About this file

This document is a Civil Revisions Narrative for a project (P-1538 SOF Armory) prepared by Stantec Consulting Services Inc. for NAVFAC, detailing multiple technical revisions across various engineering and construction drawings and specifications from July 7, 2025 to November 11, 2025. The revisions include updates to site plans, grading notes, pump stations, demolition notes, utility profiles, concrete and pavement details, and modifications to several technical specifications such as earthwork, seeding, and utility infrastructure.

Key technical changes include adding duplex grinder pump station details, updating construction sequences, modifying sewer line configurations (changing approximately 100 linear feet of force main to 8" PVC gravity sewer), adjusting site elements like turnstile and sidewalk placement, and revising specifications related to earthwork, stormwater control measures, and utility installations. The document is associated with a NAVFAC Mid-Atlantic Marine Corps Installations East Area of Responsibility (AOR) Design-Build/Design-Bid-Build Indefinite Delivery/Indefinite Quantity (IDIQ) Multiple Award Construction Contract for General Construction Services.

View the file

Other files

File Type Posted
N4008525R2507 Amendment 0013.pdf PDF
N4008525R2507 Amendment 0012.pdf PDF
N4008525R2507 Amendment 0011.pdf PDF
N4008525R2507 Amendment 0010.pdf PDF
N4008525R2507 Amendment 0009.pdf PDF
N4008525R2507 Amendment 0008.pdf PDF
Civil Dwg - Revised_v2.pdf PDF
N4008525R2507 Amendment 0007.pdf PDF
P-1219PackageSewageLiftStationInfo.pdf PDF
N4008525R2507 Amendment 0006.pdf PDF
N4008525R2507 Amendment 0005.pdf PDF
Amendment 0004 SPC Revisions.pdf PDF
BLDG P1538-1701821-B-109-REV02.pdf PDF
2025 NEW UTILITIES RATES.pdf PDF
BLDG P1538-1701821-C-523-REV02.pdf PDF
BLDG P1538-1701821-CG123-REV03.pdf PDF
Amendment 0004 - Revisions Narrative.pdf PDF
N4008525R2507 Amendment 0004.pdf PDF
Technical Amendment 0003 SPC.pdf PDF
Technical Amendment 0003 - Revisions Narrative.pdf PDF
N4008525R2507 Amendment 0003.pdf PDF
Technical Amendment 0003 DWG.pdf PDF
Attachment J - Price Proposal Form Rev1.docx DOCX document
N4008525R2507 Amendment 0002.pdf PDF
25R2507 (P1538 Seed Project) Site Visit Log.pdf PDF
MARSOC - Site Visit Contractor Access Roster.xlsx XLSX spreadsheet
Technical Amendment 0001.pdf PDF
N4008525R2507 Amendment 0001.pdf PDF
Attachment I - P1538 DWG 3 of 6.pdf PDF
Attachment G - Small Business Subcontracting Plan (SBSP) Template.docx DOCX document
Attachment J - Price Proposal Form.docx DOCX document
Attachment I - P1538 DWG 6 of 6.pdf PDF
Attachment I - P1538 DWG 5 of 6.pdf PDF
Attachment D - Past Performance Questionnaire.docx DOCX document
N4008525R2507.pdf PDF
Attachment I - P1538 DWG 4 of 6.pdf PDF
Attachment F - Small Business Participation Commitment Document (SBPCD).docx DOCX document
Attachment C - Construction and Design Experience Project Data Sheet.docx DOCX document
Attachment B - PIEE Vendor Access Instructions.pdf PDF
Attachment I - P1538 DWG 2 of 6.pdf PDF
Attachment I - P1538 DWG 1 of 6.pdf PDF
Attachment H - P1538 SPECS.pdf PDF
Attachment E - Historical Small Business Utilization.docx DOCX document
Attachment A - PPI Log Template.xlsx XLSX spreadsheet
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P-1538 SOF Armory

P-1538 Compiled Revision List

November 20, 2025 Prepared for:

NAVFAC

Prepared by:

Stantec Consulting Services Inc.

