This document is a Room Requirements specification for the JFCNF (Joint Force Command Network Facility) Interim Modular Facility located at NAVSUPPACT Hampton Roads, Norfolk, Virginia, Contract Number 1810892. It outlines detailed architectural and operational requirements for multiple room types across the facility, organized by room classification categories.
The specification covers approximately 17 distinct room types, ranging from private offices (medium and large) to operational spaces including a Watch Floor accommodating 34 occupants, training rooms, shared offices, and open office areas. Each room requirement includes space characteristics (dimensions, ceiling height, acoustics rating), detailed Uniformat specifications for construction elements (windows, doors, finishes, HVAC, fire protection, electrical service, and lighting), and FF&E (Furniture, Fixtures, and Equipment) coordination requirements. Specialized spaces include an Intel Vault with high-security mechanical locks and NATO-classified material storage requirements, multiple conference rooms ranging from small (20 persons) to medium (24 persons) with VTC capabilities, breakout rooms, briefing rooms, interview rooms, and flex spaces designed for operational flexibility. All rooms require Category 6 cabling, classified fiber optic drops, STP cabling, and audiovisual equipment infrastructure per UFC standards (UFC 3-520-01 for electrical, UFC 3-530-01 for lighting). Security compliance ranges from Class I to Class II requirements. FF&E and AV equipment are noted as separately funded bid options to the construction contract, with infrastructure to support all equipment included in the construction scope. The specification mandates coordination with the Activity during Concept Design Workshops for final FF&E determination based on in-depth operational interviews.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JFCNF INTERIM MODULAR FACILITY
NAVSUPPACT Hampton Roads, Norfolk, Virginia 1810892
5.0 ROOM REQUIREMENTS
1.2 PRIVATE OFFICE - MEDIUM
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 10'-0" W x 12'-0" D (121 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 45
Access: Keyed Lockset and Access Control - Comply with Class I security requirements.
Number of Occupants: 1
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.A Windows - - Adjacent to exterior insulated window, ATFP compliant.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C103003 Marker Boards 1 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301003.B Gypsum Wallboard
Finishes 1 - Provide accent painted GWB wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
Private office for Assistant Chief of Staff (ACOS) and NCIA Office.
Room Data Sheet applies to Room Number(s): 146, 158, 166, 206, 219, 229, 233
Where space is located along an exterior wall, provide windows. Place telecom outlets to coordinate with furniture layouts.
Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide 72" x 114" L-shaped plastic laminate height adjustable desk with full modesty panel on front desk, no modesty panel on wall, furniture mounted overheads, tackable/magnetic panel, wardrobe, and filing. Provide task chair. Provide (2) wood leg visitor chairs with glides.
PART 3 - CHAPTER 5 - Room Requirement 1.2 - Page 3
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet -
Unclassified 2 -
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified 2 -
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified 2 -
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
E102009.A Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plate for local computer and a local CATV or IPTV connection.
E201002.A Window Treatments - - Provide light filtering roller shades at exterior windows.
PART 3 - CHAPTER 5 - Room Requirement 1.2 - Page 4
5.0 ROOM REQUIREMENTS
1.3 PRIVATE OFFICE - LARGE
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 12'-0" W x 13'-6" D (161 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 45
Access: Keyed Lockset and Access Control - Comply with Class I security requirements.
Number of Occupants: 1
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.A Windows - - Adjacent to exterior insulated window, ATFP compliant.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C103003 Marker Boards 1 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301003.B Gypsum Wallboard
Finishes 1 - Provide accent painted GWB wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
Private office for Deputy Chief of Staff (DCOS).
Room Data Sheet applies to Room Number(s): 143, 157
Where space is located along an exterior wall, provide windows. Place telecom outlets to coordinate with furniture layouts.
Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide 72" x 114" L-shaped plastic laminate height adjustable desk with full modesty panel on front desk, no modesty panel on wall, furniture mounted overheads, tackable/magnetic panel, wardrobe, and filing. Provide task chair. Provide (2) wood leg visitor chairs with glides. Provide meeting table with (2) wood leg visitor chairs with casters.
