1501000 J Facility Management Final 10_07_24.docx

DOCX document 348 KB Posted

Attached to
Base Operations Support Contract for Naval Air Station Fallon, Nevada Federal contract opportunity
Solicitation number
N62473-23-R-3218
Issued by
Department of the Navy Naval Facilities Engineering Command

About this file

This document appears to be the Section J Attachments for a Base Operations Support Contract (BOSC) for Naval Air Station Fallon (NASF), Nevada. It includes various attachments that provide definitions, references, facility information, assessment guidance, and other details related to the performance of facility management services at NASF and associated areas.

The key details include: a description of the contract objectives to provide quality facility management services at a fair and reasonable price; the scope covering maintenance, repair, and minor construction for facilities and infrastructure; and the use of a combination of recurring and non-recurring work. The contract will be issued by the Department of the Navy, Naval Facilities Engineering Command. The attachments provide guidance and requirements for inventory, condition assessments, maintenance management, and other facility-related processes that the contractor will be expected to follow.

View the file

Other files for this federal contract opportunity

Other files attached to Base Operations Support Contract for Naval Air Station Fallon, Nevada, newest first.
File Type Posted
Amendment 0007.pdf PDF
Amendment 0006 Open Discussions.pdf PDF
SCA WD 2015-5597 rev 26 dtd 23DEC2024.pdf PDF
DBA General Decision NV20250029 dtd 24JAN2025.pdf PDF
0200000 F Management and Admin - 10-24-2024 AMD4.docx DOCX document
0200000 C Management and Admin - 10.24.2024 AMD4.docx DOCX document
0200000 J Management and Admin - 10.24.2024 AMD4.docx DOCX document
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
0501070 C Passenger Terminal and Cargo Handling Final - 04.05.2024.docx DOCX document
0501050 C Airfield Facilities Final - 03.25.24.docx DOCX document
0501080 - Section C Final - 04.05.2024.docx DOCX document
Sheldons CBA- wages.pdf PDF
1502000 C Facility Investment Final 10_07_24.docx DOCX document
N6247323R3218 amendment 0003 RFI Answers.pdf PDF
10-01-2022 - 2026 - CBA Signed.pdf PDF
J-0200000-18 NASF Unpopulated ELINs 10.7.xlsx XLSX spreadsheet
0200000 Section C Rewrite - 03.20.2024.docx DOCX document
1700000 J BSVE Rewrite Final 10_07_24.docx DOCX document
1503010 J Custodial Rewrite Final 10_07_24.docx DOCX document
1501000 C Facility Management Final.docx DOCX document
0501040 C Ground Electronics Final - 03.25.2024.docx DOCX document
SiteVisitAgenda.docx DOCX document
23R3218 Amendment 0002.pdf PDF
N6247323R3218 NASF BOSC SOLICITATION Amendment 0001.pdf PDF
SECNAV 5512 (May 21) Fillable.pdf PDF
J-L-01 RFI Form.docx DOCX document
J-0200000-18 NASF Unpopulated ELINs.xlsx XLSX spreadsheet
SCA WD 2015-5597 rev 25 dtd 22JUL2024.pdf PDF
NASF Exhibit A-D.pdf PDF
DBA General Decision NV20240029 dtd 05JUL2024.pdf PDF
N62473-23-R-3218 NASF BOSC SOLICITATION.pdf PDF
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION J

DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS

TABLE OF CONTENTS

ATTACHMENT NUMBER
ATTACHMENT TITLE
J-1501000-01
Definitions and Acronyms
J-1501000-02
References and Technical Documents
J-1501000-03
Listing of Government Designated Customer Interface Representatives
J-1501000-04
Facility Inventory
J-1501000-05
Site Maps
J-1501000-06
Required Meetings
J-1501000-07
Asset Tagging Guidance
J-1501000-08
Assets Requiring Condition Assessment N/A
J-1501000-09
Meter Group Descriptions and Direct Condition Rating Guidance
J-1501000-10
General Direct Condition Rating Guidance
J-1501000-11
Historical Data for Project Development Requirements N/A
J-1501000-12
Historical Data for Asset Management Services N/A
J-1501000-13
Inventory of Technical Library
J-1501000-14
Work Classification Monetary Limits

