This document comprises fire alarm system construction drawings and technical specifications for Building 332 at Marine Corps Recruit Depot Parris Island, South Carolina, prepared as preliminary RFP design submissions dated June 30, 2026.

The project requires installation of a fully compliant Emergency Voice Alarm Communication System conforming to NFPA 72 current edition standards, integrated with the installation base-wide Mass Notification System (SIRCOM Smart Alert and Legacy Waves). Key system components include a Combined Fire Alarm Control Panel/Mass Notification System (FMCP) with auxiliary audio input capability, addressable fire detectors and combination speaker/strobe notification devices throughout three floors of the building, and remote microphone panels in designated administrative areas. The contractor must provide all equipment and labor for base-wide MNS integration, including a 9dBi omni-directional 2400MHz antenna on a rooftop antenna mast with maximum 130-foot conduit length to roof termination, RF cable with maintenance loops, lightning arrestor module, and a dedicated NEMA 4X non-metallic enclosure with surge protection. Additional requirements include a 24"x24"x1" dedicated MNS mounting board, two separate 3/4-inch EMT conduit runs with shielded audio wire to facility locations and egress areas, system programming to prioritize local microphone input and MNS messages over fire alarm notifications, fire barrier penetration sealing with fire caulk, and comprehensive performance testing with Physical Security, SPAWAR MCESS, Base Fire Department, ROICC, and contractor personnel. The contractor must furnish specific USMC MNS equipment to the Base Physical Security Office for NIWC integration, including a Sircom ISU-118 speaker unit, Comnet media converter, Altronix power supply, and Powersonic battery.

View the file

Other files

File Type Posted
Amendment 0011 PPI response.pdf PDF
Amendment 0011.pdf PDF
Amendment 0010.pdf PDF
Amendment 0009.pdf PDF
Amendment 0009 PPI Responses.pdf PDF
2501 2026.08.25 Revised Documents for PPIs.pdf PDF
2501 2026.08.25 Continuation Sheet.pdf PDF
Amendment 0008.pdf PDF
Amendment 0007.pdf PDF
_CIVIL.B332 RFP Revised.pdf PDF
Amendment 0006 PPI Responses.pdf PDF
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0005 PPI Responses.pdf PDF
Beaufort Site Visit Sheet 1245 and 1246.pdf PDF
Amendment 0004.pdf PDF
Parris Island B332 Site Visit Sheet.pdf PDF
Amendment 0003 Revised Price Proposal Schedule.pdf PDF
Amendment 0003.pdf PDF
Amendment 0002 Revised Price Proposal Schedule.pdf PDF
Amendment 0002.pdf PDF
Attachment K - PI2501M Bldg 332.pdf PDF
Attachment J6 - 18918-18954.pdf PDF
Attachment J5 - 18619-18954-ASBUILT.pdf PDF
Attachment J7 - Bldg 1244-1248 Fl-Dim-Evac.pdf PDF
Amendment 0001.pdf PDF
Attachment J2 - Drawings 1245.pdf PDF
Attachment J3 - 13943-14077Part1.pdf PDF
Attachment J1 - Drawings 1246.pdf PDF
Attachment J4 - 13943-14077Part2.pdf PDF
Attachment I - MCRD VISIT REQUEST.xlsx XLSX spreadsheet
N4008526R0187 General Requirements.pdf PDF
Attachment D - Davis-Bacon Act WD SC20260008.pdf PDF
Attachment G - Contractor Base Access Request Form Bldg 1245 and 1246.docx DOCX document
Attachment C - Price Proposal Schedule.pdf PDF
Attachment A - Drawings and Specs Bldg 1245 and 1246.pdf PDF
Attachment B - SOW Bldg 1245 and 1246.pdf PDF
Attachment F - PIEE Vendor Access Instructions.pdf PDF
Attachment E - Pre-Proposal Inquiry Log.xlsx XLSX spreadsheet
Attachment H - SECNAV 5512.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R a n g e

