F4
FIRE / SMOKE BARRIER DESIGNATIONS
MECHANICAL COVER SHEET
NO SCALE
08.31.15 RFP 005
ENLARGED MAIN FLOOR
MECHANICAL ROOM PLANS
ENLARGED MECHANICAL ROOM 121 PLAN
M-200
ENLARGED MECHANICAL ROOM 110 PLAN - PIPING
M-200
ENLARGED MECHANICAL ROOM 110 PLAN - VENTILATION
M-200
MP-135, MV-135
MP-134 MV-134
01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS
MECHANICAL ISOMETRIC VIEWS
MECHANICAL ROOM 121 ISOMETRIC VIEW
M-201
MECHANICAL ROOM 110 ISOMETRIC VIEW - PIPING
M-201
MECHANICAL ROOM 110 ISOMETRIC VIEW - VENTILATION
M-201
MP-135, MV-135
MP-134 MV-134
MECHANICAL TUNNEL ISOMETRIC VIEW
M-201
MP-145, MV-145
MECHANICAL SECTIONS
EAST WEST PARTIAL SECTION AT CENTERLINE LOOKING NORTH
M-202
EAST WEST PARTIAL SECTION AT GRIDLINE 7B LOOKING NORTH
NORTH SOUTH PARTIAL SECTION AT GRIDLINE F LOOKING WEST
M-202
M-202
NO SCALE
MP-144, MV-144
MP-137, MV-137
MP-135, MV-135
EAST WEST PARTIAL SECTION AT GRIDLINE 11 LOOKING SOUTH
M-202
MP-145, MV-145
LONGITUDINAL SEAMS - REC. DUCT
TRAPEZE HANGER DUCT
WRAP VAPOR SEAL
RECTANGULAR
MITERED ELBOW
WITH VANES
TYPE RE2
RECTANGULAR
MITERED ELBOW
TYPE RE6
RECTANGULAR
RADIUS ELBOW
TYPE RE1
RECTANGULAR
RADIUS ELBOW WITH VANES
TYPE RE3
ELBOW CONSTRUCTION
RECTANGULAR
RADIUS ELBOW WITH
SQUARE THROAT
NOT ALLOWED
RECTANGULAR / OVAL / ROUND
MITERED ELBOW
WITHOUT VANES
TYPE RE4 NOT ALLOWED
OVAL / ROUND
RADIUS ELBOW
SMOOTH OR 5 GORE (MINIMUM)
BRANCH CONNECTIONS
DUCT REINFORCEMENT DETAIL
CENTRIFUGAL FAN INLET BOX
M-203
M-203
M-203
M-203
M-203
M-203
MECHANICAL DETAILS
DIFFUSER CONNECTION DETAIL
M-204
FLEX DUCT CONNECTION W/ BALANCING DAMPER ROUND DUCT TAP CONNECTION FLEX DUCT CONNECTION
DIFFUSER INSTALLATION
SUPPLY REGISTER DETAIL
M-204
M-204
M-204
M-204
M-204
COMBINATION FIRE/SMOKE DAMPER - FRONT ACCESSFIRE DAMPER THRU WALL DETAIL
M-205
M-205
ACCESS DOOR DETAIL
M-205
TRANSFER DUCT DETAIL
M-205
EXTERIOR WALL PENETRATION
NOISE CONTROL WALL PENETRATION DETAIL
PIPE THROUGH NON-FIRE RATED WALL
RATED FIRE BARRIER PENETRATION
M-206
M-206
M-206
M-206
HOT WATER COIL PIPINGFAN COIL UNIT PIPING - TWO PIPEFAN COIL UNIT PIPING - FOUR PIPE
M-206
M-206
M-206
DIELECTRIC CONNECTION DETAIL
EXPANSION TANK
SUPPORT DETAIL
PIPE SUPPORT DETAIL
M-207
M-207
M-207
M-207
EXPANSION TANK SUPPORT DETAIL
HEAT EXCHANGER/
STEAM MAIN DRIP CONNECTION
HUMIDIFIER (ELECTRIC) DETAIL
M-208
M-208
AHU PIPING DETAIL - HEATING WATERAHU PIPING DETAIL - CHILLED WATER
M-208
M-208
MICRO CLIMATE GENERATOR PIPING DETAIL
M-208
TYPICAL SEISMIC BRACING OF SUSPENDED DUCTWORK
TRANSVERSE CABLE BRACE
LONGITUDINAL BRACE
TRANSVERSE SOLID BRACE
TRANSVERSE SOLID BRACE
TRANSVERSE CABLE BRACE
TYPICAL SEISMIC BRACING OF SUSPENDED PIPING
TYPICAL SEISMIC HOUSEKEEPING PAD
M-209
M-209
M-209
UNDER FLOOR DUCTWORK DETAIL
HDPE
FRP
FLOOR DIFFUSER DETAIL
UNDER FLOOR VAV BOX DETAIL
FLOOR ACCESS PANEL DETAIL
SECTION VIEW
PLAN VIEW
M-210
M-210
M-210
M-210
AHU-1 & AHU-6
MAXIMUM DIMENSIONS
AHU-8
MAXIMUM DIMENSIONS
AHU-2 & AHU-7
MAXIMUM DIMENSIONS
AHU-4
MAXIMUM DIMENSIONS
AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8
FUNCTIONAL ARRANGEMENT DIAGRAM
M-211
M-211
M-211
M-211
M-211
AHU-11 & AHU-12
MAXIMUM DIMENSIONS
AHU-9
MAXIMUM DIMENSIONS
AHU-10
MAXIMUM DIMENSIONS
AHU-9 & AHU-10
FUNCTIONAL ARRANGEMENT DIAGRAM
AHU-11& AHU-12
FUNCTIONAL ARRANGEMENT DIAGRAM
M-212
M-212
M-212
M-212
M-212
DOAS MAXIMUM DIMENSIONS
DOAS
FUNCTIONAL ARRANGEMENT DIAGRAM
M-213
M-213
SCHEDULE GENERAL NOTES:
A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND
INSTALLED BY:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED
BY ELECTRICAL CONTRACTOR
MFR/EC =
FURNISHED LOOSE BY MANUFACTURER
INSTALLED BY ELECTRICAL CONTRACTOR
ATC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR
B. DISCONNECT TYPE:
F = FUSED
NF = NON-FUSED
C. CONTROLLER STARTER TYPE:
FV = FULL VOLTAGE
WYE = WYE-DELTA
SS = SOLID STATE (SOFT START)
MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE,
WITH THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS
FANS FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR
NAME PLATE RATING.
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
G. CURB TYPE:
MFR = STANDARD CURB BY MANUFACTURER
GC = BY GENERAL CONTRACTOR
SAC = SOUND ATTENUATOR CURB
SCHEDULE ABBREVIATIONS:
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY LF LINEAR FEET
AMCA AIR MOVEMENT and CONTROL ASSOCIATION LIQ REFRIGERANT LIQUID
APD AIR PRESSURE DROP LWT LEAVING WATER TEMPERATURE
BHP BRAKE HORSE POWER MAT'L MATERIAL
BTUH BRITISH THERMAL UNIT PER HOUR MAX. MAXIMUM
C.T.I. COOLING TECHNOLOGY INSTITUTE MBH
THOUSANDS OF BTU/HOUR
CAP. CAPACITY MCA MINIMUM CIRCUIT AMPACITY
CFM CUBIC FEET PER MINUTE MHP MOTOR HORSEPOWER
COND CONDENSER MIN. MINIMUM
COP COEFFICIENT OF PERFORMANCE MOCP MAXIMUM OVERCURRENT PROTECTION
DB DRY BULB NC NOISE CRITERIA
DB DECIBEL NO. NUMBER
DEFL. DEFLECTION NPLV NON-STANDARD PART LOAD VALUE
DIM. DIMENSION O.C. ON CENTER
EAT ENTERING AIR TEMPERATURE OA OUTSIDE AIR
EER ENERGY EFFICIENCY RATING OCP OVER-CURRENT PROTECTION
EFF EFFICIENCY OPER. OPERATING
EVAP EVAPORATOR PSI POUNDS PER SQUARE INCH
EWT ENTERING WATER TEMPERATURE PSIG POUNDS PER SQUARE INCH GAUGE
EXT. SP. EXTERNAL STATIC PRESSURE RE REFERENCE
F/GR
DEGREES FAHRENHEIT PER GRAIN REFIG. REFRIGERANT
FDB DEGREES FAHRENHEIT DRY BULB REQ'D REQUIRED
FLA FULL LOAD AMPS RLA RATED LOAD AMPS
FPM FEET PER MINUTE RPM REVOLUTIONS PER MINUTE
FT. FEET SAT SATURATION
FWB DEGREE FAHRENHEIT WET BULB SCFM STANDARD CUBIC FEET PER MINUTE
GAL U.S. GALLON SEER SEASONAL ENERGY EFFICIENCY RATIO
GPM GALLON PER MINUTE SQ. FT. SQUARE FEET
H HEIGHT SUCT REFRIGERANT SUCTION
HP HORSEPOWER TEMP TEMPERATURE
HR HOUR
Uw/CM2
MILLIONTH OF A WATT PER SQUARE CENTIMETER
IN. INCH VOLT VOLTAGE
IPLV INTEGRATED PART LOAD VALUE W WIDTH
KW KILOWATTS WB WET BULB
L LENGTH WC WATER COLUMN
LAT LEAVING AIR TEMPERATURE WG WATER GAUGE
LB POUNDS WPD WATER PRESSURE DROP
DOAS SCHEDULE
SYMBOL DOAS-1
OUTSIDE AIR FAN
CFM
50,000
MINIMUM CFM
25,000
EXTERNAL STATIC PRESSURE
2"
TYPE 10 FAN ARRAY
BHP (NOTE E)
3.74/FAN
MHP (NOTE E)
4/FAN
DISCONNECT BY (NOTE A)
MFR
DISCONNECT TYPE (NOTE B)
NF
CONTROLLER/STARTER BY (NOTE A)
MFR
CONTROLLER/STARTER TYPE (NOTE C)
VFD
EXHAUST FAN
CFM
45,000
MINIMUM CFM
22,500
EXTERNAL STATIC PRESSURE
3"
TYPE 8 FAN ARRAY
BHP (NOTE E)
7.01/FAN
MHP (NOTE E)
7.5/FAN
DISCONNECT BY (NOTE A)
MFR
DISCONNECT TYPE (NOTE B)
NF
CONTROLLER/STARTER BY (NOTE A)
MFR
CONTROLLER/STARTER TYPE (NOTE C)
VFD
VOLT- PHASE
460/3
MCA 190 A
MOCP 200 A
FAN SCHEDULE
SYMBOL SERVICE CFM
S.P.
