETAIL

M-205

TRANSFER DUCT DETAIL

M-205

EXTERIOR WALL PENETRATION

NOISE CONTROL WALL PENETRATION DETAIL

PIPE THROUGH NON-FIRE RATED WALL

RATED FIRE BARRIER PENETRATION

M-206

M-206

M-206

M-206

HOT WATER COIL PIPINGFAN COIL UNIT PIPING - TWO PIPEFAN COIL UNIT PIPING - FOUR PIPE

M-206

M-206

M-206

DIELECTRIC CONNECTION DETAIL

EXPANSION TANK

SUPPORT DETAIL

PIPE SUPPORT DETAIL

M-207

M-207

M-207

M-207

EXPANSION TANK SUPPORT DETAIL

HEAT EXCHANGER/

STEAM MAIN DRIP CONNECTION

HUMIDIFIER (ELECTRIC) DETAIL

M-208

M-208

AHU PIPING DETAIL - HEATING WATERAHU PIPING DETAIL - CHILLED WATER

M-208

M-208

MICRO CLIMATE GENERATOR PIPING DETAIL

M-208

TYPICAL SEISMIC BRACING OF SUSPENDED DUCTWORK

TRANSVERSE CABLE BRACE

LONGITUDINAL BRACE

TRANSVERSE SOLID BRACE

TRANSVERSE SOLID BRACE

TRANSVERSE CABLE BRACE

TYPICAL SEISMIC BRACING OF SUSPENDED PIPING

TYPICAL SEISMIC HOUSEKEEPING PAD

M-209

M-209

M-209

UNDER FLOOR DUCTWORK DETAIL

HDPE

FRP

FLOOR DIFFUSER DETAIL

UNDER FLOOR VAV BOX DETAIL

FLOOR ACCESS PANEL DETAIL

SECTION VIEW

PLAN VIEW

M-210

M-210

M-210

M-210

AHU-1 & AHU-6

MAXIMUM DIMENSIONS

AHU-8

MAXIMUM DIMENSIONS

AHU-2 & AHU-7

MAXIMUM DIMENSIONS

AHU-4

MAXIMUM DIMENSIONS

AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8

FUNCTIONAL ARRANGEMENT DIAGRAM

M-211

M-211

M-211

M-211

M-211

AHU-11 & AHU-12

MAXIMUM DIMENSIONS

AHU-9

MAXIMUM DIMENSIONS

AHU-10

MAXIMUM DIMENSIONS

AHU-9 & AHU-10

FUNCTIONAL ARRANGEMENT DIAGRAM

AHU-11& AHU-12

FUNCTIONAL ARRANGEMENT DIAGRAM

M-212

M-212

M-212

M-212

M-212

DOAS MAXIMUM DIMENSIONS

DOAS

FUNCTIONAL ARRANGEMENT DIAGRAM

M-213

M-213

SCHEDULE GENERAL NOTES:

A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND

INSTALLED BY:

MFR = MANUFACTURER

EC = ELECTRICAL CONTRACTOR.

MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED

BY ELECTRICAL CONTRACTOR

MFR/EC =

FURNISHED LOOSE BY MANUFACTURER

INSTALLED BY ELECTRICAL CONTRACTOR

ATC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR

B. DISCONNECT TYPE:

F = FUSED

NF = NON-FUSED

C. CONTROLLER STARTER TYPE:

FV = FULL VOLTAGE

WYE = WYE-DELTA

SS = SOLID STATE (SOFT START)

MS = MANUAL STARTER

VFD = VARIABLE FREQUENCY DRIVE

VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS

D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE,

WITH THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS

FANS FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.

E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR

NAME PLATE RATING.

F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.

G. CURB TYPE:

MFR = STANDARD CURB BY MANUFACTURER

GC = BY GENERAL CONTRACTOR

SAC = SOUND ATTENUATOR CURB

SCHEDULE ABBREVIATIONS:

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY LF LINEAR FEET

AMCA AIR MOVEMENT and CONTROL ASSOCIATION LIQ REFRIGERANT LIQUID

APD AIR PRESSURE DROP LWT LEAVING WATER TEMPERATURE

BHP BRAKE HORSE POWER MAT'L MATERIAL

BTUH BRITISH THERMAL UNIT PER HOUR MAX. MAXIMUM

C.T.I. COOLING TECHNOLOGY INSTITUTE MBH

THOUSANDS OF BTU/HOUR

CAP. CAPACITY MCA MINIMUM CIRCUIT AMPACITY

CFM CUBIC FEET PER MINUTE MHP MOTOR HORSEPOWER

COND CONDENSER MIN. MINIMUM

COP COEFFICIENT OF PERFORMANCE MOCP MAXIMUM OVERCURRENT PROTECTION

DB DRY BULB NC NOISE CRITERIA

DB DECIBEL NO. NUMBER

DEFL. DEFLECTION NPLV NON-STANDARD PART LOAD VALUE

DIM. DIMENSION O.C. ON CENTER

EAT ENTERING AIR TEMPERATURE OA OUTSIDE AIR

EER ENERGY EFFICIENCY RATING OCP OVER-CURRENT PROTECTION

EFF EFFICIENCY OPER. OPERATING

EVAP EVAPORATOR PSI POUNDS PER SQUARE INCH

EWT ENTERING WATER TEMPERATURE PSIG POUNDS PER SQUARE INCH GAUGE

EXT. SP. EXTERNAL STATIC PRESSURE RE REFERENCE

F/GR

DEGREES FAHRENHEIT PER GRAIN REFIG. REFRIGERANT

FDB DEGREES FAHRENHEIT DRY BULB REQ'D REQUIRED

FLA FULL LOAD AMPS RLA RATED LOAD AMPS

FPM FEET PER MINUTE RPM REVOLUTIONS PER MINUTE

FT. FEET SAT SATURATION

FWB DEGREE FAHRENHEIT WET BULB SCFM STANDARD CUBIC FEET PER MINUTE

GAL U.S. GALLON SEER SEASONAL ENERGY EFFICIENCY RATIO

GPM GALLON PER MINUTE SQ. FT. SQUARE FEET

H HEIGHT SUCT REFRIGERANT SUCTION

HP HORSEPOWER TEMP TEMPERATURE

HR HOUR

Uw/CM2

MILLIONTH OF A WATT PER SQUARE CENTIMETER

IN. INCH VOLT VOLTAGE

IPLV INTEGRATED PART LOAD VALUE W WIDTH

KW KILOWATTS WB WET BULB

L LENGTH WC WATER COLUMN

LAT LEAVING AIR TEMPERATURE WG WATER GAUGE

LB POUNDS WPD WATER PRESSURE DROP

DOAS SCHEDULE

SYMBOL DOAS-1

OUTSIDE AIR FAN

CFM

50,000

MINIMUM CFM

25,000

EXTERNAL STATIC PRESSURE

2"

TYPE 10 FAN ARRAY

BHP (NOTE E)

3.74/FAN

MHP (NOTE E)

4/FAN

DISCONNECT BY (NOTE A)

MFR

DISCONNECT TYPE (NOTE B)

NF

CONTROLLER/STARTER BY (NOTE A)

MFR

CONTROLLER/STARTER TYPE (NOTE C)

VFD

EXHAUST FAN

CFM

45,000

MINIMUM CFM

22,500

EXTERNAL STATIC PRESSURE

3"

TYPE 8 FAN ARRAY

BHP (NOTE E)

7.01/FAN

MHP (NOTE E)

7.5/FAN

DISCONNECT BY (NOTE A)

MFR

DISCONNECT TYPE (NOTE B)

NF

CONTROLLER/STARTER BY (NOTE A)

MFR

CONTROLLER/STARTER TYPE (NOTE C)

VFD

VOLT- PHASE

460/3

MCA 190 A

MOCP 200 A

FAN SCHEDULE

SYMBOL SERVICE CFM

S.P.

IN.

W.C.

FAN

CLASS

WHEEL

DIA.

INCHES

FAN

RPM

(NOTE F)

DRIVE

MAX.

AMCA

SONES

BACKDRAFT

DAMPER

ELECTRICAL

MANUFACTURER MODEL REMARKS

BHP

(NOTE E)

MHP

(NOTE E)

VOLT-

PHASE

DISCONNECT

CONTROLLER/STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)

SPF-1

SMOKE

PURGE

40,000

5 III 44.5

1,138

BELT

N/A

MOT 44.7 50 460-3 MFR NF MFR VFD COOK 490CA

FOR SMOKE PURGE

APPLICATION. NOTE 1

SPF-2

SMOKE

PURGE

40,000

5 III 44.5

1,138

BELT

N/A

MOT 44.7 50 460-3 MFR NF MFR VFD COOK 490CA

FOR SMOKE PURGE

APPLICATION. NOTE 1

EF-1 PAINT ROOM 905 0.6 I 12.0

1,130

BELT 9.0 MOT 0.167 0.25 115-1 MFR NF MFR MS COOK SDB

EF-2

MECH ROOM

PURGE

3,365

0.75 I 21.0 703 BELT 15 MOT 0.73 1.0 115-1 MFR NF MFR VFD COOK SDB NOTES 1 & 2

RF-7

AHU-3

RETURN

15,000

EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING

N/A

BALANCE TO 6,170 CFM

RF-10

AHU-5

RETURN

12,900

EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING

N/A

BALANCE TO 6,315 CFM

RF-NL

AHU-NL

RETURN

30,000

EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING

N/A

RF-SL

AHU-NL

RETURN

30,000

EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING

N/A

NOTES:

1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.

2. FAN SHALL RUN AT 1010 CFM FOR NORMAL OPERATION AND 3365 CFM IN EMERGENCY PURGE MODE.

HEAT RECOVERY WHEEL SCHEDULE

SYMBOL SERVICE

OA

(CFM)

EA

(CFM)

SUMMER CONDITIONS WINTER CONDITIONS

TOTAL

EFFECTIVENESS

MAX FACE

VELOCITY

(FPM)

MAX PRESSURE

DROP

(IN W.C.)