ATTACHMENT J-1501000-01

DEFINITIONS AND ACRONYMS

DEFINITION
DESCRIPTION
Assessment
A general term referring to either a survey or inspection of a facility to determine condition.
Asset
A general term used to refer to an item, such as a component, system, building or facility, that is managed by an automated data management program, e.g., FCAP.
Business Management System (BMS)
A web-based tool that provides a systematic method for the management of business processes, common practices, and process quality improvements that produce and support the most efficient and effective delivery of NAVFAC’s products and services.
CONDITION BASED MAINTENANCE MANAGEMENT
A maintenance philosophy that encompasses a condition management cycle that is sustained throughout the entire life-cycle of a facility and its constituent component sections, or assets.

Defense Readiness Reporting System (DRRS) A DoD system that facilitates the measurement of and reporting on the readiness of the military forces and supporting infrastructure.

Easement
A non-possessory right, or interest, not revocable at will, to use real property of an owner for a limited purpose.
Emergency Service Call
Service calls shall be classified as “Emergency” when the associated work requires immediate action to correct or prevent loss or damage to Government property and assets, restore disrupted essential services, or eliminate life-threatening hazards to personnel or property.
Facility
A separate individual building, structure, utility system, or other real property improvement, each item of which is subject to separate reporting and recording.
Facility Condition Assessment (FCA)
A process for evaluating the condition of shore facilities for programming and budgetary purposes.
Facilities Condition Assessment Program (FCAP)
A Navy automated data management program that utilizes historical asset lifecycle data and a structured assessment process to evaluate the condition facilities and their components.
Facility Investment
A Navy Installation Management Accounting Project (IMAP) Core Business Model (CBM) function that consists of sub-functions and activities which provide facility sustainment, restoration and modernization for all Class 1 and Class 2 real property assets.
FACILITIES LIFE CYCLE
A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.
FACILITIES MAINTENANCE MANAGEMENT
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
INFRASTRUCTURE CONDITION ASSESSMENT PROGRAM
A foundational component of Condition Based Maintenance Management (CBMM). ICAP comprises three of the four CBMM quadrants: Inventory, Assessment, and Analysis.
In-house
Performed by Government employees.
Inspection
A rigorous, detailed assessment of the condition of a facility performed to generate a fundable scope and cost estimate for prioritization and funding of maintenance and repair.
Job or Work Order
An authorization for work that requires planning and estimating and has an individual line of accounting for financial and performance evaluation.
Lease
An agreement or contract by which the owner of property grants to another the exclusive rights to possess, use, and enjoy such property for a specified period of time in exchange for consideration.
LIFE-CYCLE COSTS
A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.
MAXIMO
A specially configured software version of MAXIMO®, a commercially available computerized maintenance management system (CMMS), adopted by NAVFAC for enterprise facility asset data management.
Military Construction (MILCON) Project
A project, as defined in 10 U.S.C. Section 2801, for the construction, development, conversion or extension of any facility carried out with respect to a military installation, e.g., buildings, roads, airfield pavements, or utility systems, having a funded project cost greater than the Special Project limit specified in OPNAVINST 11010.20 Series.
PROJECT MINOR
Work within Section C that is “ordered” by the Government and may require one or more of the following: planning, engineering, coordination, and multi trades. Can include simple and complex projects. The intent of this work is for upgrade of an obsolete system or component. Project Minor work is FFP not to exceed Contractor liability of $25K in Material, Other Direct Cost and Labor. Work exceeding the Contrractor;s Liability is IDIQ under Spec Item 4 of each Annex. The intent of this work is for upgrade of an obsolete system or component.
PROJECT SPECIFIC
Work not identified in Section C and is “Ordered” by the Government on an as needed basis and may require one or more of the following: planning, engineering, coordination, and multi trades. Can include simple and complex projects. The intent of this work is to meet customer requirements for services not identified within the scope of Section C. PROJECT SPECIFIC is FFP not to exceed Contractor liability of $25K in Material, Other Direct Cost and Labor. Work exceeding the Contractors Liability is IDIQ under Spec Item 4 of each Annex.
REAL PROPERTY
Land and improvements to land (i.e., facilities). It includes equipment affixed and built into the facility as an integral part of the facility (such as heating systems), but not movable equipment (e.g., plant equipment, industrial equipment, buoys).
RESTORATION
Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.
R.S. Means
A Construction Cost Data method used for Cost Estimating
SERVICE ORDER (WORK ORDER)
Any work required to return a facility, system, equipment or component to normal working condition. Service orders are minor facility problem requests or requests for facilities-related work that are too small to be planned and estimated.
Service work Orders Calls
Service calls are received by work reception center from building occupants or designated Government or Contractor representatives; are brief in scope; and do not reasonably require detailed job planning. Multiple maintenance, repair, and minor construction requirements received for the same trade in the same building or structure at the same time will be combined into one service call as long as the service call threshold is not exceeded. Service calls for associated work, which is classified, neither as “Emergency” nor “Urgent” shall be classified as “Routine”.
Special Interest Codes (SICs)
Under the Facility Investment function, SICs used for funding projects include Sustainment (ST), Restoration and Modernization (RM), New Footprint (NF), and Demolition (DE).
Special Project
A project for one or more classes of work including repair, construction, maintenance and equipment installation, as defined in OPNAVINST 11010.20, whose funded cost exceeds the regional commander’s approval limits, and, for construction, is below the current MILCON threshold for cost.
Specialized Inspection
An inspection requiring specialized expertise, e.g., underwater inspection of a pier,

