Amendment 0008 - D15 - ITG A2L Refrigerants For Navy and MC Facilities.pdf

PDF 182 KB Posted

Attached to
DESIGN-BUILD (DB) BARRACKS INITIATIVE (PACKAGE #1), MARINE CORPS AIR STATION (MCAS) CHERRY POINT, NC
Solicitation number
N4008526R0053
Issued by

About this file

This is an Interim Technical Guidance (ITG) memorandum from the Department of the Navy, Naval Facilities Engineering Systems Command, issued April 30, 2026, regarding the adoption of Class A2L refrigerants in HVAC systems for Navy and Marine Corps facilities.

The ITG supersedes existing restrictive language in Unified Facilities Criteria (UFC) 3-401-01 (Mechanical Engineering) and UFC 4-721-01 (Permanent Party Unaccompanied Housing) that previously prohibited Class A2L refrigerants in occupied spaces. The guidance permits all refrigerant classifications per ASHRAE Standard 34, including Class A2L variants (R-454B, R-32, R-454A), when HVAC systems comply with the International Mechanical Code and ASHRAE Standard 15. Class A2L refrigerants are classified as lower toxicity with mild flammability and limited burning velocity. The ITG applies effective immediately to all new construction, renovation, repair, and equipment replacement projects across all Navy and Marine Corps facilities and funding sources, superseding comparable restrictive language in other UFCs. Compliance with adopted building codes and industry standards provides adequate safety through factory-integrated controls, improved leak detection, and enhanced ventilation features in commercially available, UL-listed equipment.

Implementation requirements direct Naval Facilities Engineering System Commands to exclude A2L systems during planning and preliminary design phases, immediately incorporate revised language into project design criteria upon design start, evaluate pre-award amendments between design release and contract award, authorize contractor-proposed substitutions during construction subject to standard approval processes, update specifications and standard designs, implement Marine Corps standard barracks designs using PTAC systems with Class A2L refrigerants, permit A2L systems in existing facilities and equipment replacements when code-compliant, and provide targeted training to mechanical engineering staff on A2L design considerations including charge minimization and leak reduction strategies.

View the file

Other files

File Type Posted
N4008526R0053 Site Visit Log.pdf PDF
Amendment 0010.pdf PDF
AMENDMENT 0009.pdf PDF
Amendment 0008 - C8 - Cherry Point Site 1 Sanitary Plan.pdf PDF
Amendment 0008 PPI Responses.pdf PDF
Amendment 0008 - D16 - Ladder 251 - Pierce Turning Performance Analysis.pdf PDF
AMENDMENT 0008.pdf PDF
Amendment 0008 - C9 - Storm Drain Replacement Exhibit.pdf PDF
AMENDMENT 0007.pdf PDF
Amendment 0007 PPI Responses.pdf PDF
AMENDMENT 0006.pdf PDF
Amendment 0006 PPI Responses.pdf PDF
AMENDMENT 0005.pdf PDF
Amendment 0005 D14 - Excerpt from Cherry Point Area Development Plan.pdf PDF
Amendment 0005 B2 Hazardous Materials Report Bldgs 4201 4294 4295 4296 4312.pdf PDF
Amendment 0005 Wage Determination NC20260018 05 18 26.pdf PDF
AMENDMENT 0004.pdf PDF
AMENDMENT 0003.pdf PDF
Attach H - MCASCP Sites Subsurface Soil Geotech Report.pdf PDF
CJA ML-25-03 Class FRCS Cherry Point - Redacted.pdf PDF
Attachment F - Small Business Participation Commitment Document (SBPCD).docx DOCX document
Attachment I - Price Proposal Schedule.xlsx XLSX spreadsheet
Attachment H - 1895345 MCAS CP DBRFP VOL3of4.pdf PDF
Attachment H - 1895345 MCAS CP DBRFP VOL4of4.pdf PDF
AMENDMENT 0002.pdf PDF
Attachment H - 1895345 MCAS CP DBRFP VOL2of4.pdf PDF
Attachment H - 1895345 MCAS CP DBRFP VOL1of4.pdf PDF
Attachment E - Historical Small Business Utilization.docx DOCX document
Attachment G - SBSP.docx DOCX document
AMENDMENT 0001 Pre-Proposal Inquiries.pdf PDF
AMENDMENT 0001.pdf PDF
AMENDMENT 0001 Attachment C - Experience Project Data Sheet.docx DOCX document
Attachment B - PIEE Vendor Access Instructions.pdf PDF
Attachment C - Construction and Design Experience Project Data Sheet.docx DOCX document
N4008526R0053.pdf PDF
Attachment A - Pre-Proposal Inquiry Log Template.xlsx XLSX spreadsheet
Attachment D - Past Performance Questionnaire.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE NAVY