PART 3 - CHAPTER 5 - Room Requirement 1.3 - Page 5
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet -
Unclassified 2 -
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified 2 -
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified 2 -
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
E102009.A Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plate for local computer and a local CATV or IPTV connection.
PART 3 - CHAPTER 5 - Room Requirement 1.3 - Page 6
5.0 ROOM REQUIREMENTS
1.4 TRAINING ROOM
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 18'-4" W x 9'-6" D (160 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 45
Access: Keyed Lockset and Access Control - Comply with Class II security requirements.
Number of Occupants: 2
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.B Windows 1 - No windows.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C102002.A Glazed Interior Doors 1 3' W x 7' H Provide a solid core wood door with vision panel.
C103003 Marker Boards 1 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301003.B Gypsum Wallboard
Finishes 1 - Provide accent painted GWB wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
Room for staff training purpose, adjacent to the JOC watchfloor. Designed to utilize furniture system components that delineate space and provide visual privacy.
Room Data Sheet applies to Room Number(s): 124
Provide location of telecom outlets to allow flexibility in the layout and utilization of this space for alternative training as required for number of occupants. Place telecom outlets to coordinate with furniture layouts. Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide modular systems furniture with height adjustable desk, wardrobe, and box/file storage for each occupant.
Provide cubicle wall height of 50" (+/- 3") with gallery panels where power is not required. Provide (1) task chair for each occupant. Provide lateral file(s) where space permits.
PART 3 - CHAPTER 5 - Room Requirement 1.4 - Page 7
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet -
Unclassified 3 -
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified 3 -
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified 3 -
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
E102009.B Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plates for local computers and a local CATV or IPTV connection.
PART 3 - CHAPTER 5 - Room Requirement 1.4 - Page 8
5.0 ROOM REQUIREMENTS
1.5 WATCH FLOOR
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 36'-0" x 47'-0" (1647 sq.ft min)
Minimum Ceiling Height: 14'-0" AFF
Acoustics: STC 50
Access: Keyed Lockset and Access Control - Comply with Class II security requirements.
Number of Occupants: 34
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.B Windows - - No windows.
B203001.A Exterior Doors 2 3' W x 7' H Exterior hollow metal door and frame.
B203008.A Exterior Door Hardware 2 - Provide exit non-keyed hardware with emergency exit device.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C102001.D Interior Doors 1 6' W x 7' H Provide solid core wood double doors.
C102007.A Interior Door Hardware 2 - Provide office locksets.
C103003 Marker Boards 4 36" W x 48" D Provide markerboard(s).
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301006 Acoustical Panels
Adhered to Walls 1 -
Provide acoustical and tackable fabric wrapped panels on longest wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
The Watch Floor must remain column free. Provide location of telecom outlets to allow flexibility in the layout and utilization of this space for alternative training purposes as required for number of occupants. Additional telecom outlets will be provided every 4-6' along perimeter of room. Provide 2 meters of additional cable coiled above ceiling for each drop for future moves.
Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide (34) 24" x 72" workstations and 34 task chairs on casters.
Located on the first floor adjacent to DCOS. Operational room with individual consoles oriented towards video wall with other operational and adminisrative spaces with direct access to the space.
Room Data Sheet applies to Room Number(s): 128
PART 3 - CHAPTER 5 - Room Requirement 1.5 - Page 9
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet -
Unclassified
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
D503005.A Security Systems - - Provide a duress alarm.
E102009.C Audiovisual Equipment - As Required
Provide large video wall surface and structure, large screen displays with in wall mounts, multiple digital signal encoders for signal distribution, room audio playback, room audio voice lift, content management solution, and multiple local CATV or
IPTV connections. Provide a collaboration capable system.
Allow shared content management with room adjacent private offices.