performed to ascertain structural condition and operational functionality of facilities.

SUSTAINMENT
Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.
UNIFORMAT CLASSIFICATION
A standard classification of building components established by the National Institute of Standards and Technology.
Acronym
Title
AICUZ
Aircraft Installation Compatibility Use Zone
BFR
Basic Facility Requirements
BMS
Business Management System https://portal.navfac.navy.mil/pls/portal/url/page/navfac_bms
CBM
Core Business Model
CBMM
Condition Based Maintenance Management
CMMS
Computerized Maintenance Management System
COR
Contracting Officer’s Representative
DE
Demolition
DPWO
Deputy Public Works Officer
DRRS
Defense Readiness Reporting System
ELINs
Exhibit Line Item Numbers
EWR
Electronic Warfare Radar Ranges
FCA
Facility Condition Assessment
FCAP
Facilities Condition Assessment Program
FFP
Firm Fixed Price
FPD
Facility Planning Document
FRES
Facility Readiness Evaluation System
FSC
Facility Service Contract
FSCM
Facilities Service Contracts Manager
GIS
Geospatial Information System
ICAP
Infrastructure Condition Assessment Program
IDIQ
Indefinite Delivery Indefinite Quantity
IMAP
Installation Management Accounting Project
IMP
Integrated Maintenance Program
iNFADS
Internet Navy Facilities Assets Data Store
IPL
Integrated Priority List
KO
Contracting Officer
MAP
Maintenance Action Plan
MCO
Marine Corps Order
MDI
Mission Dependency Index
MILCON
Military Construction
NASF
Naval Air Station Fallon
NAVFAC
Naval Facilities Engineering Command
NF
New Footprint
PM
Preventive Maintenance
POAM
Plan of Action and Milestones
PWD
Public Works Department
PWIB
Pre-work Induction Board
PWO
Public Works Officer
PWS
Performance Work Statement
RM
Restoration and Modernization
RSIP
Regional Shore Infrastructure Plan
SICs
Special Interest Codes
SPM
Single Platform MAXIMO
ST
Sustainment
SWIB
Site Work Induction Board
ToA
Terms of Art
TPOC
Technical Point of Contact
TRC
Technical Resource Center
UEM
Utilities Energy Manager
WIB
Work Induction Board
WIS
Work Induction System