IN.
W.C.
FAN
CLASS
WHEEL
DIA.
INCHES
FAN
RPM
(NOTE F)
DRIVE
MAX.
AMCA
SONES
BACKDRAFT
DAMPER
ELECTRICAL
MANUFACTURER MODEL REMARKS
BHP
(NOTE E)
MHP
(NOTE E)
VOLT-
PHASE
DISCONNECT
CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
SPF-1
SMOKE
PURGE
40,000
5 III 44.5
1,138
BELT
N/A
MOT 44.7 50 460-3 MFR NF MFR VFD COOK 490CA
FOR SMOKE PURGE
APPLICATION. NOTE 1
SPF-2
SMOKE
PURGE
40,000
5 III 44.5
1,138
BELT
N/A
MOT 44.7 50 460-3 MFR NF MFR VFD COOK 490CA
FOR SMOKE PURGE
APPLICATION. NOTE 1
EF-1 PAINT ROOM 905 0.6 I 12.0
1,130
BELT 9.0 MOT 0.167 0.25 115-1 MFR NF MFR MS COOK SDB
EF-2
MECH ROOM
PURGE
3,365
0.75 I 21.0 703 BELT 15 MOT 0.73 1.0 115-1 MFR NF MFR VFD COOK SDB NOTES 1 & 2
RF-7
AHU-3
RETURN
15,000
EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING
N/A
BALANCE TO 6,170 CFM
RF-10
AHU-5
RETURN
12,900
EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING
N/A
BALANCE TO 6,315 CFM
RF-NL
AHU-NL
RETURN
30,000
EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING
N/A
RF-SL
AHU-NL
RETURN
30,000
EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXG EXISTING
N/A
NOTES:
1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
2. FAN SHALL RUN AT 1010 CFM FOR NORMAL OPERATION AND 3365 CFM IN EMERGENCY PURGE MODE.
HEAT RECOVERY WHEEL SCHEDULE
SYMBOL SERVICE
OA
(CFM)
EA
(CFM)
SUMMER CONDITIONS WINTER CONDITIONS
TOTAL
EFFECTIVENESS
MAX FACE
VELOCITY
(FPM)
MAX PRESSURE
DROP
(IN W.C.)
WHEEL SIZE
W "x H"
ELECTRICAL
REMARKS
OA TEMP RA TEMP TEMPERED AIR
HEAT
RECOVERED
(MBH)
OA TEMP RA TEMP TEMPERED AIR
HEAT
RECOVERED
(MBH)
MOTOR
(HP)
VOLT-
PHASE
STARTER
° FDB ° FWB ° FDB ° FWB ° FDB ° FWB ° FDB ° FWB ° FDB ° FWB ° FDB ° FWB
HRW-1 DOAS
50,000 45,000
95.5 78.6 75.0 62.5 83.0 70.1
1,000
2.5 1.0 70.0 53.0 45.1 37.3 1000
63.9/68.6
920 0.8 21x153 1.0
460/3
VFD
VFD SHALL BE PROVIDED BY AHU MANUFACTURER AND
WIRED BY ELECTRICAL CONTRACTOR.
DOAS SCHEDULE CONT.
HEATING COIL - HOT WATER
EAT °F NOTE 2
LAT °F 51.5
EWT °F 130
LWT °F 50
GPM 21.3
MBH 844.4
MAX. A.P.D. IN. W.C. 0.15
W.P.D. FEET HEAD 8.69
COOLING COIL - CHILLED WATER
EAT °F DB NOTE 2
EAT °F WB NOTE 2
LAT °F DB 58.7
LAT °F WB 57.3
EWT °F 42
LWT °F 54
GPM 310.0
TOTAL MBH
2,022.0
MAX. A.P.D. IN. W.C. 1.00
W.P.D. FEET HEAD 13.40
FILTER
TYPE - OA PRE/EA PRE
MERV 8
TYPE - OA FINAL MERV 13
VELOCITY MAX 500
MAX. A.P.D. IN. W.C.
PRE FILTER MID-LIFE
0.6
MAX. A.P.D. IN. W.C.
FINAL FILTER MID-LIFE
0.75
REMARKS
NOTES 1, 3 & 4
NOTES:
1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
2. TEMPERATURE SHALL MATCH LAT OF HRW-1
3. REFER TO EQUIPMENT SOUND DATA SCHEDULE.
4.
REFER TO 1/M-213 DOAS FUNCTIONAL ARRANGEMENT DIAGRAM & 2/M-213 DOAS MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION
MECHANICAL SCHEDULES
AIR HANDLING UNIT SCHEDULE
SYMBOL AHU-11 AHU-12
SERVICE ENTRANCE ENTRANCE
SUPPLY FAN
CFM
9,000 9,000
EXTERNAL STATIC PRESSURE
1.5" 1.5"
TYPE PLENUM PLENUM
BHP (NOTE E)
5.70 5.70
MHP (NOTE E)
8 8
DISCONNECT BY (NOTE A)
MFR MFR
DISCONNECT TYPE (NOTE B)
NF NF
CONTROLLER/STARTER BY (NOTE A)
MFR MFR
VOLT- PHASE
460/3 460/3
HEATING COIL - HOT WATER
EAT °F 70 70
LAT °F 100 100
EWT °F 130 130
LWT °F 105 105
GPM 23.2 23.2
MBH 191.0 191.0
MAX. A.P.D. IN. W.C. 0.23 0.23
W.P.D. FEET HEAD 1.00 1.00
COOLING COIL - CHILLED WATER
EAT °F DB 85 85
EAT °F WB 70 70
LAT °F DB 62.3 62.3
LAT °F WB 59.9 59.9
EWT °F 42 42
LWT °F 60 60
GPM 26.0 26.0
TOTAL MBH 234.0 234.0
MAX. A.P.D. IN. W.C. 0.50 0.50
W.P.D. FEET HEAD 1.00 5.28
FILTER
TYPE - PRE MERV 8 MERV 8
TYPE - FINAL NONE NONE
REMARKS
NOTES 1, 2, & 3 NOTES 1, 2, & 3
NOTES:
1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
2. REFER TO EQUIPMENT SOUND DATA SCHEDULE.
3.
REFER TO 2/M-212 AHU-11 & AHU-12 FUNCTIONAL ARRANGEMENT DIAGRAM & 5/M-212
AHU-11 & AHU-12 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.
AIR HANDLING UNIT SCHEDULE
SYMBOL AHU-1 AHU-2 AHU-3 AHU-4 AHU-5 AHU-6 AHU-7 AHU-8 AHU-9 AHU-10 AHU-NL AHU-SL
SERVICE NORTH OFFICES NORTH EXHIBIT METRO OFFICE
TUCKER
THEATER
CAFÉ
SOUTH OFFICES SOUTH EXHIBIT MUSEUM STORE ADDITION ENTRY LEVEL NORTH LEG SOUTH LEG
SUPPLY FAN
CFM
4,000 18,000 15,000 10,500 12,900 4,000 18,000 10,500 27,000 18,500 30,000 30,000
MINIMUM CFM
2,600 15,500 11,600 5,000 9,200 3,300 15,500 6,400 22,500 14,800 15,000 15,000
EXTERNAL STATIC PRESSURE
2" 2.25"
2.00
2"
1.00
2" 2.25" 2" 3" 3"
EXISTING EXISTING
TYPE PLENUM PLENUM EXISTING PLENUM EXISTING PLENUM PLENUM PLENUM PLENUM PLENUM EXISTING EXISTING
BHP (NOTE E)
3.50 21.50 17.8 13.12 8.50 3.50 21.50 13.12 16.50 11.20 EXISTING EXISTING
MHP (NOTE E)
5.0 22 20.0 15 10 5 22 15 18 12 EXISTING EXISTING
DISCONNECT BY (NOTE A)
MFR MFR EXISTING MFR EXISTING MFR MFR MFR MFR MFR EXISTING EXISTING
DISCONNECT TYPE (NOTE B)
NF NF EXISTING NF EXISTING NF NF NF NF NF EXISTING EXISTING
CONTROLLER/STARTER BY (NOTE A)
MFR MFR EXISTING MFR EXISTING MFR MFR MFR MFR MFR EXISTING EXISTING
CONTROLLER/STARTER TYPE (NOTE C)
VFD VFD EXISTING VFD EXISTING VFD VFD VFD VFD VFD EXISTING EXISTING
MINIMUM OUTSIDE AIR CFM 825
2,850 1,800 1,150 2,350
2,850 1,150 3,750 2,600 3,000 3,000
MAXIMUM OUTSIDE AIR CFM 825
5,700 3,600 2,300 4,700
5,700 2,300 7,500 7,200 3,000 3,000
VOLT- PHASE
460/3 460/3 460/3 460/3 230/3 460/3 460/3 460/3 460/3 460/3 460/3 460/3
COOLING COIL - CHILLED WATER
EAT °F DB 71.4 70.2 81 71.7 81.2 71.4 70.2 71.7 70.8 69 EXISTING EXISTING
EAT °F WB 61.5 61.2 67 61.6 66.5 61.5 61.2 61.6 61.3 60.8 EXISTING EXISTING
LAT °F DB 48 48 54.1 48 54.4 48 48 48 48 48 EXISTING EXISTING
LAT °F WB 47.9 47.9 53.5 47.9 53.6 47.9 47.9 47.9 47.9 47.9 EXISTING EXISTING
EWT °F 42 42 42 42 42 42 42 42 42 42 42 42
LWT °F 57 58 54 58 54 57 58 58 58 58 54 54
GPM 34.6 81.4 95.0 49.0 80.0 34.6 81.4 49.0 123.0 81.0 95.0 95.0
TOTAL MBH 260.0 648.0 618.0 394.0 505.0 260.0 648.0 394.0 988.0 650.0 475.0 475.0
MAX. A.P.D. IN. W.C. 0.85 1.20 0.98 0.79 1.00 0.85 1.20 0.79 1.40 1.20 EXISTING EXISTING
W.P.D. FEET HEAD 10.00 8.00 3.90 10.00 10.40 10.00 8.00 10.00 20.00 20.00 EXISTING EXISTING
HUMIDIFIER MANIFOLD
TOTAL CAPACITY #/HR
24 220 170 90 100 35 220 90 295 290 NONE NONE
STEAM GENERATOR QTY
1 2 2 1 1 1 2 1 3 3 NONE NONE
CAPACITY #/HR PER STEAM GEN.
24 110 85 90 100 35 110 90 98 97 NONE NONE
FILTER
TYPE - PRE MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8
TYPE - FINAL MERV 13 MERV 13
N/A
MERV 13
N/A
MERV 13 MERV 13 MERV 13 MERV 13 MERV 13
N/A N/A
VELOCITY PRE/FINAL
375 475 EXISTING 425 EXISTING 375 475 425 500 500 EXISTING EXISTING
MAX. A.P.D. IN. W.C.
