This is a set of structural engineering drawings for a federal construction project, specifically showing foundation, framing, and construction details for what appears to be a military or government facility. The drawings are stamped and approved by Lucas G.A. Gelo, a Professional Engineer in North Carolina, with an approval date of 10.08.2024.
The structural drawings include comprehensive foundation plans, vault deck framing plans, roof framing plans, and detailed construction specifications across multiple areas (A, B, and C). Key structural elements include concrete foundations with reinforced steel bars, steel joist construction, metal decking systems, masonry walls (CMU construction), and various structural steel members including beams, columns, and connections. The drawings specify materials such as ASTM A615 Grade 60 reinforcing steel, concrete with specified compressive strengths, galvanized steel decking, and various anchor systems. Technical specifications cover wind load requirements, seismic design considerations, welding requirements per AWS standards, and detailed construction notes for proper installation of structural components. The project appears to involve a substantial concrete and steel structure with specialized areas including what may be secure storage or vault facilities based on the reinforced construction details shown.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
IP
T M
AR
IN
E
CO
RP
S
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
Fi le
Pa th
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
10.08.2024
ANILORACHTRON
LANOISSEFORP
E RI NN G
E
E
SEAL
0 3 2 5 8 6
LUCAS G. A. GELO
Approved by Michael Foy, PE Resident Engineer, MARSOC
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \P
-1
Ar m or y
- S tru ct
3_ ho ne w el l.r vt
/1 4/
:4
9:
P M
C O
VE
R
S H
EE
T
S-001
1701821
P-
S
O F
AR
M
O R
Y
FINAL SUBMITTAL
12916946
10.08.20204
LGG HON LGG
SL/RC
NEK
EJA
HPN
SHEET INDEX
SHEET NO SHEET TITLE
S-001 COVER SHEET
S-002 STRUCTURAL NOTES
S-003 STRUCTURAL NOTES
S-101 FOUNDATION PLAN - OVERALL
S-102 PARTIAL FOUNDATION PLAN - AREA A
S-103 PARTIAL FOUNDATION PLAN - AREA B
S-104 PARTIAL FOUNDATION PLAN - AREA C
S-105 VAULT DECK FRAMING PLAN - OVERALL
S-106 PARTIAL VAULT DECK FRAMING PLAN - AREA A
S-107 PARTIAL VAULT DECK FRAMING PLAN - AREA B
S-108 PARTIAL VAULT DECK FRAMING PLAN - AREA C
S-109 ROOF FRAMING PLAN - OVERALL
S-110 PARTIAL ROOF FRAMING PLAN - AREA A
S-111 PARTIAL ROOF FRAMING PLAN - AREA B
S-112 PARTIAL ROOF FRAMING PLAN - AREA C
S-201 STRUCTURAL SECTIONS
S-202 STRUCTURAL SECTIONS
S-501 GENERAL CONSTRUCTION DETAILS
S-502 GENERAL CONSTRUCTION DETAILS
S-503 GENERAL CONSTRUCTION DETAILS
1. BUILDING CODES............................2021 IBC "INTERNATIONAL BUILDING CODE"
UFC 1-200-01, CHANGE 1, 24 FEB 2023 "GENERAL BUILDING REQUIREMENTS"
UFC 3-301-01, CHANGE 1, 4 FEB 2022 "STRUCTURAL ENGINEERING"
UFC 4-010-01, C HANGE 2, 22 JULY 2022 "MINIMUM ANTI-TERRORISM
STANDARDS FOR BUILDINGS"
2. BUILDING RISK CATEGORY......................................................................................... II
3. SUPERIMPOSED DEAD LOADS:
a) ROOF..................................................................................................... 20 PSF
b) VAULT CONCRETE AND COLLATERAL ............................................ 110 PSF
4. DESIGN LIVE LOADS:
a) ROOF..................................................................................................... 20 PSF
ADDITIONAL JOIST BOTTOM CHORD POINT LOAD
AT EXPOSED STRUCTURE........................................................ 300 LB
b) FLOOR (OFFICE)....................................................................................50 PSF
c) FLOOR (LOBBIES AND FIRST FLOOR CORRIDORS).........................100 PSF
d) FLOOR (STORAGE)..............................................................................125 PSF
e) FLOOR (ARMORY) ...............................................................................150 PSF
f) MECHANICAL/ELECTRICAL ROOMS..................................................125 PSF
g) ELEVATED VAULT SLAB ..................................................................... 30 PSF
5. SNOW:
a) GROUND SNOW LOAD ....................................................................... 10 PSF
b) FLAT ROOF SNOW LOAD.................................................................... 10 PSF
c) SNOW EXPOSURE FACTOR, Ce .............................................................. 1.0
d) IMPORTANCE FACTOR, Is ....................................................................... 1.0
e) THERMAL FACTOR, Ct .............................................................................. 1.0
6. WIND
a) ULTIMATE WIND SPEED (RISK CAT. II)........................................... 144 MPH
b) NOMINAL WIND SPEED.................................................................... 112 MPH
c) WIND EXPOSURE CATEGORY...................................................................... B
d) INTERNAL PRESSURE COEFFICIENT ..................................................... 0.18
e) ROOF COMPONENTS AND CLADDING ........... SEE TABLE ON SHEET S001
f) WALL COMPONENTS AND CLADDING ........... SEE TABLE ON SHEET S001
g) WIND BASE SHEAR (ULTIMATE)..................................... Vx = 68K, Vy = 104K
7. SEISMIC:
a) SITE CLASS .................................................................................................. D
b) IMPORTANCE FACTOR, Ie ........................................................................ 1.0
c) MAPPED SPECTRAL RESPONSE ACCELERATION, Ss ................... 0.115 G
d) ONE SECOND PERIOD SPECTRAL RESPONSE COEFFICIENT, ..... 0.055 G
e) SHORT PERIOD SPECTRAL RESPONSE COEFFICIENT, SDS ........ 0.123 G
f) ONE SEC PERIOD SPECTRAL RESPONSE COEFFICIENT, SD1...... 0.088 G
g) SEISMIC RESPONSE COEFFICIENT, Cs .............................................. 0.035
h) RESPONSE MODIFICATION FACTOR, R................................................... 3.5
i) SEISMIC DESIGN CATEGORY .................................................................... B
j) BASIC SEISMIC FORCE RESISTING SYSTEM ..................... INTERMEDIATE
REINFORCED MASONRY SHEAR WALLS
k) ANALYSIS PROCEDURE ............................ EQUIVALENT LATERAL FORCE
l) SEISMIC BASE SHEAR ................................................................... V = 200 K
ParallelPAR.
CONT Continuous
Double Degree Demolish, Demolition
Centered Counter Sink
Depressed
Existing
Electric, Electrical
Each Face
Elevation Edge Nail
Equipment
Expansion Joint
Drawing
Diameter Diagonal Dimension
Drag Truss
Face of Steel (Studs)
Face Of
Far Side
Face of Masonry
Field Nail Floor, Flooring
Foundation
Face of Concrete
Existing
Exterior Expansion
Each Way
Finish, Finished
Finished Floor Finish Grade
Floor Joist
Future
Header Hanger
Height
Gusset
Heating/Ventilation/ Air Conditioning
Hold Down
Horizontal High Point
Grade Beam
Grade, Grading Glued Laminated Girder Truss
Footing
Each Side
Laminated Length, Angle
Include
Inside Diameter
Information
Interior Insulated
FTG
INT.
JST
L
LAM
JT. Joint Joist
HT
H.P.
HORIZ
H.V.A.C
IN
I.D.
INCL
INFO
INS
Inch
GA
GD
G.B.
FUT.
GLB
G.T.
HD
HGR
HDR
GUSS.
Gauge
Equal
F.J.
FLR
F.N.
FND
F.S.
F.O.
F.O.C.
F.O.S.
F.O.M.
FT. Feet
EQ.
EQPT.
EXP.
E.W.
F.F.
F.G.
FIN
EXT.
EXIST'G
E.S.
DO
DWG
DWL
D.T.
E.F.
E.J.
E.N.
ELV
ELEC
EA.
Dowel
Each
CSK
DBL
DEG
DEP
DEM
CTR'D
DIA
DIM
DIAG
Ditto
Pounds per Cubic Foot
Plate, Property Line
Precast Concrete
Pounds per Square Foot Pounds per Square Inch
Revision, Revised
Pressure Treated
R.,RAD.
Return
Rafters Roof
Required Reinforcement Reference
RFT.
RF.
REF.
RET.
REQ.
REINF.
REV.
Plywood Panel
Penetration
Radius
PLY.
PNL.
P.T.
P.S.I.
P.S.F.
PENT.
P.C.C.
P.C.F.
PL.
American Concrete Institute
Air Conditioning Anchor Bolt
Bottom Bottom of Footing
Above Finished Floor
American Society for Testing Materials
American Plywood Institute
Between
Blocking
Boundry Nail
Adjacent
Architect
Alternate Aluminum
Concrete Masonry Unit
Control Joint / Ceiling Joist
Connection Construction
Ceiling
Cast-in-Place
Concrete
Channel
ARCH.
C.J.
CLG
COL
CLR
CONC
CMU
C.I.P.
CONST
CONN
C
Column
Clear
A.S.T.M.
B.N.
BM
BLW.
BETWN.
BLK.
BOTT
B.O.F.
BLKG
Beam
Below
Block
A/C A.B.
A.C.I.
AL.
ADJ.
ALT.
A.P.A.
A.F.F.
Long Leg Horizontal
Mount, Mounted, Mounting
Manufacture, Manufacturer
Long Leg Vertical
Opposite Hand, Overhead Outside Diameter
MaximumMAX
Number Nominal
Opening
On Center Not To Scale
Not In Contract
Near Side
North
O.D.
O.C.
N.T.S.
OPNG
O.H.
NOM
N.S.
N.I.C.
NO.
N.
Minimum
Medium
Metal
Mezzanine
Miscellaneous Masonry Opening
Machine Bolt
Mechanical
MFR
MIN
MISC
M.O.
MTL
MT.
MECH
M.B.
MEZZ
MED
Long Pound
Live Load
Louver Masonry
Low Point
L.L.H.
L.P.
LVR
MAS
L.L.V.
L.L.
LG
LB
(E)
P PlateL
Unless Otherwise Noted Unless Noted Otherwise
Welded Wire Mesh Welded Wire Fabric WeightWT.
W.W.M.
W.W.F.
Vapor Barrier Vertical
Without
West Wood
Water Proof Working Point
With
W/O W.P.
W.PT.
W.
WD.
V.B.
U.O.N.
VERT.
U.N.O.
W/
Toe Nail
Typical Tube Steel Top of Wall
Top of Beam
Top of Steel Top of Parapet Top of Footing Top of Concrete
T.O.S.
T.S.
TYP.
T.O.W
T.N.
T.O.B.
T.O.P.
T.O.F.
T.O.C.
Sheet Metal Screw Specification(s)
Thick, Thickness
R.T. Roof Truss
S.S. Stainless Steel
Steel Structural
Stiffener Standard
Tongue & Groove Top & Bottom Symmetrical Suspended
Top of Curb
SYM
THK
T.C.
T&G T&B
STL.
STD.
STRUCT
STIFF.
SUSP.
South Schedule Section
Similar Sheet
Square
Separation
SHT.
SIM.
SPEC.
S.M.S.
SQ.
SEC.
SEP.
SCHED.
S.
Room
Rough Sawn Rough Opening
R.S.
R.O.
RM.
International Building CodeIBC Seismic Lateral Resisting SystemSLRS
GalvanizedGAL
Grade BeamGB
Masonry Control JointMCJ
Pre-Engineered Metal BuildingPEMB.
Powder Acuated FastenersP.A.F.
1.
2.
3.
4.
5.
SEE SPECIFICATIONS AND DEFERRED SUBMITTAL REQUIREMENTS ON SHEET
S-002 FOR REQUIRED SHOP DRAWING AND SUBMITTAL REQUIRMENTS TO BE
PROVIDED TO THE CONTRACTING OFFICER FOR REVIEW AND COMMENT.
STEEL REINFORCING LISTS AND QUANTITIES AND LENGTH OF ALL MATERIALS
ARE THE RESPONSIBILITY OF THE CONTRACTOR TO ASSURE COMPLIANCE
WITH THE PLANS. THE ENGINEER WILL NOT REVIEW THESE ITEMS.
REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF GENERAL COMPLIANCE
WITH THE CONTRACT DOCUMENTS. ALL ERRORS IN DETAILING, FABRICATION,
AND CORRECT FITTING OF ALL STRUCTURAL MEMBERS INCLUDING
COORDINATION WITH OTHER TRADES ARE THE RESPONSIBILITY OF THE
CONTRACTOR. SHOP DRAWING SUBMITTAL REVIEW DOES NOT CONSTITUTE
CHANGE ORDERS. ANY PROPOSED CHANGES MUST BE SUBMITTED IN A
LETTER OR DETAIL FOR APPROVAL.
SHOP DRAWINGS MUST BE SUBMITTED AT LEAST TWO WEEKS PRIOR TO THE
SCHEDULED FABRICATION DATE.
REPRODUCTION OF THESE STRUCTURAL DRAWINGS IS PROHIBITED FOR THE
PURPOSE OF PREPARING SHOP DRAWINGS. SUBCONTRACTOR/FABRICATOR
MUST PROVIDE INDEPENDENTLY CREATED DRAWINGS BASED ON THE
INFORMATION SHOWN IN THE CONTRACT DOCUMENTS.
SHOP DRAWINGS/SUBMITTALS:ABBREVIATIONS:
DESIGN BASIS: SYMBOLS:
REFERENCE SPECIFICATIONS FOR
SPECIAL INSPECTION REQUIREMENTS
A A
ZONE 45 5
3 2 3
3 2 3
ZO
N
E
WALLS
ROOF
COMPONENTS & CLADDING PRESSURE (PSF)
S-XXX
A1
A1
S-XXX
A1
S-XXX
GRID LINES - CENTER LINE
DETAIL NO.
ELEVATION NO.
SECTION NO.
SECTION
ELEVATION
DETAIL BUBBLE
GRID LINES - F.O. STUD/WALL
GRID NO.
SHEET NO. WHERE
SECTION IS SHOWN
SHEET NO. WHERE
ELEVATION IS SHOWN
SHEET NO. WHERE
DETAIL IS SHOWN
R O
O F
COMPONENTS & CLADDING NEW DESIGN
WIND PRESSURE (ULTIMATE)
ZONE
EFFECTIVE
WIND
AREA
PRESSURE
(PSF)
PRESSURE
(PSF)
1 10 21 -54
1 20 20 -52
1 50 19 -49
1 100 18 -47
2 10 -65
2 20 -60
2 50 -54
2 100 -50
3 10
3 20
3 50
3 100
4 10 39 -39
4 20 39 -39
4 50 36 -37
4 100 34 -36
4 500 28 -32
5 10 -72
5 20 -72
5 50 -64
5 100 -57
5 500 -43
W
AL
LS
-112
-102
-89
-79
ZO
N
E
8.. RAIN:
a) INTENSITY, i ....................................................................................4.25 in/hr
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
IP
T M
AR
IN
E
CO
RP
S
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
10.08.2024
ANILORACHTRON
LANOISSEFORP
E RI NN G
E
E
SEAL
0 3 2 5 8 6
LUCAS G. A. GELO
Approved by Michael Foy, PE Resident Engineer, MARSOC
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \P
-1
Ar m or y
- S tru ct
3_ ho ne w el l.r vt
/1 4/
:4
9:
P M
ST
R
U C
TU
R
AL
N
O
TE
S
S-002
1701821
P-
S
O F
AR
M
O R
Y
FINAL SUBMITTAL
12916947
10.08.20204
LGG HON LGG
SL/RC
NEK
EJA
HPN
STRUCTURAL NOTES
3.1.10
3.1.11
2.0.1
2.0.2
2.0.3
3.0
2.0 FOUNDATION:1.0 GENERAL NOTES:
CONCRETE:
REINFORCING STEEL:3.1
A.
B.
C.
D.
E.
F.
G.
A.
B.
C.
D.
THE PROJECT SPECIFICATIONS (A BOOK OF SPECIFICATIONS WHEN PROVIDED)
ARE A PART OF THE CONTRACT DOCUMENTS. IF THERE IS A DISCREPANCY
FOUND BETWEEN THE SPECIFICATIONS AND THE DRAWINGS, SPECIFICATIONS
TAKE PRECEDENCE, HOWEVER THE MATTER MUST BE PROMPTLY SUBMITTED
TO THE CONTRACTING OFFICER FOR CLARIFICATION. WORK PERFORMED BY
THE CONTRACTOR WITHOUT SUCH A CLARIFICATION MUST BE AT
CONTRACTOR'S OWN RISK AND EXPENSE.
EXAMINE THE STRUCTURAL DRAWINGS AND THE SPECIFICATIONS AND NOTIFY
THE ENGINEER & CONTRACTING OFFICER OF DISCREPANCIES IN ELEVATIONS,
DIMENSIONS, AND SITE CONDITIONS INCLUDING ERRORS BEFORE PROCEEDING
WITH WORK. OMISSIONS AND CONFLICTS BETWEEN THE VARIOUS ELEMENTS
OF THE DRAWINGS (AND SPECIFICATIONS) MUST BE RESOLVED IN WRITING
WITH THE ENGINEER/ARCHITECT & CONTRACTING OFFICER PRIOR TO START OF
WORK.
THE DRAWINGS (AND SPECIFICATIONS) REPRESENT THE COMPLETED
STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION.
PROVIDE ALL MEASURES AND MEANS NECESSARY TO PROTECT PERSONS AND
THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES MUST INCLUDE,
BUT NOT BE LIMITED TO BRACING, SHORING, ETC. OBSERVATION VISITS BY THE
ARCHITECT OR ENGINEER DOES NOT INCLUDE REVIEW OF THESE MEASURES.
TYPICAL DETAILS MUST BE USED WHENEVER APPLICABLE WHETHER
SPECIFICALLY REFERENCED OR NOT.
DRAWINGS MUST NOT BE SCALED FOR CONSTRUCTION PURPOSES.
PIPES OR DUCTS MUST NOT BE PLACED IN STRUCTURAL MEMBERS UNLESS
SPECIFICALLY DETAILED OR APPROVED BY THE ENGINEER & CONTRACTING
OFFICER.
REFER TO ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
SIZE AND LOCATION OF DOOR AND WINDOW OPENINGS, UNLESS
OTHERWISE NOTED.
SIZE AND LOCATION OF INTERIOR AND EXTERIOR NON-BEARING
PARTITIONS.
SIZE AND LOCATION OF CURBS, FLOOR DRAINS, SLOPES, DEPRESSED
AREAS, CHANGES IN LEVEL, RAMPS, CHAMFERS, GROOVES, INSERTS, ETC.,
EXCEPT AS SHOWN.
SIZE AND LOCATION OF FLOOR AND ROOF OPENINGS, EXCEPT AS SHOWN.
FLOOR AND ROOF FINISHES.
STAIR FRAMING AND DETAILS, EXCEPT AS SHOWN.
DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR THE
FOLLOWING:
PIPE RUNS, SLEEVES, HANGERS, TRENCHES, SLAB OPENINGS, ETC.,
EXCEPT AS SHOWN OR NOTED.
ELECTRICAL CONDUITS, BOXES, OUTLETS.
CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL AND PLUMBING
FIXTURES.
SIZE AND LOCATION OF MACHINE AND EQUIPMENT BASES, ANCHOR BOLTS,
ETC.
ASTM REFERENCES ARE FROM THE LATEST ISSUE AND LATEST REVISION,
UNLESS OTHERWISE NOTED.
INVESTIGATE THE SITE DURING CLEARING AND EXCAVATION FOR UNSUITABLE
CONDITIONS, UNCONSOLIDATED AND UNDOCUMENTED FILLS, BURIED
STRUCTURES, UTILITIES, ETC., AND IMMEDIATELY NOTIFY THE
ARCHITECT/ENGINEER & CONTRACTING OFFICER OF SITE CONDITIONS NOT
REFLECTED ON THE DRAWINGS OR DIFFERENT FROM MAXIMUM OR MINIMUM
DIMENSIONS INDICATED, INCLUDING CONFLICT IN GRADES, ADVERSE SOIL
CONDITIONS, GROUNDWATER PRESENT, DEEPENED FOOTINGS, UNCOVERED
AND UNEXPECTED UTILITY LINES, ETC.
CONSTRUCTION MATERIALS, IF PLACED ON STRUCTURAL MEMBERS, MUST BE
SPREAD OUT SUCH THAT THE LOADING DOES NOT EXCEED THE DESIGN LIVE
LOADS. PROVIDE SHORING AND BRACING WHERE CONSTRUCTION LOADING
EXCEEDS THE DESIGN STRENGTH OF THE STRUCTURAL MEMBERS OR THE
STRUCTURAL STRENGTH HAS NOT BEEN ATTAINED OR THE STRUCTURE IS NOT
COMPLETE.
DETERMINE THE LOCATION OF UTILITY SERVICES IN AREAS TO BE EXCAVATED
BEFORE BEGINNING EXCAVATION. EXERCISE EXTREME CAUTION IN
EXCAVATING AND TRENCHING. DAMAGE CAUSED AS A RESULT OF FAILING TO
EXACTLY LOCATE AND PRESERVE EXISTING UNDERGROUND UTILITIES IS THE
RESPONSIBILITY OF THE CONTRACTOR.
THE CAD DRAWINGS FILES ARE THE PROPERTY OF NAVFAC AND WILL NOT BE
RELEASED TO THE CONTRACTOR OR SUNBCONTRACTOR FOR THIER USE.
STRUCTURAL DRAWINGS TO BE USED IN CONJUNCTION WITH ARCHITECTURAL
DRAWINGS BY: MBF ARCHITECTS
SLAB ON GRADE
MIN. f'c
4,000 psi 4,000 psi
SLAB ON GRADE REINFORCEMENT MUST BE POSITIONED AT MID-DEPTH.
SHOP DRAWINGS FOR SIZE AND LAYOUT OF REINFORCING REBARS ARE
REQUIRED WHEN NOTED IN THE LIST OF REQUIRED SHOP DRAWINGS.
3.0.11
3.0.12
3.0.13
3.0.14
PROVIDE CONSTRUCTION OR CONTROL JOINTS IN SLAB ON GRADE AS SHOWN
ON PLANS UNLESS SPECIFIED OTHERWISE. LOCATION OF JOINTS NOT
SPECIFICALLY INDICATED MUST BE REVIEWED BY THE STRUCTURAL ENGINEER &
CONTRACTING OFFICER PRIOR TO PLACING REINFORCING STEEL.
NON-SHRINK GROUT MUST BE FROM A PRODUCT THAT SPECIFIES A MINIMUM
COMPRESSIVE STRENGTH AT 28 DAYS OF 7,000 psi PER ASTM C109. GROUTING
OF BASE PLATES PRIOR TO PLUMBING OF COLUMN IS NOT PERMITTED.
PROJECTING CORNERS OF SLABS, BEAMS, WALLS, COLUMNS, ETC., MUST BE
FORMED WITH A 3/4" CHAMFER OR TOOLED EDGE, UNLESS OTHERWISE NOTED.
CONCRETE WHICH DURING THE LIFE OF THE STRUCTURE WILL BE SUBJECT TO
FREEZING TEMPERATURES WHILE WET, MUST HAVE A WATER CEMENT RATIO
NOT EXCEEDING 0.45 BY WEIGHT AND MUST CONTAIN ENTRAINED AIR PER ACI
613. SUCH CONCRETE MUST INCLUDE EXTERIOR SLABS, PERIMETER
FOUNDATIONS, EXTERIOR CURBS, ETC.
3.0.1
3.0.2
3.0.3
3.0.4
3.0.5
3.0.6
3.0.7
3.0.8
3.0.9
3.0.10
CEMENT MUST CONFORM TO ASTM C150, TYPE II / V
AGGREGATES FOR NORMAL WEIGHT CONCRETE MUST CONFORM TO ASTM C33,
1 1/2" MAXIMUM SIZE.
ADMIXTURES MUST NOT BE USED WITHOUT PRIOR APPROVAL OF THE ENGINEER
& CONTRACTING OFFICER. ADMIXTURES USED TO INCREASE THE WORKABILITY
OF THE CONCRETE MUST NOT REDUCE THE STRENGTH OF CONCRETE. FLY ASH
(POZZOLAN) IF PERMITED BY SPECIFICATIONS MUST NOT EXCEED 25% FOR SLAB
ON GRADE AND 25% FOR OTHER CONCRETE.
THE MIX DESIGN, INCLUDING PROPORTIONS OF MATERIALS FOR A ONE YARD
BATCH, MUST BE SUBMITTED TO THE ENGINEER OF RECORD & CONTRACTING
OFFICER FOR REVIEW PRIOR TO ORDERING CONCRETE.
READY-MIX CONCRETE MUST BE MIXED AND DELIVERED IN ACCORDANCE WITH
ASTM C94.
REINFORCING BARS AND INSERTS MUST BE SECURED IN PLACE PRIOR TO
PLACING CONCRETE.
CONDUITS EMBEDDED HORIZONTALLY IN THE SLAB MUST HAVE AN OUTSIDE
DIAMETER NO GREATER THAN 1/3 THE THICKNESS OF THE SLAB. CONDUIT MUST
NOT BE EMBEDDED IN A SLAB THAT IS LESS THAN 3 1/2" THICK. EXCEPT FOR
LOCAL OFFSETS, MIN. CLEAR DISTANCE BETWEEN CONDUITS MUST BE 6".
NON-STRUCTURAL STEEL MEMBERS EMBEDDED IN CONCRETE MUST BE
GALVANIZED OR PAINTED. DAMAGED GALVANIZED AREAS MUST BE REPAIRED
PRIOR TO EMBEDMENT.
CONCRETE MUST HAVE A MAXIMUM DRY DENSITY OF 150 pcf.
MINIMUM CONCRETE COMPRESSIVE STRENGTHS AT 28 DAYS.
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED
TO EARTH:.............................................................................. 3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
NO.6 THROUGH NO.18 BAR .......................................... 2"
NO.5 BAR, W31 OR D31 WIRE, AND SMALLER ...........1 1/2"
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT
WITH GROUND:
SLABS, WALLS, JOISTS:
NO.14 AND NO.18 BAR ...................................................1 1/2"
NO.11 BAR AND SMALLER ............................................ 3/4"
BEAMS, COLUMNS:
PRIMARY REINFORCEMENT, TIES, STIRRUPS............1 1/2"
DETAILING, FABRICATION AND ERECTION OF REINFORCING BARS MUST BE IN
ACCORDANCE WITH ACI MANUAL OF STANDARD PRACTICE FOR DETAILING
REINFORCED CONCRETE STRUCTURES, ACI 315-LATEST ADOPTED EDITION.
REINFORCING MUST BE ADEQUATELY SUPPORTED TO PREVENT DISPLACEMENT
BY CONCRETE PLACEMENT OR WORKERS.
REINFORCING BARS EXCEPT BARS TO BE WELDED MUST CONFORM TO THE
"STANDARD SPECIFICATION FOR DEFORMED BILLET STEEL BARS FOR
CONCRETE REINFORCEMENT", ASTM A615 GRADE 60. BARS TO BE WELDED
MUST CONFORM TO ASTM A706.
WELDING OF REINFORCING BARS TO BE IN ACCORDANCE WITH "STRUCTURAL
WELDING CODE-REINFORCING STEEL", AWS D1.4. REINFORCING STEEL TO BE
WELDED MUST HAVE A MAXIMUM CARBON EQUIVALENT (CE) OF 0.75. SPECIAL
INSPECTION IS REQUIRED. TESTING IS REQUIRED FOR WELDS THICKER THAN
5/16".
WHERE CONTINUOUS BARS ARE CALLED OUT IN FOOTINGS, SPLICES MAY BE
USED. WHERE BARS ARE SHOWN SPLICED, THEY MAY RUN CONTINUOUS AT
CONTRACTOR'S OPTION.
REINFORCING BAR BENDS MUST BE MADE COLD.
UNLESS OTHERWISE SHOWN, WALL VERTICAL REINFORCING MUST BE
POSITIONED AT THE CENTER OF THE WALL.
DOWELS BETWEEN FOOTINGS AND WALLS MUST BE THE SAME GRADE, SIZE,
AND SPACING AS VERTICAL REINFORCING.
REINFORCING BARS MUST BE PROVIDED WITH THE FOLLOWING CONCRETE
COVER:
CONT. WALL
FOOTING
MIN. FTG. WIDTH MIN. FTG. THICKNESS MIN. EMBEDMENT
COLUMN
FOOTING
2'-0"
MIN. FOOTING SIZES
SUBMIT COMPACTION TEST REPORTS FOR FILL BY A QUALIFIED TESTING LAB
TO ARCHITECT/ENGINEER & CONTRACTING OFFICER BEFORE FOUNDATION
PLACEMENT. LOOSE SOIL AND FILL DIRT MUST BE COMPACTEDTO A MINIMUM
OF 95% MAXIMUM DENSITY.
THE FOOTING EXCAVATIONS MUST BE KEPT FREE FROM LOOSE MATERIAL AND
STANDING WATER AND MUST BE NEAT AND TRUE TO LINE BEFORE CONCRETE
IS PLACED.
ABANDONED FOOTINGS, UTILITIES, ETC. THAT INTERFERE WITH NEW
CONSTRUCTION MUST BE REMOVED.
WALL FOOTINGS ARE CONTINUOUS POURED CONCRETE WITH CONTINUOUS
REINFORCING PLACED 3" CLEAR OF BOTTOM AND SIDES.
UNLESS OTHERWISE NOTED, WALL FOOTINGS ARE CENTERED UNDER WALLS
AND COLUMN FOOTINGS UNDER COLUMNS.
PROVIDE FOR DESIGN AND INSTALLATION OF CRIBBING, SHEATHING AND
SHORING REQUIRED TO SAFELY RETAIN GRADES.
PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM SURFACE, GROUND, AND
OR SEEPAGE WATER.
12" 18"
18"12"3'-0"
FOUNDATION DESIGN IS BASED ON A MAXIMUM NET ALLOWABLE SOIL
BEARING PRESSURE OF 3,000 PSF FOLLOWING A SURCHARGE PERIOD AS
STATED IN A GEOTECHNICAL INVESTIGATION REPORT BY TERRACON
DATED OCTOBER 13, 2023.
FOOTING DEPTHS SHOWN ARE A MINIMUM AND MAY REQUIRE DEEPENING
BASED ON SITE CONDITIONS.
FOOTINGS MUST BEAR ON FIRM UNDISTURBED OR COMPACTED SOIL.
MINIMUM FOOTING DIMENSIONS AND EMBEDMENTS MUST BE AS FOLLOWS:
1.
A.
B.
C.
D.
E.
F.
G.
2.
DEFERRED SUBMITTALS:
THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL
THEIR DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN
REVIEWED BY THE ARCHITECT OR ENGINEER OF RECORD AND
THAT THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE
WITH THE DESIGN OF THE BUILDING. SUBMITTALS ARE TO BE
SEALED BY A REGISTERED PROFESSIONAL ENGINEER.
STRUCTURAL STEEL AND DECK SHOP DRAWINGS
STRUCTURAL STEEL CONNECTIONS AND CALCULATIONS
SUPPORT ANCHORAGE OF MECHANICAL, ELECTRICAL AND
PLUMBING EQUIPMENT AND COMPONENTS
SLAB ON GRADE CONTROL JOINT PLAN (PE SEAL NOT
REQUIRED FOR THIS ITEM)
LADDERS, GUARDRAILS, HANDRAILS, AND THEIR COMPONENTS
COLD-FORMED FRAMING / METAL STUDS CALCULATIONS AND
SHOP DRAWINGS INCLUDING LAYOUT, TYPICAL CONSTRUCTION
DETAILS, AND CONNCETIONS (ITEMS SHOWN IN PLANS ARE
MINIMUM SIZES REQUIRED.)
CONCRETE FRAMING SHOP DRAWINGS INCLUDING SIZE,
LAYOUT OF REINFORCING BARS AND TEMPORARY FORMWORK
LAYOUT AND SUPPORT.
THE ABOVE LISTED SUBMITTAL DOCUMENTS SHALL BE STAMPED
AND SIGNED BY A REGISTERED PROFESSIONAL ENGINEER.
BEAMS, COLUMNS & ELEVATED SLABS
FOOTINGS & ALL OTHER CONCRETE 3,000 psi
2.0.4
2.0.5
2.0.6
2.0.7
2.0.8
2.0.9
2.0.10
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.1.7
3.1.8
3.1.9
1.0.1
1.0.2
1.0.3
1.0.4
1.0.5
1.0.6
1.0.7
1.0.8
1.0.9
1.0.10
1.0.11
1.0.12
1.0.13
1.0.14
3.3.4
3.3.1
3.3.2
3.3.3
3.3.5
3.3.6
3.3.7
3.3.8
3.3.9
3.3 MECHANICAL ANCHORS IN HARDENED
CONCRETE AND MASONRY
(EXPANSION ANCHORS):
A.
B.
ANCHORS TO BE INSTALLED IN HOLES DRILLED WITH CARBIDE-TIPPED DRILL
BITS. ANCHORS TO BE INSTALLED PER MANUFACTURER'S WRITTEN
INSTRUCTIONS.
WHEN INSTALLING DRILLED EXPANSION ANCHORS IN EXISTING REINFORCED
CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE
EXISTING REINFORCEMENT.
MAINTAIN A MINIMUM CLEARANCE OF 25 mm[1"] BETWEEN THE REINFORCEMENT
AND THE DRILLED EXPANSION ANCHORS. EXPANSION ANCHORS MUST NOT BE
USED AT CONCRETE CURBS.
EXPANSION ANCHOR SYSTEMS:
CONCRETE: USE ONLY EXPANSION ANCHOR SYSTEMS THAT HAVE BEEN
ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH THE PROVISIONS OF
ICC-ES AC193. ANCHOR SYSTEMS SHOULD BE APPROVED FOR USE WITH
CRACKED CONCRETE AND SEISMIC DESIGN CATEGORIES A-F PER
SECTION 2.0 OF THE ICC EVALUATIONS SERVICES REPORT. ANCHOR
SYSTEM MUST BE INSTALLED PER THE REQUIREMENTS OF THE ICC-ES
EVALUATION SERVICES REPORT FOR THE SPECIFIC ANCHOR, AND AS
REQUIRED BY THE MANUFACTURER.
MASONRY: USE ONLY EXPANSION ANCHOR SYSTEMS THAT HAVE BEEN
ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH THE PROVISIONS OF ICC-
ES AC01. ANCHOR SYSTEMS SHOULD BE APPROVED FOR SEISMIC USE
DETAILED IN THE CONDITIONS OF USE LISTED IN THE ICC-ES EVALUATION
SERVICES REPORT. ANCHOR SYSTEM MUST BE INSTALLED PER THE
REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES REPORT FOR THE
SPECIFIC ANCHOR, AND AS REQUIRED BY THE MANUFACTURER.
UNDERCUT ANCHOR SYSTEMS:
CONCRETE: USE ONLY UNDERCUT ANCHOR SYSTEMS THAT HAVE BEEN ISSUED
AN ICC-ES REPORT IN ACCORDANCE WITH THE PROVISIONS OF ICC-ES AC193.
ANCHOR SYSTEMS SHOULD BE APPROVED FOR USE IN CRACKED CONCRETE
AND SEISMIC DESIGN CATEGORIES A-F PER SECTION 2.0 OF THE ICC
EVALUATIONS SERVICES REPORT. ANCHOR SYSTEM MUST BE INSTALLED
PER THE REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES REPORT
FOR SPECIFIC ANCHOR, AND AS REQUIRED BY THE MANUFACTURER.
WHERE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS OR APPLICABLE
ICC-ES EVALUATION SERVICES REPORT CALL FOR THE APPLICATION OF AN
INSTALLATION TORQUE, THE SPECIFIED TORQUE MUST BE APPLIED WITH
CALIBRATED TORQUE WRENCH. THE SPECIFIED INSTALLATION TORQUE MUST
NOT BE EXCEEDED.
ANCHORS ARE TYPICALLY AVAILABLE IN ELECTRO-GALVANIZED CARBON STEEL,
HOT DIPPED GALVANIZED CARBON STEEL, AND STAINLESS STEEL. USE OF
ELECTRO-GALVANIZED CARBON STEEL ANCHORS IS TYPICALLY LIMITED TO DRY,
INTERIOR LOCATIONS, UNLESS OTHERWISE NOTED. STAINLESS STEEL OR HOT-
DIPPED GALVANIZED ANCHORS ARE GENERALLY. SUITABLE FOR APPLICATIONS
EXPOSED TO EXTERIOR WEATHER CONDITIONS. FINAL AUTHORITY ON TYPE OF
ANCHOR COATING UTILIZED RESTS WITH THE STRUCTURAL ENGINEER OF
RECORD & CONTRACTING OFFICER AND MUST BE APPROVED BY SUCH.
EXPANSION ANCHORS FOR NON-VIBRATION ISOLATED MECHANICAL EQUIPMENT
RATED OVER 10HP ARE NOT PERMITTED BY ASCE 7-10 SECTION 13.6.5.5.
ANCHORS INSTALLED IN OVERHEAD CONDITIONS FOR NON- VIBRATION
ISOLATED EQUIPMENT WITH RECIPROCATING OR ROTATING MECHANISMS MUST
BE UNDERCUT ANCHORS.
THE SPECIAL INSPECTOR MUST BE ON THE JOBSITE CONTINUOUSLY DURING
ANCHOR INSTALLATIONS, UNLESS OTHERWISE NOTED IN ICC-ES ESR, TO VERIFY
ANCHOR TYPE, ANCHOR DIMENSIONS, CONCRETE TYPE, CONCRETE
COMPRESSIVE STRENGTH, HOLE DIMENSIONS ANCHOR SPACINGS, EDGE
DISTANCES, SLAB THICKNESS, ANCHOR EMBEDMENT, AND TIGHTENING
TORQUE.
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.2.7
3.2.8
3.2.9
3.2.10
3.2 ADHESIVE, ANCHOR RODS AND REBAR
IN HARDENED CONCRETE (EPOXY
ANCHORS):
A.
B.
ADHESIVE ANCHOR INSTALLATIONS MUST COMPLY WITH MANUFACTURER'S
WRITTEN INSTRUCTIONS AND SPECIFICATIONS, INLCUDING ICC-ES REPORTS
DUST MUST BE BLOWN FROM THE HOLE WITH COMPRESSED AIR TO
ENSURESURFACE. ADDITIONALLY, THE HOLE MUST BE BRUSHED WITH A NYLON
BRUSH THEN BLOWN AGAIN WITH COMPRESSED AIR.
ADHESIVE MUST ONLY BE APPLIED TO DRY SURFACES.
BASE MATERIAL TEMPERATURE MUST BE 40°F OR ABOVE AT TIME OF
INSTALLATION. FOR BEST RESULTS, MATERIAL SHOULD BE 70°F-80°F.
WHEN INSTALLING EPOXY ANCHORS INTO MASONRY, ANCHORS MUST BE
INSTALLED IN SOLID GROUTED CELLS ONLY.
CHEMICAL ANCHOR SYSTEMS:
CONCRETE: USE ONLY ADHESIVE ANCHOR SYSTEMS THAT HAVE BEEN
ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH PROVISIONS OF OF ICC-
ES AC308. ANCHOR SYSTEM SHOULD BE APPROVED FOR USE IN CRACKED
CONCRETE AND SEISMIC DESIGN CATEGORIES A-F PER SECTION 2.0 OF THE
ICC-ES EVALUATION SERVICES REPORT. ANCHOR SYSTEM MUST BE
INSTALLED PER REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES
REPORT FOR SPECIFIC ANCHOR, AND AS REQUIRED BY THE
MANUFACTURER.
GROUT-FILLED MASONRY UNITS: USE ONLY ADHESIVE ANCHORSYSTEMS
THAT HAVE BEEN ISSUED AN ICC-ES REPORT INACCORDANCE WITH
PROVISIONS OF ISS-ES AC58. ANCHORSYSTEMS MUST BE INSTALLED PER
REQUIREMENTS OF ICC-ESEVALUATION SERVICES REPORT FOR THE
SPECIFIC ANCHOR,AND AS REQUIRED BY THE MANUFACTURER.
ANCHOR RODS:
RODS MUST BE ASTM A36 THREADED RODS WITH ASTM A563 GRADE A NUTS
AND ANSI B18.22.1 TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS
DESIGNATED AS ASTM A193 GRADE B7 THREADED RODS MUST USE ASTM A563
GRADE DH HEAVY HEX NUTS AND ASTM F436 WASHERS.
REINFORCEMENT BARS: ASTM A615 GRADE 60 STEEL.
REMOVE GREASE, OIL, RUST AND OTHER LAITANCE FROM RODS AND DOWELS
PRIOR TO INSTALLATION.
SPECIAL INSPECTION REQUIREMENTS MUST BE DICTATED BY SECTION 4.0 OF
THE ICC-ES EVALUATION SERVICES REPORT. SPECIAL INSPECTION MUST
VERIFY ANCHOR TYPE, ANCHOR DIMENSIONS, CONCRETE TYPE, CONCRETE
COMPRESSIVE STRENGTH, HOLE DIMENSIONS, ANCHOR SPACINGS, EDGE
DISTANCES, SLAB THICKNESS, ANCHOR EMBEDMENT, AND TIGHTENING
TORQUE.
CONTRACTOR'S OPTION TO USE OTHER MANUFACTURER'S PRODUCTS ONLY
WITH PRIOR APPROVAL OF THE ENGINEER & CONTRACTING OFFICER. SUBMIT
MANUFACTURER'S LITERATURE AND PRODUCT INSTALLATION FOR REVIEW.
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
IP
T M
AR
IN
E
CO
RP
S
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
10.08.2024
ANILORACHTRON
LANOISSEFORP
E RI NN G
E
E
SEAL
0 3 2 5 8 6
LUCAS G. A. GELO
Approved by Michael Foy, PE Resident Engineer, MARSOC
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \P
-1
Ar m or y
- S tru ct
3_ ho ne w el l.r vt
/1 4/
:4
9:
P M
ST
R
U C
TU
R
AL
N
O
TE
S
S-003
1701821
P-
S
O F
AR
M
O R
Y
FINAL SUBMITTAL
12916948
10.08.20204
LGG HON LGG
SL/RC
NEK
EJA
HPN
3.4.1
4.0.1
4.0.2
4.0.3
4.0.4
4.0.8
4.0.9
4.0.10
4.0.11
4.0.12
4.0.13
4.0.14
4.0.15
4.0.17
4.0.18
4.0.19
4.0.20
4.0.21
4.0.5
4.0.6
4.0.7
4.0.16
3.4.2
3.4.3
3.4.4
3.4.5
3.4.6
3.4.7
3.4 POWDER ACTUATED FASTENERS IN
HARDENED CONCRETE, MASONRY,
AND STEEL (SHOT PINS):
4.0 MASONRY:
POWDER ACTUATED FASTENING SYSTEMS:
CONCRETE MASONRY UNITS
MASONRY COMPONENTS
DESIGN STRENGTH: f'm = 2000 psi
MORTAR (TYPE S)
GROUT
STRENGTH @ 28 DAYS
2000 psi
3000 psi
2000 psi
MASONRY WORK MUST CONFORM TO INTERNATIONAL BUILDING CODE
(IBC), LATEST ADOPTED EDITION AS LISTED HEREIN.
CONCRETE MASONRY UNITS MUST BE MEDIUM WEIGHT UNITS IN
ACCORDANCE WITH ASTM C90 WITH MAXIMUM LINEAR SHRINKAGE OF 0.065%.
CEMENT MUST BE AS SPECIFIED FOR CONCRETE.
MORTAR MUST CONFORM TO ASTM C270
EXCERPTS FROM ASTM C270:
CCELLS BELOW GRADE MUST BE FULLY GROUTED UNLESS OTHERWISE
NOTED. ADDITIONALLY, CELLS WITH REINFORCING MUST BE FILLED SOLID
WITH GROUTED UNLESS OTHERWISE NOTED WITHIN THE SECTIONS AND
TYPICAL DETAILS.
NOTED.
GROUT MUST BE CONSOLIDATED WITH A MECHANICAL VIBRATOR.
MINIMUM 4000 rpm, 3/4" MAXIMUM HEAD. PROVIDE INSPECTION AND
CLEANOUT HOLES AT THE BASE OF GROUTED CELLS FOR LIFTS
GREATER THAN 5'-0".
WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL
CONSTRUCTION JOINTS MUST BE FORMED BY STOPPING THE GROUT
POUR 1 1/2" BELOW TOP OF THE UPPERMOST UNIT.
UNLESS OTHERWISE NOTED, MASONRY MUST BE CONSTRUCTED
WITH A RUNNING BOND PATTERN.
ELECTRIC CONDUIT BOXES AND/OR OTHER OBSTRUCTIONS ARE NOT
PERMITTED IN CELLS CONTAINING REINFORCING, UNLESS APPROVED BY
THE ENGINEER & CONTRACTING OFFICER.
UNLESS OTHERWISE SHOWN ON THE PLANS, LAP SPLICES OF
REINFORCING STEEL IN MASONRY MUST BE PER SCHEDULE.
HORIZONTAL REINFORCEMENT BARS MUST BE PLACED IN BOND BEAM
MASONRY UNITS.
LINTEL REINFORCEMENT BARS MUST BE PLACED IN LINTEL BEAM BLOCK.
VERTICAL REINFORCEMENT BARS MUST BE PLACED AT THE CENTER OFTHE
WALL UNLESS OTHERWISE SHOWN. VERTICAL BARS ARE TO BE TIED OR
OTHERWISE FIXED IN POSITION AT INTERVALS OF NOT MORE THAN 200
BAR DIAMETERS AND AT TOP AND BOTTOM.
ANCHOR BOLTS MUST BE SET WITH TEMPLATES AND HELD IN PLACE
PRIOR TO GROUTING.
PROVIDE A MINIMUM OF ONE BAR DIAMETER OF GROUT BETWEEN MAIN
REINFORCING AND MASONRY UNITS. PROVIDE A MINIMUM OF 1"
GROUT AROUND BOLTS EMBEDDED IN MASONRY.
TABLE 2 PROPERTY SPECIFICATION REQUIREMENTSA
MORTAR TYPE
AVG. COMPRESSIVE
STRENGTH AT 28
DAYS, MIN.
WATER
RETENTION,
MIN. %
AIR
CONTENT,
MAX. %B
AGGREGATE RATIO
(MEASURED IN DAMP,
LOOSE CONDITIONS)
GROUT MUST CONFORM TO ASTM C476.
EXCERPTS FROM ASTM C476:
CEMENT-
LIME
MORTAR
CEMENT
MASONRY
CEMENT
M
S
N
O
M
S
N
O
M
S
N
O
2500 psi
1800 psi
750 psi
350 psi
2500 psi
1800 psi
750 psi
350 psi
2500 psi
1800 psi
750 psi
350 psi
75 12
75 12
75 14
75 14
75 12
75 12
75 18
75 18
75 20
75 20
C
C
C
C
D
D
NOT LESS THAN 2 1
AND NOT MORE THAN
3 1
2 THE SUM OF
SEPARATE VOLUMES
OF CEMENTITIOUS
MATERIALS
A
LABORATORY PREPARED MORTAR ONLY
B
SEE NOTE
C
WHEN STRUCTURAL REINFORCEMENT IS INCORPORATED IN CEMENT-LINE OR
CEMENT MORTAR, THE MAX. AIR CONTENT MUST BE 12%.
D
WHEN STRUCTURAL REINFORCEMENT IS INCORPORATED IN MASONRY OR
CEMENT MORTAR, THE MAX. AIR CONTENT MUST BE 18%.
PROPORTIONS BY VOLUME (CEMENTITIOUS MATERIALS)
MORTAR TYPE
PORTLAND
CEMENT OR
BLENDED
CEMENT
CEMENT-
LIME
MORTAR
CEMENT
M
S
N
O
M
M
S
S
N
O
1/2
M
M
S
S
N
O
1/2
M S N M S N
TABLE 1 PROPORTION SPECIFICATION REQUIREMENTS
MASONRY
CEMENT
MORTAR
CEMENT
NOT LESS THAN
2 1
4 AND NOT
MORE THAN 31
THE SUM OF
SEPARATE
VOLUMES OF
CEMENTITIOUS
MATERIALS
AGGREGATE
RATIO (MEASURED
IN DAMP, LOOSE
CONDITIONS)
HYDRATED
LIME OR LIME
PUTTY
1/4
OVER 1/4 TO 1/2
OVER 1/2 TO 1 1/4
OVER 1 1/4 TO 2 1/2
MORTAR JOINTS MUST BE STRAIGHT, CLEAN AND UNIFORM IN THICKNESS,
AND MUST BE TOOLED AS SHOWN ON THE PLANS OR AS SPECIFIED (FLUSH
JOINTS IF NO SPECIAL TREATMENT SPECIFIED). UNLESS OTHERWISE
SPECIFIED OR DETAILED ON THE PLANS, HORIZONTAL AND VERTICAL MORTAR
JOINTS MUST BE 3/8" THICK WITH FULL MORTAR COVERAGE ON THE
FACE SHELL.
OVERHANGING MORTAR DROPPINGS AND DEBRIS MUST BE REMOVED
FROM CELLS RECEIVING GROUT. FAILURE TO REMOVE DEBRIS MUST BE
CAUSE FOR REJECTION OF WALL AND REPAIR OR REWORK NECESSARY
MUST BE ENTIRELY AT CONTRACTOR'S EXPENSE.
VERTICAL HEAD JOINTS MUST BE BUTTERED WELL FOR A THICKNESS EQUAL
TO THE FACE SHELL OF THE BLOCK AND THESE JOINTS MUST BE SHOVED
TIGHTLY SO THAT THE MORTAR BONDS WELL TO BOTH BLOCKS. IF IT IS
NECESSARY TO MOVE A BLOCK SO AS TO OPEN A JOINT, THE BLOCK MUST
BE REMOVED FROM THE WALL, CLEANED AND SET IN FRESH MORTAR
TABLE 2103.12
GROUT PROPORTIONS BY VOLUME FOR MASONRY CONSTRUCTION
PARTS BY VOLUME
OF PORTLAND
CEMENT OR
BLENDED CEMENT
PARTS BY
VOLUME OF
HYDRATED
LIME OR LIME
PUTTY
AGGREGATE, MEASURED IN A DAMP,
LOOSE CONDITION
FINE COARSE
TYPE
FINE GROUT 1 0-1/10
1 0-1/10COARSE
GROUT
2 1/4-3 TIMES THE
SUM OF THE
VOLUMES OF THE
CEMENTITIOUS
MATERIALS
2 1/4-3 TIMES THE
SUM OF THE
VOLUMES OF THE
CEMENTITIOUS
MATERIALS
1-2 TIMES THE SUM
OF THE VOLUMES
OF THE
CEMENTITIOUS
MATERIALS
4.0.8.1 SPECIFIED COMPRESSIVE STRENGTH- PROPORTIONS ESTABLISHED
BY 28-DAY COMPRESSIVE STRENGTH TESTS IN ACCORDANCE WITH
TEST METHOD C 1019 THAT OBTAIN THE SPECIFIED COMPRESSIVE
STRENGTH. THE GROUT MUST BE MIXED TO A SLUMP OF 8 in. TO 11
in. AS DETERMNINED BY TEST METHOD C 143/C 143M AND MUST HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 psi AT 28 DAYS.
A.
B.
C.
CONCRETE: FOR GENERAL CONCRETE AND LIGHTWEIGHT CONCRETE:
POWDER ACTUATED FASTENING SYSTEMS MUST BE INSTALLED PER
REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES REPORT FOR THE
SPECIFIC FASTENER, AND AS REQUIRED BY THE MANUFACTURER.
MASONRY: POWDER ACTUATED FASTENING SYSTEMS MUST BE INSTALLED
PER THE REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES REPORT
FOR SPECIFIC FASTENER, AND AS REQUIRED BY THE MANUFACTURER.
STEEL: POWDER ACTUATED FASTENING SYSTEMS MUST BE INSTALLED
PER THE REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES REPORT
FOR THE SPECIFIC FASTENER, AND AS REQUIRED BY THE
MANUFACTURER.
WHEN INSTALLING POWDER ACTUATED FASTENERS IN EXISTING NON-
PRESTRESSED REINFORCED CONCRETE, USE CARE AND CAUTION TO AVOID
HITTING OR DAMAGE TO THE EXISTING REINFORCING BARS. MAINTAIN A MINIMUM
CLEARANCE OF 1" BETWEEN THE REINFORCEMENT AND THE FASTENER.
POWDER ACTUATED FASTENERS ARE NOT PERMITTED BY ASCE 7-16 SECTION
13.4.5 FOR SEISMIC TENSION LOAD APPLICATIONS. POWDER ACTUATED
FASTENERS MUST NOT BE USED TO CARRY SEISMIC TENSION LOADS (EXCEPT
FOR VERTICAL SEISMIC LOAD PRODUCED BY SELF-WEIGHT OF THE
COMPONENTS SUPPORTED) OR IN CRACKED CONCRETE UNLESS PRE-
APPROVED FOR SUCH LOADING BY THE ENFORCEMENT AGENCY.
THE USE OF POWDER DRIVEN FASTENERS FOR TENSION LOADS IS LIMITED TO
SUPPORT OF MINOR LOADS LIKE ACOUSTICAL CEILINGS, DUCTWORK CONDUITS,
ETC.
ALLOWABLE TENSION LOADS MUST BE LIMITED TO LESS THAN 100 POUNDS.
POWDER ACTUATED FASTENERS MAY BE USED FOR SEISMIC SHEAR, WHEN
THEY ARE SPECIFICALLY LISTED FOR SERVICE IN RESISTING LATERAL LOADS
IN AREAS SUBJECT TO EARTHQUAKE.
MINIMUM EDGE DISTANCE FOR ACTUATED FASTENERS MUST BE THE LARGER
OF THE VALUES GIVEN IN ASTM E 1190 OR THE APPLICABLE ICC-ES
EVALUATION SERVICES REPORT.
FOR MASONRY WORK INSPECTIONS SEE INSPECTION AND TESTING
SPECIFICATIONS.
REFER TO MASONRY CONSTRUCTION DETAILS ON SHEET S-501 AND S-502.
5.0.1
5.0.2
5.0.3
5.0.4
5.0.5
5.0.6
5.0.7
5.0.8
5.0.9
5.0.10
5.0.11
STRUCTURAL STEEL:5.0
THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL MUST BE IN
ACCORDANCE WITH "AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
AND STEEL CONSTRUCTION MANUAL AISC 360, LATEST ADOPTED EDITION.
EXCEPT AS AMENDED IN IBC CHAPTER 22.
CONNECTIONS MUST BE DETAILED IN ACCORDANCE WITH LATEST EDITION OF
AISC "DETAILING FOR STEEL CONSTRUCTION" AND IN ACCORDANCE WITH
UFC-3-301-01, 2-9.1.
STEEL FURNISHED FOR STRUCTURAL LOAD-CARRYING PURPOSES MUST BE
PROPERLY IDENTIFIED FOR CONFORMITY TO THE SPECIFIED GRADES SHOWN
BELOW AND IN ACCORDANCE WITH ASTM STANDARDS AND PROVISIONS OF IBC
CHAPTER 22. STEEL THAT IS NOT READILY IDENTIFIABLE AS TO GRADE FROM
MARKING AND TEST RECORDS MUST BE TESTED TO DETERMINE CONFORMITY TO:
A. WIDE FLANGE ASTM F992 (Fy=50 ksi) B. ANGLES AND CHANNELS ASTM A36 (Fy=36 ksi) C. PLATES ASTM A36 (Fy=36 ksi) D. HSS (RECTANGULAR) ASTM A500 GRADE C (Fy=50 ksi)
E. ANCHOR RODS ASTM F1554 GRADE 36 AT GRAVITY COLUMN
COLUMN ENDS MUST BE MILLED.
EXTERIOR STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE WEATHER MUST
BE HOT-DIPPED GALVANIZED AFTER FABRICATION. ZINC COATING MUST
CONFORM TO ASTM A123 (G-60 U.O.N.).
WELDING DONE AFTER GALVANIZING MUST BE PROTECTED WITH TWO COATS OF
GALVANIZING PROTECTANT METALLIC BARRIER. CONTRACTOR MUST USE
VENTILATION WHILE PERFORMING THIS WORK AS REQUIRED BY OSHA.
STEEL FABRICATION MUST BE PERFORMED IN AN APPROVED FABRICATION SHOP.
STEEL FABRICATOR MUST VERIFY DIMENSIONS WITH ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
METAL ITEMS, INCLUDING CONNECTORS, EXPOSED TO THE WEATHER MUST BE
HOT-DIPPED GALVANIZED AFTER FABRICATION.
STRUCTURAL STEEL MUST BE DELIVERED TO THE JOB SITE FREE OF EXCESSIVE
RUST, MILL SCALE, GREASE, ETC.
SUBMIT SHOP DRAWINGS TO THE STRUCTURAL ENGINEER & CONTRACTING
OFFICER FOR REVIEW PRIOR TO FABRICATION FOR STRUCTURAL STEEL
MEMBERS AND ACCESSORIES.
STEEL JOISTS:5.1
5.1.1
5.1.2
5.1.3
FABRICATION AND ERECTION OF STEEL JOISTS MUST BE IN ACCORDANCE
WITH THE LATEST SPECIFICATIONS AND CODE OF STANDARD PRACTICE OF
THE STEEL JOIST INSTITUTE.
JOISTS MUST BE DESIGNED FOR A MINIMUM NET UPLIFT OF 20 PSF,
UNLESS NOTED OTHERWISE.
SEE PLANS FOR JOIST DESIGNATIONS.
STEEL DECK:5.2
METAL DECKING MUST BE DESIGNED, FABRICATED AND ERECTED IN
ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE
SPECIFICATIONS.
WELDING OF METAL DECKING MSUT CONFORM TO AWS D1.3,
"STRUCTURAL WELDING CODE-SHEET STEEL"
METAL DECK MUST BE GALVANIZED AND SHOP-PRIMED STEEL SHEET:
ASTM A653, STRUCTURAL STEEL (55) GRADE 33 or 50, G60 ZINC COATING;
CLEAN, PRETREATED, AND PRIMED WITH MANUFACTURER'S STANDARD
BAKED-ON, RUST-INHIBITIVE PRIMER. COLOR MUST BE THE
MANUFACTURER'S STANDARD UNLESS OTHERWISE NOTED ON THE
ARCHITECTURAL PLANS
METAL DECK MUST HAVE A 3-SPAN CONDITION UNLESS NOTED
OTHERWISE AND HAVE HAVE INTERLOCKING SEAM SIDELAPS.
FASTEN ROOF DECK PANELS TO STEEL SUPPORTING MEMBERS SCREWS
AS INDICATED ON THE ROOF DECK DETAIL ON THESE DRAWINGS. FASTEN
SIDELAPS OF PANELS BETWEEN SUPPORTS WITH No. 10 SELF-DRILLING
CARBON STEEL SCREWS AS INDICATED ON THE ROOF DECK DETAIL ON
THESE DRAWINGS. INSTALL DECK ENDS OVER SUPPORTING FRAMING
WITH A 1-1/2" MINIMUM END BEARING AND LAP JOINTS 2". FASTEN ROOF
DECK PANELS TO DIAPHRAGM PERIMETER, i.e. EDGE ANGLES, WITH 5/8"
PUDDLE WELDS AT 1'-0"" O.C. TYPICAL UNLESS NOTED OTHERWISE.
PROVIDE MISCELLANEOUS DECK ACCESSORIES NOT SPECIFICALLY NOTED
ON THESE DRAWINGS AS REQUIRED TO SUBSTRATE A COMPLETE DECK
INSTALLATION. THESE ACCESSORIES MUST INCLUDE RIDGE AND VALLEY
PLATES, FINISH STRIPS, END CLOSURES, REINFORCING CHANNELS, AND
WELD COVER PLATES AT CHANGES IN DIRECTION OF DECK PANELS
ACCORDING TO DECK MANUFACTURER'S WRITTEN INSTRUCTIONS.
ACCESSORIES ACCORDING TO APPLICABLE SPECIFICATIONS AND
COMMENTARY IN SDI PUBLICATION No. 30, MANUFACTURER'S WRITTEN
INSTRUCTIONS AND REQUIREMENTS IN THESE DOCUMENTS.
INSTALL TEMPORARY SHORING BEFORE PLACING DECK PANELS, IF
REQUIRED TO MEET DEFLECTION LIMITATIONS.
PLACE DECK PANELS ON SUPPORTING FRAME AND ADJUST TO FINAL
POSITION WITH ENDS ACCURATELY ALIGNED AND BEARING ON
SUPPORTING FRAME BEFORE BEING PERMANENTLY FASTENED. DO NOT
STRETCH OR CONTRACT SIDELAP INTERLOCKS.
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
5.2.6
5.2.7
5.2.8
5.2.9
STRUCTURAL NOTES
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
F G H
IF G H J
1/ 2"
/8
1/ 2" x1
C1
F11 F10 F10 F10
F10F10F10F11
A4 S-201
A4 S-201B4
S-201
C4 S-201
B3 S-201
C4 S-201
C4 S-201
C4 S-201
C4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
F4
HSS6X
6X
3/8
F4
F4
HSS6X
6X
3/8
F4
F4
F4
F4
F4
S-103 A4
S-102 A4
S-104 A4
B3 S-201
B C D x1
C2 14 x1 C2 14 x1 C2 x1
C1 14 x1 C2 14 x1 C2 14 x1 C2
HSS6X
6X
3/8
HSS6X
6X
3/8
HSS6X
6X
3/8
HSS6X
6X
3/8
HSS6X
6X
3/8
25' - 0" 25' - 0" 36' - 8 3/8"
263' - 3 5/8"
HSS6X
6X
3/8
B4 S-201
K
27' - 3 1/2" 24' - 8 1/2" 27' - 6 3/8" 39' - 5 1/8"36' - 11 1/2"
WF3 (-1' - 4")
WF2.5
WF2.5
WF3
WF2.5 (-1' - 4")WF2.5 (-1' - 4")
WF2.5 (-1' - 4")
WF2.5 (-1' - 4")WF2.5 (-1' - 4")
(-1' - 4")
(-1' - 4")
(-1' - 4")
WF2.5 (-1' - 4")
WF2.5 (-1' - 4")
WF2.5 (-1' - 4")
WF2.5
WF2.5 (-1' - 4")
W F2 .5 1' 4"
W F2 .5 1' 4"
1' 4"
1' 4"
1' 4"
1' 4"
W F2 .5
W F2 .5
W F2 .5
W F2 .5
W F2 .5 1' 4"
1' 4"
W F2 .5
1' 4"
W F2 .5
W F2 .5 1' 4"
W F2 .5 1' 4"
W F2 .5 1' 4"
HATCHED AREA TO RECEIVE 4"
CONCRETE SLAB ON GRADE
REINFORCED WITH 6 X 6 - W2.9 X W2.9
WELDED WIRE REINFORCING.
WELDED WIRE TO BE PROVIDED IN
SHEETS, NOT ROLLS. SLAB TO BEAR
ON 4" OF COMPACTED, POROUS FILL.
PROVIDE MINIMUM 10 MIL
REINFORCED VAPOR BARRIER
BETWEEN SLAB AND POROUS FILL.
2' -8
W F2 .5
2' -8
W F2 .5
A
0.1
0.6
1.5
2.5
3.3
3.9
E
MASONRY
PIER
MASONRY.
PIER
MASONRY
PIER
F7
F5
F7
20' - 8 3/8"
F7 F7 F7 F7
1.
2.
3.
4.
5.
6.
7.
8.
FOUNDATION PLAN NOTES:
ENTIRE AREA TO RECEIVE 6" CONCRETE SLAB ON GRADE REINFORCED
WITH 6 X 6 - W4 X W4 WELDED WIRE REINFORCING, UNLESS NOTED
OTHERWISE. WELDED WIRE TO BE PROVIDED IN SHEETS, NOT ROLLS.
SLAB TO BEAR ON 4" OF COMPACTED, POROUS FILL. PROVIDE MINIMUM
10 MIL REINFORCED VAPOR BARRIER BETWEEN SLAB AND POROUS FILL.
CJ (CONSTRUCTION OR CONTROL JOINTS - CONTRACTOR'S OPTION) TO
BE PLACED AT COLUMN CENTERLINES AND SPACED AT 12'-0" O.C. MAX.
EACH WAY. SEE TYPICAL DETAIL.
"MASONRY PIER" WHERE NOTED ON PLAN TO RECEICE #5 VERTICAL
REINFORCING AT FOUR CONSECUTIVE CELLS CENTERED UNDER
FRAMING ABOVE
MARKS SHOWN THUS (-X'-XX") INDICATE TOP OF FOOTING BELOW
FINISHED FIRST FLOOR ELEVATION. CONTRACTOR MUST COORDINATE
TOP OF FOOTING ELEVATIONS WITH ARCHITECTURAL, MECHANICAL,
ELECTRICAL, PLUMBING, AND CIVIL DRAWINGS. THE STRUCTURAL
ENGINEER MUST BE NOTIFIED OF CONFLICTS OR DISCREPANCIES IN
TOP OF FOOTING ELEVATIONS.
CONTRACTOR MUST COORDINATE WITH SITE DRAWINGS AND PROVIDE
FOOTING STEPS AS REQUIRED. SEE TYPICAL DETAIL.
REFERENCE FINISH SLAB ELEVATION TO BE 0'-0", UNLESS NOTED THUS
(-__'-__") ON PLAN. SEE CIVIL DRAWINGS FOR ACTUAL FINISHED FLOOR
ELEVATION.
SEE TYPICAL CONSTRUCTION DETAILS ON SHEETS S-501, S-502 & S-503.
SEE GENERAL NOTES ON SHEETS S-001 & S-002.
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
IP
T M
AR
IN
E
CO
RP
S
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
10.08.2024
ANILORACHTRON
LANOISSEFORP
E RI NN G
E
E
SEAL
0 3 2 5 8 6
LUCAS G. A. GELO
Approved by Michael Foy, PE Resident Engineer, MARSOC
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \P
-1
Ar m or y
- S tru ct
3_ ho ne w el l.r vt
/1 4/
:4
9:
P M
FO
U
N D
AT
IO
N P
LA
N
O
VE
R
AL
L
S-101
1701821
P-
S
O F
AR
M
O R
Y
FINAL SUBMITTAL
12916949
10.08.20204
LGG HON LGG
SL/RC
NEK
EJA
HPN
ALL DIMENSIONS ARE TO FACE OF
CMU. UNLESS OTHERWISE NOTED
SCALE: 1/16" = 1'-0"B3 FOUNDATION PLAN
N
GRAPHIC SCALE: 1/16"=1'-0"
16' 0 8' 16' 32'
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
C4 S-201
A4 S-201
A4 S-201
F4 F4
18' - 0" 7' - 11 7/8"
8'
3/
8" 6'
0"
1/ 2"
/4
1'
4"
1'
4"
HSS6X
6X
3/8 ( -1' - 4" ) ( -1' - 4" )
/4
1/ 2"
6'
0"
A4 S-201
B
B4 S-201
B4 S-201
B4 S-201
A4 S-201
W F2 .5 1' 4"
WF2.5 (-1' - 4")
W F2 .5 1' 4"
WF2.5 (-1' - 4")
W F2 .5
W F2 .5
HATCHED AREA TO RECEIVE 4"
CONCRETE SLAB ON GRADE REINFORCED
WITH 6 X 6 - W2.9 X W2.9 WELDED WIRE
REINFORCING. WELDED WIRE TO BE
PROVIDED IN SHEETS, NOT ROLLS. SLAB
TO BEAR ON 4" OF COMPACTED, POROUS
FILL. PROVIDE MINIMUM 10 MIL
REINFORCED VAPOR BARRIER BETWEEN
SLAB AND POROUS FILL.
METAL STAIR - BY
OTHERS - SEE
ARCH. DWGS.
A
HSS6X
6X
3/8
10' - 11 5/8"
6'
3/
4"
/4
/4
0.1
3.9
1'-4 x 3'-4"
THICKENED SLAB @
BOTT. OF STAIRS -
SEE ARCH. DWGS.
CONSTRUCTION
OR CONTROL
JOINT - SEE
PLAN NOTES
C L
O F
M
AS
O N
R Y
6'
8"
1.
2.
3.
4.
5.
6.
7.
8.
FOUNDATION PLAN NOTES:
ENTIRE AREA TO RECEIVE 6" CONCRETE SLAB ON GRADE REINFORCED
WITH 6 X 6 - W4 X W4 WELDED WIRE REINFORCING, UNLESS NOTED
OTHERWISE. WELDED WIRE TO BE PROVIDED IN SHEETS, NOT ROLLS.
SLAB TO BEAR ON 4" OF COMPACTED, POROUS FILL. PROVIDE MINIMUM
10 MIL REINFORCED VAPOR BARRIER BETWEEN SLAB AND POROUS FILL.
CJ (CONSTRUCTION OR CONTROL JOINTS - CONTRACTOR'S OPTION) TO
BE PLACED AT COLUMN CENTERLINES AND SPACED AT 12'-0" O.C. MAX.
EACH WAY. SEE TYPICAL DETAIL.
"MASONRY PIER" WHERE NOTED ON PLAN TO RECEICE #5 VERTICAL
REINFORCING AT FOUR CONSECUTIVE CELLS CENTERED UNDER
FRAMING ABOVE
MARKS SHOWN THUS (-X'-XX") INDICATE TOP OF FOOTING BELOW
FINISHED FIRST FLOOR ELEVATION. CONTRACTOR MUST COORDINATE
TOP OF FOOTING ELEVATIONS WITH ARCHITECTURAL, MECHANICAL,
ELECTRICAL, PLUMBING, AND CIVIL DRAWINGS. THE STRUCTURAL
ENGINEER MUST BE NOTIFIED OF CONFLICTS OR DISCREPANCIES IN
TOP OF FOOTING ELEVATIONS.
CONTRACTOR MUST COORDINATE WITH SITE DRAWINGS AND PROVIDE
FOOTING STEPS AS REQUIRED. SEE TYPICAL DETAIL.
REFERENCE FINISH SLAB ELEVATION TO BE 0'-0", UNLESS NOTED THUS
(-__'-__") ON PLAN. SEE CIVIL DRAWINGS FOR ACTUAL FINISHED FLOOR
ELEVATION.
SEE TYPICAL CONSTRUCTION DETAILS ON SHEETS S-501, S-502 & S-503.
SEE GENERAL NOTES ON SHEETS S-001 & S-002.
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
IP
T M
AR
IN
E
CO
RP
S
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
10.08.2024
ANILORACHTRON
LANOISSEFORP
E RI NN G
E
E
SEAL
0 3 2 5 8 6
LUCAS G. A. GELO
Approved by Michael Foy, PE Resident Engineer, MARSOC
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \P
-1
Ar m or y
- S tru ct
3_ ho ne w el l.r vt
/1 4/
:4
9:
P M
PA
R
TI
AL
F O
U N
D
AT
IO
N
P
LA
N
AR
EA
A
S-102
1701821
P-
S
O F
AR
M
O R
Y
FINAL SUBMITTAL
12916950
10.08.20204
LGG HON LGG
SL/RC
NEK
EJA
HPN
SCALE: 1/8" = 1'-0"A4 PARTIAL FOUNDATION PLAN - AREA A
GRAPHIC SCALE: 1/8"=1'-0"
8' 0 4' 8' 16'
GRAPHIC SCALE: 1"=60'
60' 0 120'60'
N
SCALE: 1" = 60'-0"D4 KEY PLAN
N
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
A4 S-201
B4 S-201
C4 S-201
1/ 2"
/8
1/ 2"
/4
B3 S-201
/8
/4
1/ 4"
/8
4'
0" 4'
0"
9' - 11 5/8" 29' - 4 3/4" 10' - 0"
C4 S-201
C4 S-201
C4 S-201
C4 S-201
C4 S-201
C4 S-201
C4 S-201
B C D
/4
( -1' - 4" )
( -1' - 4" )
( -1' - 4" )
( -1' - 4" )
1'
4"
1'
4"
1'
4"
1'
4"
/8
6'
0"
4'
0" 4'
0"
WF2.5 (-1' - 4")
1' 4"
WF3 (-1' - 4")
W F2
.5 W
F2 .5
W F2
.5
WF2.5
WF2.5
WF2.5
WF2.5
1' 4"
W F2
.5 1' 4"
W F2
.5
W F2
.5 W
F2 .5
HATCHED AREA TO RECEIVE 4"
CONCRETE SLAB ON GRADE REINFORCED
WITH 6 X 6 - W2.9 X W2.9 WELDED WIRE
REINFORCING. WELDED WIRE TO BE
PROVIDED IN SHEETS, NOT ROLLS. SLAB
TO BEAR ON 4" OF COMPACTED, POROUS
FILL. PROVIDE MINIMUM 10 MIL
REINFORCED VAPOR BARRIER BETWEEN
SLAB AND POROUS FILL.
20' - 8 3/8" 25' - 0" 25' - 0"
C L
O F
M
AS
O N
R Y
C L
O F
M
AS
O N
R Y
C L
O F
M
AS
O N
R Y
/8
/8
CL OF
MASONRY
/8
/8
CL OF
MASONRY
0.1
3.9
E
MASONRY
PIER
MASONRY.
PIER
MASONRY
PIER
CONSTRUCTION
OR CONTROL
JOINT - SEE
PLAN NOTES
70' - 8 3/8"
F7 (-1' - 4")
F5 (-1' - 4")
F7 (-1' - 4")
MASONRY.
PIER
F5
(-1' - 4")
1.
2.
3.
4.
5.
6.
7.
8.
FOUNDATION PLAN NOTES:
ENTIRE AREA TO RECEIVE 6" CONCRETE SLAB ON GRADE REINFORCED
WITH 6 X 6 - W4 X W4 WELDED WIRE REINFORCING, UNLESS NOTED
OTHERWISE. WELDED WIRE TO BE PROVIDED IN SHEETS, NOT ROLLS.
SLAB TO BEAR ON 4" OF COMPACTED, POROUS FILL. PROVIDE MINIMUM
10 MIL REINFORCED VAPOR BARRIER BETWEEN SLAB AND POROUS FILL.
CJ (CONSTRUCTION OR CONTROL JOINTS - CONTRACTOR'S OPTION) TO
BE PLACED AT COLUMN CENTERLINES AND SPACED AT 12'-0" O.C. MAX.
EACH WAY. SEE TYPICAL DETAIL.
"MASONRY PIER" WHERE NOTED ON PLAN TO RECEICE #5 VERTICAL
REINFORCING AT FOUR CONSECUTIVE CELLS CENTERED UNDER
FRAMING ABOVE
MARKS SHOWN THUS (-X'-XX") INDICATE TOP OF FOOTING BELOW
FINISHED FIRST FLOOR ELEVATION. CONTRACTOR MUST COORDINATE
TOP OF FOOTING ELEVATIONS WITH ARCHITECTURAL, MECHANICAL,
ELECTRICAL, PLUMBING, AND CIVIL DRAWINGS. THE STRUCTURAL
ENGINEER MUST BE NOTIFIED OF CONFLICTS OR DISCREPANCIES IN
TOP OF FOOTING ELEVATIONS.
CONTRACTOR MUST COORDINATE WITH SITE DRAWINGS AND PROVIDE
FOOTING STEPS AS REQUIRED. SEE TYPICAL DETAIL.
REFERENCE FINISH SLAB ELEVATION TO BE 0'-0", UNLESS NOTED THUS
(-__'-__") ON PLAN. SEE CIVIL DRAWINGS FOR ACTUAL FINISHED FLOOR
ELEVATION.
SEE TYPICAL CONSTRUCTION DETAILS ON SHEETS S-501, S-502 & S-503.
SEE GENERAL NOTES ON SHEETS S-001 & S-002.
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
IP
T M
AR
IN
E
CO
RP
S
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
10.08.2024
ANILORACHTRON
LANOISSEFORP
E RI NN G
E
E
SEAL
0 3 2 5 8 6
LUCAS G. A. GELO
Approved by Michael Foy, PE Resident Engineer, MARSOC
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \P
-1
Ar m or y
- S tru ct
3_ ho ne w el l.r vt
/1 4/
:4
9:
P M
PA
R
TI
AL
F O
U N
D
AT
IO
N
P
LA
N
AR
EA
B
S-103
1701821
P-
S
O F
AR
M
O R
Y
FINAL SUBMITTAL
12916951
10.08.20204
LGG HON LGG
SL/RC
NEK
EJA
HPN
10.08.2024
SCALE: 1/8" = 1'-0"A4 PARTIAL FOUNDATION PLAN - AREA B
N
SCALE: 1" = 60'-0"D4 KEY PLAN
GRAPHIC SCALE: 1/8"=1'-0"
8' 0 4' 8' 16'
GRAPHIC SCALE: 1"=60'
60' 0 120'60'
N
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
F G H J
C4 S-201
/8
/4
/4
/8
27' - 3 1/2" 24' - 8 1/2" 27' - 6 3/8" 25' - 5 1/8" 14' - 0" x1
C1 14 x1 C2 14 x1 C2 14 x1 C2 x1
C1 14 x1 C2 14 x1 C2 14 x1 C2
HSS6X
6X
3/8
HSS6X6X3/8
HSS6X
6X
3/8
HSS6X6X3/8
HSS6X
6X
3/8
HSS6X6X3/8
(-1' - 4")
F11
36' - 4 5/8"
0'
/8
C4 S-201
C4 S-201
B3 S-201
B3 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
A4 S-201
K
WF2.5 (-1' - 4")
WF3 (-1' - 4")
WF2.5 (-1' - 4")
W F2 .5 1' 4"
W F2 .5 1' 4"
W F2 .5 1' 4"
(-1' - 4") F10 (-1' - 4")
F10 (-1' - 4")
F10 (-1' - 4")
F10 (-1' - 4")
F10 (-1' - 4")
F10 (-1' - 4")
F11 (-1' - 4")
F4
(-1' - 4") F4
(-1' - 4") F4
(-1' - 4") F4
(-1' - 4") F4
(-1' - 4") F4
/4
155' - 7 7/8"
1/ 2"
/8
/2
5/ 8"
C4 S-201
C4 S-201
0.1
0.6
1.5
2.5
3.3
3.9
E
MASONRY.
PIER
MASONRY.
PIER
MASONRY
PIER
F5 (-1' - 4")
F7 (-1' - 4")
F7 (-1' - 4")
MASONRY.
PIER
MASONRY.
PIER
MASONRY.
PIER
MASONRY.
PIER
F7 (-1' - 4")
F7 (-1' - 4")
MASONRY
PIER
F5 (-1' - 4")
MASONRY
PIERF5
(-1' - 4")
CONSTRUCTION
OR CONTROL
JOINT - SEE
PLAN NOTES
W F2 .5 1' 4"
W F2 .5 1' 4"
F7 (-1' - 4")
F7 (-1' - 4")
1.
2.
3.
4.
5.
6.
7.
8.
FOUNDATION PLAN NOTES:
ENTIRE AREA TO RECEIVE 6" CONCRETE SLAB ON GRADE REINFORCED
WITH 6 X 6 - W4 X W4 WELDED WIRE REINFORCING, UNLESS NOTED
OTHERWISE. WELDED WIRE TO BE PROVIDED IN SHEETS, NOT ROLLS.
SLAB TO BEAR ON 4" OF COMPACTED, POROUS FILL. PROVIDE MINIMUM
10 MIL REINFORCED VAPOR BARRIER BETWEEN SLAB AND POROUS FILL.
CJ (CONSTRUCTION OR CONTROL JOINTS - CONTRACTOR'S OPTION) TO
BE PLACED AT COLUMN CENTERLINES AND SPACED AT 12'-0" O.C. MAX.
EACH WAY. SEE TYPICAL DETAIL.
"MASONRY PIER" WHERE NOTED ON PLAN TO RECEICE #5 VERTICAL
REINFORCING AT FOUR CONSECUTIVE CELLS CENTERED UNDER
FRA…