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

1322 PATTERSON AVENUE SE SUITE 1000

WASHINGTON NAVY YARD DC 20374-5065

11000

CHENG/090

30 April 2026

From: Chief Engineer, Naval Facilities Engineering Systems Command

Subj: INTERIM TECHNICAL GUIDANCE - ALIGNING TO INDUSTRY STANDARDS FOR

CLASS A2L REFRIGERANTS

Ref: (a) Unified Facilities Criteria (UFC) 3-401-01, Mechanical Engineering, Change 1

(b) UFC 4-721-01, Permanent Party Unaccompanied Housing, Change 1

(c) UFC 1-200-01, DoD Building Code, Change 4

(d) International Mechanical Code® (IMC), 2024 Edition

(e) American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE)

Standard 15-2024, Safety Standard for Refrigeration Systems

(f) ASHRAE Standard 34-2024, Designation and Safety Classification of Refrigerants

(g) National Defense Authorization Act (NDAA) FY24, Public Law 118-31, Section 2831

(h) NDAA FY22, Public Law 117-81, Section 2842

(i) Federal Register, Vol. 90, No. 114, Monday, June 16, 2025, Page 25249

(j) MCICOM Letter, Commander, Marine Corps Installations Command to Commander, Naval Facilities Engineering Systems Command, Subj: U.S. Marine Corps Design and Code Standards, dated 13 Apr 2026

Encl: (1) UFC Language Revisions for Class A2L Refrigerants

1. Purpose. To align Department of the Navy and Marine Corps facility criteria with current industry standards and building codes by removing UFC restrictions on the use of Class A2L refrigerants in Heating, Ventilation, and Air Conditioning (HVAC) systems as described in this Interim Technical Guidance (ITG). This ITG addresses commercial equipment and refrigerant availability constraints and enables adoption of industry-standard commercial systems.

2. Applicability. This ITG is effective until superseded or cancelled and applies to all new construction and existing Navy and Marine Corps facilities, including renovation, repair, and equipment replacement projects, for all facility types, project phases, and funding sources. Effective immediately, this ITG supersedes references (a), paragraph 2-5.2, and (b), paragraph 3-12, and similar restrictive language in other UFCs that restrict Class A2L refrigerants in occupied spaces beyond the requirements of adopted building codes, including as specified in references (c) through (f).

3. Background. Current UFC language in references (a), paragraph 2-5.2, and (b), paragraph 3- 12, restricts the use of Class A2L refrigerants in occupied spaces by requiring refrigerant-containing components, such as piping and heat exchangers, to be located in unoccupied mechanical rooms or exterior locations. These provisions are not aligned with current building code requirements and industry standards. The HVAC industry has transitioned to A2L refrigerants (e.g. R-454B, R-32, and R-454A) as standard alternatives to R-410A.

Modern A2L refrigerant systems are widely available as UL-listed commercial products

Subj: ALIGNING TO INDUSTRY STANDARDS FOR CLASS A2L REFRIGERANTS meeting current building codes and industry standards. Current UFC restrictions necessitate the use of non-A2L alternatives. These alternatives often entail higher life cycle costs and limited maintenance support, particularly for Variable Refrigerant Flow (VRF) and modern packaged HVAC systems, significantly constraining design flexibility. This ITG removes these restrictions while maintaining safety through compliance with adopted building codes and industry standards.

4. Discussion.

a. Refrigerant Safety and Code Compliance. Class A2L refrigerants per reference (f) are classified as lower toxicity (A) and lower flammability (2L mildly flammable with limited burning velocity). A2L refrigerants include R-454B and R-32, among others, which maintain comparable or superior performance to traditional refrigerants such as R-410A. References (d) and (e) establish the applicable safety requirements for A2L refrigerants.

b. Equipment Availability and Industry Standards. VRF systems and packaged and split systems utilize A2L refrigerants. These systems incorporate advancements in technology including factory-integrated safety controls, improved leak detection, and enhanced ventilation features that address the underlying safety concerns driving current UFC language restricting use of A2L refrigerants. Commercially available, UL-listed A2L equipment provides proven, code-compliant solutions with improved efficiency and standardized maintenance support.

c. Legal and Statutory Considerations. Reference (g), Section 2831, establishes uniform design standards for covered military unaccompanied housing. The statutory no-waiver provision in § 2831(c)(2) applies exclusively to minimum floor area requirements under 10 U.S.C. § 2856(b)(1). Removal of A2L refrigerant restrictions does not violate this provision and does not affect minimum floor area requirements.

Reference (h) requires Federal Register publication for changes affecting VRF systems, which was completed by reference (i). Removing A2L restrictions aligns with previously published UFC guidance and the NDAA intent to prevent undue restrictions on specific technologies without prior public review.

d. Design and Safety Requirements. HVAC systems using Class A2L refrigerants shall comply with references (d) and (e), including refrigerant charge limits, refrigerant detection and mechanical ventilation (where applicable), equipment and installation provisions, and system labeling. HVAC equipment, including packaged systems using Class A2L refrigerants, shall be listed and labeled in accordance with applicable UL standards and installed in accordance with the listing and ly factory-assembled, tested, and listed as a complete system with integrated safety controls for refrigerant detection, mitigation, and ignition source management, as required by applicable standards. Designers shall follow standard code compliance processes and document compliance in design submittals. Required safety systems shall be commissioned and tested prior to system acceptance.