ATTACHMENT J-1501000-02

REFERENCES AND TECHNICAL DOCUMENTS

Reference
Title
OPNAVINST 11010.20
Navy Facilities Projects
OPNAVINST 11000.16
Command Responsibility for Shore Activity Land and Facilities
NAVFACINST 11010.45
Regional Planning Instruction (Site Approval Process)
DODD 6055.9
DoD Explosives Safety Management and the DoD Explosives Safety Board
UFC 2-000-5N
Facility Planning Criteria for Navy/Marine Corps Shore Installations
NAVFAC P-78
Real Property Inventory Procedures Manual
OPNAVINST 11011.10
Utilization of Navy Real Property
SECNAVINST 11011.47
Acquisition, Management, and Disposal of Real Property and Real Property Interests by the Department of the Navy

J-1501000-03 Listing of Government Designated Customer Interface Representatives

Command/Activity
Facility Description
Job Title
Telephone
NASF Contracting Officer
Building 307, PWD
KO
775-426-4450
NASF Public Works Officer (PWO)
Building 307, PWD
PWO
775-426-2712
NASF Deputy Public Works Officer (DPWO)
Building 307, PWD
DPWO
775-426-2398
Facility Support Contract Manger (FSCM)
Building 307, PWD
FSCM/COR
775-426-2971
Facility Manager
Building 307, PWD
FACILITY MANAGER
775-426-2409
Engineering
Building 307, PWD
PM&EB BRANCH HEAD
775-426-2926
Senior Performance Assessment Representative (SPAR)
Building 307, PWD
SPAR
775-426-3207

ATTACHMENT J-1501000-04

FACILITY INVENTORY

See J-1502000-03 for Inventory

ATTACHMENT J-1501000-05

SITE MAPS

Will be provided after award as a separate attachment

ATTACHMENT J-1501000-06

REQUIRED MEETINGS

Meeting Title
Location
Average Duration
Frequency
Work Induction Board
PW Conf Room, \
1 hour
Weekly
Outstanding Work Order Status Review
PW Conf Room,
2 hours
Weekly
Customer Project Status Review
CO’s Conf Room,
2 hours
Monthly

ATTACHMENT J-1501000-07

ASSET TAGGING GUIDANCE

The Contractor shall label all assets following the format below. All fields indicated align to asset data stored in MAXIMO.

· Asset tagging label must printed on a fade/water resistant material.

· Font must be Times New Roman.

· Font size no less then 18 pt.

· Tag must read, “Asset # XXXXXX”.

ATTACHMENT J-1501000-08

ASSETS REQUIRING CONDITION ASSESSMENT

ATTACHMENT J-1501000-09

METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE

B2030410 - Overhead Doors

Meter & Description
Direct Condition Rating Guidance
Condition
CR-1000- Record the condition of the Controls
GREEN: Controls function properly

AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-1000- Record the condition of the Door
GREEN: Door has minimal damage and corrosion, is square and securely fastened

AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation

CR-1000- Record the condition of the Guides
GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned

AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned

CR-1000- Record the condition of the Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating

AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

B2030901 - Hangar Doors

Meter & Description
Direct Condition Rating Guidance
Condition
CR-1000- Record the condition of the Brakes
GREEN: Brakes have minimal wear

AMBER: Brakes have noticeable wear, may exhibit unusual noise, but are still operational RED: Brakes have significant wear, excessive noise, or may not function properly

CR-1000- Record the condition of the Controls
GREEN: Controls function properly
CR-1000- Record the condition of the Door
GREEN: Door has minimal damage and corrosion, is square and securely fastened

AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation

CR-1000- Record the condition of the Guides
GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned

AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned

CR-1000- Record the condition of the Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating

RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

D1010110 - Hydraulic Elevators

Description
How to Assess & Enter Meter Value for Condition Rating (CR-1000)
Condition

Notes to Field Assessor:

*Do not select “Green(+)” unless Condition_Date = Install_Date*

· For “GREEN” may assign either G or G(-)

· For “AMBER” may assign any of A(+), A or A(-)

· For “RED” may assign any of R(+), R or R(-)

CR-1000 - Record the condition of the Elevator Assembly

GREEN:

· Car Supporting Platform/Frame has no damage, is structurally sound

· Car Operating Panel/Indicator has minimal damage and corrosion, fully operational

· Car Doors have minimal damage or wear, door operation is smooth

· Controls function properly

· Hydraulic Piston Well has minimal damage, deterioration, no cracks or leaks, fully secured

AMBER:

· Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity

· Car Operating Panel/Indicator has noticeable damage and corrosion, still operational

· Car Doors have noticeable damage or wear, doors are operational but may need adjustments

· Controls need calibrating

· Hydraulic Piston Well has noticeable damage, deterioration, but no cracks or leaks, still operational

RED:

· Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired

· Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired

· Car Doors have significant damage or corrosion, doors are operationally impaired

· Controls are damaged and/or not operational

· Hydraulic Piston Well has significant damage, deterioration, cracks or leaks, operationally impaired

D1010140 - Traction Geared Elevators

Description
How to Assess & Enter Meter Value for Condition Rating (CR-1000)
Condition

Notes to Field Assessor:

· For “GREEN” may assign either G or G(-)

CR-1000 - Record the condition of the Elevator Assembly
GREEN:

· Car Supporting Platform/Frame has no damage, is structurally sound.

· Car Operating Panel/Indicator has minimal damage and corrosion, fully operational.

· Safety Buffers have minimal deterioration or damage, fully operational.

· Motor operates properly, free of excessive noise/vibration, or overheating.

· Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure.

AMBER:

· Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity.

Car Operating Panel/Indicator has noticeable damage and corrosion, still operational.

· Safety Buffers have noticeable deterioration or damage, still operational

· Car Doors have noticeable damage or wear, doors are operational but may need adjustments.

· Controls need calibrating.

· Motor exhibits unusual noise/vibration, but still operational, may require maintenance.

· Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable.

RED:

· Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired.

· Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired.

· Safety Buffers have significant deterioration or damage, operationally impaired.

· Car Doors have significant damage or corrosion, doors are operationally impaired.

· Controls are damaged and/or not operational.

· Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired.

· Anchors/Cables/Tie Backs have noticeable damage, deterioration and/or corrosion, loosely secured or unstable, may jeopardize safety.

D1010150 - Traction Gearless Elevators

Description
How to Assess & Enter Meter Value for Condition Rating (CR-1000)
Condition

Notes to Field Assessor:

· For “GREEN” may assign either G or G(-)

CR-1000 - Record the condition of the Elevator Assembly
GREEN:

· Car Supporting Platform/Frame has no damage, is structurally sound.

· Car Operating Panel/Indicator has minimal damage and corrosion, fully operational.

· Safety Buffers have minimal deterioration or damage, fully operational.

· Car Doors have minimal damage or wear, door operation is smooth

· Controls function properly.

· Motor operates properly, free of excessive noise/vibration, or overheating

· Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure.

AMBER:

· Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity.

Car Operating Panel/Indicator has noticeable damage and corrosion, still operational.

· Safety Buffers have noticeable deterioration or damage, still operational

· Car Doors have noticeable damage or wear, doors are operational but may need adjustments.

· Controls need calibrating.

· Motor exhibits unusual noise/vibration, but still operational, may require maintenance.

· Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable.

RED:

· Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired.

· Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired.

· Safety Buffers have significant deterioration or damage, operationally impaired.

· Car Doors have significant damage or corrosion, doors are operationally impaired.

· Controls are damaged and/or not operational.

· Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired.

· Anchors/Cables/Tie Backs have noticeable damage, deterioration and/or corrosion, loosely secured or unstable, may jeopardize safety.