Refrigerator

R e fr ig e ra to r

R e fr ig e ra to r

R e fr ig e ra to r

R e fr ig e ra to r

F

F

F

F F

F

F F

FMCP

S

S S S

S S

S

S S S S S S S

S S S S S SS S S

S

F

F

F

F

DUTY DESK

DUTY BUNK

107A

LOUNGE

STOR

ISN OFFICE

TOILET

LAUNDRY

108A

KITCHEN

140A MECH

LAUNDRY

MINI MART

STORAGE

SLEEPING UNIT B

SLEEPING UNIT A

SLEEPING UNIT B

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT C

SLEEPING UNIT C

SLEEPING UNIT D

SLEEPING UNIT D

SLEEPING UNIT B

SLEEPING UNIT B

ELEC

STAIR LOBBY

STOR

JANITOR

STOR

MECH

CORRIDOR

CORRIDOR

VEST

128A

STOR

STOR

ENTRY PORCH

CORRIDOR

ENTRY

ELEC

VEST

147A

ENTRY PORCH

ENTRY

EXT BALCONY

EXT BALCONY

SB

SB SB

SB

SB

SB

SB

SB SB

SB SB SB SB

SBSB SB

SB SB

SBSB

MM x4

WP

WP

WP

WP

15 cd15 cd

15 cd

15 cd

15 cd 15 cd 15 cd 15 cd

15 cd

15 cd

15 cd

15 cd15 cd

15 cd

GENERAL SHEET NOTES:

1. FOR FIRE ALARM/MASS NOTIFICATION GENERAL NOTES AND

LEGEND, SEE SHEET FA001.

A B

C D

1 2 3 4 5

1 2 3 4 5

F ile

P ri n t

M

A

P.

STCETIHCRA

FB

BERN N.C

.NEW

CERT. NO.

UTCETIHCRA

DERET

SI

G E R

N

OI

TA

R

OP

RO

C

LAR

CAROLINANORTH

50679

E

N A V F A C DRAWING NO.

D

AS NOTED

SYM. DESCRIPTION DATE APP.

REVISIONS

E C

B A

P.W. DWG. NO.

DRAWN BY

CHECKED BY

SUPERVISOR

APPROVED DATE

ENGINEERING DIRECTOR

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

PARRIS ISLAND, S.C.

MARINE CORPS RECRUIT DEPOT

SCALE

HQMC

PROJ. NO.

SIZE

F

CODE IDENT. NO.

CONSTR. CONTR. NO.

SHEET

80091

DO N

OT U

SE F

OR

CONSTRUCTIO

N

PRELIM

IN

ARY

C U s e rs \k a ri .c ra n e

\D o c u m e n ts \2

F

IR

E k a ri .c ra n e .r v t

/1

/2

:0

:4

A

M

RFP DESIGN SUBMITTAL

FA101

REPAIR BUILDING 332

KEC

KEC

Approver

FIRE ALARM FIRST FLOOR PLAN - CONSTRUCTION

30 JUNE 2026

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

N

SCALE: 1/8" = 1'-0"

B1

FIRE ALARM FIRST FLOOR PLAN - CONSTRUCTION

1 REVISIONS 8/11/26

F F

S

S S S

S S S S S S S S S S S S S

S S S S S S S SS S S S

F

F

F

F

F

SLEEPING UNIT B

SLEEPING UNIT B

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT E

SLEEPING UNIT F

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT B

SLEEPING UNIT B

STOR

LOUNGE

LAUNDRY

MECH

MECHANICAL

ELEC

STAIR LOBBY

ELEC

CORRIDOR

CORRIDOR

VEST

229A

EXT BALCONY

STOR

JANITOR

EXT BALCONY

STOR

CORRIDOR

VEST

238A

SB SB SB SB SB SB SB SB SB SB SB SB SB

SB SB SB SB SB SB SB SBSB SB SB SB

SB

MM x2

15 cd 15 cd 15 cd

30 cd

15 cd

15 cd

30 cd

15 cd

15 cd

15 cd 15 cd

GENERAL SHEET NOTES:

1. FOR FIRE ALARM/MASS NOTIFICATION GENERAL NOTES AND

LEGEND, SEE SHEET FA001.

A B

C D

1 2 3 4 5

1 2 3 4 5 n t

M

A

P.

STCETIHCRA

FB

BERN N.C

.NEW

CERT. NO.

UTCETIHCRA

DERET

SI

G E R

N

OI

TA

R

OP

RO

C

LAR

CAROLINANORTH

50679

E

N A V F A C DRAWING NO.

D

AS NOTED

SYM. DESCRIPTION DATE APP.

REVISIONS

E C

B A

P.W. DWG. NO.

DRAWN BY

CHECKED BY

SUPERVISOR

APPROVED DATE

ENGINEERING DIRECTOR

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

PARRIS ISLAND, S.C.

MARINE CORPS RECRUIT DEPOT

SCALE

HQMC

PROJ. NO.

SIZE

F

CODE IDENT. NO.

CONSTR. CONTR. NO.

SHEET

80091

DO N

OT U

SE F

OR

CONSTRUCTIO

N

PRELIM

IN

ARY

C U s e rs \k a ri .c ra n e

\D o c u m e n ts \2

F

IR

E k a ri .c ra n e .r v t

/1

/2

:0

:4

A

M

RFP DESIGN SUBMITTAL

FA102

REPAIR BUILDING 332

KEC

KEC

Approver

FIRE ALARM SECOND FLOOR PLAN - CONSTRUCTION

30 JUNE 2026

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

N

SCALE: 1/8" = 1'-0"

B1

LIFE SAFETY SECOND FLOOR PLAN - CONSTRUCTION

1 REVISIONS 8/11/26

S

S S S

S S S S S S S S S S S S S

S S S S S S S SS S S S

S

S S S

S S S S S S S S S S S S S

S S S S S S S SS S S S

F F

F

F

F

F

F

GENERAL SHEET NOTES:

1. FOR FIRE ALARM/MASS NOTIFICATION GENERAL NOTES AND

LEGEND, SEE SHEET FA001.

SLEEPING UNIT B

SLEEPING UNIT B

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT E

SLEEPING UNIT F

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT A

SLEEPING UNIT B

SLEEPING UNIT B

STOR

STOR

CORRIDOR

CORRIDOR

MECH

LAUNDRY

STAIR LOBBY

MECH

ELEC

ELEC

LOUNGE

CORRIDOR

JANITOR

EXT BALCONY

STOR

EXT BALCONY

VEST

338A

VEST

329A

SB SB SB SB SB SB SB SB SB SB SB SB SB SB

SBSBSBSBSBSBSBSBSBSBSBSB

MM x2

WP

WP

15 cd 15 cd 15 cd

30 cd

15 cd

15 cd

15 cd

30 cd

15 cd 15 cd 15 cd

A B

C D

1 2 3 4 5

1 2 3 4 5 n t

M

A

P.

STCETIHCRA

FB

BERN N.C

.NEW

CERT. NO.

UTCETIHCRA

DERET

SI

G E R

N

OI

TA

R

OP

RO

C

LAR

CAROLINANORTH

50679

E

N A V F A C DRAWING NO.

D

AS NOTED

SYM. DESCRIPTION DATE APP.

REVISIONS

E C

B A

P.W. DWG. NO.

DRAWN BY

CHECKED BY

SUPERVISOR

APPROVED DATE

ENGINEERING DIRECTOR

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

PARRIS ISLAND, S.C.

MARINE CORPS RECRUIT DEPOT

SCALE

HQMC

PROJ. NO.

SIZE

F

CODE IDENT. NO.

CONSTR. CONTR. NO.

SHEET

80091

DO N

OT U

SE F

OR

CONSTRUCTIO

N

PRELIM

IN

ARY

C U s e rs \k a ri .c ra n e

\D o c u m e n ts \2

F

IR

E k a ri .c ra n e .r v t

/1

/2

:0

:4

A

M

RFP DESIGN SUBMITTAL

FA103

REPAIR BUILDING 332

KEC

KEC

Approver

FIRE ALARM THIRD FLOOR PLAN - CONSTRUCTION

30 JUNE 2026

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

N

1 REVISIONS 8/11/26

SCALE: 1/8" = 1'-0"

B1

FIRE ALARM THIRD FLOOR PLAN - CONSTRUCTION

MAXIMUM CONDUIT LENGTH

TO ROOF TERMINATION = 130'

8"X8"X8" PULL BOX

REMOTE

MIC

PROVIDE A NON-METALLIC 18"HX16"WX10"D NEMA 4X ENCLOSURE WITH RAISED COVER AND

PAD LOCKABLE LATCHES W/ INTERIOR MOUNTING PLATE (INTEGRA 181610HLL OR EQUAL),

CENTERED ON THE MNS MOUNTING AREA BOARD. PROVIDE 3/4" RMC WITH 3 CONDUCTORS,

12 GAUGE ELECTRICAL WIRE FROM THE ENCLOSURE TO A DEDICATED 120VAC/15A

ELECTRICAL CIRCUIT. PROVIDE A DEDICATED LOCKABLE BREAKER FROM THE SAME POWER

PANEL UTILIZED BY THE FACP. INSTALL AC SURGE PROTECTION DEVICE (120V, 15A MAX,

ISLATROL HSP-121BT1RU OR EQUAL) IN LINE WITH POWER CIRCUIT INSIDE THE LOWER LEFT

CORNER OF THE ENCLOSURE. THE AC SURGE DEVICE MUST BE WIRED IN SERIES WITH A

DUAL AC ELECTRICAL OUTLET MOUNTED INSIDE THE MNS ENCLOSURE LOCATED ABOVE THE

SURGE DEVICE ON THE BOTTOM RIGHT SIDE OF THE MNS ENCLOSURE. PROVIDE AND

CONNECT BUILDING EARTH GROUND TO THE BOTTOM LEFT CORNER OF THE BACKPLATE

INSIDE THE ENCLOSURE. SEE BREAKOUT.

PROVIDE TWO (2) 3/4-INCH ELECTRICAL METAL TUBING WITH 18 AWG SHIELDED AUDIO

WIRE FROM THE NEMA-4 ENCLOSURE TO TWO (2) DIFFERENT CENTRAL FACILITY

LOCATIONS (E.G. DUTY ROOM, ADMINISTRATION AREA, CENTRAL HALLWAY, ETC.) AT

THESE LOCATIONS TERMINATE EMT IN A FLUSH MOUNTED 4"x4"x2" EMT BOX. ENSURE

THE TWO CONDUIT/WIRING RUNS AND THE EMT FLUSH MOUNT ENCLOSURES ARE

LABELED FOR "BASE MNS USE''. CONTINUE CONDUIT/WIRING RUN TO TWO OPPOSITE

EGRESS AREAS OF THE BUILDING. TERMINATE EMT IN A FLUSH MOUNTED 4"X4"X2"

RIGID BOX TWO FEET ABOVE THE LEFT SIDE OF DOORS. LABEL FOR MNS USE. THESE

LOCATIONS WILL BE INSTALLED WITH ADDITIONAL MNS SPEAKERS.

MAY BE COMBINED INTO

ONE CONDUIT FOR

ROUTING PURPOSES

(LOCATED IN MAIN ENTRANCE)

PROVIDE 8"x8"x8" PULL BOX ABOVE/ADJACENT TO THE MNS EQUIPMENT AREA. PROVIDE 1.5" RMC FROM MNS ENCLOSURE TO THE PULL BOX AND 1.5" RMC FROM THE PULL BOX TO A POINT 4 FEET ABOVE THE APEX OF THE ROOFLINE. GROUND THE RMC MAST TO THE BUILDING GROUND. PROVIDE THE RMC IN THE MOST DIRECT VERTICAL ROUTE POSSIBLE, IF SHARP BENDS ARE REQUIRED THEN UTILIZE ADDITIONAL PULL BOXES APPROPRIATELY. TERMINATE THE TOP OF THE EXTERIOR RMC WITH A U.L. LISTED WEATHER HEAD. INSTALL 50 OHM, LMR-600 RF CABLE IN THE RMC. PROVIDE A THREE FOOT CABLE LENGTH MAINTENANCE LOOP AT BOTH ENDS OF THE CABLE ROUTE AND TERMINATE CABLE WITH A STRAIGHT MALE N-TYPE CONNECTOR; LEAVE THE RF CABLE UNTERMINATED AT THE MNS MOUNTING AREA AND CLEARLY LABEL RF CABLE FOR " BASE MNS". TEST RF CABLE FOR PROPER CONNECTIVITY. INSTALL ONE 9DBI OMNI-DIRECTIONAL ANTENNA, COM HGV-2409U OR, MOBILE MARK 0D9-2400 OR EQUAL, ON TOP OF ROOFTOP ANTENNA MAST. DIRECTIONAL ANTENNA MAY BE MOUNTED ON FACILITIES BELOW ROOFLINE IF PLACEMENT OF ANTENNA LOCATION IS PRE-APPROVED BY SPAWAR OR PHYSICAL SECURITY PERSONNEL DURING THE DESIGN STAGES. REFER ANY QUESTIONS TO PMO PHYSICAL SECURITY OFFICE OR NIWC MNS SME. (843)718-4759

MNS AND MONITORING NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

THE FIRE ALARM AND DETECTION SYSTEM IS TO BE FULLY COMPLIANT WITH THE

CURRENT EDITION OF NFPA 72 FOR AN EMERGENCY VOICE ALARM COMMUNICATION

SYSTEM. THE SYSTEM MUST INTEGRATE WITH THE INSTALLATION BASE-WIDE MASS

NOTIFICATION SYSTEM (SIRCOM SMART ALERT [SISA] AND LEGACY WAVES).

THE FMCP MUST BE CAPABLE OF ACCEPTING AN AUXILIARY LINE LEVEL AUDIO INPUT OF

1 VOLT PK-PK OR .707 VRMS.

FACP MUST BE CONFIGURED TO ACCEPT DRY CONTACT INPUT FROM THE USMC MNS

INTERFACE TO ALERT THE FIRE ALARM PANEL THAT A MNS MESSAGE IS FORTHCOMING.

THE FIRE ALARM PANEL MUST BE CONFIGURED SO THAT WHILE THIS INPUT IS ACTIVE

(CONTACT CLOSED) THE FIRE ALARM PANEL MUST ROUTE AUDIO PROVIDED BY THE MNS

INTERFACE DIRECTLY TO ALL CONNECTED FIRE ALARM SPEAKERS. THE SYSTEM MUST BE

PROGRAMMED SO THIS EXTERNAL AUDIO INPUT WILL RECEIVE PRIORITY AND OVERRIDE

ALL FIRE ALARM NOTIFICATION SO LONG AS THE INPUT IS ACTIVE. WHEN THE INPUT

GOES INACTIVE (CONTACT OPEN) THE EXTERNAL AUDIO ROUTING WILL CEASE AND THE

FIRE ALARM PANEL MUST AUTOMATICALLY RETURN TO THE PRIOR NOTIFICATION

PROGRAM THAT WAS ACTIVE BEFORE THE MNS MESSAGE. FACP LOCAL MIC HAS

PRIORITY OVER ALL ANNOUNCEMENTS. A FACP SUPERVISORY ALARM IS NOT REQUIRED

WHEN THE MNS IS ACTIVATED.

CONTRACTOR MUST PROVIDE ALL EQUIPMENT AND LABOR REQUIRED TO CONNECT THE

NEW FIRE ALARM AND DETECTION SYSTEM TO BASE WIDE AREA MNS. ALL PROGRAMMING

AND CONNECTIONS MUST BE IN ACCORDANCE WITH THE BASE STANDARDS AND

APPROVED BY THE FIRE ALARM REPORTING SYSTEM (FARS) ADMINISTRATOR.

UTILIZE COMBINATION SPEAKER/STROBE NOTIFICATION DEVICES WHENEVER POSSIBLE.