WHEEL SIZE

W "x H"

ELECTRICAL

REMARKS

OA TEMP RA TEMP TEMPERED AIR

HEAT

RECOVERED

(MBH)

OA TEMP RA TEMP TEMPERED AIR

HEAT

RECOVERED

(MBH)

MOTOR

(HP)

VOLT-

PHASE

STARTER

° FDB ° FWB ° FDB ° FWB ° FDB ° FWB ° FDB ° FWB ° FDB ° FWB ° FDB ° FWB

HRW-1 DOAS

50,000 45,000

95.5 78.6 75.0 62.5 83.0 70.1

1,000

2.5 1.0 70.0 53.0 45.1 37.3 1000

63.9/68.6

920 0.8 21x153 1.0

460/3

VFD

VFD SHALL BE PROVIDED BY AHU MANUFACTURER AND

WIRED BY ELECTRICAL CONTRACTOR.

DOAS SCHEDULE CONT.

HEATING COIL - HOT WATER

EAT °F NOTE 2

LAT °F 51.5

EWT °F 130

LWT °F 50

GPM 21.3

MBH 844.4

MAX. A.P.D. IN. W.C. 0.15

W.P.D. FEET HEAD 8.69

COOLING COIL - CHILLED WATER

EAT °F DB NOTE 2

EAT °F WB NOTE 2

LAT °F DB 58.7

LAT °F WB 57.3

EWT °F 42

LWT °F 54

GPM 310.0

TOTAL MBH

2,022.0

MAX. A.P.D. IN. W.C. 1.00

W.P.D. FEET HEAD 13.40

FILTER

TYPE - OA PRE/EA PRE

MERV 8

TYPE - OA FINAL MERV 13

VELOCITY MAX 500

MAX. A.P.D. IN. W.C.

PRE FILTER MID-LIFE

0.6

MAX. A.P.D. IN. W.C.

FINAL FILTER MID-LIFE

0.75

REMARKS

NOTES 1, 3 & 4

NOTES:

1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.

2. TEMPERATURE SHALL MATCH LAT OF HRW-1

3. REFER TO EQUIPMENT SOUND DATA SCHEDULE.

4.

REFER TO 1/M-213 DOAS FUNCTIONAL ARRANGEMENT DIAGRAM & 2/M-213 DOAS MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION

MECHANICAL SCHEDULES

AIR HANDLING UNIT SCHEDULE

SYMBOL AHU-11 AHU-12

SERVICE ENTRANCE ENTRANCE

SUPPLY FAN

CFM

9,000 9,000

EXTERNAL STATIC PRESSURE

1.5" 1.5"

TYPE PLENUM PLENUM

BHP (NOTE E)

5.70 5.70

MHP (NOTE E)

8 8

DISCONNECT BY (NOTE A)

MFR MFR

DISCONNECT TYPE (NOTE B)

NF NF

CONTROLLER/STARTER BY (NOTE A)

MFR MFR

VOLT- PHASE

460/3 460/3

HEATING COIL - HOT WATER

EAT °F 70 70

LAT °F 100 100

EWT °F 130 130

LWT °F 105 105

GPM 23.2 23.2

MBH 191.0 191.0

MAX. A.P.D. IN. W.C. 0.23 0.23

W.P.D. FEET HEAD 1.00 1.00

COOLING COIL - CHILLED WATER

EAT °F DB 85 85

EAT °F WB 70 70

LAT °F DB 62.3 62.3

LAT °F WB 59.9 59.9

EWT °F 42 42

LWT °F 60 60

GPM 26.0 26.0

TOTAL MBH 234.0 234.0

MAX. A.P.D. IN. W.C. 0.50 0.50

W.P.D. FEET HEAD 1.00 5.28

FILTER

TYPE - PRE MERV 8 MERV 8

TYPE - FINAL NONE NONE

REMARKS

NOTES 1, 2, & 3 NOTES 1, 2, & 3

NOTES:

1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.

2. REFER TO EQUIPMENT SOUND DATA SCHEDULE.

3.

REFER TO 2/M-212 AHU-11 & AHU-12 FUNCTIONAL ARRANGEMENT DIAGRAM & 5/M-212

AHU-11 & AHU-12 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.

AIR HANDLING UNIT SCHEDULE

SYMBOL AHU-1 AHU-2 AHU-3 AHU-4 AHU-5 AHU-6 AHU-7 AHU-8 AHU-9 AHU-10 AHU-NL AHU-SL

SERVICE NORTH OFFICES NORTH EXHIBIT METRO OFFICE

TUCKER

THEATER

CAFÉ

SOUTH OFFICES SOUTH EXHIBIT MUSEUM STORE ADDITION ENTRY LEVEL NORTH LEG SOUTH LEG

SUPPLY FAN

CFM

4,000 18,000 15,000 10,500 12,900 4,000 18,000 10,500 27,000 18,500 30,000 30,000

MINIMUM CFM

2,600 15,500 11,600 5,000 9,200 3,300 15,500 6,400 22,500 14,800 15,000 15,000

EXTERNAL STATIC PRESSURE

2" 2.25"

2.00

2"

1.00

2" 2.25" 2" 3" 3"

EXISTING EXISTING

TYPE PLENUM PLENUM EXISTING PLENUM EXISTING PLENUM PLENUM PLENUM PLENUM PLENUM EXISTING EXISTING

BHP (NOTE E)

3.50 21.50 17.8 13.12 8.50 3.50 21.50 13.12 16.50 11.20 EXISTING EXISTING

MHP (NOTE E)

5.0 22 20.0 15 10 5 22 15 18 12 EXISTING EXISTING

DISCONNECT BY (NOTE A)

MFR MFR EXISTING MFR EXISTING MFR MFR MFR MFR MFR EXISTING EXISTING

DISCONNECT TYPE (NOTE B)

NF NF EXISTING NF EXISTING NF NF NF NF NF EXISTING EXISTING

CONTROLLER/STARTER BY (NOTE A)

MFR MFR EXISTING MFR EXISTING MFR MFR MFR MFR MFR EXISTING EXISTING

CONTROLLER/STARTER TYPE (NOTE C)

VFD VFD EXISTING VFD EXISTING VFD VFD VFD VFD VFD EXISTING EXISTING

MINIMUM OUTSIDE AIR CFM 825

2,850 1,800 1,150 2,350

2,850 1,150 3,750 2,600 3,000 3,000

MAXIMUM OUTSIDE AIR CFM 825

5,700 3,600 2,300 4,700

5,700 2,300 7,500 7,200 3,000 3,000

VOLT- PHASE

460/3 460/3 460/3 460/3 230/3 460/3 460/3 460/3 460/3 460/3 460/3 460/3

COOLING COIL - CHILLED WATER

EAT °F DB 71.4 70.2 81 71.7 81.2 71.4 70.2 71.7 70.8 69 EXISTING EXISTING

EAT °F WB 61.5 61.2 67 61.6 66.5 61.5 61.2 61.6 61.3 60.8 EXISTING EXISTING

LAT °F DB 48 48 54.1 48 54.4 48 48 48 48 48 EXISTING EXISTING

LAT °F WB 47.9 47.9 53.5 47.9 53.6 47.9 47.9 47.9 47.9 47.9 EXISTING EXISTING

EWT °F 42 42 42 42 42 42 42 42 42 42 42 42

LWT °F 57 58 54 58 54 57 58 58 58 58 54 54

GPM 34.6 81.4 95.0 49.0 80.0 34.6 81.4 49.0 123.0 81.0 95.0 95.0

TOTAL MBH 260.0 648.0 618.0 394.0 505.0 260.0 648.0 394.0 988.0 650.0 475.0 475.0

MAX. A.P.D. IN. W.C. 0.85 1.20 0.98 0.79 1.00 0.85 1.20 0.79 1.40 1.20 EXISTING EXISTING

W.P.D. FEET HEAD 10.00 8.00 3.90 10.00 10.40 10.00 8.00 10.00 20.00 20.00 EXISTING EXISTING

HUMIDIFIER MANIFOLD

TOTAL CAPACITY #/HR

24 220 170 90 100 35 220 90 295 290 NONE NONE

STEAM GENERATOR QTY

1 2 2 1 1 1 2 1 3 3 NONE NONE

CAPACITY #/HR PER STEAM GEN.

24 110 85 90 100 35 110 90 98 97 NONE NONE

FILTER

TYPE - PRE MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8

TYPE - FINAL MERV 13 MERV 13

N/A

MERV 13

N/A

MERV 13 MERV 13 MERV 13 MERV 13 MERV 13

N/A N/A

VELOCITY PRE/FINAL

375 475 EXISTING 425 EXISTING 375 475 425 500 500 EXISTING EXISTING

MAX. A.P.D. IN. W.C.

PRE FILTER MID-LIFE

0.6 0.45 EXISTING 0.65 EXISTING 0.6 0.45 0.65 0.6 0.6 EXISTING EXISTING

MAX. A.P.D. IN. W.C.

FINAL FILTER MID-LIFE

0.75 0.6

N/A

0.75

N/A

0.75 0.6 0.75 0.75 0.75

N/A N/A

REMARKS

NOTES 1, 2, & 5 NOTES 1, 2, & 6 NOTES 3, 4, & 11 NOTES 1, 2,& 7 NOTES 3, 4, & 11 NOTES 1, 2, & 5 NOTES 1, 2, & 6 NOTES 1, 2, & 8 NOTES 1, 2, & 9 NOTES 1, 2, & 10

NOTES 3 & 4 NOTES 3 & 4

NOTES:

1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.

2. REFER TO EQUIPMENT SOUND DATA SCHEDULE.

3. EXISTING TO REMAIN

4. REFER TO FAN SCHEDULE FOR RETURN FAN INFORMATION.

5.

REFER TO 1/M-211AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 3/M-211 AHU-1 & AHU-6 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.

6.

REFER TO 1/M-211 AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 4/M-211 AHU-2 & AHU-7 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.

7.

REFER TO 1/M-211 AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 5/M-211 AHU-4 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.

8.

REFER TO 1/M-211 AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 2/M-211 AHU-8 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.

9.

REFER TO 1/M-212 AHU-9 & AHU-10 FUNCTIONAL ARRANGEMENT DIAGRAM & 3/M-212 AHU-9 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.

10.

REFER TO 1/M-212 AHU-9 & AHU-10 FUNCTIONAL ARRANGEMENT DIAGRAM & 4/M-212 AHU-10 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.

11. PROVIDE ELECTRIC STEAM HUMIDIFIER FOR SCHEDULED CAPACITY. MOUNT MANIFOLD IN SUPPLY DUCTWORK.

MECHANICAL SCHEDULES

05.20.16 RFP 221

TERMINAL AIR BOX SCHEDULE - SINGLE DUCT REHEAT

SYMBOL

AREA SERVED

CFM

HEATING COIL (NOTES 5 & 6)

MIN.

INLET

SIZE (IN.)

CONTROL

TYPE

(NOTE 3)

SENSOR

TYPE

(NOTE 4)

MFR MODEL REMARKS

COOLING

MAX.

HEATING

MAX.

MIN.

EAT

°F

LAT

°F

EWT

°F

MAX.

GPM

VAV-1.1 BREAKROOM

1,435 1,435 1,435

55 95 130 6.3 12 B 4 PRICE SDV NOTES 1 & 2

VAV-1.2 B&U STAFF AREA 850 850 850 55 95 130 3.7 9 B 4 PRICE SDV NOTES 1 & 2

VAV-1.3 OFFICE 405 335 335 55 95 130 1.5 7 A 4 PRICE SDV NOTES 1 & 2

VAV-2.1 LOBBY

3,140 3,140 3,140

55 95 130 13.8 24x16 B 1 PRICE SDV NOTES 1 & 2

VAV-2.2 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-2.3 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-2.4 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-2.5 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-2.6 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-3.1 ATS

1,000 1,000 1,000

55 95 130 4.4 10 B 4 PRICE SDV NOTES 1 & 2

VAV-3.2 SECURITY OFICE 430 195 195 55 95 130 0.9 5 A 4 PRICE SDV NOTES 1 & 2

VAV-3.3 OFFICE 150 100 100 55 95 130 0.5 4 A 4 PRICE SDV NOTES 1 & 2

VAV-3.4 METRO OFFICE 290 225 225 55 95 130 1.0 6 A 4 PRICE SDV NOTES 1 & 2

VAV-3.5 CONFERENCE 310 310 310 55 95 130 1.4 6 B 4 PRICE SDV NOTES 1 & 2

VAV-3.6 LOBBY

3,420 3,420 3,420

55 95 130 15.0 24x16 B 1 PRICE SDV NOTES 1 & 2

VAV-3.7 LOBBY

3,420 3,420 3,420

55 95 130 15.0 24x16 B 1 PRICE SDV NOTES 1 & 2

VAV-3.8 RAMP

2,940 2,940 2,940

55 95 130 12.9 24x16 B 1 PRICE SDV NOTES 1 & 2

VAV-4.1

TUCKER

PROJECTION

1,400 1,400 1,400

55 95 130 6.2 12 B 4 PRICE SDV NOTES 1 & 2

VAV-5.1 STORAGE 240 240 240 55 95 130 1.1 5 B 4 PRICE SDV NOTES 1 & 2

VAV-5.2

CAFÉ BOH

1,740

515 515 55 95 130 2.3 14 A 4 PRICE SDV NOTES 1 & 2

VAV-5.3

CAFÉ

2,200 2,200 2,200

55 95 130 9.7 16 B 1 PRICE SDV NOTES 1 & 2

VAV-5.4 LOBBY

2,160 2,160 2,160

55 95 130 9.5 16 B 1 PRICE SDV NOTES 1 & 2

VAV-5.5 LOBBY

2,160 2,160 2,160

55 95 130 9.5 16 B 1 PRICE SDV NOTES 1 & 2

VAV-5.6 RAMP

1,940 1,940 1,940

55 95 130 8.5 12 B 1 PRICE SDV NOTES 1 & 2

VAV-6.1 OFFICE 295 215 215 55 95 130 0.9 6 A 4 PRICE SDV NOTES 1 & 2

VAV-6.2 IR OFFICE

1,230 1,230 1,230

55 95 130 5.4 12 B 4 PRICE SDV NOTES 1 & 2

VAV-6.3 IR MEETING 680 680 680 55 95 130 3.0 8 B 4 PRICE SDV NOTES 1 & 2

VAV-6.4 OFFICE 900 900 900 55 95 130 4.0 10 B 4 PRICE SDV NOTES 1 & 2

VAV-6.5 STORAGE 360 360 360 55 95 130 1.6 6 B 4 PRICE SDV NOTES 1 & 2

VAV-7.1 LOBBY

3,140 3,140 3,140

55 95 130 13.8 24x16 B 1 PRICE SDV NOTES 1 & 2

VAV-7.2 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-7.3 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-7.4 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-7.5 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-7.6 EXHIBIT

2,475 2,475 2,475

55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2

VAV-8.1

MUSEUM STORE

OFFICES

495 360 360 55 95 130 1.6 7 A 4 PRICE SDV NOTES 1 & 2

VAV-8.2

MUSEUM STORE

OFFICES

370 235 235 55 95 130 1.0 6 A 4 PRICE SDV NOTES 1 & 2

VAV-8.3

MUSEUM STORE

STORAGE

725 725 725 55 95 130 3.2 9 B 4 PRICE SDV NOTES 1 & 2

VAV-8.4

MUSEUM STORE

STORAGE

850 850 850 55 95 130 3.7 9 B 4 PRICE SDV NOTES 1 & 2

TERMINAL AIR BOX SCHEDULE - SINGLE DUCT REHEAT CONT.

SYMBOL

AREA SERVED

CFM

HEATING COIL (NOTES 5 & 6)

MIN.

INLET

SIZE (IN.)

CONTROL

TYPE

(NOTE 3)

SENSOR

TYPE

(NOTE 4)

MFR MODEL REMARKS

COOLING

MAX.

HEATING

MAX.

MIN.

EAT

°F

LAT

°F

EWT

°F

MAX.

GPM

VAV-9.1 EXHIBIT

3,725 3,725 3,725

55 95 130 16.4 24x16 B 1 PRICE SDV

NOTES 1, 2, & 7

VAV-9.2 EXHIBIT

3,725 3,725 3,725

55 95 130 16.4 24x16 B 1 PRICE SDV

NOTES 1, 2, & 7

VAV-9.3 MEZZANINE

2,700 2,370 2,370

55 95 130 10.4 16 A 1 PRICE SDV

NOTES 1, 2, & 7

VAV-9.4 MEZZANINE

2,700 2,370 2,370

55 95 130 10.4 16 A 1 PRICE SDV

NOTES 1, 2, & 7

VAV-9.5

MEZZANINE/EXHIBIT

3,600 3,600 3,600

55 95 130 15.8 24x16 B 1 PRICE SDV

NOTES 1, 2, & 7

VAV-9.6

MEZZANINE/EXHIBIT

3,600 3,600 3,600

55 95 130 15.8 24x16 B 1 PRICE SDV

NOTES 1, 2, & 7

VAV-9.7 VOLUNTEER OFFICE 445 360 360 55 95 130 1.6 7 A 4 PRICE SDV NOTES 1 & 2

VAV-9.8 OFFICE 405 350 350 55 95 130 1.5 7 A 4 PRICE SDV NOTES 1 & 2

VAV-9.9 MULTIPURPOSE 920 920 920 55 95 130 4.0 10 B 4 PRICE SDV NOTES 1 & 2

VAV-9.10 MULTIPURPOSE 920 920 920 55 95 130 4.0 10 B 4 PRICE SDV NOTES 1 & 2

VAV-9.11 VESTIBULE 200 105 105 55 95 130 0.5 5 A 1 PRICE SDV NOTES 1 & 2

VAV-9.12 CATERING 615 350 350 55 95 130 1.5 8 A 4 PRICE SDV NOTES 1 & 2

VAV-9.13 CORRIDOR 160 105 105 55 95 130 0.5 4 A 1 PRICE SDV NOTES 1 & 2

VAV-10.1 CORRIDOR 440 200 200 55 95 130 0.9 7 A 1 PRICE SDV NOTES 1 & 2

VAV-10.2 SCREENING

2,080 2,080 2,080

55 95 130 9.2 14 B 1 PRICE SDV NOTES 1 & 2

VAV-10.3 OFFICE 490 220 220 55 95 130 1.0 7 A 4 PRICE SDV NOTES 1 & 2

VAV-10.4 SECURITY

2,160 2,160 2,160

55 95 130 9.5 16 B 1 PRICE SDV NOTES 1 & 2

VAV-10.5 SECURED VESTIBULE 390 170 170 55 95 130 0.7 6 A 1 PRICE SDV NOTES 1 & 2

VAV-10.6 TICKETING

2,310 2,310 2,310

55 95 130 10.2 16 B 1 PRICE SDV NOTES 1 & 2

VAV-10.7 OFFICE 355 155 155 55 95 130 0.7 6 A 4 PRICE SDV NOTES 1 & 2

VAV-10.8 CORRIDOR 960 330 330 55 95 130 1.5 10 A 1 PRICE SDV NOTES 1 & 2

VAV-10.9 CORRIDOR 520 180 180 55 95 130 0.8 7 A 1 PRICE SDV NOTES 1 & 2

VAV-10.10 LOBBY

1,640 1,640 1,640

55 95 130 7.2 14 B 1 PRICE SDV

NOTES 1, 2, & 8

VAV-10.11 LOBBY

1,640 1,640 1,640

55 95 130 7.2 14 B 1 PRICE SDV

NOTES 1, 2, & 8

VAV-10.12 LOBBY

1,640 1,640 1,640

55 95 130 7.2 14 B 1 PRICE SDV

NOTES 1, 2, & 8

VAV-10.13 ENTRY

2,130 2,130 2,130

55 95 130 9.4 14 B 1 PRICE SDV

NOTES 1, 2, & 8

NOTES:

1.

NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER ARI STANDARD 885-98

USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE.

2.

TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC.

3. SEE SHEET M-512 FOR DESCRIPTION OF CONTROL TYPE.

4.

SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE.

5. HEATING COIL IS BASED ON HEATING AIR FLOW. WATER PRESSURE DROP OF REHEAT COILS SHALL NOT EXCEED 5'. PROVIDE REHEAT COILS SEPARATE

FROM BOXES IF REQUIRED TO MEET WATER PRESSURE DROP REQUIREMENTS.

6.

HEATING COIL SELECTION SHALL BE BASED ON A FIXED LEAVING AIR TEMPERATURE AND VARIABLE FLOW (GPM). PROVIDE FINAL MAXIMUM FLOW

RATE (GPM) TO TEST AND BALANCE & TEMPERATURE CONTROLS CONTRACTORS.

7. CONTROLS SHALL BE 24V.

8. VAV LOCATED IN UNDERFLOOR VAULT.

FAN COIL UNIT SCHEDULE - HYDRONIC

SYMBOL SERVICE CFM

MIN. OA

CFM

EAT COOLING COIL HEATING COIL ELECTRICAL

MANUFACTURER MODEL REMARKS

DB °F WB °F

TOTAL

MBH

SENSIBLE

MBH

GPM

EWT

°F

LWT

°F

W.P.D.

FT. HD

TOTAL

MBH

GPM

EWT

°F

LWT

°F

W.P.D.

FT. HD

POWER

(W)

RPM

VOLT-

PHASE

DISCONNECT STARTER

BY (NOTE A) TYPE (NOTE B) TYPE (NOTE A)

FCU-1 TC 890

N/A

75 62 24.7 20.3 3.1 42 58 3.2

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCB

FCU-2 TC 890

N/A

75 62 24.7 20.3 3.1 42 58 3.2

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCB

FCU-3 TC 890

N/A

75 62 24.7 20.3 3.1 42 58 3.2

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCB

FCU-4 TC 890

N/A

75 62 24.7 20.3 3.1 42 58 3.2

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCB

FCU-5 TC 890

N/A

75 62 24.7 20.3 3.1 42 58 3.2

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCB

FCU-6 TC 890

N/A

75 62 24.7 20.3 3.1 42 58 3.2

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCB

FCU-7 TC 890

N/A

75 62 24.7 20.3 3.1 42 58 3.2

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCB

FCU-8 NORTH EMR 921

N/A

85 63 33.3 32.3 4.6 42 57 6.5

N/A N/A N/A N/A N/A

1,100

115-1 MFR NF FV TRANE FCB

FCU-9

ED

STORAGE

N/A

75 62 11.5 11.5 2.0 42 58 1.5

N/A N/A N/A N/A N/A

40 630 115-1 MFR NF FV TRANE FCB

FCU-10 SOUTH EMR

3,000 N/A

80 63 78.0 77.0 9.9 42 59 1.5

N/A N/A N/A N/A N/A 1 1/2 HP

815 208-3 MFR NF FV TRANE BCHC

FCU-11 TC 287

N/A

75 62 5.9 4.7 0.8 42 58 8.8

N/A N/A N/A N/A N/A

1,480

115-1 MFR NF FV TRANE FCC

FCU-12 TC 287

N/A

75 62 5.9 4.7 0.8 42 58 8.8

N/A N/A N/A N/A N/A

1,480

115-1 MFR NF FV TRANE FCC

FCU-13

SERVICE

ENTRY

N/A

75 62 8.0 7.5 1.0 42 58 0.7 10.0 1.0 130 109 4.6 40 815 115-1 MFR NF FV TRANE FCD

FCU-14

NORTH

CORRIDOR

N/A

75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125

1,100

115-1 MFR NF FV TRANE FCD

FCU-15

NORTH

CORRIDOR

N/A

75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125

1,100

115-1 MFR NF FV TRANE FCD

FCU-16

NORTH

CORRIDOR

N/A

75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125

1,100

115-1 MFR NF FV TRANE FCD

FCU-17

NORTH

CORRIDOR

N/A

75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125

1,100

115-1 MFR NF FV TRANE FCD

FCU-18

NORTH

CORRIDOR

N/A

75 62 3.0 3.0 0.5 42 54 1.0 12.0 0.8 130 99 1.0 40 825 115-1 MFR NF FV TRANE FCD

FCU-19 ELEC

1,500 N/A

80 63 37.5 36.7 5.5 42 56 0.5

N/A N/A N/A N/A N/A 1/2 HP

515 208-3 MFR NF FV TRANE BCHC

FCU-20 MECH

3,365 3,365

95 75 78.0 76.0 4.9 42 76 0.5 175.0 5.8 130 71 1.2 2 HP

1,050

208-3 MFR NF VFD TRANE BCHC NOTE 1

FCU-21 NORTH ELEC 980 45 75 62 17.8 17.4 2.6 42 56 2.2 15.4 0.8 130 92 4.2 165

1,090

115-1 MFR NF FV TRANE FCD

FCU-22

NORTH

CORRIDOR

N/A

75 62 6.0 5.8 0.8 42 58 1.2 14.2 1.3 130 108 2.3 40 825 115-1 MFR NF FV TRANE FCD

FCU-23

NORTH

CORRIDOR

N/A

75 62 6.2 6.0 0.8 42 58 1.2 13.9 1.2 130 107 2.3 40 825 115-1 MFR NF FV TRANE FCD

FCU-24

NORTH

CORRIDOR

N/A

75 62 3.1 2.5 0.4 42 58 1.0 7.7 0.5 130 99 1.4 40

1,080

115-1 MFR NF FV TRANE FCD

FCU-25

SOUTH

CORRIDOR

N/A

75 62 3.1 2.5 0.4 42 58 1.0 7.7 0.5 130 99 1.4 40

1,080

115-1 MFR NF FV TRANE FCD

FCU-26

SOUTH

CORRIDOR

N/A

75 62 6.2 6.0 0.8 42 58 1.2 13.9 1.2 130 107 2.3 40 825 115-1 MFR NF FV TRANE FCD

FCU-27

SOUTH

CORRIDOR

N/A

75 62 6.2 5.8 0.8 42 58 1.2 15.5 1.4 130 107 2.3 40 825 115-1 MFR NF FV TRANE FCD

FCU-28 SOUTH ELEC

1,050 N/A

75 62 22.4 22.0 6.1 42 53 10.4

N/A N/A N/A N/A N/A

1,085

115-1 MFR NF FV TRANE FCD

FCU-29

SOUTH

CORRIDOR

N/A

75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150

1,075

115-1 MFR NF FV TRANE FCD

FCU-30

SOUTH

CORRIDOR

N/A

75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150

1,075

115-1 MFR NF FV TRANE FCD

FCU-31

SOUTH

CORRIDOR

N/A

75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150

1,075

115-1 MFR NF FV TRANE FCD

NOTES:

1.

FCU IS 100% RAW OUTSIDE AIR. UNIT SHALL RUN AT 1010 CFM FOR NORMAL OPERATION AND 3365 CFM IN EMERGENCY PURGE MODE. HEATING EAT 0 °F.

MECHANICAL SCHEDULES

RFP 05211.03.15

AIR CURTAIN SCHEDULE

SYMBOL SERVICE CFM

OVERALL

DIMENSIONS

L x H x D (IN.)

HEATING COIL

ELECTRICAL

MANUFACTURER MODEL REMARKS

HP

VOLT-

PHASE

FLA

DISCONNECT

TYPE EWT LWT GPM MBH

BY (NOTE A) TYPE (NOTE B)

ACR-1

SHIPPING/

RECEIVING

20,700

155 x 36 x 28

HOT

WATER

130 110 40 447 10 460-3 13.0 MFR NF MARS AIR BD 18

NOTES 1, 2

NOTES:

1.

MANUFACTURER SHALL PROVIDE FACTORY WIRED MOTOR STARTER, DISCONNECT, AND CONTROL TRANSFORMER AS REQUIRED FOR SINGLE POINT POWER CONNECTION

2. MANUFACTURER SHALL PROVIDE TIME DELAY RELAY AND REMOTE THERMOSTAT. SEE SPECIFICATIONS FOR DETAILS.

RELIEF VAV SCHEDULE

SYMBOL

AREA SERVED

CFM

MIN.

INLET

SIZE (IN.)

CONTROL

TYPE

(NOTE 3)

MANUFACTURER MODEL REMARKS

BOX

MAX.

BOX MIN.

EX-01

B&U OFFICE AREA (AHU-1)

750 750 9 D PRICE SDE

NOTES 1, 2

EX-02

TUCKER PROJECTION (AHU-4)

800 800 9 D PRICE SDE

NOTES 1, 2

EX-03

NORTH LEG (AHU-NL) 2,700 2,700

16 D PRICE SDE

NOTES 1, 2

EX-04

METRO OFFICES (AHU-3) 2,115

495 14 C PRICE SDE

NOTES 1, 2

EX-05

MENS RESTROOM (AHU-3) 1,125 1,125

12 D PRICE SDE

NOTES 1, 2

EX-06

WOMENS RESTROOM (AHU-5)

905 905 10 C PRICE SDE

NOTES 1, 2

EX-07

FOOD SERVICE (AHU-5) 3,325 1,210

24x16 C PRICE SDE

NOTES 1, 2

EX-08

SOUTH LEG (AHU-SL) 2,700 2,700

16 D PRICE SDE

NOTES 1, 2

EX-09

MUSEUM STORE (AHU-8) 2,070 1,035

14 C PRICE SDE

NOTES 1, 2

EX-10

IR OFFICE AREA (AHU-6)

785 785 9 D PRICE SDE

NOTES 1, 2

EX-11

TUCKER THEATER (AHU-4) 1,270

235 12 C PRICE SDE

NOTES 1, 2

EX-12

ADDITION EXHAUST (AHU-9/AHU-10) 2,790 2,790

16 D PRICE SDE

NOTES 1, 2

NOTES:

1.

NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED

PER ARI STANDARD 885-98 USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE.

2.

TOTAL AIR PRESSURE DROP OF TAB SHALL NOT EXCEED 0.50" WC.

3. SEE M-512 FOR DESCRIPTION OF CONTROL TYPE.

LOUVER SCHEDULE

SYMBOL SERVICE CFM

SIZE

W x H

(IN.)

FREE

AREA

VEL. FPM

S.P.

IN.

W.C.

FINISH MANUFACTURER MODEL

L-1 MAKEUP AIR

4,400

78x48 338 0.01 NOTE 1 RUSKIN ET125-30

L-2 SMOKE PURGE

30,000

84X84 975 0.1 NOTE 1 RUSKIN ET125-30

NOTES:

1. BAKED ENAMEL FINISH ON PRETREATED PRIME PAINT. STANDARD COLOR - SELECTION BY ARCHITECT.

UNIT HEATER SCHEDULE - HOT WATER

SYMBOL TYPE CFM MBH GPM

EWT

°F

LWT

°F

W.P.D.

FT.

HEAD

ELECTRICAL

CONTROL MANUFACTURER MODEL

HP RPM

VOLT-

PHASE

DISCONNECT

CONTROLLER/

STARTER

BY

(NOTE A)

TYPE

(NOTE B)

BY (NOTE A)

UH-1 HORIZONTAL 350 4.9 0.5 130 110 0.0

1/40 1,350

115-1 MFR NF MFR NOTE 1 TRANE UHS

UH-2 HORIZONTAL 630 13.2 1.3 130 110 0.1

1/20

900 115-1 MFR NF MFR NOTE 1 TRANE UHS

UH-3 HORIZONTAL

1,100

26.5 2.7 130 110 0.3

1/12

900 115-1 MFR NF MFR NOTE 1 TRANE UHS

UH-4 HORIZONTAL

1,100

26.5 2.7 130 110 0.3

1/12

900 115-1 MFR NF MFR NOTE 1 TRANE UHS

UH-5 HORIZONTAL 630 13.2 1.3 130 110 0.1

1/20

900 115-1 MFR NF MFR NOTE 1 TRANE UHS

NOTES:

1.

REFER TO 2/M-518.

COIL SCHEDULE - WATER

SYMBOL SERVICE

SIZE

L x H

(IN.)

CFM

EAT LAT

TOTAL

MBH

A.P.D.

IN.

W.C.

EWT

°F

LWT

°F

GPM

W.P.D.

FT.

HEAD

MANUFACTURER REMARKS

°FDB °FDB

HC-1

NORTH LEG

AHU

56x106

20,000

66 100 748 0.1 130 110 75.0 1.0 CUSTOM

NOTE 1, SIZE LISTED IS TOTAL

SIZE FOR 3 SECTIONS

HC-2

SOUTH LEG

AHU

56x106

20,000

66 100 748 0.1 130 110 75.0 1.0 CUSTOM

NOTE 1, SIZE LISTED IS TOTAL

SIZE FOR 3 SECTIONS

HC-3 AHU-3 18x102

15,000

50 60 165 0.4 130 110 16.5 3.1 CARRIER NOTE 1

HC-4 AHU-5 48x82

12,900

50 60 142 0.07 130 110 11.4 1.0 MCQUAY

NOTE 1, SIZE LISTED IS TOTAL

SIZE FOR 2 SECTIONS

HC-5

TUCKER

THEATER

36x20

2,775

48 70 67 0.40 130 92 3.5 0.1 NOTE 3 NOTE 2

HC-6

TUCKER

THEATER

36x20

2,775

48 70 67 0.40 130 92 3.5 0.1 NOTE 3 NOTE 2

NOTES:

1. COILS TO BE INSTALLED IN EXISTING AIR HANDLERS TO REPLACE STEAM HEAT COILS. VERIFY DIMENSIONS AND CONNECTIONS PRIOR TO ORDERING COILS.

2. COILS TO BE INSTALLED IN EXISTING DUCTWORK. VERIFY DIMENSIONS AND CONNECTIONS PRIOR TO ORDERING COILS.

3. REFER TO SPECIFICATION SECTION 23 82 16 FOR APROVED MANUFACTURERS.

FAN COIL UNIT SCHEDULE - HYDRONIC CONT.

SYMBOL SERVICE CFM

MIN. OA

CFM

EAT COOLING COIL HEATING COIL ELECTRICAL

MANUFACTURER MODEL REMARKS

DB °F WB °F

TOTAL

MBH

SENSIBLE

MBH

GPM

EWT

°F

LWT

°F

W.P.D.

FT. HD

TOTAL

MBH

GPM

EWT

°F

LWT

°F

W.P.D.

FT. HD

POWER

(W)

RPM

VOLT-

PHASE

DISCONNECT STARTER

BY (NOTE A) TYPE (NOTE B) TYPE (NOTE A)

FCU-32

SOUTH

CORRIDOR

N/A

75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150

1,075

115-1 MFR NF FV TRANE FCD

FCU-33

SOUTH

CORRIDOR

N/A

75 62 3.0 3.0 0.5 42 54 1.0 12.0 0.8 130 99 1.0 40 825 115-1 MFR NF FV TRANE FCD

FCU-34 SW MECH 550

N/A

75 62 10.2 9.9 1.4 42 56 1.1

N/A N/A N/A N/A N/A

1,080

115-1 MFR NF FV TRANE FCD

FCU-35

SHIPPING/

RECEIVING

980 55 75 62 16.2 14.0 2.4 42 56 2.5 29.8 2.2 130 103 2.0 160

1,090

115-1 MFR NF FV TRANE FCD

FCU-36 TC 211

N/A

75 62 5.0 3.8 0.7 42 58 6.1

N/A N/A N/A N/A N/A

60 980 115-1 MFR NF FV TRANE FCB

FCU-37

TICKETING

CLOSET

211 338 75 62 10.9 7.7 1.4 42 58 7.7

N/A N/A N/A N/A N/A

1,050

115-1 MFR NF FV TRANE FCB

FCU-38 TC 211

N/A

75 62 5.0 3.8 0.7 42 58 6.1

N/A N/A N/A N/A N/A

60 980 115-1 MFR NF FV TRANE FCB

FCU-39

DREAM

WALL

N/A

85 63 33.3 32.3 4.6 42 57 6.5

N/A N/A N/A N/A N/A

1,100

115-1 MFR NF FV TRANE FCB

FCU-40

CONTROL

ROOM

N/A

85 63 33.3 32.3 4.6 42 57 6.5

N/A N/A N/A N/A N/A

1,100

115-1 MFR NF FV TRANE FCB

FCU-41

CONTROL

ROOM

N/A

85 63 33.3 32.3 4.6 42 57 6.5

N/A N/A N/A N/A N/A

1,100

115-1 MFR NF FV TRANE FCB

FCU-42 EMR 256

N/A

75 62 9.1 6.2 1.3 42 58 5.0

N/A N/A N/A N/A N/A

40 825 115-1 MFR NF FV TRANE FCB

MECHANICAL SCHEDULES

NO SCALE

07.28.15 RFP 002

10.30.15 RFP 052

02.02.16 RFP 112

EXISTING COOLING TOWER SCHEDULE

SYMBOL SERVICE

MIN.

C.T.I.

TONS

MAX

GPM

MIN GPM

CONDENSING

WATER

AMBIENT

CONDITIONS

FAN DATA

OPERATING

WEIGHT

ELECTRICAL

MANUFACTURER MODEL

VOLT-

PHASE

DISCONNECT

CONTROLLER/STARTER

EWT °F LWT °F °FDB °FWB

NUMBER

OF FANS

HP

BY

(NOTE A)

TYPE

(NOTE B)

BY

(NOTE A)

TYPE

(NOTE C)

SCCR

CT-1 CH-1 & CH-2 600 1890.0 900.0 95 85 90 78 2 40 32150 460 EXISTING EXISTING EXISTING EXISTING EXISTING BAC VT1-680

EXISTING CHILLER SCHEDULE (WATER COOLED)

SYMBOL SERVICE REFRIGERANT

CAPACITY/PERFORMANCE

EVAPORATOR PERFORMANCE CONDENSER PERFORMANCE ELECTRICAL

MANUFACTURER MODEL REMARKS

DESIGN

TONS

STAGES OF

UNLOADING

MAX. KW/TON AT % LOAD

NPLV

KW/TON

EWT

°F

LWT

°F

GPM

MAXIMUM

PRESS DROP

FT. HEAD

FOULING

FACTOR

EWT

°F

LWT

°F

GPM

MAXIMUM

PRESS DROP

FT. HEAD

FOULING

FACTOR

VOLT-

PHASE

MOCP

AMPS

DISCONNECT

CONTROLLER/STARTER

BY

(NOTE A)

TYPE

(NOTE B)

BY

(NOTE A)

TYPE

(NOTE C)

100 75 50 25

CH-1

WHOLE

BUILDING

123 300 INFINITE 0.59 0.44 0.33 0.40 0.38 52 42 745.0 10.0 0.0001 85 95 930.0 5.0 0.0001

460/3

500.0 EXISTING EXISTING MFR VFD YORK YT J3A3C3 NOTE 1

CH-2

WHOLE

BUILDING

123 300 INFINITE 0.59 0.44 0.33 0.40 0.38 52 42 745.0 10.0 0.0001 85 95 930.0 5.0 0.0001

460/3

500.0 EXISTING EXISTING MFR VFD YORK YT J3A3C3 NOTE 1

NOTES:

1. CHILLERS ARE EXISTING TO BE RELOCATED.

EQUIPMENT SOUND DATA

SYMBOL

MAXIMUM ALLOWABLE DISCHARGE GENERATED NOISE IN DB RE 10

WATTS MAXIMUM ALLOWABLE INLET GENERATED NOISE IN DB RE 10

WATTS MAXIMUM ALLOWABLE RADIATED GENERATED NOISE IN DB RE 10

WATTS

OCTAVE BAND CENTER FREQUENCY OCTAVE BAND CENTER FREQUENCY OCTAVE BAND CENTER FREQUENCY

63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

AHU-1 87 83 77 100 92 94 87 79 80 77 73 91 70 74 68 59 81 75 70 85 75 65 59 54

AHU-2 91 92 99 96 90 85 83 81 85 86 100 93 82 78 75 73 80 79 78 82 76 63 59 59

AHU-4 84 88 84 98 93 92 88 85 78 84 82 89 67 70 67 59 80 79 78 82 76 63 59 59

AHU-6 87 83 77 100 92 94 87 79 80 77 73 91 70 74 68 59 81 75 70 85 75 65 59 54

AHU-7 91 92 99 96 90 85 83 81 85 86 100 93 82 78 75 73 80 79 78 82 76 63 59 59

AHU-8 84 88 84 98 93 92 88 85 78 84 82 89 67 70 67 59 80 79 78 82 76 63 59 59

AHU-9 93 94 98 97 93 89 87 84 84 90 102 90 84 84 83 77 80 79 78 82 76 63 59 59

AHU-10 89 89 101 100 95 92 88 80 89 89 100 97 88 86 84 76 80 79 78 82 76 63 59 59

AHU-11 78 80 87 71 72 70 65 54 92 92 91 83 80 79 74 69 82 74 72 60 54 48 41 28

AHU-12 78 80 87 71 72 70 65 54 92 92 91 83 80 79 74 69 82 74 72 60 54 48 41 28

CH-3 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 67 73 62 59 71 69 57 51