D1010901 – Lifts

Description
How to Assess & Enter Meter Value for Condition Rating (CR-1000)
Condition

Notes to Field Assessor:

· For “GREEN” may assign either G or G(-)

CR-1000 - Record the condition of the Lift Assembly
GREEN:

· Controls function properly

· Motor operates properly, free of excessive noise/vibration, or overheating

· Platform has little to no damage or deterioration, and is structurally sound

AMBER:

· Controls need calibrating

· Motor exhibits unusual noise/vibration, but still operational, may require maintenance

· Platform has noticeable damage or deterioration, but still structurally sound

RED:

· Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

· Platform has significant damage or deterioration, may be loose or unstable

D1020110 – Escalators

Description
How to Assess & Enter Meter Value for Condition Rating (CR-1000)
Condition

Notes to Field Assessor:

· For “GREEN” may assign either G or G(-)

CR-1000 - Record the condition of the Escalator Assembly
GREEN:

· Controls function properly

· Motor operates properly, free of excessive noise/vibration, or overheating

· Handrails have minimal damage or corrosion, and are fully secured

· Platform has little to no damage or deterioration, and is structurally sound

· Step Risers/Tread have minimal damage or deterioration, fully secured and aligned

· Comb Plates have minimal deterioration and damage, and are not loose or displaced

AMBER:

· Controls need calibrating.

· Motor exhibits unusual noise/vibration, but still operational, may require maintenance

· Handrails have noticeable damage or corrosion, slightly loose but still operational

· Platform has noticeable damage or deterioration, but still structurally sound

· Step Risers/Tread have noticeable damage or deterioration, are mostly secure and operational

· Comb Plates have noticeable deterioration and damage, but are not loose or displaced

RED:

· Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

· Comb Plates have significant deterioration and damage, may be noticeably loose, displaced, or misaligned

· Handrails have significant damage or corrosion, noticeable loose or missing

· Platform has significant damage or deterioration, may be loose or unstable

· Step Risers/Tread have significant deterioration, damage, corrosion, or are loose or misaligned

D1090902 - Cranes and Hoists

Description
How to Assess & Enter Meter Value for Condition Rating (CR-1000)
Condition

Notes to Field Assessor:

· For “GREEN” may assign either G or G(-)

CR-1000 - Record the condition of the Brakes
GREEN:

· Brakes have minimal wear Hook has minimal damage or wear, and is fully secured

· Controls function properly

· Crane Unit shows minimal signs of wear, no loose components, structurally sound, fully operational

· Guide Wheels show little to no wear or damage, are securely fastened, and fully functional

· Motor operates properly, free of excessive noise/vibration, or overheating

· Structural Frame has minimal damage and corrosion, is square and securely fastened

· Trolley Drive has minimal to no damage, operation is smooth, fully functional

CR-1000 - Record the condition of the Chains/Hooks
AMBER:

· Brakes have noticeable wear, may exhibit unusual noise, but are still operational Hook has noticeable damage or wear, but is still securely fastened Controls need calibrating

· Crane Unit shows noticeable signs of damage or wear, but no loose or missing components, and still operational

· Guide Wheels have noticeable wear, may have slight damage, but are secure and still operational

· Motor exhibits unusual noise/vibration, but still operational, may require maintenance

· Structural Frame has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety

· Trolley Drive has noticeable damage, wear, may require adjustments but is fully functional

CR-1000 - Record the condition of the Controls
RED:

· Brakes have significant wear, excessive noise, or may not function properly

· Hook has significant damage, connections not secure

· Controls are damaged and/or not operational

· Crane Unit shows significant signs of damage or wear, may have missing or loose components, comprised structural integrity, or is operationally impaired

· Guide Wheels have significant damage, may be loose, displaced, missing, or operationally impaired

· Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

· Structural Frame has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation

· Trolley Drive has significant damage or wear, operation is significantly impaired

D3020130 - Boiler, Cast Iron, Hot Water, Gas

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational

AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5365 - Record the condition of the Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion

AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes RED: Firebox has significant damage or corrosion, cracks or holes may be present