Stantec Project Number:

215617058

November 6, 2024

1. Sheets CU101 & C-529: Added duplex grinder pump station detail.

July 7, 2025

1. Sheet CG100: Added construction sequence, maintenance plan, and grading note 10.

2. Sheet CG121: Added silt fence outlets, added silt fence, added compost sock.

3. Sheet CG123: Added silt fence outlets, added silt fence, added compost sock.

4. Sheet CU102: Added P-1219 pump update.

5. Sheet CU203: Added min cover to pipe in profile.

6. Sheet CU204: Added min cover to pipe in profile.

7. Sheet C-523: Added stockpile detail.

8. Sheet C-522: Added temporary seeding detail. Updated sliding gate detail.

9. Sheet C-523: Added typical swale detail. Updated SCM notes.

10. Sheet C-528: Updated pre-packed grinder lift station and add P-1219 pump updates.

September 19, 2025

11. Sheet CD100: Added additional demolition note #11.

12. Sheet CD101: Updated keynote #8 to demolish the existing power pole and guy wires.

13. Sheet CS101: Moved the turnstile and concrete sidewalk far enough from the sliding gate plan west of them so that there is sufficient clearance for the gate to open.

14. Sheet CS103: Add jointing plan.

15. Sheet CG101: Updated the 24’ contour and sidewalk spot elevations.

16. Sheet CG123: Added keynote #15 and layer controlled to show the gravel filter strip.

17. Sheet CU101: Corrected keynotes #1 and #2; Deleted keynotes #19 and #26 and associated blocks in the model file.

18. Sheet CU207: Corrected profiles A1 and A4

19. Sheet CU208: Corrected profile A2

20. Sheet C-511: Deleted detail C2, Asphalt Pavement Patch

21. Sheet C-512: Added Card Reader and Card Reader Pedestal details.

22. Sheet C-513: Added NCDEQ Permanent Seeding detail.

23. Sheet C-516: Added concrete jointing details.

24. Spec 31 00 00: Sections 3.3.3, 3.4.3, 3.4.5, 3.6.2, 3.6.6.1, and 3.6.6.2 have been updated.

25. Spec 32 01 16.71: Spec has been removed.

26. Spec 32 12 13: Spec has been removed.

27. Spec 32 12 16.16: Spec has been removed.

28. Spec 32 16 19: Spec has been edited to remove all items related to curb and gutter.

29. Spec 33 05 07.13: Spec has been removed.

30. Spec 33 05 23: Spec has been added.

31. Spec 33 40 00: Section 2.4.1 and 3.8.1 have been removed.

October 7, 2025

1. Sheet CG123: Changed keynote #9 from “Storm Water Control Measure” to “Outlet Riser”. Added additional keynote #16. Added key trench to plan view. Extended the riprap to the sediment fence outlet.

2. Sheet B-109: Deleted “with a minimum of one settlement plate per 5,000SF area of new fill” in settlement monitoring requirements #2 and added #5-7. Surcharge toe of slope added to plan view and annotated as “Surcharge toe of slope typ. Surcharge side slopes must be 1H:1V or flatter”. Number of settlement plates was significantly reduced, rearranged and renumbered in plan view.

3. Sheet C-523: Updated Bio-retention section and notes in detail A1 per provided markup.

4. Specification Section 01 57 19: Updated Paragraphs 1.5.1.1.1.2, 1.5.1.1.1.3, and 1.7.3b per provided markup.

5. Specification Section 31 00 00: Updated Paragraph 3.2.2.

November 11, 2025

1. Sheet CU102: Changed approximately 100-lf of 2.5” force main to 8” PVC gravity sewer and added another manhole.

2. Sheet CU202: Updated the force main/sewer profile to reflect changes identified in Note 1 above.

3. Sheet CU208: Updated jack and bore for an 8” PVC gravity sewer line with a 16” DIP casing.

Project Number: 215617058
A-3

image1.emf image2.png image3.png