DOAS-1 95 101 100 94 93 89 83 77 97 103 100 87 87 84 77 73 80 79 78 82 76 63 59 59

CHILLER SCHEDULE (WATER COOLED)

SYMBOL SERVICE REFRIGERANT

CAPACITY/PERFORMANCE

EVAPORATOR PERFORMANCE CONDENSER PERFORMANCE ELECTRICAL NOTE 3

MANUFACTURER MODEL REMARKS

DESIGN

TONS

STAGES OF

UNLOADING

MAX. KW/TON AT % LOAD (NOTE 1)

NPLV

KW/TON

EWT

°F

LWT

°F

GPM

MAXIMUM

PRESS DROP

FT. HEAD

FOULING

FACTOR

EWT

°F

LWT

°F

GPM

MAXIMUM

PRESS DROP

FT. HEAD

FOULING

FACTOR

VOLT-

PHASE

MCA

MOCP

AMPS

DISCONNECT

CONTROLLER/STARTER

BY

(NOTE A)

TYPE

(NOTE B)

BY

(NOTE A)

TYPE

(NOTE C)

SCCR

100 75 50 25

CH-3

HEAT

RECOVERY

134A 90 INFINITE 0.96 1.01 1.05 1.15 1.05 52 42 190.0 20.0 0.0001 110 130 130.0 5.0 0.0001

460/3

139.0 200.0 MFR NF MFR VFD 65000 TRANE RTWD NOTES 2 & 4

NOTES:

1. BASED ON WATER CONDITIONS LISTED IN SCHEDULE.

2. REFER TO SPECIFICATION SECTION 23 64 16 FOR ADDITIONAL INFORMATION.

3. ELECTRICAL CONNECTIONS SHALL ACCOMMODATE THE WIRE SIZES AND QUANTITIES SHOWN ON THE ELECTRICAL DRAWINGS.

4.

PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.

5.

REFER TO EQUIPMENT SOUND DATA SCHEDULE.

PUMP SCHEDULE

SYMBOL SERVICE GPM

PUMP FT.

HEAD AT

DESIGN

MIMIMUM

PUMP

EFFICIENCY

INLET/IMPEL.

SIZE IN.

ELECTRICAL

MANUFACTURER MODEL REMARKS

HP

(NOTE E)

RPM

VOLT-

PHASE

DISCONNECT

CONTROLLER/STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)

PHWP-1

PRIMARY HEATING

WATER - HX

400.0 14 66

5/5.125

1,750

460/3

MFR NF MFR MS B&G 1510 4AC

PHWP-2

PRIMARY HEATING

WATER - HRC

130.0 23 67

3/5.375

1.5

1,750 460/3

MFR NF MFR MS B&G 1510 2.5AB

SHWP-1

SECONDARY HEATING

WATER

800.0 70 82

6/9.25

1,750

460/3

MFR NF MFR VFD B&G 1510 5E

DUTY, NOTE 1

SHWP-2

SECONDARY HEATING

WATER

800.0 70 82

6/9.25

1,750 460/3

MFR NF MFR VFD B&G 1510 5E

STANDBY, NOTE 1

HWCP-1

HEATING WATER COIL -

DOAS

25.0 21 53

1.25/4.625

0.5

1,750 460/3

MFR NF MFR MS B&G 60 1.25x1.25x5.25

PCWP-1

PRIMARY CHILLED

WATER

745.0 38 79

6/8.125

1,750 460/3

MFR NF MFR MS B&G 1510 5BC

PCWP-2

PRIMARY CHILLED

WATER

745.0 38 79

6/8.125

1,750 460/3

MFR NF MFR MS B&G 1510 5BC

PCWP-3

PRIMARY CHILLED

WATER

745.0 38 79

6/8.125

1,750

460/3

MFR NF MFR MS B&G 1510 5BC

PCP-1

PRIMARY CHILLED

WATER - HRC

190.0 41 75

3/6.875

1,750 460/3

MFR NF MFR VFD B&G 1510 2.5AB

SCWP-1

SECONDARY CHILLED

WATER

1350.0 60 76

8/8.75

1,750

460/3

MFR NF MFR VFD B&G 1510 6BC

LEAD, NOTE 1

SCWP-2

SECONDARY CHILLED

WATER

1350.0 60 76

8/8.75

1,750 460/3

MFR NF MFR VFD B&G 1510 6BC

LAG, NOTE 1

NOTES:

1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.

EXISTING PUMP SCHEDULE

SYMBOL SERVICE GPM

PUMP FT.

HEAD AT

DESIGN

MIMIMUM

PUMP

EFFICIENCY

INLET/IMPEL.

SIZE IN.

ELECTRICAL

MANUFACTURER MODEL REMARKS

HP

(NOTE E)

RPM

VOLT-

PHASE

DISCONNECT

CONTROLLER/STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)

CP-1 CONDENSER PUMP 960.0 60 EXISTING EXISTING 25

1,750 460/3

EXISTING EXISTING EXISTING EXISTING TACO FE5010

CP-2 CONDENSER PUMP 960.0 60 EXISTING EXISTING 25

1,750 460/3

EXISTING EXISTING EXISTING EXISTING TACO FE5010

CP-3 CONDENSER PUMP 960.0 60 EXISTING EXISTING 25

1,750 460/3

EXISTING EXISTING EXISTING EXISTING TACO FE5010

HEAT EXCHANGER SCHEDULE - STEAM TO WATER

SYMBOL SERVICE

WATER STEAM

HEATING

SURFACE FT

FOULING

FACTOR

MANUFACTURER MODEL REMARKS

GPM

W.P.D.

FT. HEAD

EWT

°F

LWT

°F

PSIG

(NOTE 1)

LB/HR

HX-1

HEATING

WATER

400.0 0.9 110 150 15 8346 188 0.00149 B&G SU 20 3-4

NOTES:

1. STEAM PRESSURE INDICATED IS THE PRESSURE AVAILABLE DOWNSTREAM OF THE CONTROL VALVE.

PRESSURE REDUCING VALVE SCHEDULE

SYMBOL SERVICE

LB/HR

INLET

PRESSURE

PSI

OUTLET

PRESSURE

PSI

VALVE

SIZE

MANUFACTURER MODEL REMARKS

PRV-1 HX-1 2100 125 30

1 1/2"

ARMSTRONG GP-1000 NOTE 1

PRV-2 HX-1 6300 125 30

3"

ARMSTRONG GP-1000 NOTE 1

NOTES:

1. PRV VALVE TO BE LOW VELOCITY TYPE WITH MAXIMUM RADIATED SOUND < 85dBA

TRAP SCHEDULE

SYMBOL SERVICE TYPE

SAFETY

FACTOR

SIZE

LB/HR.

(NOTE 1)

PRESSURE

DIFFERENTIAL

MANUFACTURER MODEL REMARKS

T-1 DRIP IB 100%

3/4"

12 125 SPIRAX B1H-125 NOTES 5 & 6

T-2 DRIP IB 100%

3/4"

12 30 SPIRAX B1H-125 NOTES 5 & 6

T-3 DRIP IB 100%

3/4"

12 30 SPIRAX B1H-125 NOTES 5 & 6

T-4 HX-1 F&T 25%

2 1/2"

10450 0.25 SPIRAX FTB-125

NOTES 2, 3, & 4

T-5 HX-1 F&T 25%

2 1/2"

10450 0.25 SPIRAX FTB-125

NOTES 2, 3, & 4

NOTES:

1. CAPACITY LISTED IS FOR EACH TRAP AND INCLUDES SAFETY FACTOR.

2.

SUITABLE TO 125 PSIG, SIDE INLET & OUTLET, SS FLOAT MECHANISM AND VALVE, CAST IRON BODY, BALANCED PRESSURE

THERMOSTATIC AIR VENT, ALL INTERNALS REPLACEABLE IN-LINE.

3.

CAPACITY AT OTHER DIFFERENTIAL PRESSURES SHALL BE AT LEAST 525#/HR AT 10 PSID, AND 1080#/HR AT 75 PSID.

4. WITH INTEGRAL VACUUM BREAKER.

5.

SIDE INLET AND OUTLET INVERTED BUCKET TRAP, 250 PSIG RATED. CAST IRON BODY, ALL INTERNAL COMPONENTS

OF STAINLESS STEEL AND REPLACABLE IN-LINE.

6.

CAPACITY AT OTHER DIFFERENTIAL PRESSURES SHALL BE AT LEAST 150#/HR AT 10 PSID, AND 420#/HR AT 75 PSID.

GRILLES REGISTERS & DIFFUSERS SCHEDULE

SYMBOL MAT'L TYPE

MARGIN

(NOTE 1)

INLET

SIZE

(INCH)

FACE

SIZE

(INCH)

INTEGRAL

BALANCING

DAMPER

FINISH MANUFACTURER MODEL REMARKS

CD-1 STEEL LOUVER FACE LAY-IN SEE DWG. 24x24 NO WHITE PRICE SCD

STAMPED LOUVER DROP FACE. MINIMUM OF

TWO STEPDOWN DIFFUSION CONES

CD-2 STEEL ROUND CONE

1 1/4"

SEE DWG. INLET +6 YES WHITE PRICE RCDE

CD-3 STEEL LOUVER FACE LAY-IN SEE DWG. 12x12 YES WHITE PRICE SCD-FR

STAMPED LOUVER DROP FACE. MINIMUM OF

TWO STEPDOWN DIFFUSION CONES

RG-1 STEEL

PERFORATED

FACE

LAY-IN

N/A

24x24 NO WHITE PRICE PDDR FACE ONLY - NON DUCTED

RG-2 STEEL 45° DEFLECTION

1 1/4"

SEE DWG. INLET +2 NO WHITE PRICE 530

SG-1 STEEL

DOUBLE

DEFLECTION

1 1/4"

SEE DWG. INLET +2 YES WHITE PRICE 520

FRONT BLADES VERTICAL UNLESS NOTED

OTHERWISE

SG-2 STEEL

DOUBLE

DEFLECTION

1 1/4"

SEE DWG. INLET +2 YES NOTE 3 PRICE SDG

FRONT BLADES VERTICAL UNLESS NOTED

OTHERWISE

SG-3 STEEL 45° DEFLECTION

1 1/4"

SEE DWG. INLET +2 NO WHITE PRICE 530

EG-1 STEEL

PERFORATED

FACE

LAY-IN SEE DWG. 24x24 NO WHITE PRICE PDDR

EG-2 STEEL

PERFORATED

FACE

LAY-IN SEE DWG. 16x16 YES WHITE PRICE PDDR

EG-3 STEEL 45° DEFLECTION

1 1/4"

SEE DWG. INLET +2 NO WHITE PRICE 530

EG-4 STEEL 45° DEFLECTION

1 1/4"

SEE DWG. INLET +2 YES WHITE PRICE 530

NOTES:

1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.