PART 3 - CHAPTER 5 - Room Requirement 1.5 - Page 10
5.0 ROOM REQUIREMENTS
1.6 SHARED OFFICE
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: Varies, refer to plan
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 45
Access: Keyed Lockset and Access Control - Comply with Class I or II security requirements as required.
Number of Occupants: Varies, refer to plan for occupants. Ranges from 2 to 4.
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.A Windows - - Adjacent to exterior insulated window, ATFP compliant.
Code Description Qty Size Specifc Requirements
C102007.A Interior Door Hardware 1 - Provide office locksets.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C103003 Marker Boards 1 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
Shared office for 2 to 4 people with open office style workstations.
Room Data Sheet applies to Room Number(s): 133, 159, 218, 241, 242, 243, 244, 245, 246, 247, 248, 249
Where spaces are along exterior walls, provide windows, except for room 133 - no windows. Share Offices are to remain column free. Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide modular systems furniture with height adjustable desk, wardrobe, and box/file storage for each occupant.
Provide cubicle wall height of 50" (+/- 3") with gallery panels where power is not required. Provide (1) task chair for each occupant. Provide lateral file(s) where space permits.
PART 3 - CHAPTER 5 - Room Requirement 1.6 - Page 11
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet -
Unclassified
1 per Work
Station
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified
1 per Work
Station
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified
1 per Work
Station
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
E102009.B Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plates for local computers and a local CATV or IPTV connection.
PART 3 - CHAPTER 5 - Room Requirement 1.6 - Page 12
5.0 ROOM REQUIREMENTS
1.7 OPEN OFFICE
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: Varies, refer to plan
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 45
Access: Keyed Lockset and Access Control - Door hardware must be compliant with security level (Class I or II).
Number of Occupants: Varies, refer to plan for occupants.
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.A Windows - - Adjacent to exterior insulated window, ATFP compliant.
C102007.A Interior Door Hardware 2 - Provide office locksets.
C102002.A Glazed Interior Doors 2 - Provide a solid core wood door with vision panel.
B203008.A Exterior Door Hardware 1 - Provide exit non-keyed hardware with emergency exit device.
B203001.A Exterior Doors 1 3' W x 7' H Exterior hollow metal door and frame.
C103003 Marker Boards 1 per 10 occupants 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
Open office workspace with printing areas and collaboration areas. A central gathering area within open office spaces to allow short briefings and discussion. A collaborative work space is allocated at 16 NSF/PN (1.5 SM/PN) with a table capable of seating four (4) to eight (8). Refer to floor plan and department program requirements for each divisions collaborative work space.
Room Data Sheet applies to Room Number(s): 141, 144, 154, 165, 203, 208, 228, 231, 237
Where spaces are located on the first floor provide exterior doors and hardware. Where office spaces are larger and required by code to have additional doors, provide to meet code requirements. A minimum of two (2) interior doors for each open office is required. Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide modular systems furniture with height adjustable desk, wardrobe, and box/file storage for each occupant.
Provide cubicle wall height of 50" (+/- 3") with gallery panels where power is not required. Provide (1) task chair for each occupant. Provide lateral file(s) where space permits. Provide (1) rectangular collaboration table with (5-9) chairs.
PART 3 - CHAPTER 5 - Room Requirement 1.7 - Page 13
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet -
Unclassified 1 per Work Area
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified 1 per Work Area
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified 1 per Work Area
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
D503001.A Work Area Outlet -
Unclassified
1 per Print
Station
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified
1 per Print
Station
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
E102009.D Audiovisual Equipment - As Required
Provide multi flat screen displays with in wall mounts. Provide signall plates for local computers. Provide a collaboration capable solution.
PART 3 - CHAPTER 5 - Room Requirement 1.7 - Page 14
5.0 ROOM REQUIREMENTS
1.8 INTEL VAULT
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 12'-0" W x 10'-0" D (121 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 50
Access: High security mechanical lock - Door hardware must be compliant with security level Class II.
Number of Occupants: 1
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.B Windows - - No windows.
C102007.C Vault Door Hardware 1 - Provide high security lock with electrical strike, high security door contact, request to exit, and mechanical lock.
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C3010 CMU Wall Finish - - Painted CMU.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C3030 / C3040
Ceiling Finishes Interior
Coatings and Special
Finishes
- - Paint exposed structure.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
Access directly to the EMB.
Room Data Sheet applies to Room Number(s): 147
Interior walls to be a minimum of 6 inches (15cm) thick, CMU or concrete with minimum furring of 2-1/2" metal stud wall and
5/8" GWB. Space requires man bars for opening greater than 6 inches (15cm). Room to follow AD070-001 - Storage of NATO calssified material 4. Strong-rooms and vaults requirements. Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide 72" x 114" L-shaped plastic laminate height adjustable desk with full modesty panel on front desk, no modesty panel on wall, furniture mounted overheads, tackable/magnetic panel, wardrobe, and filing. Provide task chair. Provide (2) wood leg visitor chairs with glides.
PART 3 - CHAPTER 5 - Room Requirement 1.8 - Page 15
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
E101005 Security and Vault
Equipment 1 36" x 80" Provide steel high security door with tamper proof hinges.
E102009.B Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plates for local computers and a local CATV or IPTV
PART 3 - CHAPTER 5 - Room Requirement 1.8 - Page 16
5.0 ROOM REQUIREMENTS
2.1 BREAKOUT ROOM - SMALL
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 8'-0" x 9'-0" (72 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 50
Access: Keyed Lockset and Access Control
Number of Occupants: Seating for 6 PN
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.B Windows - - No windows.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C103003 Marker Boards 1 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301003.B Gypsum Wallboard
Finishes 1 - Provide accent painted GWB wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
Small breakout room adjacent to the JOC.
Room Data Sheet applies to Room Number(s): 130, 131, 132
Spaces must comply with Class II security requirements. Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide 36" W x 72" D rectangular table with six (6) conference chairs on casters. Provide electrical and data in center of conference table. Provide a waste receptacle.
PART 3 - CHAPTER 5 - Room Requirement 2.1 - Page 19
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet 2 - Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
D503005.A Electronic Security
Systems
- As Required
Card Reader, IDS, MD. IAW with UFC 4-021-02 and DoDM
5200.01
E102009.E Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plate for local computer and a local CATV or IPTV connection. Audio Playback . Shared content management with watch floor.
PART 3 - CHAPTER 5 - Room Requirement 2.1 - Page 20
5.0 ROOM REQUIREMENTS
2.2 BREAKOUT ROOM - MEDIUM
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 16'-6" W x 13'-0" D (215 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 50
Access: Keyed Lockset and Access Control
Number of Occupants: Seating for 8 PN
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.A Windows - - Adjacent to exterior insulated window, ATFP compliant.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C103003 Marker Boards 2 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301003.B Gypsum Wallboard
Finishes 1 - Provide accent painted GWB wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
Medium breakout room adjacent to the J7.
Room Data Sheet applies to Room Number(s): 224, 234, 235, 236
Spaces must comply with Class I security requirements. Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide 36" W x 84" D rectangular table with eight (8) conference chairs on casters. Provide electrical and data in center of conference table. Provide a waste receptacle.
PART 3 - CHAPTER 5 - Room Requirement 2.2 - Page 21
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet -
Unclassified 10 -
Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified 10 -
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified 10 -
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
D503005.A Security Systems - - Provide a duress alarm.
E102009.F Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plate for local computer and a local CATV or IPTV connection. Audio Playback . Collaboration capabilities.
E201002.B Window Treatments - - Provide double roller shade with both light filtering and black out applications.
PART 3 - CHAPTER 5 - Room Requirement 2.2 - Page 22
5.0 ROOM REQUIREMENTS
2.4 BRIEFING ROOM
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 13'-7 1/2" W x 16'-6" D (431 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 50
Access: Keyed Lockset and Access Control
Number of Occupants: Seating for 12 PN
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.B Windows - - No windows.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C103003 Marker Boards 3 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301003.B Gypsum Wallboard
Finishes 1 - Provide accent painted GWB wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
Space for media conference room.
Room Data Sheet applies to Room Number(s): 115
The briefing room requires VTC capabilities and monitor. Space must comply with Class II security requirements. Space must be column free, open and unobstructed. Povide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide (4) 36" W x 72" D nesting rectangular tables with twelve (12) nesting chairs on casters. Provide electrical and data in center of conference table. Provide waste receptable.
PART 3 - CHAPTER 5 - Room Requirement 2.4 - Page 25
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet 14 - Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.B Work Area Outlet 14 -
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.C Work Area Outlet -
Classified As Required
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required - Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified As Required
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
D503005.A Electronic Security - As Required Card Reader, IDS, MD. IAW with UFC 4-021-02 and DoDM
5200.01
E102009.H Audiovisual Equipment - As Required
Provide Medium Video wall + structure. Several in room confidance monitors. In-wall mounts. Encoders for didtribution. Multible PTZ Cameras, VTC base unit. Room audio playback and voice lift. Content management solution with collaboration capabilities. Credenza for equipment housing.
Message signs and Local CATV or IPTV Connection.
PART 3 - CHAPTER 5 - Room Requirement 2.4 - Page 26
5.0 ROOM REQUIREMENTS
2.5 COORDINATION ROOM
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 13'-6" W x 12'-0" D (161 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 50
Access: Keyed Lockset and Access Control
Number of Occupants: Seating for 8 PN
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.B Windows - - No windows.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C103003 Marker Boards 2 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301006 Acoustical Panels
Adhered to Walls 1 -
Provide acoustical and tackable fabric wrapped panels on longest wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
A separate, small conference room with US network infrastructure capability, room to be adjacent to the JOC, is required.
Room Data Sheet applies to Room Number(s): 128A
Space must comply with Class II security requirements. Provide wireless drops as required for coverage.
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide (2) 72"W x 36"D rectangular nesting tables. Provide eight (8) nesting or stacking chairs with casters. Provide waste receptable.
PART 3 - CHAPTER 5 - Room Requirement 2.5 - Page 27
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet 10 - Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.B Work Area Outlet 10 -
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
E102009.I Audiovisual Equipment - As Required
Provide Large Video flat screen displays with in-wall mounts.
Adapter signal Plates.Rroom audio playback and voice lift.
Credenza for housing equipment. Shared content management with watch floor.
PART 3 - CHAPTER 5 - Room Requirement 2.5 - Page 28
5.0 ROOM REQUIREMENTS
2.6 INTERVIEW ROOM
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 13'-6" W x 12'-0" D (161 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 50
Access: Keyed Lockset and Access Control
Number of Occupants: Seating for 6 PN
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.A Windows - - Adjacent to exterior insulated window, ATFP compliant.
C102007.A Interior Door Hardware 1 - Provide office locksets.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C103003 Marker Boards 1 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301006 Acoustical Panels
Adhered to Walls 1 -
Provide acoustical and tackable fabric wrapped panels on longest wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
Room for interviews with VTC capability is required for panel interviews and to accommodate six (6) people for J4 Department.
Interview room sized at sized at 16 NSF/PN (1.5 sm/PN).
Room Data Sheet applies to Room Number(s): 209
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide 36" W x 84" D rectangular table with eight (8) conference chairs on casters. Provide electrical and data in center of conference table.
VTC capabilities. Space must comply with Class I security requirements. Provide wireless drops as required for coverage.
PART 3 - CHAPTER 5 - Room Requirement 2.6 - Page 29
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet 6 - Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
E102009.A Audiovisual Equipment - As Required
Provide flat screen display with in-wall mount. Provide signal wall plate for local computer and a local CATV or IPTV connection.
E201002.B Window Treatments - - Provide double roller shade with both light filtering and black
PART 3 - CHAPTER 5 - Room Requirement 2.6 - Page 30
5.0 ROOM REQUIREMENTS
2.7 CONFERENCE ROOM - SMALL
Space Characteristics
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 18'-6" W x 24'-0" D (448 sq ft min)
Minimum Ceiling Height: 9'-0" AFF
Acoustics: STC 50
Access: Keyed Lockset and Access Control
Number of Occupants: Seating for 20 PN
Other/Special Requirements:
Uniformat
Section Description Qty Size Specific Requirements
B202001.A Windows 3 - Adjacent to exterior insulated window, ATFP compliant.
C102007.B Interior Door Hardware 1 - Provide classroom locksets.
C102001.A Interior Doors 1 3' W x 7' H Provide a solid core wood door.
C103003 Marker Boards 3 36" W x 48" D Provide markerboard(s).
C103004.A Identifying Devices
Wayfinding Signage 1 - Provide room identifying signage.
C301003.A Gypsum Wallboard
Finishes
- - Painted GWB.
C301006 Acoustical Panels
Adhered to Walls 3 -
Provide acoustical and tackable fabric wrapped panels on longest wall.
C302005 Carpet Tile - 24" x 24" Tile Provide carpet tile with attached backing.
C302007.A Wall Base Finishes - 4" Cove Provide rubber cove wall base.
C303001 Acoustical Ceiling Tiles and Panels
- 24" X 24" Tile Provide acoustical ceiling tiles.
C303005 Suspension Systems - 15mm “T” Grid Provide 15mm factory finished metal “T” grid for 24" X 24" ACT.
D30 HVAC - -
Provide heating, ventilation, and air conditioning for temperature control.
D40 Fire Protection - - Provide Fire Alarm / Mass Notification and Fire Suppression
Room Data Sheet applies to Room Number(s): 153, 156, 169, 220, 256
FF&E Information for Coordination:
FF&E and AV Equipment will be funded separately as a bid option to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor's Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design Workship (CDW). Space will accommodate, at a minimum, the following:
FF&E: Provide 48'' x 144'' conference table with (11) conference chairs on casters. Provide electrical and data in center of conference table. Provide a minimum of (9) side conference chairs. Provide waste receptable.
Where room is located along exterior walls, provide windows. Space must comply with Class II security requirements. Provide wireless drops as required for coverage.
A small conference room shared among the JFCNF Divisions to accommodate 20 personnel equipped with dual displays screens and video-teleconferencing (VTC). Conference room to include multimedia projection capability at facility desk with white boards on both side walls.
PART 3 - CHAPTER 5 - Room Requirement 2.7 - Page 31
D5010 Electrical Service and
Distribution
- As Required
Provide general purpose receptacles and discrete connections to utilization equipment. The design drawings must conform to
UFC 3-520-01.
D5020 Lighting and Branch
Wiring
Provide LED lighting fixtures and automatic control, and emergency lighting. Emergency lighting fixtures via battery pack or central lighting inverter. The design drawings must conform to UFC 3-530-01.
D503001.A Work Area Outlet 22 - Provide two (2) Category 6 Cabling Drops to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503005.A Electronic Security As Required As Required Card Reader, IDS, MD. IAW with UFC 4-021-02 and DoDM
5200.01
D503001.B Work Area Outlet 22 -
Provide one (1) OM4 Multimode and one (1) Singlemode Fiber
Cabling Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
D503001.E Work Area Outlet -
Classified
Provide two (2) Category 6 STP Cabling Drops to Outlet
(Includes conduit, box, cabling, jacks, etc.)
D503001.D Work Area Outlet (Media) As Required Provide one (1) Category 6 Cabling Drop, one (1) Coaxial Drop to Outlet (Includes conduit, box, cabling, jacks, etc.)
E102009.J Audiovisual Equipment - As Required
Provide flat screen displays with in-wall mounts. Provide signal wall plate for local computer and a local CATV or IPTV connection. VTC Video Bar camera. Room Audio voice lift and playback. Credenza for the equipment. Multi Network connectivity. System message signs. Collaboration Solution.
E201002.B Window Treatments - - Provide double roller shade with both light filtering and black