PRE FILTER MID-LIFE
0.6 0.45 EXISTING 0.65 EXISTING 0.6 0.45 0.65 0.6 0.6 EXISTING EXISTING
MAX. A.P.D. IN. W.C.
FINAL FILTER MID-LIFE
0.75 0.6
N/A
0.75
N/A
0.75 0.6 0.75 0.75 0.75
N/A N/A
REMARKS
NOTES 1, 2, & 5 NOTES 1, 2, & 6 NOTES 3, 4, & 11 NOTES 1, 2,& 7 NOTES 3, 4, & 11 NOTES 1, 2, & 5 NOTES 1, 2, & 6 NOTES 1, 2, & 8 NOTES 1, 2, & 9 NOTES 1, 2, & 10
NOTES 3 & 4 NOTES 3 & 4
NOTES:
1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
2. REFER TO EQUIPMENT SOUND DATA SCHEDULE.
3. EXISTING TO REMAIN
4. REFER TO FAN SCHEDULE FOR RETURN FAN INFORMATION.
5.
REFER TO 1/M-211AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 3/M-211 AHU-1 & AHU-6 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.
6.
REFER TO 1/M-211 AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 4/M-211 AHU-2 & AHU-7 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.
7.
REFER TO 1/M-211 AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 5/M-211 AHU-4 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.
8.
REFER TO 1/M-211 AHU-1, AHU-2, AHU-4, AHU-6, AHU-7 & AHU-8 FUNCTIONAL ARRANGEMENT DIAGRAM & 2/M-211 AHU-8 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.
9.
REFER TO 1/M-212 AHU-9 & AHU-10 FUNCTIONAL ARRANGEMENT DIAGRAM & 3/M-212 AHU-9 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.
10.
REFER TO 1/M-212 AHU-9 & AHU-10 FUNCTIONAL ARRANGEMENT DIAGRAM & 4/M-212 AHU-10 MAXIMUM DIMENSIONS FOR ADDITIONAL INFORMATION.
11. PROVIDE ELECTRIC STEAM HUMIDIFIER FOR SCHEDULED CAPACITY. MOUNT MANIFOLD IN SUPPLY DUCTWORK.
MECHANICAL SCHEDULES
05.20.16 RFP 221
TERMINAL AIR BOX SCHEDULE - SINGLE DUCT REHEAT
SYMBOL
AREA SERVED
CFM
HEATING COIL (NOTES 5 & 6)
MIN.
INLET
SIZE (IN.)
CONTROL
TYPE
(NOTE 3)
SENSOR
TYPE
(NOTE 4)
MFR MODEL REMARKS
COOLING
MAX.
HEATING
MAX.
MIN.
EAT
°F
LAT
°F
EWT
°F
MAX.
GPM
VAV-1.1 BREAKROOM
1,435 1,435 1,435
55 95 130 6.3 12 B 4 PRICE SDV NOTES 1 & 2
VAV-1.2 B&U STAFF AREA 850 850 850 55 95 130 3.7 9 B 4 PRICE SDV NOTES 1 & 2
VAV-1.3 OFFICE 405 335 335 55 95 130 1.5 7 A 4 PRICE SDV NOTES 1 & 2
VAV-2.1 LOBBY
3,140 3,140 3,140
55 95 130 13.8 24x16 B 1 PRICE SDV NOTES 1 & 2
VAV-2.2 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-2.3 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-2.4 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-2.5 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-2.6 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-3.1 ATS
1,000 1,000 1,000
55 95 130 4.4 10 B 4 PRICE SDV NOTES 1 & 2
VAV-3.2 SECURITY OFICE 430 195 195 55 95 130 0.9 5 A 4 PRICE SDV NOTES 1 & 2
VAV-3.3 OFFICE 150 100 100 55 95 130 0.5 4 A 4 PRICE SDV NOTES 1 & 2
VAV-3.4 METRO OFFICE 290 225 225 55 95 130 1.0 6 A 4 PRICE SDV NOTES 1 & 2
VAV-3.5 CONFERENCE 310 310 310 55 95 130 1.4 6 B 4 PRICE SDV NOTES 1 & 2
VAV-3.6 LOBBY
3,420 3,420 3,420
55 95 130 15.0 24x16 B 1 PRICE SDV NOTES 1 & 2
VAV-3.7 LOBBY
3,420 3,420 3,420
55 95 130 15.0 24x16 B 1 PRICE SDV NOTES 1 & 2
VAV-3.8 RAMP
2,940 2,940 2,940
55 95 130 12.9 24x16 B 1 PRICE SDV NOTES 1 & 2
VAV-4.1
TUCKER
PROJECTION
1,400 1,400 1,400
55 95 130 6.2 12 B 4 PRICE SDV NOTES 1 & 2
VAV-5.1 STORAGE 240 240 240 55 95 130 1.1 5 B 4 PRICE SDV NOTES 1 & 2
VAV-5.2
CAFÉ BOH
1,740
515 515 55 95 130 2.3 14 A 4 PRICE SDV NOTES 1 & 2
VAV-5.3
CAFÉ
2,200 2,200 2,200
55 95 130 9.7 16 B 1 PRICE SDV NOTES 1 & 2
VAV-5.4 LOBBY
2,160 2,160 2,160
55 95 130 9.5 16 B 1 PRICE SDV NOTES 1 & 2
VAV-5.5 LOBBY
2,160 2,160 2,160
55 95 130 9.5 16 B 1 PRICE SDV NOTES 1 & 2
VAV-5.6 RAMP
1,940 1,940 1,940
55 95 130 8.5 12 B 1 PRICE SDV NOTES 1 & 2
VAV-6.1 OFFICE 295 215 215 55 95 130 0.9 6 A 4 PRICE SDV NOTES 1 & 2
VAV-6.2 IR OFFICE
1,230 1,230 1,230
55 95 130 5.4 12 B 4 PRICE SDV NOTES 1 & 2
VAV-6.3 IR MEETING 680 680 680 55 95 130 3.0 8 B 4 PRICE SDV NOTES 1 & 2
VAV-6.4 OFFICE 900 900 900 55 95 130 4.0 10 B 4 PRICE SDV NOTES 1 & 2
VAV-6.5 STORAGE 360 360 360 55 95 130 1.6 6 B 4 PRICE SDV NOTES 1 & 2
VAV-7.1 LOBBY
3,140 3,140 3,140
55 95 130 13.8 24x16 B 1 PRICE SDV NOTES 1 & 2
VAV-7.2 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-7.3 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-7.4 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-7.5 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-7.6 EXHIBIT
2,475 2,475 2,475
55 95 130 10.9 16 B 1 PRICE SDV NOTES 1 & 2
VAV-8.1
MUSEUM STORE
OFFICES
495 360 360 55 95 130 1.6 7 A 4 PRICE SDV NOTES 1 & 2
VAV-8.2
MUSEUM STORE
OFFICES
370 235 235 55 95 130 1.0 6 A 4 PRICE SDV NOTES 1 & 2
VAV-8.3
MUSEUM STORE
STORAGE
725 725 725 55 95 130 3.2 9 B 4 PRICE SDV NOTES 1 & 2
VAV-8.4
MUSEUM STORE
STORAGE
850 850 850 55 95 130 3.7 9 B 4 PRICE SDV NOTES 1 & 2
TERMINAL AIR BOX SCHEDULE - SINGLE DUCT REHEAT CONT.
SYMBOL
AREA SERVED
CFM
HEATING COIL (NOTES 5 & 6)
MIN.
INLET
SIZE (IN.)
CONTROL
TYPE
(NOTE 3)
SENSOR
TYPE
(NOTE 4)
MFR MODEL REMARKS
COOLING
MAX.
HEATING
MAX.
MIN.
EAT
°F
LAT
°F
EWT
°F
MAX.
GPM
VAV-9.1 EXHIBIT
3,725 3,725 3,725
55 95 130 16.4 24x16 B 1 PRICE SDV
NOTES 1, 2, & 7
VAV-9.2 EXHIBIT
3,725 3,725 3,725
55 95 130 16.4 24x16 B 1 PRICE SDV
NOTES 1, 2, & 7
VAV-9.3 MEZZANINE
2,700 2,370 2,370
55 95 130 10.4 16 A 1 PRICE SDV
NOTES 1, 2, & 7
VAV-9.4 MEZZANINE
2,700 2,370 2,370
55 95 130 10.4 16 A 1 PRICE SDV
NOTES 1, 2, & 7
VAV-9.5
MEZZANINE/EXHIBIT
3,600 3,600 3,600
55 95 130 15.8 24x16 B 1 PRICE SDV
NOTES 1, 2, & 7
VAV-9.6
MEZZANINE/EXHIBIT
3,600 3,600 3,600
55 95 130 15.8 24x16 B 1 PRICE SDV
NOTES 1, 2, & 7
VAV-9.7 VOLUNTEER OFFICE 445 360 360 55 95 130 1.6 7 A 4 PRICE SDV NOTES 1 & 2
VAV-9.8 OFFICE 405 350 350 55 95 130 1.5 7 A 4 PRICE SDV NOTES 1 & 2
VAV-9.9 MULTIPURPOSE 920 920 920 55 95 130 4.0 10 B 4 PRICE SDV NOTES 1 & 2
VAV-9.10 MULTIPURPOSE 920 920 920 55 95 130 4.0 10 B 4 PRICE SDV NOTES 1 & 2
VAV-9.11 VESTIBULE 200 105 105 55 95 130 0.5 5 A 1 PRICE SDV NOTES 1 & 2
VAV-9.12 CATERING 615 350 350 55 95 130 1.5 8 A 4 PRICE SDV NOTES 1 & 2
VAV-9.13 CORRIDOR 160 105 105 55 95 130 0.5 4 A 1 PRICE SDV NOTES 1 & 2
VAV-10.1 CORRIDOR 440 200 200 55 95 130 0.9 7 A 1 PRICE SDV NOTES 1 & 2
VAV-10.2 SCREENING
2,080 2,080 2,080
55 95 130 9.2 14 B 1 PRICE SDV NOTES 1 & 2
VAV-10.3 OFFICE 490 220 220 55 95 130 1.0 7 A 4 PRICE SDV NOTES 1 & 2
VAV-10.4 SECURITY
2,160 2,160 2,160
55 95 130 9.5 16 B 1 PRICE SDV NOTES 1 & 2
VAV-10.5 SECURED VESTIBULE 390 170 170 55 95 130 0.7 6 A 1 PRICE SDV NOTES 1 & 2
VAV-10.6 TICKETING
2,310 2,310 2,310
55 95 130 10.2 16 B 1 PRICE SDV NOTES 1 & 2
VAV-10.7 OFFICE 355 155 155 55 95 130 0.7 6 A 4 PRICE SDV NOTES 1 & 2
VAV-10.8 CORRIDOR 960 330 330 55 95 130 1.5 10 A 1 PRICE SDV NOTES 1 & 2
VAV-10.9 CORRIDOR 520 180 180 55 95 130 0.8 7 A 1 PRICE SDV NOTES 1 & 2
VAV-10.10 LOBBY
1,640 1,640 1,640
55 95 130 7.2 14 B 1 PRICE SDV
NOTES 1, 2, & 8
VAV-10.11 LOBBY
1,640 1,640 1,640
55 95 130 7.2 14 B 1 PRICE SDV
NOTES 1, 2, & 8
VAV-10.12 LOBBY
1,640 1,640 1,640
55 95 130 7.2 14 B 1 PRICE SDV
NOTES 1, 2, & 8
VAV-10.13 ENTRY
2,130 2,130 2,130
55 95 130 9.4 14 B 1 PRICE SDV
NOTES 1, 2, & 8
NOTES:
1.
NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER ARI STANDARD 885-98
USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE.
2.
TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC.
3. SEE SHEET M-512 FOR DESCRIPTION OF CONTROL TYPE.
4.
SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE.
5. HEATING COIL IS BASED ON HEATING AIR FLOW. WATER PRESSURE DROP OF REHEAT COILS SHALL NOT EXCEED 5'. PROVIDE REHEAT COILS SEPARATE
FROM BOXES IF REQUIRED TO MEET WATER PRESSURE DROP REQUIREMENTS.
6.
HEATING COIL SELECTION SHALL BE BASED ON A FIXED LEAVING AIR TEMPERATURE AND VARIABLE FLOW (GPM). PROVIDE FINAL MAXIMUM FLOW
RATE (GPM) TO TEST AND BALANCE & TEMPERATURE CONTROLS CONTRACTORS.
7. CONTROLS SHALL BE 24V.
8. VAV LOCATED IN UNDERFLOOR VAULT.
FAN COIL UNIT SCHEDULE - HYDRONIC
SYMBOL SERVICE CFM
MIN. OA
CFM
EAT COOLING COIL HEATING COIL ELECTRICAL
MANUFACTURER MODEL REMARKS
DB °F WB °F
TOTAL
MBH
SENSIBLE
MBH
GPM
EWT
°F
LWT
°F
W.P.D.
FT. HD
TOTAL
MBH
GPM
EWT
°F
LWT
°F
W.P.D.
FT. HD
POWER
(W)
RPM
VOLT-
PHASE
DISCONNECT STARTER
BY (NOTE A) TYPE (NOTE B) TYPE (NOTE A)
FCU-1 TC 890
N/A
75 62 24.7 20.3 3.1 42 58 3.2
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCB
FCU-2 TC 890
N/A
75 62 24.7 20.3 3.1 42 58 3.2
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCB
FCU-3 TC 890
N/A
75 62 24.7 20.3 3.1 42 58 3.2
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCB
FCU-4 TC 890
N/A
75 62 24.7 20.3 3.1 42 58 3.2
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCB
FCU-5 TC 890
N/A
75 62 24.7 20.3 3.1 42 58 3.2
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCB
FCU-6 TC 890
N/A
75 62 24.7 20.3 3.1 42 58 3.2
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCB
FCU-7 TC 890
N/A
75 62 24.7 20.3 3.1 42 58 3.2
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCB
FCU-8 NORTH EMR 921
N/A
85 63 33.3 32.3 4.6 42 57 6.5
N/A N/A N/A N/A N/A
1,100
115-1 MFR NF FV TRANE FCB
FCU-9
ED
STORAGE
N/A
75 62 11.5 11.5 2.0 42 58 1.5
N/A N/A N/A N/A N/A
40 630 115-1 MFR NF FV TRANE FCB
FCU-10 SOUTH EMR
3,000 N/A
80 63 78.0 77.0 9.9 42 59 1.5
N/A N/A N/A N/A N/A 1 1/2 HP
815 208-3 MFR NF FV TRANE BCHC
FCU-11 TC 287
N/A
75 62 5.9 4.7 0.8 42 58 8.8
N/A N/A N/A N/A N/A
1,480
115-1 MFR NF FV TRANE FCC
FCU-12 TC 287
N/A
75 62 5.9 4.7 0.8 42 58 8.8
N/A N/A N/A N/A N/A
1,480
115-1 MFR NF FV TRANE FCC
FCU-13
SERVICE
ENTRY
N/A
75 62 8.0 7.5 1.0 42 58 0.7 10.0 1.0 130 109 4.6 40 815 115-1 MFR NF FV TRANE FCD
FCU-14
NORTH
CORRIDOR
N/A
75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125
1,100
115-1 MFR NF FV TRANE FCD
FCU-15
NORTH
CORRIDOR
N/A
75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125
1,100
115-1 MFR NF FV TRANE FCD
FCU-16
NORTH
CORRIDOR
N/A
75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125
1,100
115-1 MFR NF FV TRANE FCD
FCU-17
NORTH
CORRIDOR
N/A
75 62 6.0 4.5 0.7 42 59 0.5 24.0 3.6 130 116 4.1 125
1,100
115-1 MFR NF FV TRANE FCD
FCU-18
NORTH
CORRIDOR
N/A
75 62 3.0 3.0 0.5 42 54 1.0 12.0 0.8 130 99 1.0 40 825 115-1 MFR NF FV TRANE FCD
FCU-19 ELEC
1,500 N/A
80 63 37.5 36.7 5.5 42 56 0.5
N/A N/A N/A N/A N/A 1/2 HP
515 208-3 MFR NF FV TRANE BCHC
FCU-20 MECH
3,365 3,365
95 75 78.0 76.0 4.9 42 76 0.5 175.0 5.8 130 71 1.2 2 HP
1,050
208-3 MFR NF VFD TRANE BCHC NOTE 1
FCU-21 NORTH ELEC 980 45 75 62 17.8 17.4 2.6 42 56 2.2 15.4 0.8 130 92 4.2 165
1,090
115-1 MFR NF FV TRANE FCD
FCU-22
NORTH
CORRIDOR
N/A
75 62 6.0 5.8 0.8 42 58 1.2 14.2 1.3 130 108 2.3 40 825 115-1 MFR NF FV TRANE FCD
FCU-23
NORTH
CORRIDOR
N/A
75 62 6.2 6.0 0.8 42 58 1.2 13.9 1.2 130 107 2.3 40 825 115-1 MFR NF FV TRANE FCD
FCU-24
NORTH
CORRIDOR
N/A
75 62 3.1 2.5 0.4 42 58 1.0 7.7 0.5 130 99 1.4 40
1,080
115-1 MFR NF FV TRANE FCD
FCU-25
SOUTH
CORRIDOR
N/A
75 62 3.1 2.5 0.4 42 58 1.0 7.7 0.5 130 99 1.4 40
1,080
115-1 MFR NF FV TRANE FCD
FCU-26
SOUTH
CORRIDOR
N/A
75 62 6.2 6.0 0.8 42 58 1.2 13.9 1.2 130 107 2.3 40 825 115-1 MFR NF FV TRANE FCD
FCU-27
SOUTH
CORRIDOR
N/A
75 62 6.2 5.8 0.8 42 58 1.2 15.5 1.4 130 107 2.3 40 825 115-1 MFR NF FV TRANE FCD
FCU-28 SOUTH ELEC
1,050 N/A
75 62 22.4 22.0 6.1 42 53 10.4
N/A N/A N/A N/A N/A
1,085
115-1 MFR NF FV TRANE FCD
FCU-29
SOUTH
CORRIDOR
N/A
75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150
1,075
115-1 MFR NF FV TRANE FCD
FCU-30
SOUTH
CORRIDOR
N/A
75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150
1,075
115-1 MFR NF FV TRANE FCD
FCU-31
SOUTH
CORRIDOR
N/A
75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150
1,075
115-1 MFR NF FV TRANE FCD
NOTES:
1.
FCU IS 100% RAW OUTSIDE AIR. UNIT SHALL RUN AT 1010 CFM FOR NORMAL OPERATION AND 3365 CFM IN EMERGENCY PURGE MODE. HEATING EAT 0 °F.
MECHANICAL SCHEDULES
RFP 05211.03.15
AIR CURTAIN SCHEDULE
SYMBOL SERVICE CFM
OVERALL
DIMENSIONS
L x H x D (IN.)
HEATING COIL
ELECTRICAL
MANUFACTURER MODEL REMARKS
HP
VOLT-
PHASE
FLA
DISCONNECT
TYPE EWT LWT GPM MBH
BY (NOTE A) TYPE (NOTE B)
ACR-1
SHIPPING/
RECEIVING
20,700
155 x 36 x 28
HOT
WATER
130 110 40 447 10 460-3 13.0 MFR NF MARS AIR BD 18
NOTES 1, 2
NOTES:
1.
MANUFACTURER SHALL PROVIDE FACTORY WIRED MOTOR STARTER, DISCONNECT, AND CONTROL TRANSFORMER AS REQUIRED FOR SINGLE POINT POWER CONNECTION
2. MANUFACTURER SHALL PROVIDE TIME DELAY RELAY AND REMOTE THERMOSTAT. SEE SPECIFICATIONS FOR DETAILS.
RELIEF VAV SCHEDULE
SYMBOL
AREA SERVED
CFM
MIN.
INLET
SIZE (IN.)
CONTROL
TYPE
(NOTE 3)
MANUFACTURER MODEL REMARKS
BOX
MAX.
BOX MIN.
EX-01
B&U OFFICE AREA (AHU-1)
750 750 9 D PRICE SDE
NOTES 1, 2
EX-02
TUCKER PROJECTION (AHU-4)
800 800 9 D PRICE SDE
NOTES 1, 2
EX-03
NORTH LEG (AHU-NL) 2,700 2,700
16 D PRICE SDE
NOTES 1, 2
EX-04
METRO OFFICES (AHU-3) 2,115
495 14 C PRICE SDE
NOTES 1, 2
EX-05
MENS RESTROOM (AHU-3) 1,125 1,125
12 D PRICE SDE
NOTES 1, 2
EX-06
WOMENS RESTROOM (AHU-5)
905 905 10 C PRICE SDE
NOTES 1, 2
EX-07
FOOD SERVICE (AHU-5) 3,325 1,210
24x16 C PRICE SDE
NOTES 1, 2
EX-08
SOUTH LEG (AHU-SL) 2,700 2,700
16 D PRICE SDE
NOTES 1, 2
EX-09
MUSEUM STORE (AHU-8) 2,070 1,035
14 C PRICE SDE
NOTES 1, 2
EX-10
IR OFFICE AREA (AHU-6)
785 785 9 D PRICE SDE
NOTES 1, 2
EX-11
TUCKER THEATER (AHU-4) 1,270
235 12 C PRICE SDE
NOTES 1, 2
EX-12
ADDITION EXHAUST (AHU-9/AHU-10) 2,790 2,790
16 D PRICE SDE
NOTES 1, 2
NOTES:
1.
NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED
PER ARI STANDARD 885-98 USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE.
2.
TOTAL AIR PRESSURE DROP OF TAB SHALL NOT EXCEED 0.50" WC.
3. SEE M-512 FOR DESCRIPTION OF CONTROL TYPE.
LOUVER SCHEDULE
SYMBOL SERVICE CFM
SIZE
W x H
(IN.)
FREE
AREA
VEL. FPM
S.P.
IN.
W.C.
FINISH MANUFACTURER MODEL
L-1 MAKEUP AIR
4,400
78x48 338 0.01 NOTE 1 RUSKIN ET125-30
L-2 SMOKE PURGE
30,000
84X84 975 0.1 NOTE 1 RUSKIN ET125-30
NOTES:
1. BAKED ENAMEL FINISH ON PRETREATED PRIME PAINT. STANDARD COLOR - SELECTION BY ARCHITECT.
UNIT HEATER SCHEDULE - HOT WATER
SYMBOL TYPE CFM MBH GPM
EWT
°F
LWT
°F
W.P.D.
FT.
HEAD
ELECTRICAL
CONTROL MANUFACTURER MODEL
HP RPM
VOLT-
PHASE
DISCONNECT
CONTROLLER/
STARTER
BY
(NOTE A)
TYPE
(NOTE B)
BY (NOTE A)
UH-1 HORIZONTAL 350 4.9 0.5 130 110 0.0
1/40 1,350
115-1 MFR NF MFR NOTE 1 TRANE UHS
UH-2 HORIZONTAL 630 13.2 1.3 130 110 0.1
1/20
900 115-1 MFR NF MFR NOTE 1 TRANE UHS
UH-3 HORIZONTAL
1,100
26.5 2.7 130 110 0.3
1/12
900 115-1 MFR NF MFR NOTE 1 TRANE UHS
UH-4 HORIZONTAL
1,100
26.5 2.7 130 110 0.3
1/12
900 115-1 MFR NF MFR NOTE 1 TRANE UHS
UH-5 HORIZONTAL 630 13.2 1.3 130 110 0.1
1/20
900 115-1 MFR NF MFR NOTE 1 TRANE UHS
NOTES:
1.
REFER TO 2/M-518.
COIL SCHEDULE - WATER
SYMBOL SERVICE
SIZE
L x H
(IN.)
CFM
EAT LAT
TOTAL
MBH
A.P.D.
IN.
W.C.
EWT
°F
LWT
°F
GPM
W.P.D.
FT.
HEAD
MANUFACTURER REMARKS
°FDB °FDB
HC-1
NORTH LEG
AHU
56x106
20,000
66 100 748 0.1 130 110 75.0 1.0 CUSTOM
NOTE 1, SIZE LISTED IS TOTAL
SIZE FOR 3 SECTIONS
HC-2
SOUTH LEG
AHU
56x106
20,000
66 100 748 0.1 130 110 75.0 1.0 CUSTOM
NOTE 1, SIZE LISTED IS TOTAL
SIZE FOR 3 SECTIONS
HC-3 AHU-3 18x102
15,000
50 60 165 0.4 130 110 16.5 3.1 CARRIER NOTE 1
HC-4 AHU-5 48x82
12,900
50 60 142 0.07 130 110 11.4 1.0 MCQUAY
NOTE 1, SIZE LISTED IS TOTAL
SIZE FOR 2 SECTIONS
HC-5
TUCKER
THEATER
36x20
2,775
48 70 67 0.40 130 92 3.5 0.1 NOTE 3 NOTE 2
HC-6
TUCKER
THEATER
36x20
2,775
48 70 67 0.40 130 92 3.5 0.1 NOTE 3 NOTE 2
NOTES:
1. COILS TO BE INSTALLED IN EXISTING AIR HANDLERS TO REPLACE STEAM HEAT COILS. VERIFY DIMENSIONS AND CONNECTIONS PRIOR TO ORDERING COILS.
2. COILS TO BE INSTALLED IN EXISTING DUCTWORK. VERIFY DIMENSIONS AND CONNECTIONS PRIOR TO ORDERING COILS.
3. REFER TO SPECIFICATION SECTION 23 82 16 FOR APROVED MANUFACTURERS.
FAN COIL UNIT SCHEDULE - HYDRONIC CONT.
SYMBOL SERVICE CFM
MIN. OA
CFM
EAT COOLING COIL HEATING COIL ELECTRICAL
MANUFACTURER MODEL REMARKS
DB °F WB °F
TOTAL
MBH
SENSIBLE
MBH
GPM
EWT
°F
LWT
°F
W.P.D.
FT. HD
TOTAL
MBH
GPM
EWT
°F
LWT
°F
W.P.D.
FT. HD
POWER
(W)
RPM
VOLT-
PHASE
DISCONNECT STARTER
BY (NOTE A) TYPE (NOTE B) TYPE (NOTE A)
FCU-32
SOUTH
CORRIDOR
N/A
75 62 7.2 6.4 0.7 42 65 0.3 26.4 1.6 130 98 1.2 150
1,075
115-1 MFR NF FV TRANE FCD
FCU-33
SOUTH
CORRIDOR
N/A
75 62 3.0 3.0 0.5 42 54 1.0 12.0 0.8 130 99 1.0 40 825 115-1 MFR NF FV TRANE FCD
FCU-34 SW MECH 550
N/A
75 62 10.2 9.9 1.4 42 56 1.1
N/A N/A N/A N/A N/A
1,080
115-1 MFR NF FV TRANE FCD
FCU-35
SHIPPING/
RECEIVING
980 55 75 62 16.2 14.0 2.4 42 56 2.5 29.8 2.2 130 103 2.0 160
1,090
115-1 MFR NF FV TRANE FCD
FCU-36 TC 211
N/A
75 62 5.0 3.8 0.7 42 58 6.1
N/A N/A N/A N/A N/A
60 980 115-1 MFR NF FV TRANE FCB
FCU-37
TICKETING
CLOSET
211 338 75 62 10.9 7.7 1.4 42 58 7.7
N/A N/A N/A N/A N/A
1,050
115-1 MFR NF FV TRANE FCB
FCU-38 TC 211
N/A
75 62 5.0 3.8 0.7 42 58 6.1
N/A N/A N/A N/A N/A
60 980 115-1 MFR NF FV TRANE FCB
FCU-39
DREAM
WALL
N/A
85 63 33.3 32.3 4.6 42 57 6.5
N/A N/A N/A N/A N/A
1,100
115-1 MFR NF FV TRANE FCB
FCU-40
CONTROL
ROOM
N/A
85 63 33.3 32.3 4.6 42 57 6.5
N/A N/A N/A N/A N/A
1,100
115-1 MFR NF FV TRANE FCB
FCU-41
CONTROL
ROOM
N/A
85 63 33.3 32.3 4.6 42 57 6.5
N/A N/A N/A N/A N/A
1,100
115-1 MFR NF FV TRANE FCB
FCU-42 EMR 256
N/A
75 62 9.1 6.2 1.3 42 58 5.0
N/A N/A N/A N/A N/A
40 825 115-1 MFR NF FV TRANE FCB
MECHANICAL SCHEDULES
NO SCALE
07.28.15 RFP 002
10.30.15 RFP 052
02.02.16 RFP 112
EXISTING COOLING TOWER SCHEDULE
SYMBOL SERVICE
MIN.
C.T.I.
TONS
MAX
GPM
MIN GPM
CONDENSING
WATER
AMBIENT
CONDITIONS
FAN DATA
OPERATING
WEIGHT
ELECTRICAL
MANUFACTURER MODEL
VOLT-
PHASE
DISCONNECT
CONTROLLER/STARTER
EWT °F LWT °F °FDB °FWB
NUMBER
OF FANS
HP
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C)
SCCR
CT-1 CH-1 & CH-2 600 1890.0 900.0 95 85 90 78 2 40 32150 460 EXISTING EXISTING EXISTING EXISTING EXISTING BAC VT1-680
EXISTING CHILLER SCHEDULE (WATER COOLED)
SYMBOL SERVICE REFRIGERANT
CAPACITY/PERFORMANCE
EVAPORATOR PERFORMANCE CONDENSER PERFORMANCE ELECTRICAL
MANUFACTURER MODEL REMARKS
DESIGN
TONS
STAGES OF
UNLOADING
MAX. KW/TON AT % LOAD
NPLV
KW/TON
EWT
°F
LWT
°F
GPM
MAXIMUM
PRESS DROP
FT. HEAD
FOULING
FACTOR
EWT
°F
LWT
°F
GPM
MAXIMUM
PRESS DROP
FT. HEAD
FOULING
FACTOR
VOLT-
PHASE
MOCP
AMPS
DISCONNECT
CONTROLLER/STARTER
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C)
100 75 50 25
CH-1
WHOLE
BUILDING
123 300 INFINITE 0.59 0.44 0.33 0.40 0.38 52 42 745.0 10.0 0.0001 85 95 930.0 5.0 0.0001
460/3
500.0 EXISTING EXISTING MFR VFD YORK YT J3A3C3 NOTE 1
CH-2
WHOLE
BUILDING
123 300 INFINITE 0.59 0.44 0.33 0.40 0.38 52 42 745.0 10.0 0.0001 85 95 930.0 5.0 0.0001
460/3
500.0 EXISTING EXISTING MFR VFD YORK YT J3A3C3 NOTE 1
NOTES:
1. CHILLERS ARE EXISTING TO BE RELOCATED.
EQUIPMENT SOUND DATA
SYMBOL
MAXIMUM ALLOWABLE DISCHARGE GENERATED NOISE IN DB RE 10
WATTS MAXIMUM ALLOWABLE INLET GENERATED NOISE IN DB RE 10
WATTS MAXIMUM ALLOWABLE RADIATED GENERATED NOISE IN DB RE 10
WATTS
OCTAVE BAND CENTER FREQUENCY OCTAVE BAND CENTER FREQUENCY OCTAVE BAND CENTER FREQUENCY
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
AHU-1 87 83 77 100 92 94 87 79 80 77 73 91 70 74 68 59 81 75 70 85 75 65 59 54
AHU-2 91 92 99 96 90 85 83 81 85 86 100 93 82 78 75 73 80 79 78 82 76 63 59 59
AHU-4 84 88 84 98 93 92 88 85 78 84 82 89 67 70 67 59 80 79 78 82 76 63 59 59
AHU-6 87 83 77 100 92 94 87 79 80 77 73 91 70 74 68 59 81 75 70 85 75 65 59 54
AHU-7 91 92 99 96 90 85 83 81 85 86 100 93 82 78 75 73 80 79 78 82 76 63 59 59
AHU-8 84 88 84 98 93 92 88 85 78 84 82 89 67 70 67 59 80 79 78 82 76 63 59 59
AHU-9 93 94 98 97 93 89 87 84 84 90 102 90 84 84 83 77 80 79 78 82 76 63 59 59
AHU-10 89 89 101 100 95 92 88 80 89 89 100 97 88 86 84 76 80 79 78 82 76 63 59 59
AHU-11 78 80 87 71 72 70 65 54 92 92 91 83 80 79 74 69 82 74 72 60 54 48 41 28
AHU-12 78 80 87 71 72 70 65 54 92 92 91 83 80 79 74 69 82 74 72 60 54 48 41 28
CH-3 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 67 73 62 59 71 69 57 51
DOAS-1 95 101 100 94 93 89 83 77 97 103 100 87 87 84 77 73 80 79 78 82 76 63 59 59
CHILLER SCHEDULE (WATER COOLED)
SYMBOL SERVICE REFRIGERANT
CAPACITY/PERFORMANCE
EVAPORATOR PERFORMANCE CONDENSER PERFORMANCE ELECTRICAL NOTE 3
MANUFACTURER MODEL REMARKS
DESIGN
TONS
STAGES OF
UNLOADING
MAX. KW/TON AT % LOAD (NOTE 1)
NPLV
KW/TON
EWT
°F
LWT
°F
GPM
MAXIMUM
PRESS DROP
FT. HEAD
FOULING
FACTOR
EWT
°F
LWT
°F
GPM
MAXIMUM
PRESS DROP
FT. HEAD
FOULING
FACTOR
VOLT-
PHASE
MCA
MOCP
AMPS
DISCONNECT
CONTROLLER/STARTER
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C)
SCCR
100 75 50 25
CH-3
HEAT
RECOVERY
134A 90 INFINITE 0.96 1.01 1.05 1.15 1.05 52 42 190.0 20.0 0.0001 110 130 130.0 5.0 0.0001
460/3
139.0 200.0 MFR NF MFR VFD 65000 TRANE RTWD NOTES 2 & 4
NOTES:
1. BASED ON WATER CONDITIONS LISTED IN SCHEDULE.
2. REFER TO SPECIFICATION SECTION 23 64 16 FOR ADDITIONAL INFORMATION.
3. ELECTRICAL CONNECTIONS SHALL ACCOMMODATE THE WIRE SIZES AND QUANTITIES SHOWN ON THE ELECTRICAL DRAWINGS.
4.
PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
5.
REFER TO EQUIPMENT SOUND DATA SCHEDULE.
PUMP SCHEDULE
SYMBOL SERVICE GPM
PUMP FT.
HEAD AT
DESIGN
MIMIMUM
PUMP
EFFICIENCY
INLET/IMPEL.
SIZE IN.
ELECTRICAL
MANUFACTURER MODEL REMARKS
HP
(NOTE E)
RPM
VOLT-
PHASE
DISCONNECT
CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
PHWP-1
PRIMARY HEATING
WATER - HX
400.0 14 66
5/5.125
1,750
460/3
MFR NF MFR MS B&G 1510 4AC
PHWP-2
PRIMARY HEATING
WATER - HRC
130.0 23 67
3/5.375
1.5
1,750 460/3
MFR NF MFR MS B&G 1510 2.5AB
SHWP-1
SECONDARY HEATING
WATER
800.0 70 82
6/9.25
1,750
460/3
MFR NF MFR VFD B&G 1510 5E
DUTY, NOTE 1
SHWP-2
SECONDARY HEATING
WATER
800.0 70 82
6/9.25
1,750 460/3
MFR NF MFR VFD B&G 1510 5E
STANDBY, NOTE 1
HWCP-1
HEATING WATER COIL -
DOAS
25.0 21 53
1.25/4.625
0.5
1,750 460/3
MFR NF MFR MS B&G 60 1.25x1.25x5.25
PCWP-1
PRIMARY CHILLED
WATER
745.0 38 79
6/8.125
1,750 460/3
MFR NF MFR MS B&G 1510 5BC
PCWP-2
PRIMARY CHILLED
WATER
745.0 38 79
6/8.125
1,750 460/3
MFR NF MFR MS B&G 1510 5BC
PCWP-3
PRIMARY CHILLED
WATER
745.0 38 79
6/8.125
1,750
460/3
MFR NF MFR MS B&G 1510 5BC
PCP-1
PRIMARY CHILLED
WATER - HRC
190.0 41 75
3/6.875
1,750 460/3
MFR NF MFR VFD B&G 1510 2.5AB
SCWP-1
SECONDARY CHILLED
WATER
1350.0 60 76
8/8.75
1,750
460/3
MFR NF MFR VFD B&G 1510 6BC
LEAD, NOTE 1
SCWP-2
SECONDARY CHILLED
WATER
1350.0 60 76
8/8.75
1,750 460/3
MFR NF MFR VFD B&G 1510 6BC
LAG, NOTE 1
NOTES:
1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
EXISTING PUMP SCHEDULE
SYMBOL SERVICE GPM
PUMP FT.
HEAD AT
DESIGN
MIMIMUM
PUMP
EFFICIENCY
INLET/IMPEL.
SIZE IN.
ELECTRICAL
MANUFACTURER MODEL REMARKS
HP
(NOTE E)
RPM
VOLT-
PHASE
DISCONNECT
CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
CP-1 CONDENSER PUMP 960.0 60 EXISTING EXISTING 25
1,750 460/3
EXISTING EXISTING EXISTING EXISTING TACO FE5010
CP-2 CONDENSER PUMP 960.0 60 EXISTING EXISTING 25
1,750 460/3
EXISTING EXISTING EXISTING EXISTING TACO FE5010
CP-3 CONDENSER PUMP 960.0 60 EXISTING EXISTING 25
1,750 460/3
EXISTING EXISTING EXISTING EXISTING TACO FE5010
HEAT EXCHANGER SCHEDULE - STEAM TO WATER
SYMBOL SERVICE
WATER STEAM
HEATING
SURFACE FT
FOULING
FACTOR
MANUFACTURER MODEL REMARKS
GPM
W.P.D.
FT. HEAD
EWT
°F
LWT
°F
PSIG
(NOTE 1)
LB/HR
HX-1
HEATING
WATER
400.0 0.9 110 150 15 8346 188 0.00149 B&G SU 20 3-4
NOTES:
1. STEAM PRESSURE INDICATED IS THE PRESSURE AVAILABLE DOWNSTREAM OF THE CONTROL VALVE.
PRESSURE REDUCING VALVE SCHEDULE
SYMBOL SERVICE
LB/HR
INLET
PRESSURE
PSI
OUTLET
PRESSURE
PSI
VALVE
SIZE
MANUFACTURER MODEL REMARKS
PRV-1 HX-1 2100 125 30
1 1/2"
ARMSTRONG GP-1000 NOTE 1
PRV-2 HX-1 6300 125 30
3"
ARMSTRONG GP-1000 NOTE 1
NOTES:
1. PRV VALVE TO BE LOW VELOCITY TYPE WITH MAXIMUM RADIATED SOUND < 85dBA
TRAP SCHEDULE
SYMBOL SERVICE TYPE
SAFETY
FACTOR
SIZE
LB/HR.
(NOTE 1)
PRESSURE
DIFFERENTIAL
MANUFACTURER MODEL REMARKS
T-1 DRIP IB 100%
3/4"
12 125 SPIRAX B1H-125 NOTES 5 & 6
T-2 DRIP IB 100%
3/4"
12 30 SPIRAX B1H-125 NOTES 5 & 6
T-3 DRIP IB 100%
3/4"
12 30 SPIRAX B1H-125 NOTES 5 & 6
T-4 HX-1 F&T 25%
2 1/2"
10450 0.25 SPIRAX FTB-125
NOTES 2, 3, & 4
T-5 HX-1 F&T 25%
2 1/2"
10450 0.25 SPIRAX FTB-125
NOTES 2, 3, & 4
NOTES:
1. CAPACITY LISTED IS FOR EACH TRAP AND INCLUDES SAFETY FACTOR.
2.
SUITABLE TO 125 PSIG, SIDE INLET & OUTLET, SS FLOAT MECHANISM AND VALVE, CAST IRON BODY, BALANCED PRESSURE
THERMOSTATIC AIR VENT, ALL INTERNALS REPLACEABLE IN-LINE.
3.
CAPACITY AT OTHER DIFFERENTIAL PRESSURES SHALL BE AT LEAST 525#/HR AT 10 PSID, AND 1080#/HR AT 75 PSID.
4. WITH INTEGRAL VACUUM BREAKER.
5.
SIDE INLET AND OUTLET INVERTED BUCKET TRAP, 250 PSIG RATED. CAST IRON BODY, ALL INTERNAL COMPONENTS
OF STAINLESS STEEL AND REPLACABLE IN-LINE.
6.
CAPACITY AT OTHER DIFFERENTIAL PRESSURES SHALL BE AT LEAST 150#/HR AT 10 PSID, AND 420#/HR AT 75 PSID.
GRILLES REGISTERS & DIFFUSERS SCHEDULE
SYMBOL MAT'L TYPE
MARGIN
(NOTE 1)
INLET
SIZE
(INCH)
FACE
SIZE
(INCH)
INTEGRAL
BALANCING
DAMPER
FINISH MANUFACTURER MODEL REMARKS
CD-1 STEEL LOUVER FACE LAY-IN SEE DWG. 24x24 NO WHITE PRICE SCD
STAMPED LOUVER DROP FACE. MINIMUM OF
TWO STEPDOWN DIFFUSION CONES
CD-2 STEEL ROUND CONE
1 1/4"
SEE DWG. INLET +6 YES WHITE PRICE RCDE
CD-3 STEEL LOUVER FACE LAY-IN SEE DWG. 12x12 YES WHITE PRICE SCD-FR
STAMPED LOUVER DROP FACE. MINIMUM OF
TWO STEPDOWN DIFFUSION CONES
RG-1 STEEL
PERFORATED
FACE
LAY-IN
N/A
24x24 NO WHITE PRICE PDDR FACE ONLY - NON DUCTED
RG-2 STEEL 45° DEFLECTION
1 1/4"
SEE DWG. INLET +2 NO WHITE PRICE 530
SG-1 STEEL
DOUBLE
DEFLECTION
1 1/4"
SEE DWG. INLET +2 YES WHITE PRICE 520
FRONT BLADES VERTICAL UNLESS NOTED
OTHERWISE
SG-2 STEEL
DOUBLE
DEFLECTION
1 1/4"
SEE DWG. INLET +2 YES NOTE 3 PRICE SDG
FRONT BLADES VERTICAL UNLESS NOTED
OTHERWISE
SG-3 STEEL 45° DEFLECTION
1 1/4"
SEE DWG. INLET +2 NO WHITE PRICE 530
EG-1 STEEL
PERFORATED
FACE
LAY-IN SEE DWG. 24x24 NO WHITE PRICE PDDR
EG-2 STEEL
PERFORATED
FACE
LAY-IN SEE DWG. 16x16 YES WHITE PRICE PDDR
EG-3 STEEL 45° DEFLECTION
1 1/4"
SEE DWG. INLET +2 NO WHITE PRICE 530
EG-4 STEEL 45° DEFLECTION
1 1/4"
SEE DWG. INLET +2 YES WHITE PRICE 530
NOTES:
1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.