5. Action. All Naval Facilities Engineering System Commands will implement the requirements of Enclosure (1) for HVAC systems as follows:

a. Planning and Preliminary Design. Do not exclude HVAC systems using Class A2L refrigerants from consideration when developing planning and preliminary design deliverables including project scope, basis of design documents, and cost estimates.

b. Design Phase.

i. After Design Start and prior to Design Release: Immediately incorporate Enclosure (1) language revisions into project design criteria and specifications.

ii. Between Design Release and Contract Award: Evaluate the impacts and make a determination regarding issuance of a pre-award amendment to incorporate Enclosure (1) language revisions, considering equipment availability, cost, schedule, energy efficiency, and life cycle costs.

c. Construction Phase. After contract award, contractor-proposed substitutions to Class A2L refrigerant systems are authorized subject to standard substitution approval processes. Substitutions must demonstrate equivalent or superior performance, compliance with references (d) and (e), and inclusion of all code-required safety systems.

d. Specifications and Standard Designs. Update UFGS specifications, standard facility designs, and design-build request for proposal packages to reflect Enclosure (1) language revisions. Remove or revise language that excludes or restricts Class A2L refrigerants beyond adopted code requirements.

e. Marine Corps Standard Designs. Implement the standard barracks design identified in reference (j), enclosure (2), for all Marine Corps unaccompanied housing new construction and repair by replacement projects. This standard design is based on Packaged Terminal Air Conditioner (PTAC) systems with Class A2L refrigerants with all code-required safety systems.

f. Existing Facilities and Equipment Replacement. For FSRM projects and equipment replacement in existing facilities, HVAC systems using Class A2L refrigerants are permitted when code compliant, including compliance with references (d) and (e).

Evaluate existing spaces for accommodation of required safety systems as described herein.

g. Design Staff Training. Mechanical Engineering Technical Discipline Leads (TDL), in coordination with PDC4 Design Directors, shall implement targeted training on A2L refrigerants and associated design considerations, including refrigerant charge minimization, leak reduction strategies, system selection, and applicable code requirements. Training shall be provided to the design community of practice to support consistent implementation of this ITG.

6. Point of Contact. For clarification or additional information related to A2L refrigerant systems, please contact the Mechanical Engineering (TDL), Mr. Stephen Ericson, P.E. at

(757) 322-4242 or Stephen.C.Ericson3.civ@us.navy.mil.

S. KEITH HAMILTON, P.E.

Chief Engineer and Assistant Commander for Planning, Design and Construction

Copy to:

NAVFAC Atlantic NAVFAC Pacific NAVFAC Mid-Atlantic NAVFAC Southeast NAVFAC Washington

NAVFAC EURAFCENT

NAVFAC Northwest NAVFAC Southwest NAVFAC Far East NAVFAC Hawaii NAVFAC Marianas

OPNAV N4

CNIC N4

MCICOM GF

DASN (I&F)

ENCLOSURE (1)

UFC LANGUAGE REVISIONS FOR CLASS A2L REFRIGERANTS

UFC 3-401-01 MECHANICAL ENGINEERING

Current Language (Delete):

2-5.2 \1\ Flammability Classification Restriction. /1/ \1\ Comply with ASHRAE Standard 15. Distribution and use of ASHRAE Standard 34 flammability classified refrigerants of 2L and higher refrigerants is limited to non-occupied machine or mechanical rooms, complying with ASHRAE Standard 15, or to the exterior of the building.

Such refrigerants are also permitted in non-occupied rooms (example: telecommunication rooms) with the following features:

building exterior access only perimeter walls continuous from exterior wall to exterior wall or adjacent interior partition, or combination thereof perimeter walls continuous from finished floor to roof deck or floor deck above perimeter walls continuous through all concealed spaces including those above ceiling no openings or transfer paths to adjacent occupied spaces /1/

New Paragraph (Effective Immediately):

[X-X] REFRIGERANT CLASSIFICATION AND SELECTION. All refrigerant classifications per ASHRAE Standard 34, including Class A1, A2L, and other approved classifications, are permitted when HVAC systems comply with the International Mechanical Code and ASHRAE Standard 15. HVAC systems using Class A2L refrigerants shall comply with applicable UFC criteria, including UFC 3-410- 01, and ASHRAE Standard 15 requirements for refrigerant detection and mechanical ventilation (where required), charge limit compliance, and other safeguards required by adopted codes.

UFC 4-721-01 PERMANENT PARTY UNACCOMPANIED HOUSING

Current Language (Delete):

3-12 HEATING, VENTILATION, AND AIR CONDITIONING (HVAC). HVAC systems using Class A2L (flammable) refrigerants must keep all refrigerant lines and containment vessels (i.e. heat exchangers) exterior to the occupied spaces.