ALL NOTIFICATION DEVICES WILL BE LABELED "ALERT " FIRE MARKINGS ARE NOT USED

SINCE THIS IS A COMBINATION FIRE AND VOICE EVACUATION SYSTEM. ALL STROBES

UTILIZED MUST BE WHITE/CLEAR (THE USE OF DISPLAY SIGNS ARE NOT AUTHORIZED FOR

INSTALLATION/USE AT EGRESS POINTS OF FACILITY).

ENSURE MNS EQUIPMENT AREA IS ADJACENT TO THE FACP. DISTANCE FROM THE FACP

MUST NOT EXCEED 15 CONDUIT FEET. CLEARLY MARK FOR "BASE MNS"

THE FIRE SYSTEM CONTRACTOR IS RESPONSIBLE FOR PROVIDING SPEAKERS FOR EACH

FACILITY TO MEET ALL MASS NOTIFICATION SYSTEM INTELLIGIBILITY REQUIREMENTS IN

ACCORDANCE WITH UFC 4-021-01 AND UFC 3-600-01. ALL SPEAKERS/STROBES WILL BE

LABELED "ALERT" ALL STROBES UTILIZED MUST BE WHITE.

ON THE EXTERIOR ANTENNA MAST OF FACILITY PROVIDE ONE 9DBI OMNI-DIRECTIONAL

2400MHZ ANTENNA OR PRE-APPROVED 9DBI DIRECTIONAL 2400MHZ ANTENNA AND

ASSOCIATED IN-LINE LIGHTNING ARRESTOR MODULE AND GROUNDING OF THE ANTENNA

MAST.

PROVIDE A SINGLE REMOTE MICROPHONE PANEL LOCATED IN THE DUTY ROOM OR MAIN

ADMINISTRATIVE OFFICE AS REQUIRED BY BUILDING SIZE AND DESIGN. IF A REMOTE

MICROPHONE IS UTILIZED THEN A REMOTE MICROPHONE EXTENDER PANEL MAY BE

REQUIRED TO ALLOW FOR AN ADDITIONAL MNS AUXILIARY INPUT TO THE FACP. THIS IS

DEPENDANT ON FACP MODEL.

ALL KNOWN BUILDING STRUCTURAL FIRE BARRIER PENETRATIONS MUST BE SEALED

WITH FIRE CAULK. IF UNCONFIRMED THEN SEAL STRUCTURAL PENETRATIONS WITH FIRE

CAULK. DRESS AND SECURE ALL WIRE, CABLES, AND EQUIPMENT IN A NEAT AND

PROFESSIONAL MANNER ENSURE THE ENCLOSURE AND INSTALLATION AREA IS CLEAN

AND FREE OF ANY DEBRIS. CONNECT ALL NEWLY INSTALLED EQUIPMENT/MATERIALS AND

TEST FOR PROPER OPERATION. CONDUCT LOCAL/REMOTE DIAGNOSTICS AND

LOCAL/REMOTE AUDIO ACTIVATION. INSTALLED COMPONENTS MUST BE PERFORMANCE

TESTED BY PHYSICAL SECURITY, SPAWAR MCESS, BASE FIRE DEPARTMENT, ROICC, AND

CONTRACTOR PERSONNEL.

REFER TO SPAWAR MNS SME'S, BASE PHYSICAL SECURITY PERSONNEL, MCO 5530.14B-

PHYSICAL SECURITY PROGRAM GUIDE, AND UFC 04-021-01 MASS NOTIFICATION SYSTEMS

FOR ADDITIONAL MARINE CORPS SPECIFIC GUIDANCE.

SPAWAR/NIWC POINT OF CONTACTS:

WILLIAM FERNANDEZ (843) 218-6730

WILLIAM.J.FERNANDEZ6.CIV@US.NAVY.MIL

R.K. BIFF BROWN (843) 218-6292 / (843) 718-4759

ROBERT.K.BROWN1.CTR@US.NAVY.MIL

REMOTE MIC

EXTENDER

PANEL

(AS REQUIRED)

ALARM PRIORITY:

1. LOCAL MICROPHONE

2. MASS NOTIFICATION SYSTEM

3. FIRE ALARM

3/4" RMC 3/4" RMC

PROVIDE 4"X4"X2" EMT BOX

TO HOUSE ADDRESSABLE

MONITOR MODULE AS

REQUIRED BY FACP DESIGN

1-1/2" RMC

USMC MNS

MOUNTING

AREA AND

ENCLOSURE

TO COMMUNICATIONS ROOM

EQUIPMENT RACK

1" EMT

*FACP CONTRACTOR/GENERAL CONTRACTOR MUST FURNISH

THE FOLLOWING EQUIPMENT TO THE PMO-BASE PHYSICAL

SECURITY OFFICE: FOR NAVAL INFORMATION WARFARE

CENTER (NIWC) SECURITY INSTALLATION AND INTEGRATION.

1 EACH SIRCOM ISU-118, VHF (INDOOR SPEAKER UNIT)

1 EACH COMNET CNFE1002SAC1B-M (ETHERNET ELECTRICAL TO OPTICAL MEDIA CONVERTER)

1 EACH ALTRONIX AL300ULX (POWER SUPPLY CHARGER)

1 EACH POWERSONIC PS12120 (BATTERY)

COMBINED

FACP/MNS

(FMCP)

FACP EXTERNAL MNS

AUDIO INPUT AND

CONTACT CLOSURE

FIRE ALARM DETECTORS

AND NOTIFICATION DEVICES

FIRE ALARM REPORTING

AND MONITORING SYSTEM

ADDITIONAL SUPERVISED POWER

SUPPLY FOR PANEL OPERATION,

AUDIO AMPLIFIERS, AND STROBE

ACTIVATION AS REQUIRED, BASED

ON BUILDING DESIGN AND

OVERALL LOAD REQUIREMENTS

RADIO

TRANSMITTER

1-1/2" RMC

PROVIDE USMC MASS NOTIFICATION SYSTEM

MOUNTING BOARD. PROVIDE DEDICATED WALL SPACE

FOR A 24"X24"X1'' MOUNTING BOARD ADJACENT TO

THE FACP. ENSURE THE MOUNTING BOARD IS

CLEARLY MARKED FOR "BASE MNS". SEE NOTE NO. 6

MIC

A B

C D

1 2 3 4 5

1 2 3 4 5 n t

M

A

P.

STCETIHCRA

FB

BERN N.C

.NEW

CERT. NO.

UTCETIHCRA

DERET

SI

G E R

N

OI

TA

R

OP

RO

C

LAR

CAROLINANORTH

50679

E

N A V F A C DRAWING NO.

D

AS NOTED

SYM. DESCRIPTION DATE APP.

REVISIONS

E C

B A

P.W. DWG. NO.

DRAWN BY

CHECKED BY

SUPERVISOR

APPROVED DATE

ENGINEERING DIRECTOR

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

PARRIS ISLAND, S.C.

MARINE CORPS RECRUIT DEPOT

SCALE

HQMC

PROJ. NO.

SIZE

F

CODE IDENT. NO.

CONSTR. CONTR. NO.

SHEET

80091

DO N

OT U

SE F

OR

CONSTRUCTIO

N

PRELIM

IN

ARY

C U s e rs \k a ri .c ra n e

\D o c u m e n ts \2

F

IR

E k a ri .c ra n e .r v t

/1

/2

:0

:4

A

M

RFP DESIGN SUBMITTAL

FA502

REPAIR BUILDING 332

60038126

KEC

KEC

Approver

FIRE ALARM DETAILS

30 JUNE 2026

NOT TO SCALE

A1

FIRE ALARM/MASS NOTIFICATION SYSTEM BASE-WIDE INTERFACE

1 REVISIONS 8/11/26

Sheets
FA101 - FIRE ALARM FIRST FLOOR PLAN - CONSTRUCTION
FA102 - FIRE ALARM SECOND FLOOR PLAN - CONSTRUCTION
FA103 - FIRE ALARM THIRD FLOOR PLAN - CONSTRUCTION
FA502 - FIRE ALARM DETAILS

File details come from the government source that posted it. Updated .