2. ALL RUN OUT DUCTWORK TO DIFFUSERS SHALL BE NECK SIZE UNLESS OTHERWISE NOTED.

3. FINISH SPECIFIED BY ARCHITECT.

DUST COLLECTOR SCHEDULE

SYMBOL SERVICE

COLLECTOR

TYPE

CFM

S.P.

IN.

W.C.

INLET

SIZE

DROP

OUT BIN

CAPACITY

ELECTRICAL

MANUFACTURER MODEL REMARKS

HP

VOLT-

PHASE

DISCONNECT

CONTROLLER/STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)

DC-1

WORK ROOM

123A

CYCLONE

1,450

10.5

6"

29 GAL. 2

208/1

MFR NF MFR MS LAGUNA

MOBILE

CYCLONE

NOTE 1

NOTES:

1. PROVIDE DUST COLLECTION HOSE KIT.

MOTOR OPERATED DAMPER SCHEDULE

SYMBOL SERVICE

SIZE

W x H

(IN.)

CFM

OPPOSED OR

PARALLEL

BLADES

HORIZONTAL

OR VERTICAL

BLADES

INSULATED

ACTUATOR

TYPE

ACTUATOR

STYLE

POWER

FAILURE

POSITION

POSITIVE

POSITION

FEEDBACK

REMARKS

MAX. MIN.

MOD-1

NORTH SMOKE

PURGE

48x24

40,000 40,000

PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2

MOD-2

SOUTH SMOKE

PURGE

48x24

40,000 40,000

PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2

MOD-3 OUTSIDE AIR 60x60

50,000 25,000

OPPOSED HORIZONTAL YES ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-4 DOAS RELIEF 60x60

45,000 22,500

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-5

NORTH EXHIBIT

(AHU-2 RELIEF)

60x24

5,130 2,565

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-6

SOUTH EXHIBIT

(AHU-7 RELIEF)

60x24

5,130 2,565

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-7 AHU-9 RELIEF 26x26

5,170 1,795

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-8 AHU-10 RELIEF 26x26

5,270 2,030

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-9

AHU-NL

OUTSIDE AIR

24x14

3,000 3,000

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-10

AHU-SL

OUTSIDE AIR

24x14

3,000 3,000

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-11

AHU-3 OUTSIDE

AIR

24x18

3,600 1,800

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-12

AHU-5 OUTSIDE

AIR

26x18

4,700 2,350

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-13 EF-1 12x8 805 805 OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-14 EF-2 18x18

3,365 1,010

OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1

MOD-15

AHU -NL SMOKE

PURGE

60x48

30,000 30,000

PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2

MOD-16

AHU -SL SMOKE

PURGE

60x48

30,000 30,000

PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2

MOD-17

AHU - 3 SMOKE

EVACUATION

54x36

15,000 15,000

PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2

NOTES:

1. COORDINATE DAMPER ACTUATOR LOCATION AND MOUNTING REQUIREMENTS WITH TEMPERATURE CONTROL CONTRACTOR.

2. DAMPER IS CONTROLLED BY FIRE ALARM SYSTEM. POSITION FEEDBACK SHALL BE SENT TO FIRE ALARM SYSTEM.

LINEAR DIFFUSERS & GRILLES SCHEDULE

SYMBOL MATERIAL

SLOT

WIDTH

NO.

SLOTS

LENGTH

PLENUM

REQUIRED

PLENUM

INSULATION

PLENUM

INLET SIZE

PATTERN

CONTROL

REQUIRED

INTEGRAL

BALANCING

DAMPER

FINISH MANUFACTURER MODEL REMARKS

LD-1 ALUMINUM

1 1/4"

72"

YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE AS

NOTES 1, 2, & 3

LD-2 ALUMINUM

1 1/2"

60"

YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE JS

NOTES 1, 2, 3, & 6

LD-3 ALUMINUM

2"

60"

YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE AS

NOTES 1, 2, & 3

LD-4 ALUMINUM

2 1/2"

48"

YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE JS

NOTES 1, 2, & 3

LD-5 ALUMINUM

2"

48"

YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE JS

NOTES 1, 2, 3, & 5

LDE-1 ALUMINUM

3"

20"

YES NONE SEE DWG. NO NO NOTE 4 PRICE JS

NOTES 1, 2, & 3

LDR-1 ALUMINUM

1 1/2"

60"

NO

N/A N/A

NO NO NOTE 4 PRICE JS

NOTES 1, 2, 3, & 6

LDR-2 ALUMINUM

2"

60"

YES NONE

N/A

NO NO NOTE 4 PRICE AS

NOTES 1, 2, & 3

NOTES:

1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.

2. PROVIDE WITH CONCEALED FASTENERS.

3. REFER TO ARCHITECTURAL DRAWINGS FOR TRIM DETAILS.

4. REFER TO ARCHITECTURAL DRAWINGS FOR FINISH DETAILS.

5. CONTRACTOR MAY PROVIDE ONE CONTINUOUS 16' DIFFUSER OR MULTIPLE SHORTER DIFFUSERS. FIELD VERIFY REQUIRED LENGTH.

6. PROVIDE BLANKOFFS AS REQUIRED FOR CONTINUOUS APPEARANCE. FIELD VERIFY REQUIRED LENGTHS.

MECHANICAL SCHEDULES

RFP 05211.03.15

PUMP SCHEDULE

SYMBOL SERVICE GPM

PUMP FT.

HEAD AT

DESIGN

MIMIMUM

PUMP

EFFICIENCY

INLET/IMPEL.

SIZE IN.

ELECTRICAL

MANUFACTURER MODEL REMARKS

HP

(NOTE E)

RPM

VOLT-

PHASE

DISCONNECT

CONTROLLER/STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)

PCWP-1

PRIMARY CHILLED

WATER

515.0 35 84% 6.75 7.5

1,750

460/3

MFR NF MFR MS B&G 1510 4AD

DUTY, NOTE 2

PCWP-2

PRIMARY CHILLED

WATER

515.0 35 84% 6.75 7.5

1,750 460/3

MFR NF MFR MS B&G 1510 4AD

DUTY, NOTE 2

PCWP-3

PRIMARY CHILLED

WATER

515.0 35 84% 6.75 7.5

1,750 460/3

MFR NF MFR MS B&G 1510 4AD

STANDBY, NOTE 2

PCP-1

PRIMARY CHILLED

WATER - HRC

136.0 41 74% 6.625 3

1,750 460/3

MFR NF MFR VFD B&G 1510 2.5AC-es NOTE 2

SCWP-1

SECONDARY CHILLED

WATER

1050.0 56 72% 8.25 25

1,750 460/3

MFR NF MFR VFD B&G 1510 6BD

LEAD, NOTE 1, 2

SCWP-2

SECONDARY CHILLED

WATER

1050.0 56 72% 8.25 25

1,750

460/3

MFR NF MFR VFD B&G 1510 6BD

LAG, NOTE 1, 2

NOTES:

1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.

2. FOR BID OPTION #8 PROVIDE THESE PUMPS IN PLACE OF THE PUMPS SCHEDULED ON SHEET M-306. PUMPS NOT LISTED IN THIS SCHEDULE ARE TO BE PROVIDED AS SCHEDULED ON M-306.

BID OPTION #8

REPLACEMENT CHILLER SCHEDULE (WATER COOLED)

SYMBOL SERVICE REFRIGERANT

CAPACITY/PERFORMANCE

EVAPORATOR PERFORMANCE CONDENSER PERFORMANCE ELECTRICAL

MANUFACTURER MODEL REMARKS

DESIGN

TONS

STAGES OF

UNLOADING

MAX. KW/TON AT % LOAD

NPLV

KW/TON

EWT

°F

LWT

°F

GPM

MAXIMUM

PRESS DROP

FT. HEAD

FOULING

FACTOR

EWT

°F

LWT

°F

GPM

MAXIMUM

PRESS DROP

FT. HEAD

FOULING

FACTOR

VOLT-

PHASE

MOCP

AMPS

DISCONNECT

CONTROLLER/STARTER

BY

(NOTE A)

TYPE

(NOTE B)

BY

(NOTE A)

TYPE

(NOTE C)

100 75 50 25

CH-1

WHOLE

BUILDING

134a 300 INFINITE 0.666 0.485 0.341 0.411 0.401 56 42 515.0 20.0 0.0001 85 100 600.0 10.0 .00025

460/3

500.0 MFR NF MFR VFD DAIKIN WSC NOTE 1

CH-2

WHOLE

BUILDING

134a 300 INFINITE 0.666 0.485 0.341 0.411 0.401 56 42 515.0 20.0 0.0001 85 100 600.0 10.0 .00025

460/3

500.0 MFR NF MFR VFD DAIKIN WSC NOTE 1

NOTES:

1.

FOR BID OPTION #8, PROVIDE NEW CHILLERS AND REMOVE THE EXISTING CHILLERS.

2. THE ABOVE INFORMATION IS FOR PERFORMANCE REQUIREMENTS. INITIALLY THE CONDENSER WATER FLOW WILL BE 900 GPM. CONDENSER PRESSURE DROP AT 900 GPM SHALL NOT EXCEDE 13FT.

CHILLED WATER/CONDENSER WATER FLOW DIAGRAM - WEST MECHANICAL ROOM

KEYNOTES CONT'DKEYNOTES

M-400

MECHANICAL FLOW DIAGRAMS

SYMBOL: DESCRIPTION:

HEATING WATER FLOW DIAGRAM SYMBOL LIST KEYNOTES

HEATING WATER FLOW DIAGRAM - SOUTHWEST MECHANICAL ROOM

M-401

AIR FLOW DIAGRAM

NO SCALE

M-402

GENERAL CONTROL NOTES

CONTROL SYMBOLS LIST

SYMBOL: DESCRIPTION:

CONTROL SYMBOLS LIST

SYMBOL: DESCRIPTION:

GENERAL CONTROL NOTES GENERAL CONTROL NOTES

MECHANICAL CONTROL DIAGRAMS

AIR HANDLER REPORT GENERATION

SUPPLY FAN VFD CONTROL

EXHAUST INTERLOCK SCHEDULE

SYSTEM

INTERLOCKED EXHAUST

ZONES

REMARKS

AHU-1 NOTE 1

AHU-2 NOTE 1

AHU-3 NOTE 1

AHU-4 NOTE 1

AHU-5 NOTE 1

AHU-6 NOTE 1

AHU-7 NOTE 1

NOTES:

1. INTERLOCK ZONE FAN OPERATION THROUGH THE FMCS

WITH RESPECTIVE AHU IN ACCORDANCE WITH AHU

SEQUENCE OF OPERATION.

TYPICAL FOR AHU-1, AHU-2, AHU-4, AHU-6, AHU-7, AHU-8, AHU-9, AHU-10

AIR HANDLING UNIT CONTROL - AHU-A

AHU-8 NOTE 1

AHU-9 NOTE 1

AHU-10 NOTE 1

TYPICAL FOR AHU-1, AHU-2, AHU-4, AHU-6, AHU-7, AHU-8, AHU-9, AHU-10M-501

M-501

M-501

TYPICAL FOR AHU-1, AHU-2, AHU-4, AHU-6, AHU-7, AHU-8, AHU-9, AHU-10

AIR HANDLING UNIT CONTROL - AHU-A

M-502

AIR HANDLING UNIT CONTROL: AHU-B

TYPICAL FOR AHU-11 AND AHU-12M-503

SUPPLY / RETURN FAN VFD CONTROL

NO SCALE

TYPICAL FOR AHU-3

AIR HANDLING UNIT CONTROL - AHU-C

TYPICAL FOR AHU-3M-504

M-504

M-504

MECHANICAL CONTROL DIAGRAMS

08.20.15 RFI 185

TYPICAL FOR AHU-3

AIR HANDLING UNIT CONTROL - AHU-C

M-505

SUPPLY / RETURN FAN VFD CONTROL

TYPICAL FOR AHU-5

AIR HANDLING UNIT CONTROL - AHU-D

TYPICAL FOR AHU-5M-506

M-506

M-506

MECHANICAL CONTROL DIAGRAMS

08.20.15 RFI 185

TYPICAL FOR AHU-5

AIR HANDLING UNIT CONTROL - AHU-D

M-507

TYPICAL FOR AHU-NL, AHU-SL

AIR HANDLING UNIT CONTROL - AHU-E

TYPICAL FOR AHU-NL, AHU-SL

SUPPLY / RETURN FAN VFD CONTROL

M-508

M-508

M-508

TYPICAL FOR AHU-NL, AHU-SL

AIR HANDLING UNIT CONTROL - AHU-E

M-509

SUPPLY & EXHAUST FAN VFD CONTROL

DOAS UNIT WITH ENERGY RECOVERY WHEEL CONTROL - DOAS-1

TYPICAL FOR DOAS-1

DOAS REPORT GENERATION

GLOBAL REFERENCE POINTS

NO SCALE

M-510

M-510

M-510

M-510

DOAS UNIT WITH ENERGY RECOVERY WHEEL CONTROL - DOAS-1

M-511

TAB CONTROL W/ HOT WATER REHEAT: TAB-A

CONSTANT VOLUME TAB CONTROL: TAB-B

M-512

M-512

CONSTANT VOLUME TAB CONTROL RELIEF: TAB-D

VARIABLE VOLUME TAB CONTROL RELIEF: TAB-C

M-512

M-512

TERMINAL AIR BOX REPORT GENERATION

VARIABLE FREQUENCY DRIVE CONTROL

M-513

M-513

HEAT EXCHANGER CONTROL

HEATING WATER

SECONDARY PUMP CONTROL

CHILLED WATER SECONDARY PUMP CONTROL

M-514

M-514

M-514

WATER COOLED CHILLER CONTROLS

CHILLER PLANT REPORT GENERATION

KEYNOTES

M-515

M-515

WATER COOLED CHILLER CONTROLS

M-516

HEAT RECOVERY CHILLER CONTROL: HRC-A

HEAT RECOVERY CHILLER REPORT GENERATION

M-517

M-517

EXHAUST FAN CONTROL -

CONTINUOUS OPERATION: FAN-AUNIT HEATER CONTROL

AIR CURTAIN CONTROL

M-518

M-518

M-518

LIGHTING CONTROL INTERFACE

M-518

FAN COIL UNIT CONTROL: FCU-B

FAN COIL UNIT CONTROL - COOLING ONLY: FCU-C

FAN COIL UNIT CONTROL: FCU-A

M-519

M-519

M-519

CHILLER ROOM EXHAUST FAN AND MAKE-UP

AIR CONTROL DIAGRAM - FAN-B

M-520

ATRIUM SMOKE PURGE CONTROL DIAGRAM

SMOKE CONTROL PANEL DIAGRAM

M-521

M-521

SMOKE PURGE FLOW DIAGRAM

NO SCALE

M-522

MECHANICAL DEMOLITION NOTES:KEYNOTES:

MECHANICAL DEMO NOTE SHEET

COMPOSITE KEY PLAN

MD-100

MAIN LEVEL PARTIAL FLOOR PLAN -

MECHANICAL DEMO - AREA 3.1

MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 3.1

MD-130

MECHANICAL DEMO - AREA 4.1

MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 4.1

MD-131

MECHANICAL DEMO - AREA 2.1

MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 2.1

MD-132

MECHANICAL DEMO - AREA 2.2

MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 2.2

MD-134.1

MECHANICAL PIPING GENERAL NOTES:

PIPING NOTE SHEET

COMPOSITE KEY PLAN

MP-100

VISITOR CENTER ELEVATION

MP-100

SCALE B

SCALE B

SCALE A

PIPING - AREA 1.2

MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 1.2

MP-120

02.01.16 RFI 583

PIPING - AREA 3.1

MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 3.1

MP-134

09.22.15 RFP 034 - TAP BOX

PIPING - AREA 2.2

MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 2.2

MP-134.1

PIPING - AREA 4.1

MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 4.1

MP-135

08.05.15 ARCH LIGHT FEED PERMANENT ROUTING - ISSUED AS RFP 007

03.18.16 RFI 755

, RFP 183

PIPING - AREA 2.1

MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 2.1

MP-136

07.28.15 RFP 002

MECHANICAL VENTILATION GENERAL NOTES:

VENTILATION NOTE SHEET

COMPOSITE KEY PLAN

MV-100

VISITOR CENTER ELEVATION

MV-100

SCALE B

SCALE B

VENTILATION - AREA 1.2

MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 1.2

MV-120

05.10.16 RFP 145D

07.13.16 RFP 258

abarwick Callout

OUTSIDE DIMENSIONS OF BRANCH CONNECTIONS?

abarwick Callout

CAN THESE DIFFUSERS BE MOUNTED IN SOFFIT FACE AS SHOWN ON ATTACHED A-458?

THEY ARE NOT CURRENTLY SHOWN ON OUR RCP.

VENTILATION - AREA 2.2

MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 2.2

MV-134.1

01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS

VENTILATION - AREA 3.1

MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 3.1

MV-134

08.05.15 ARCH LIGHT FEED PERMANENT ROUTING - ISSUED AS RFP 007

10.30.15 RFP 052

12.16.15 RFI 424

01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS

03.08.16 RFP 151

03.08.16 RFP 100R1

VENTILATION - AREA 4.1

MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 4.1

MV-135

08.05.15 ARCH LIGHT FEED PERMANENT ROUTING - ISSUED AS RFP 007

10.30.15 RFP 052

12.16.15 RFI 424

01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS

01.20.16 RFI 426

02.23.16 RFI 424

03.08.16 RFP 151

03.08.16 RFP 100R1

03.15.16 RFP 157

03.18.16 RFP 159

03.23.16 RFP 151R1

VENTILATION - AREA 2.1

MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 2.1

MV-136

07.28.15 RFP 002

ELECTRICAL LIGHTING SYMBOL LIST ELECTRICAL POWER SYMBOL LIST

LUMINAIRE SYMBOL KEY

ELECTRICAL SYSTEMS SYMBOL LIST

ELECTRICAL DEMOLITION SYMBOL LIST

TYPICAL ELECTRICAL MOUNTING HEIGHTS

FIRE / SMOKE BARRIER DESIGNATIONS

ELECTRICAL COVER SHEET

ELECTRICAL DEMOLITION NOTES:

ELECTRICAL INSTALLATION NOTES:

GENERAL ELECTRICAL NOTES:

ONE LINE DIAGRAM NOTES:

ELECTRICAL COVER SHEET

Museum of Westward Expansion - Consolidated Responsibility Matrix (Contract 1 Unless Otherwise Noted)

Items to be Provided and Installed Refer To Electrical

Contractor Facility AV Contractor

Exhibit AV Contractor

(Not in Contract 1)

Network Contractor

Radio Contractor

Structured Cabling Contractor

Access Control / Intrusion Detection

Contractor

Video Surveillance Field Devices

Contractor

Video Surveillance Control

Contractor Notes

Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Main Power Service Panel Boards

E Series Drawings x x

• Main Power Service Panel Board Circuit Breaker(s)

E Series Drawings x x

• Main Power Service Conduit

E Series Drawings x x

• Main Power Service Conductors

E Series Drawings x x

• Main Power Service Terminations

E Series Drawings x

Transformers

E Series Drawings x x

• Transformer Conduit

E Series Drawings x x

• Transformer Conductors

E Series Drawings x x

• Transformer Terminations

E Series Drawings x

Isolated Ground Wiring System E Series Drawings x x

• Isolated Ground Conduit

E Series Drawings x x

• Isolated Ground Conductors

E Series Drawings x x

• Isolated Ground Terminations

E Series Drawings x◊

Distribution Panel Boards

E Series Drawings x x

• Distribution…