2. ALL RUN OUT DUCTWORK TO DIFFUSERS SHALL BE NECK SIZE UNLESS OTHERWISE NOTED.
3. FINISH SPECIFIED BY ARCHITECT.
DUST COLLECTOR SCHEDULE
SYMBOL SERVICE
COLLECTOR
TYPE
CFM
S.P.
IN.
W.C.
INLET
SIZE
DROP
OUT BIN
CAPACITY
ELECTRICAL
MANUFACTURER MODEL REMARKS
HP
VOLT-
PHASE
DISCONNECT
CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
DC-1
WORK ROOM
123A
CYCLONE
1,450
10.5
6"
29 GAL. 2
208/1
MFR NF MFR MS LAGUNA
MOBILE
CYCLONE
NOTE 1
NOTES:
1. PROVIDE DUST COLLECTION HOSE KIT.
MOTOR OPERATED DAMPER SCHEDULE
SYMBOL SERVICE
SIZE
W x H
(IN.)
CFM
OPPOSED OR
PARALLEL
BLADES
HORIZONTAL
OR VERTICAL
BLADES
INSULATED
ACTUATOR
TYPE
ACTUATOR
STYLE
POWER
FAILURE
POSITION
POSITIVE
POSITION
FEEDBACK
REMARKS
MAX. MIN.
MOD-1
NORTH SMOKE
PURGE
48x24
40,000 40,000
PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2
MOD-2
SOUTH SMOKE
PURGE
48x24
40,000 40,000
PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2
MOD-3 OUTSIDE AIR 60x60
50,000 25,000
OPPOSED HORIZONTAL YES ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-4 DOAS RELIEF 60x60
45,000 22,500
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-5
NORTH EXHIBIT
(AHU-2 RELIEF)
60x24
5,130 2,565
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-6
SOUTH EXHIBIT
(AHU-7 RELIEF)
60x24
5,130 2,565
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-7 AHU-9 RELIEF 26x26
5,170 1,795
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-8 AHU-10 RELIEF 26x26
5,270 2,030
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-9
AHU-NL
OUTSIDE AIR
24x14
3,000 3,000
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-10
AHU-SL
OUTSIDE AIR
24x14
3,000 3,000
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-11
AHU-3 OUTSIDE
AIR
24x18
3,600 1,800
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-12
AHU-5 OUTSIDE
AIR
26x18
4,700 2,350
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-13 EF-1 12x8 805 805 OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-14 EF-2 18x18
3,365 1,010
OPPOSED HORIZONTAL NO ELECTRIC PROPORTIONAL NO YES NOTE 1
MOD-15
AHU -NL SMOKE
PURGE
60x48
30,000 30,000
PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2
MOD-16
AHU -SL SMOKE
PURGE
60x48
30,000 30,000
PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2
MOD-17
AHU - 3 SMOKE
EVACUATION
54x36
15,000 15,000
PARALLEL HORIZONTAL NO ELECTRIC TWO POSITION NO YES NOTES 1 & 2
NOTES:
1. COORDINATE DAMPER ACTUATOR LOCATION AND MOUNTING REQUIREMENTS WITH TEMPERATURE CONTROL CONTRACTOR.
2. DAMPER IS CONTROLLED BY FIRE ALARM SYSTEM. POSITION FEEDBACK SHALL BE SENT TO FIRE ALARM SYSTEM.
LINEAR DIFFUSERS & GRILLES SCHEDULE
SYMBOL MATERIAL
SLOT
WIDTH
NO.
SLOTS
LENGTH
PLENUM
REQUIRED
PLENUM
INSULATION
PLENUM
INLET SIZE
PATTERN
CONTROL
REQUIRED
INTEGRAL
BALANCING
DAMPER
FINISH MANUFACTURER MODEL REMARKS
LD-1 ALUMINUM
1 1/4"
72"
YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE AS
NOTES 1, 2, & 3
LD-2 ALUMINUM
1 1/2"
60"
YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE JS
NOTES 1, 2, 3, & 6
LD-3 ALUMINUM
2"
60"
YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE AS
NOTES 1, 2, & 3
LD-4 ALUMINUM
2 1/2"
48"
YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE JS
NOTES 1, 2, & 3
LD-5 ALUMINUM
2"
48"
YES WRAPPED SEE DWG. YES YES NOTE 4 PRICE JS
NOTES 1, 2, 3, & 5
LDE-1 ALUMINUM
3"
20"
YES NONE SEE DWG. NO NO NOTE 4 PRICE JS
NOTES 1, 2, & 3
LDR-1 ALUMINUM
1 1/2"
60"
NO
N/A N/A
NO NO NOTE 4 PRICE JS
NOTES 1, 2, 3, & 6
LDR-2 ALUMINUM
2"
60"
YES NONE
N/A
NO NO NOTE 4 PRICE AS
NOTES 1, 2, & 3
NOTES:
1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.
2. PROVIDE WITH CONCEALED FASTENERS.
3. REFER TO ARCHITECTURAL DRAWINGS FOR TRIM DETAILS.
4. REFER TO ARCHITECTURAL DRAWINGS FOR FINISH DETAILS.
5. CONTRACTOR MAY PROVIDE ONE CONTINUOUS 16' DIFFUSER OR MULTIPLE SHORTER DIFFUSERS. FIELD VERIFY REQUIRED LENGTH.
6. PROVIDE BLANKOFFS AS REQUIRED FOR CONTINUOUS APPEARANCE. FIELD VERIFY REQUIRED LENGTHS.
MECHANICAL SCHEDULES
RFP 05211.03.15
PUMP SCHEDULE
SYMBOL SERVICE GPM
PUMP FT.
HEAD AT
DESIGN
MIMIMUM
PUMP
EFFICIENCY
INLET/IMPEL.
SIZE IN.
ELECTRICAL
MANUFACTURER MODEL REMARKS
HP
(NOTE E)
RPM
VOLT-
PHASE
DISCONNECT
CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
PCWP-1
PRIMARY CHILLED
WATER
515.0 35 84% 6.75 7.5
1,750
460/3
MFR NF MFR MS B&G 1510 4AD
DUTY, NOTE 2
PCWP-2
PRIMARY CHILLED
WATER
515.0 35 84% 6.75 7.5
1,750 460/3
MFR NF MFR MS B&G 1510 4AD
DUTY, NOTE 2
PCWP-3
PRIMARY CHILLED
WATER
515.0 35 84% 6.75 7.5
1,750 460/3
MFR NF MFR MS B&G 1510 4AD
STANDBY, NOTE 2
PCP-1
PRIMARY CHILLED
WATER - HRC
136.0 41 74% 6.625 3
1,750 460/3
MFR NF MFR VFD B&G 1510 2.5AC-es NOTE 2
SCWP-1
SECONDARY CHILLED
WATER
1050.0 56 72% 8.25 25
1,750 460/3
MFR NF MFR VFD B&G 1510 6BD
LEAD, NOTE 1, 2
SCWP-2
SECONDARY CHILLED
WATER
1050.0 56 72% 8.25 25
1,750
460/3
MFR NF MFR VFD B&G 1510 6BD
LAG, NOTE 1, 2
NOTES:
1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
2. FOR BID OPTION #8 PROVIDE THESE PUMPS IN PLACE OF THE PUMPS SCHEDULED ON SHEET M-306. PUMPS NOT LISTED IN THIS SCHEDULE ARE TO BE PROVIDED AS SCHEDULED ON M-306.
BID OPTION #8
REPLACEMENT CHILLER SCHEDULE (WATER COOLED)
SYMBOL SERVICE REFRIGERANT
CAPACITY/PERFORMANCE
EVAPORATOR PERFORMANCE CONDENSER PERFORMANCE ELECTRICAL
MANUFACTURER MODEL REMARKS
DESIGN
TONS
STAGES OF
UNLOADING
MAX. KW/TON AT % LOAD
NPLV
KW/TON
EWT
°F
LWT
°F
GPM
MAXIMUM
PRESS DROP
FT. HEAD
FOULING
FACTOR
EWT
°F
LWT
°F
GPM
MAXIMUM
PRESS DROP
FT. HEAD
FOULING
FACTOR
VOLT-
PHASE
MOCP
AMPS
DISCONNECT
CONTROLLER/STARTER
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C)
100 75 50 25
CH-1
WHOLE
BUILDING
134a 300 INFINITE 0.666 0.485 0.341 0.411 0.401 56 42 515.0 20.0 0.0001 85 100 600.0 10.0 .00025
460/3
500.0 MFR NF MFR VFD DAIKIN WSC NOTE 1
CH-2
WHOLE
BUILDING
134a 300 INFINITE 0.666 0.485 0.341 0.411 0.401 56 42 515.0 20.0 0.0001 85 100 600.0 10.0 .00025
460/3
500.0 MFR NF MFR VFD DAIKIN WSC NOTE 1
NOTES:
1.
FOR BID OPTION #8, PROVIDE NEW CHILLERS AND REMOVE THE EXISTING CHILLERS.
2. THE ABOVE INFORMATION IS FOR PERFORMANCE REQUIREMENTS. INITIALLY THE CONDENSER WATER FLOW WILL BE 900 GPM. CONDENSER PRESSURE DROP AT 900 GPM SHALL NOT EXCEDE 13FT.
CHILLED WATER/CONDENSER WATER FLOW DIAGRAM - WEST MECHANICAL ROOM
KEYNOTES CONT'DKEYNOTES
M-400
MECHANICAL FLOW DIAGRAMS
SYMBOL: DESCRIPTION:
HEATING WATER FLOW DIAGRAM SYMBOL LIST KEYNOTES
HEATING WATER FLOW DIAGRAM - SOUTHWEST MECHANICAL ROOM
M-401
AIR FLOW DIAGRAM
NO SCALE
M-402
GENERAL CONTROL NOTES
CONTROL SYMBOLS LIST
SYMBOL: DESCRIPTION:
CONTROL SYMBOLS LIST
SYMBOL: DESCRIPTION:
GENERAL CONTROL NOTES GENERAL CONTROL NOTES
MECHANICAL CONTROL DIAGRAMS
AIR HANDLER REPORT GENERATION
SUPPLY FAN VFD CONTROL
EXHAUST INTERLOCK SCHEDULE
SYSTEM
INTERLOCKED EXHAUST
ZONES
REMARKS
AHU-1 NOTE 1
AHU-2 NOTE 1
AHU-3 NOTE 1
AHU-4 NOTE 1
AHU-5 NOTE 1
AHU-6 NOTE 1
AHU-7 NOTE 1
NOTES:
1. INTERLOCK ZONE FAN OPERATION THROUGH THE FMCS
WITH RESPECTIVE AHU IN ACCORDANCE WITH AHU
SEQUENCE OF OPERATION.
TYPICAL FOR AHU-1, AHU-2, AHU-4, AHU-6, AHU-7, AHU-8, AHU-9, AHU-10
AIR HANDLING UNIT CONTROL - AHU-A
AHU-8 NOTE 1
AHU-9 NOTE 1
AHU-10 NOTE 1
TYPICAL FOR AHU-1, AHU-2, AHU-4, AHU-6, AHU-7, AHU-8, AHU-9, AHU-10M-501
M-501
M-501
TYPICAL FOR AHU-1, AHU-2, AHU-4, AHU-6, AHU-7, AHU-8, AHU-9, AHU-10
AIR HANDLING UNIT CONTROL - AHU-A
M-502
AIR HANDLING UNIT CONTROL: AHU-B
TYPICAL FOR AHU-11 AND AHU-12M-503
SUPPLY / RETURN FAN VFD CONTROL
NO SCALE
TYPICAL FOR AHU-3
AIR HANDLING UNIT CONTROL - AHU-C
TYPICAL FOR AHU-3M-504
M-504
M-504
MECHANICAL CONTROL DIAGRAMS
08.20.15 RFI 185
TYPICAL FOR AHU-3
AIR HANDLING UNIT CONTROL - AHU-C
M-505
SUPPLY / RETURN FAN VFD CONTROL
TYPICAL FOR AHU-5
AIR HANDLING UNIT CONTROL - AHU-D
TYPICAL FOR AHU-5M-506
M-506
M-506
MECHANICAL CONTROL DIAGRAMS
08.20.15 RFI 185
TYPICAL FOR AHU-5
AIR HANDLING UNIT CONTROL - AHU-D
M-507
TYPICAL FOR AHU-NL, AHU-SL
AIR HANDLING UNIT CONTROL - AHU-E
TYPICAL FOR AHU-NL, AHU-SL
SUPPLY / RETURN FAN VFD CONTROL
M-508
M-508
M-508
TYPICAL FOR AHU-NL, AHU-SL
AIR HANDLING UNIT CONTROL - AHU-E
M-509
SUPPLY & EXHAUST FAN VFD CONTROL
DOAS UNIT WITH ENERGY RECOVERY WHEEL CONTROL - DOAS-1
TYPICAL FOR DOAS-1
DOAS REPORT GENERATION
GLOBAL REFERENCE POINTS
NO SCALE
M-510
M-510
M-510
M-510
DOAS UNIT WITH ENERGY RECOVERY WHEEL CONTROL - DOAS-1
M-511
TAB CONTROL W/ HOT WATER REHEAT: TAB-A
CONSTANT VOLUME TAB CONTROL: TAB-B
M-512
M-512
CONSTANT VOLUME TAB CONTROL RELIEF: TAB-D
VARIABLE VOLUME TAB CONTROL RELIEF: TAB-C
M-512
M-512
TERMINAL AIR BOX REPORT GENERATION
VARIABLE FREQUENCY DRIVE CONTROL
M-513
M-513
HEAT EXCHANGER CONTROL
HEATING WATER
SECONDARY PUMP CONTROL
CHILLED WATER SECONDARY PUMP CONTROL
M-514
M-514
M-514
WATER COOLED CHILLER CONTROLS
CHILLER PLANT REPORT GENERATION
KEYNOTES
M-515
M-515
WATER COOLED CHILLER CONTROLS
M-516
HEAT RECOVERY CHILLER CONTROL: HRC-A
HEAT RECOVERY CHILLER REPORT GENERATION
M-517
M-517
EXHAUST FAN CONTROL -
CONTINUOUS OPERATION: FAN-AUNIT HEATER CONTROL
AIR CURTAIN CONTROL
M-518
M-518
M-518
LIGHTING CONTROL INTERFACE
M-518
FAN COIL UNIT CONTROL: FCU-B
FAN COIL UNIT CONTROL - COOLING ONLY: FCU-C
FAN COIL UNIT CONTROL: FCU-A
M-519
M-519
M-519
CHILLER ROOM EXHAUST FAN AND MAKE-UP
AIR CONTROL DIAGRAM - FAN-B
M-520
ATRIUM SMOKE PURGE CONTROL DIAGRAM
SMOKE CONTROL PANEL DIAGRAM
M-521
M-521
SMOKE PURGE FLOW DIAGRAM
NO SCALE
M-522
MECHANICAL DEMOLITION NOTES:KEYNOTES:
MECHANICAL DEMO NOTE SHEET
COMPOSITE KEY PLAN
MD-100
MAIN LEVEL PARTIAL FLOOR PLAN -
MECHANICAL DEMO - AREA 3.1
MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 3.1
MD-130
MECHANICAL DEMO - AREA 4.1
MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 4.1
MD-131
MECHANICAL DEMO - AREA 2.1
MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 2.1
MD-132
MECHANICAL DEMO - AREA 2.2
MAIN LEVEL PARTIAL FLOOR PLAN - MECHANICAL DEMO - AREA 2.2
MD-134.1
MECHANICAL PIPING GENERAL NOTES:
PIPING NOTE SHEET
COMPOSITE KEY PLAN
MP-100
VISITOR CENTER ELEVATION
MP-100
SCALE B
SCALE B
SCALE A
PIPING - AREA 1.2
MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 1.2
MP-120
02.01.16 RFI 583
PIPING - AREA 3.1
MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 3.1
MP-134
09.22.15 RFP 034 - TAP BOX
PIPING - AREA 2.2
MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 2.2
MP-134.1
PIPING - AREA 4.1
MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 4.1
MP-135
08.05.15 ARCH LIGHT FEED PERMANENT ROUTING - ISSUED AS RFP 007
03.18.16 RFI 755
, RFP 183
PIPING - AREA 2.1
MAIN LEVEL PARTIAL FLOOR PLAN - PIPING - AREA 2.1
MP-136
07.28.15 RFP 002
MECHANICAL VENTILATION GENERAL NOTES:
VENTILATION NOTE SHEET
COMPOSITE KEY PLAN
MV-100
VISITOR CENTER ELEVATION
MV-100
SCALE B
SCALE B
VENTILATION - AREA 1.2
MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 1.2
MV-120
05.10.16 RFP 145D
07.13.16 RFP 258
abarwick Callout
OUTSIDE DIMENSIONS OF BRANCH CONNECTIONS?
abarwick Callout
CAN THESE DIFFUSERS BE MOUNTED IN SOFFIT FACE AS SHOWN ON ATTACHED A-458?
THEY ARE NOT CURRENTLY SHOWN ON OUR RCP.
VENTILATION - AREA 2.2
MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 2.2
MV-134.1
01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS
VENTILATION - AREA 3.1
MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 3.1
MV-134
08.05.15 ARCH LIGHT FEED PERMANENT ROUTING - ISSUED AS RFP 007
10.30.15 RFP 052
12.16.15 RFI 424
01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS
03.08.16 RFP 151
03.08.16 RFP 100R1
VENTILATION - AREA 4.1
MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 4.1
MV-135
08.05.15 ARCH LIGHT FEED PERMANENT ROUTING - ISSUED AS RFP 007
10.30.15 RFP 052
12.16.15 RFI 424
01.14.16 RFP 100 - EXHIBIT CEILING REVISIONS
01.20.16 RFI 426
02.23.16 RFI 424
03.08.16 RFP 151
03.08.16 RFP 100R1
03.15.16 RFP 157
03.18.16 RFP 159
03.23.16 RFP 151R1
VENTILATION - AREA 2.1
MAIN LEVEL PARTIAL FLOOR PLAN - VENTILATION - AREA 2.1
MV-136
07.28.15 RFP 002
ELECTRICAL LIGHTING SYMBOL LIST ELECTRICAL POWER SYMBOL LIST
LUMINAIRE SYMBOL KEY
ELECTRICAL SYSTEMS SYMBOL LIST
ELECTRICAL DEMOLITION SYMBOL LIST
TYPICAL ELECTRICAL MOUNTING HEIGHTS
FIRE / SMOKE BARRIER DESIGNATIONS
ELECTRICAL COVER SHEET
ELECTRICAL DEMOLITION NOTES:
ELECTRICAL INSTALLATION NOTES:
GENERAL ELECTRICAL NOTES:
ONE LINE DIAGRAM NOTES:
ELECTRICAL COVER SHEET
Museum of Westward Expansion - Consolidated Responsibility Matrix (Contract 1 Unless Otherwise Noted)
Items to be Provided and Installed Refer To Electrical
Contractor Facility AV Contractor
Exhibit AV Contractor
(Not in Contract 1)
Network Contractor
Radio Contractor
Structured Cabling Contractor
Access Control / Intrusion Detection
Contractor
Video Surveillance Field Devices
Contractor
Video Surveillance Control
Contractor Notes
Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Provides Installs Main Power Service Panel Boards
E Series Drawings x x
• Main Power Service Panel Board Circuit Breaker(s)
E Series Drawings x x
• Main Power Service Conduit
E Series Drawings x x
• Main Power Service Conductors
E Series Drawings x x
• Main Power Service Terminations
E Series Drawings x
Transformers
E Series Drawings x x
• Transformer Conduit
E Series Drawings x x
• Transformer Conductors
E Series Drawings x x
• Transformer Terminations
E Series Drawings x
Isolated Ground Wiring System E Series Drawings x x
• Isolated Ground Conduit
E Series Drawings x x
• Isolated Ground Conductors
E Series Drawings x x
• Isolated Ground Terminations
E Series Drawings x◊
Distribution Panel Boards
E Series Drawings x x
• Distribution…