CR-5370 - Record the condition of the Flue
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational

AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5380 - Record the condition of the Fuel System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational

AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured

CR-5690 - Record the condition of the Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure

AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3020134 - Boiler, Cast Iron, Steam, Gas

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational

AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5365 - Record the condition of the Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion
CR-5520 - Record the condition of the Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational

AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5365 - Record the condition of the Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion
CR-5380 - Record the condition of the Fuel System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational

RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

CR-5690 - Record the condition of the Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure

AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3020138 - Boiler, Cast Iron, Steam, Gas/Oil

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational

AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5345 - Record the condition of the Feed Water System
GREEN: Feed Water System has no damage or leaks, fully operational

AMBER: Feed Water System has noticeable damage or corrosion, may have slight leaks but still operational RED: Feed Water System has significant damage or corrosion, noticeable leaks, and does not function properly

CR-5365 - Record the condition of the Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion
CR-5370 - Record the condition of the Flue
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational

AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3020901 - Boiler, Cast Iron, HW, Oil

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational

AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5365 - Record the condition of the Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion
CR-5370 - Record the condition of the Flue
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational

AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5380 - Record the condition of the Fuel System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational

RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

CR-5690 - Record the condition of the Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure

AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3020902 - Boiler, Cast Iron, Steam, Oil

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational

AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5365 - Record the condition of the Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion
CR-5520 - Record the condition of the Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030130 - Chiller, Reciprocating, Water Cooled

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational

AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage

AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5295 - Record the condition of the Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured

AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5305 - Record the condition of the Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage

RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5565 - Record the condition of the Receiver Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030135 - Chiller, Reciprocating, Air Cooled

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational

AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage

RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5175 - Record the condition of the Condenser Fan(s) Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating

RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5295 - Record the condition of the Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
CR-5305 - Record the condition of the Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage
CR-5520 - Record the condition of the Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5565 - Record the condition of the Receiver Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

CR-5690 - Record the condition of the Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure

AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3030140 - Chiller, Centrifugal, Water Cooled

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5110 - Record the condition of the Centrifugal Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating

RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational

AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage

RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5210 - Record the condition of the Controls/Sensors
GREEN: Controls function properly
CR-5295 - Record the condition of the Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
CR-5305 - Record the condition of the Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage
CR-5530 - Record the condition of the Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5565 - Record the condition of the Receiver Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030145 - Chiller, Gas Absorption, Water Cooled

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5000 - Record the condition of the Absorber
GREEN: Absorber has minimal damage and corrosion, but no leaks

AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired

CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational

AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage

RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5295 - Record the condition of the Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
CR-5305 - Record the condition of the Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage
CR-5430 - Record the condition of the Heat Generator
GREEN: Heating Element has little to no damage or corrosion, and is fully operational

AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, operationally impaired

CR-5520 - Record the condition of the Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5555 - Record the condition of the Receiver
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030150 - Chiller, Steam Absorption, Water Cooled

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5000 - Record the condition of the Absorber
GREEN: Absorber has minimal damage and corrosion, but no leaks

AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired

CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational

AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage

RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5295 - Record the condition of the Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
CR-5305 - Record the condition of the Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage
CR-5430 - Record the condition of the Heat Generator
GREEN: Heating Element has little to no damage or corrosion, and is fully operational

AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, operationally impaired

CR-5520 - Record the condition of the Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion

AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5555 - Record the condition of the Receiver
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure

AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030310 - Cooling Tower, Galvanized

Meter & Description
Direct Condition Rating Guidance
Condition
CR-5025 - Record the condition of the Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking

AMBER: Sump has noticeable damage or corrosion, but no leaking RED: Sump has significant damage or corrosion, and noticeable leaking, operationally impaired

CR-5280 - Record the condition of the Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional

AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional RED: Conductivity Electrodes have significant damage and corrosion, loose or missing connections, operationally impaired

CR-5325 - Record the condition of the Fan Assembly
GREEN: Fan blades are in balance and free of damage or corrosion

AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired