1. BASIS OF DESIGN EQUIPMENT NOTED WITHIN THIS SET OF DRAWINGS IS NOT PROPRIETARY. OTHER MANUFACTURER'S MAY BE SUBMITTED FOR REVIEW AND APPROVAL.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL ACCESSORIES REQUIRED FOR MANUFACTURER RECOMMENDED OPERATION.
PROVIDE COMPLETE AND FUNCTIONAL SYSTEMS TO OPERATE IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND LOCAL CODES.
3. BEFORE INSTALLATION AND ERECTION OF PIPING, ALL DIMENSIONS AND ROUTING MUST BE VERIFIED IN FIELD.
4. PLUMBING CONTRACTOR MUST COORDINATE LOCATION OF PLUMBING EQUIPMENT, FIXTURES, AND PIPING WITH OTHER TRADES INCLUDING BUT NOT LIMITED TO STRUCTURAL, FIRE PROTECTION, COMMUNICATION, MECHANICAL AND ELECTRICAL, CIVIL, STRUCTURAL, AND OTHER DISCIPLINES.
5. ALL PIPING MUST BE NEW, CLEAN, AND FREE FROM SCALE AND DIRT AT TIME OF INSTALLATION.
6. ALL PIPING TO BE SUPPORTED IN ACCORDANCE WITH SPECIFICATIONS.
7. PROVIDE PIPE HANGERS TO SUPPORT ALL PIPING AND THE CONTENTS OF THE PIPING.
8. FOR PIPE SIZES NOT SHOWN ON FLOOR PLANS, SEE SCHEDULES AND/OR DIAGRAMS.
9. ALL SANITARY WASTE PIPING SHOWN ON PLANS MUST BE CONCEALED BELOW SLAB, UNLESS OTHERWISE NOTED.
10. KEEP ALL UNDERGROUND PIPING CLEAR OF FOOTINGS AND FOUNDATION. PROVIDE PIPE SLEEVES LARGE ENOUGH TO ALLOW FOR REQUIRED LATERAL MOVEMENT OF PIPES
PASSING THROUGH MASONRY OR CONCRETE WALLS.
11. ALL DRAINS THAT REMOVE FLOOR WATER MUST HAVE FINAL SLOPE RECHECKED BY THE CONTRACTOR BEFORE THE SURROUNDING SLAB IS POURED.
12. ALL WALL MOUNTED CLEANOUTS MUST BE 18" AFF (TO BOP), UNLESS OTHERWISE NOTED.
13. ALL EXTERIOR CLEANOUTS SHOWN IN PAVED AREAS MUST BE SET FLUSH IN A 24"X24"X8" THICK CONCRETE PAD.
14. ALL WATER PIPING LOCATED IN EXTERIOR WALLS MUST BE RUN ON INTERIOR SIDE OF WALL INSULATION.
15. ALL DOMESTIC WATER PIPING (COLD, HOT AND RECIRCULATION) MUST BE ROUTED TIGHT TO STRUCTURE, IN CEILING SPACE, UNLESS OTHERWISE NOTED.
16. INSTALL PIPING SO THAT ALL VALVES ARE ACCESSIBLE.
17. PROVIDE A WATER HAMMER ARRESTOR ON THE SUPPLY TO EACH QUICK CLOSING VALVE, UNLESS OTHERWISE NOTED.
18. PROVIDE VACUUM BREAKERS ON ALL WALL HYDRANTS, HOSE BIBBS AND THREADED FAUCET SPOUTS.
19. PLUMBING VENTS LOCATED IN EXTERIOR WALLS MUST BE OFFSET 4'-0" IN CEILING AT ROOF PENETRATION.
20. ALL PIPING SHOWN ON PLANS MUST BE CONCEALED ABOVE CEILING OR IN WALLS UNLESS NOTED OTHERWISE.
21. ALL INTERIOR SANITARY CLEAN-OUTS MUST BE SET FLUSH WITH EITHER FINISHED FLOOR OR FINISHED WALLS.
22. DESIGN AND CONSTRUCTION MUST BE PREFORMED IN ACCORDANCE WITH THE CURRENT GOVERNMENT STANDARDS INCLUDING BUT NOT LIMITED TO: PRODUCTS, INSTALLATION AND TESTING. CONTRACTOR MUST BE FAMILIAR WITH STANDARDS UFGS, UFC, AND ECB REQUIREMENTS.
23. CONTRACTOR MUST PROVIDE ROUGH-IN, INTERCONNECTING PIPING, SUITABLE STOPS, CAST BRASS TRAP, AND FINAL CONNECTION AS REQUIRED FOR ALL EQUIPMENT PROVIDED
BY CONTRACTING OFFICER AND/OR OTHERS.
24. ALL VALVES THAT ARE NOT ADJACENT TO THE FIXTURE OR APPLIANCE MUST BE IDENTIFIED, INDICATING THE FIXTURE OR APPLIANCE SERVED.
25. PROVIDE UL LISTED PENETRATIONS SYSTEM AT FIRE RATTED WALLS/ FLOORS/ PARTITIONS.
26. OFFSET PLUMBING PIPING AS NECESSARY TO CLEAR STRUCTURAL FRAMING.
BOTTOMBTM
REQUEST FOR PROPOSALRFP
ELECTRIC WATER COOLEREWC
URINALUR
WATER CLOSETWC
LAVATORYLAV
HOT WATER RECIRCHWR
P-103
GENERAL NOTESLEGEND AND ABBREVIATIONS
DOMESTIC COLD WATER PIPING - CW
SHEET KEYNOTE DESIGNATION
PIPE TURNING UP
PIPE TURNING DOWN
ISOLATION VALVE
WH WALL HYDRANT DESIGNATION
FD-A FLOOR DRAIN DESIGNATION
AFF ABOVE FINISHED FLOOR
CO CLEANOUT
DN DOWN
ELECT ELECTRICAL
FFE FINISHED FLOOR ELEVATION
HGT HEIGHT
KW KILOWATT
NB NICKEL BRONZE
TYP TYPICAL
GPH GALLONS PER HOUR
CHECK VALVE
DIA DIAMETER
APPROX APPROXIMATE
GPF GALLONS PER FLUSH
GAL GALLONS
°F DEGREES FAHRENHEIT
VOL VOLUME
P-1 PLUMBING FIXTURE DESIGNATION
WH-1 WATER HEATER DESIGNATION
VTR VENT THRU ROOF
FD FLOOR DRAIN
LBS POUNDS
THRU THROUGH
UON UNLESS OTHERWISE NOTED
PIPE WITH ISOLATION VALVE IN RISER
PIPE CONTINUATION
DOMESTIC HOT WATER PIPING - HW
DOMESTIC HOT WATER RECIRC PIPING - HWR
SANITARY WASTE PIPING - W
CO CLEANOUT DESIGNATION
ENLARGED PLAN REFERENCE
AFG ABOVE FINISHED GRADE
BLDG BUILDING
FT FEET
HP HORSE POWER
HZ HERTZ
RPM REVOLUTIONS PER MINUTE
DIRECTION OF SLOPE DOWN
WATER HAMMER ARRESTER WITH PDI SYMBOL'A'
DIRECTION OF FLOW
BOP BOTTOM OF PIPE
TEMP TEMPERATURE
RECIRC RECIRCULATION
MANUAL BALANCING VALVE
∅ PHASE
W WASTE
V VENT
HW HOT WATER
PH PHASE
MAX MAXIMUM
MIN MINIMUM
CW COLD WATER
CONT CONTINUATION
DIMEN DIMENSION
IN INCHES
MTG MOUNTING
BFP-1 BACKFLOW PREVENTER
WCO WALL CLEANOUT
ABV ABOVE
WASTE PIPING ISOMETRIC
WATER PIPING ISOMETRIC
BTUH BRITISH THERMAL UNITS PER HOUR
EQUIP EQUIPMENT
F° DEGREE FAHRENHEIT
GPM GALLONS PER MINUTE
NO NUMBER
RM ROOM
SANITARY VENT PIPING - V
HB HOSE BIBB DESIGNATION
ET-1 EXPANSION TANK DESIGNATION
HWRP-1 HOT WATER RECIRC PUMP DESIGNATION
MV-1 MIXING VALVE DESIGNATION
TP-1 TRAP PRIMER DESIGNATION
PROPANE GAS PIPING - GG
AHU-1 AIR HANDLING UNIT
ABA ARCHITECTURAL BARRIER'S ACT
SD SHOWER DRAIN DESIGNATION
EXISTING TO POINT OF DEMOLITION SYMBOL
NEW TO EXISTING SYMBOL
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:1
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-001
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
P
LU
M B
IN
G
L E
G E
N D
S , N
O T
E S
A N
D A
B B
R E
V
IA
T
IO
N S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -0 a p u g lie s e
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881061 358279
LIMIT OF SAWCUT OF
EXISTING STRUCTURE
DISCONNECT EXISTING
PLUMBING-CAP FOR
SHOWER DRAIN
LIMIT OF SAWCUT OF
EXISTING STRUCTURE
LIMIT OF SAWCUT OF
EXISTING STRUCTURE
2"
4"
4"
2"
2"
4" CO
2" CO
1" DOMESTIC CW SERVICE 3
0' 1' 5' 10' 15'1'
1/4"=1'-0"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:1
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
PD101
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
F
LO
O R
P
LA
N P
LU
M
B
IN
G
V
IS
IT
O
R C
O N
T R
O L
C E
N
TE
R
D E
M O
LI
TI
O N
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P D a p u g lie s e
SCALE: 1/4" = 1'-0"
FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - DEMOLITION GRAPHIC SCALE(S)
DEMOLITION KEYNOTES#
1. DISCONNECT EXISTING FIXTURES FOR NEW TO EXISTING CONNECTION OF
SANITARY AND DOMESTIC WATER.
2. DEMOLISH INSTANTANEOUS WATER HEATER, ASSOCIATED WATER PIPING
AND APPURTENANCES.
3. DEMOLISH 1" DOMESTIC CW SERVICE.
4. SANITARY PIPING NOT IN SAWCUT AREA MAY BE CAPPED ABANDONED IN
PLACE.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881062 358280
R E
F
0' 1' 5' 10' 15'1'
1/4"=1'-0"
MECH/ELEC
VESTIBULE
TOILET
MUD ROOM
COMM
LOCKER ROOM
WAITING
OFFICE
INTERVIEW
OFFICE
SHOWER
ADMIN/COPY
SIPRNET
EXIST
BREAKROOM
MV-1
ET-1BFP-1
WH-1
SD
P-1
P-9
FD-A
PROPOSEDEXISTING
WCO
CO
P-2
P-1
P-4
P-5
4"
4"
2"
2"
VC-AHU-1
VC-AHU-2
LAUNDRY
P-8
TOILET
P-2
2"
JANITOR
P-7
P-3
HALLWAY
HALLWAY
MOTHER'S
DAYROOM
HALLWAY
HOUSEKEEPING PAD
FD-A
HALLWAY
FD-A
3" VTR
4"
WCOWCO
4" VTR4
2"
INVERT = 93.4 FT
wco 4"
WCO
RISER 2
RISER 1
RISER 3
RISER 4
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:2
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-101
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
F
LO
O R
P
LA
N P
LU
M
B
IN
G
V
IS
IT
O
R C
O N
TR
O
L C
E N
T E
R
S A
N
IT
A R
Y
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -1 a p u g lie s e
PLAN
NORTH
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
SHEET KEYNOTES#
SCALE: 1/4" = 1'-0"
FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - SANITARY
A. SANITARY WASTE (W) PIPING MUST BE ROUTED IN WALLS AND BELOW
SLAB, UNLESS OTHERWISE NOTED.
B. SANITARY VENT (V) PIPING MUST BE ROUTED IN WALLS AND TIGHT TO
STRUCTURE ABOVE, UNLESS OTHERWISE NOTED.
C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE
SCHEDULE ON SHEET P-601.
D. MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY, SEE
MECHANICAL DRAWINGS.
1. FOR CONTINUATION OF SANITARY PIPE BELOW GRADE, SEE CIVIL UTILITY
PLAN ON SHEET CU101.
2. NON-PERFORATED 4" PVC PASSIVE STACK UP THROUGH ROOF WITH TEE
OPEN TO AGGREGATE BED (PASSIVE RADON MITIGATION). TERMINATE
ABOVE SNOWFALL CLOSURE. SEE RADON PIPING SYSTEM DETAIL ON
SHEET P-501.
3. MATCH EXISTING SANITARY INVERT FOR NEW TO EXISTING CONNECTION.
CONTRACTOR TO FIELD VERIFY.
4. EXISTING 4" VTR. CONTRACTOR TO FIELD VERIFY LOCATION FOR NEW TO
EXISTING CONNECTION.
5. MECHANICAL EQUIPMENT SHOWN FOR CLARITY.
NOTE: FINISHED FLOOR ELEVATION = 95.41 FT.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881063 358281
R E
F
0' 1' 5' 10' 15'1'
1/4"=1'-0"
MECH/ELEC
VESTIBULE
TOILET
MUD ROOM
COMM
LOCKER ROOM
WAITING
OFFICE
INTERVIEW
OFFICE
SHOWER
ADMIN/COPY
SIPRNET
EXIST
BREAKROOM
MV-1
ET-1
BFP-1
WH-1
SD
P-1
P-9
FD-A
PROPOSEDEXISTING
2" CW SERVICE
BUILDING MAIN
ISOLATION VALVE
HB
HWRP-1
3/4"
1 1/4"
2"
VC-AHU-1
VC-AHU-2
3/4"
G
PROPANE GAS LINE ENTRANCE.
SEE CIVIL SITE UTILITY PLAN FOR
LOCATION OF PROPANE GAS TANK.
P-6
P-5
P-4
P-1
P-2
3/4"
WM-1
WH
WH
TOILET
MOTHER'S
P-8
P-3
P-7
P-2
ID/CHECK-IN
HALLWAY
DAYROOM
HALLWAY
HALLWAY
JANITOR
HOUSEKEEPING PAD
FD-A
HALLWAY
FD-A
VC-UH-1
3/4"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:2
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-102
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
F
LO
O R
P
LA
N P
LU
M
B
IN
G
V
IS
IT
O
R C
O N
T R
O L
C E
N
TE
R
D O
M E
S T
IC
W
A
TE
R
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -1 a p u g lie s e
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
SHEET KEYNOTES#
SCALE: 1/4" = 1'-0"
FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - DOMESTIC WATER
PLAN
NORTH
A. DOMESTIC WATER (CW, HW, AND HWR) PIPING MUST BE ROUTED IN
WALLS AND TIGHT TO STRUCTURE ABOVE, UNLESS OTHERWISE
NOTED.
B. PROPANE GAS (G) PIPING MUST BE ROUTED TIGHT TO STRUCTURE
ABOVE, UNLESS OTHERWISE NOTED.
C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE
SCHEDULE ON SHEET P-601.
D. MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY, SEE
MECHANICAL DRAWINGS.
1. PROVIDE TRAP PRIMER SERVING FLOOR DRAIN. SEE AUTOMATIC TRAP
PRIMER DETAIL ON SHEET P-501.
2. ROUTE FULL SIZE DISCHARGE FROM BACKFLOW PREVENTER TO FLOOR
DRAIN WITH 2" AIR GAP. SEE WATER SERVICE DETAIL ON SHEET P-503.
3. FOR CONTINUATION OF DOMESTIC COLD WATER SERVICE PIPE BELOW
GRADE, SEE CIVIL UTILITY PLAN ON SHEET CU101.
4. PROVIDE ISOLATION VALVE, MANUAL BALANCING VALVE AND CHECK
VALVE FOR END OF RUN DOMESTIC HOT WATER RECIRC PIPING LOOP.
SEE MANUAL BALANCING VALVE DETAIL ON SHEET P-501.
5. FOR CONTINUATION OF PROPANE GAS PIPE BELOW GRADE SEE CIVIL
UTILITY PLAN .
6. PROVIDE PROPANE GAS PIPE CONNECTION TO EQUIPMENT. SEE GAS
PIPING CONNECTION DETAIL ON SHEET P-503 AND GAS PIPING DIAGRAM
ON SHEET P-502.
7. MECHANICAL EQUIPMENT SHOWN FOR CLARITY.
8. PROVIDE 12"x12" CEILING ACCESS PANEL FOR ACCESS TO ISOLATION
VALVE FOR WALL HYDRANT.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881064 358282
0' 1' 5' 10' 15'1'
1/4"=1'-0"
STOR/JAN
CORR
WAITING
INSPECTION
OFFICE
RFI/SECURE
ROOM
RESTROOM
MECH/ELEC
ET-2
FD-A
WCO
P-4
3"
MV-2
COMM
WCO
WH-2
3" VTR
4"
4"
INVERT = -7.2'
4"
2"
BREAKROOM
P-7
P-2
P-1
B C D
CO
2"
PIPE TURN DOWN TO INVERT
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:2
:3
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \I n s p e c ti o n S ta ti o n
W
P
C u tl e r_
IS
P
L U
M R
.r v t
P-103
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
F
LO
O R
P
LA
N P
LU
M
B
IN
G
IN
S
P E
C
TI
O N
S
TA
TI
O
N
S A
N
IT
A R
Y
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D C
C O
R E
P -1 a p u g lie s e
PLAN
NORTH
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
SHEET KEYNOTES#
SCALE: 1/4" = 1'-0"
FLOOR PLAN PLUMBING - INSPECTION STATION - SANITARY
A. SANITARY WASTE (W) PIPING MUST BE ROUTED IN WALLS AND BELOW
SLAB, UNLESS OTHERWISE NOTED.
B. SANITARY VENT (V) PIPING MUST BE ROUTED IN WALLS AND TIGHT TO
STRUCTURE ABOVE, UNLESS OTHERWISE NOTED.
C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE
SCHEDULE ON SHEET P-601.
D. MECHANICAL AND ELECTRICAL EQUIPMENT SHOWN FOR REFERENCE
ONLY, SEE MECHANICAL DRAWINGS.
NOTE: FINISHED FLOOR ELEVATION = 0.0 FT. FOR ACTUAL FIRST FLOOR ELEVATION OF THE STRUCTURE REFER TO CIVIL SITE DRAWINGS.
1. FOR CONTINUATION OF SANITARY PIPE BELOW GRADE, SEE CIVIL UTILITY
PLAN ON SHEET CU101.
2. NON-PERFORATED 4" PVC PASSIVE STACKUP THROUGH ROOF WITH TEE
OPEN TO AGGREGATE BED (PASSIVE RADON MITIGATION). TERMINATE
ABOVE SNOWFALL CLOSURE. SEE RADON PIPING SYSTEM DETAIL ON
SHEET P-501.
3. SANITARY INVERT TO BE BELOW THE FROST PENETRATION OF 86 INCHES
(7.2FT).
4. STORM GUTTERS / DOWNSPOUTS SHOWN FOR COORDINATION
PURPOSES. SEE ARCHITECTURAL DRAWINGS AND CIVIL DRAWINGS FOR
ADDITIONAL DETAIL AND FURTHER COORDINATION.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881065 358283
0' 1' 5' 10' 15'1'
1/4"=1'-0"
STOR/JAN
CORR
BREAKROOM
WAITING
INSPECTION
OFFICE
RFI/SECURE
ROOM
RESTROOM
MECH/ELEC
ET-2
FD-A
WH
HB
HWRP-2
P-4
WH
BUILDING MAIN
ISOLATION VALVE
MV-2
3/4"
IS-AHU-1
PROPANE GAS LINE
ENTRANCE. SEE CIVIL SITE
UTILITY PLAN FOR LOCATION
OF PROPANE GAS TANK.
P-6
3/4"
G
2" CW
SERVICE
WH-2
P-2
P-1
ELECTRICAL
PANELS (REF ONLY)
WM-2
P-7
B C D
BFP-2 IS-UH-1
G
G
3/4"
1 1/2"
3/4"
ELECTRICAL
PANELS (REF ONLY)
7 7
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:2
:4
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \I n s p e c ti o n S ta ti o n
W
P
C u tl e r_
IS
P
L U
M R
.r v t
P-104
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
F
LO
O R
P
LA
N P
LU
M
B
IN
G
IN
S
P E
C T
IO
N
S T
A T
IO
N
D
O M
E S
T
IC
W A
TE
R
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D C
C O
R E
P -1 a p u g lie s e
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
SHEET KEYNOTES#
SCALE: 1/4" = 1'-0"
FLOOR PLAN PLUMBING - INSPECTION STATION - DOMESTIC WATER
PLAN
NORTH
A. DOMESTIC WATER (CW, HW, AND HWR) PIPING MUST BE ROUTED IN
WALLS AND TIGHT TO STRUCTURE ABOVE, UNLESS OTHERWISE
NOTED.
B. PROPANE GAS (G) PIPING MUST BE ROUTED TIGHT TO STRUCTURE
ABOVE, UNLESS OTHERWISE NOTED.
C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE
SCHEDULE ON SHEET P-601.
D. MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY, SEE
MECHANICAL DRAWINGS.
1. PROVIDE TRAP PRIMER SERVING FLOOR DRAIN. SEE AUTOMATIC TRAP
PRIMER DETAIL ON SHEET P-501.
2. ROUTE FULL SIZE DISCHARGE FROM BACKFLOW PREVENTER TO FLOOR
DRAIN WITH 2" AIR GAP. SEE WATER SERVICE DETAIL ON SHEET P-503.
3. FOR CONTINUATION OF DOMESTIC COLD WATER SERVICE PIPE BELOW
GRADE, SEE CIVIL UTILITY PLAN ON SHEET CU101.
4. PROVIDE ISOLATION VALVE, MANUAL BALANCING VALVE AND CHECK
VALVE FOR END OF RUN DOMESTIC HOT WATER RECIRC PIPING LOOP.
SEE BALANCING VALVE DETAIL ON SHEET P-501.
5. FOR CONTINUATION OF PROPANE GAS PIPE BELOW GRADE SEE CIVIL
UTILITY PLAN ON SHEET CU101.
6. PROVIDE PROPANE GAS PIPE CONNECTION TO EQUIPMENT. SEE GAS
PIPING CONNECTION DETAIL AND GAS PIPING DIAGRAM ON SHEET P-503,
AND GAS PIPING DIAGRAM - INSPECTION STATION ON SHEET P-502.
7. STORM GUTTERS / DOWNSPOUTS SHOWN FOR COORDINATION
PURPOSES. SEE ARCHITECTURAL DRAWINGS AND CIVIL DRAWINGS FOR
ADDITIONAL DETAIL AND FURTHER COORDINATION.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881066 358284
BACK TO HOT WATER RECIRC PUMP
MANUAL BALANCING VALVE
WITH TEST PORTS (1/2" VENTURI VALVE)
ISOLATION VALVE (TYP.)
NOTE:
1. BALANCING VALVE ON END OF RUN LOOP MUST BE SET AT 1.0 GPM EACH.
TO
PLUMBING
FIXTURES
UNION (TYP)
FROM HOT WATER
GENERATION
SYSTEM
CHECK VALVE (TYP.)
3/4"
FINISH GRADE
LENGTH VARIES
W/ DEPTH OF
INVERT BELOW
SURFACE
INVERT
CAST IRON COVER
AND FRAME
8"
2'-0" SQUARE
CONCRETE
PIPE SIZE SAME
AS SERVICE
LINE
UPPER END OF SERVICE LINE
COLD WATER
GATE VALVE (TYP)
FINISH
FLOOR1/2"
SUPPORT VERTICALLY
AS REQUIRED ON
WALL
AUTOMATIC
TRAP PRIMER
NOTE:
1. TRAP PRIMER VALVE MUST BE
INSTALLED A MINIMUM OF 12"
ABOVE THE FLOOD PLANE OF THE
FIXTURE BEING SERVED.
SEE FLOOR DRAIN
DETAIL. (THIS
SHEET)
SEE FLOOR DRAIN
SCHEDULE P-602, FOR
STRAINER & GRATE
TYPE
FINISH FLOOR
4" DEEP SEAL TRAP SEE FLOOR DRAIN
SCHEDULE P-602, FOR
PIPE SIZE
SET RIM OF GRATE
FLUSH WITH
FINISHED FLOOR
SEE FLOOR DRAIN
SCHEDULE P-602, FOR
MODEL NUMBER
SEE
AUTOMATIC
TRAP PRIMER
DETAIL. (THIS
SHEET)
MULTIPLE PIPE RUNS SINGLE PIPE RUN
INSULATION
SADDLE (TYP)
STEEL PIPE
STRAP
BOLT AND
CLAMPING
NUT (TYP.)
LENGTH AS REQUIRED
STEEL CHANNEL
CLEVIS HANGER
(SIZE AS
REQUIRED)
THREADED
ROD
INSULATION SADDLE
SUPPORT FROM
STRUCTURE
THREADED ROD
SUPPORT FROM
STRUCTURE
4" RADON
VENT PIPE
SLAB ON GRADE
4" PASSIVE
RADON STACK
THROUGH ROOF
ROOF
FLASHING ELECTRICAL JUNCTION
BOX (IN CASE OF FAN NEEDED
TO ACTIVATE THE SYSTEM)
FILL
AGGREGATE BED
TEE OPEN TO
AGGREGATE BED
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:3
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-501
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
P
LU
M B
IN
G
D E
T A
IL
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -5 a p u g lie s e
NOT TO SCALE
MANUAL BALANCING VALVE DETAIL
NOT TO SCALE
EXTERIOR TWO-WAY CLEANOUT DETAIL
NOT TO SCALE
AUTOMATIC TRAP PRIMER DETAIL
NOT TO SCALE
FLOOR DRAIN DETAIL
NOT TO SCALE
TYPICAL PIPE SUPPORT DETAIL
NOT TO SCALE
RADON PIPING SYSTEM DETAIL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881067 358285
EXTERIOR
BACKER ROD
WATERPROOF SEALANT
INTERIOR
INSULATION
PIPE
WALL
NOTE:
1. WHERE PIPE IS PENETRATING A FIRE-RATED
PARTITION, PROVIDE UL APPROVED FIRE CAULK.
STAINLESS
STEEL
DRAWBAND
ESCUTCHEON
PLATES WHERE
EXPOSED
PACK WITH
FIBERGLASS AND
SEAL BOTH SIDES
PIPE SLEEVE (SET
AND ANCHOR
DURING WALL
CONSTRUCTION)
PIPE
FINISHED FLOOR
LINK-SEAL PLATE
CAST-IN-PLACE PIPE SLEEVE
AND LINK-SEAL
NOTE:
1. WHERE PIPE IS PENETRATING A FIRE-RATED
PARTITION, PROVIDE UL APPROVED FIRE CAULK.
BACKER ROD
WATERPROOF SEALANT
INSULATION
PIPE
WALL
ESCUTCHEON
PLATES WHERE
EXPOSED
PACK WITH
FIBERGLASS AND
SEAL BOTH SIDES
PIPE SLEEVE (SET
AND ANCHOR
DURING WALL
CONSTRUCTION)
INSULATION
VC-AHU-1
(60 CFH)
3/4" PROPANE GAS MAIN
SERVING BUILDING FROM LP-
GAS TANK
BUILDING
EXTERIOR
WALL
FINISH FLOOR
G
G
SEE GAS PIPING CONNECTION
DETAIL. (SHEET P-503)
G
GRADE
NOTES:
1. EXHAUST VENT MUST TERMINATE ON EXTERIOR OF BUILDING A MINIMUM OF 3 FT. ABOVE INTAKES OR 10 FT AWAY FROM INTAKES.
2. CONTRACTOR MUST COORDINATE INCOMING GAS PRESSURE SERVICE WITH UTILITY PROVIDER AND PROVIDE SECONDARY
REGULATOR AS REQUIRED.
3/4"
3/4"
VC-AHU-2
(60 CFH)
G
EXHAUST TO
ATMOSPHERE. SEE
MECHANICAL FOR
ROUTING AND
TERMINATION.
3/4"
EXHAUST AND INTAKE TO
ATMOSPHERE. SEE
MECHANICAL FOR
ROUTING AND
TERMINATION.
DIELECTRIC COUPLING
3/4"
VC-UH-1
(12 CFH)
IS-AHU-1
(80 CFH)
BUILDING
EXTERIOR
WALL
FINISH FLOOR
G
SEE GAS PIPING CONNECTION
DETAIL. (SHEET P-503)
G
GRADE
NOTES:
1. EXHAUST VENT MUST TERMINATE ON EXTERIOR OF BUILDING A MINIMUM OF 3 FT.
ABOVE INTAKES OR 10 FT AWAY FROM INTAKES.
2. CONTRACTOR MUST COORDINATE INCOMING GAS PRESSURE SERVICE WITH UTILITY
PROVIDER AND PROVIDE SECONDARY REGULATOR AS REQUIRED.
3/4"
EXHAUST TO ATMOSPHERE. SEE
MECHANICAL FOR ROUTING AND
TERMINATION.
G
DIELECTRIC COUPLING
3/4" PROPANE GAS MAIN
SERVING BUILDING FROM LP-
GAS TANK
G
3/4"
IS-UH-1
(12 CFH)
3/4"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:3
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-502
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
P
LU
M B
IN
G
D E
T A
IL
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -5 a p u g lie s e
NOT TO SCALE
TYPICAL PIPE SLEEVE THRU EXTERIOR WALL DETAIL
NOT TO SCALE
TYPICAL PIPE PENETRATION THRU SLAB DETAIL
NOT TO SCALE
TYPICAL PIPE THRU INTERIOR WALL DETAIL
NOT TO SCALE
GAS PIPING DIAGRAM - VISITOR CONTROL CENTER
NOT TO SCALE
GAS PIPING DIAGRAM - INSPECTION STATION
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881068 358286
STRAINER
BFP-1 (VISITOR'S CENTER)
BFP-2 (INSPECTION STATION)
MINIMUM 18"
MAIN BUILDING
ISOLATION VALVE
2"
DISCHARGE TO
FLOOR DRAIN.
TO SITE
DRAIN DN
UNION (TYP)
NOTE:
1. SEE CIVIL DRAWING SITE UTILITY PLAN FOR ADDITIONAL INFORMATION, AND DEPTH OF BURY.
2" TO BUILDING
M
WM-1 (VISITOR'S CENTER)
WM-2 (INSPECTION STATION)
CONCENTRIC
REDUCER (TYP)
* STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE WITHOUT INLINE APPURTENANCES MUST BE
INSTALLED UP / DOWNSTREAM OF FLOW CONTROL BALANCING VALVE PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
NOTES:
1. SECURELY FASTEN AQUASTAT TO HOT WATER RECIRC. PIPE.
2. SEE ELECTRICAL DRAWINGS FOR WIRING.
3. PROVIDE AUTOMATIC TIMER KIT/AQUASTAT WITH ABILITY TO CONTROL PUMP AS FOLLOWS:
UNION (TYP.)
PUMP
MOTOR WITH
TIMER
NORMALLY
CLOSED
PUMP SUCTION AND DISCHARGE FLANGE
TAP, FOR PRESSURE GAUGE CONNECTIONS
PRESSURE
GAUGE
NEEDLE
VALVE
MANUAL
BALANCING VALVE
WITH TEST PORTS
CHECK
VALVE
AUTOMATIC TIMER
KIT/AQUASTAT
ISOLATION VALVE
(TYP)
• ADI 24/7 TIME CLOCK
> OCCUPIED MODE = PUMP ON
> UNOCCUPIED MODE = PUMP OFF
• TEMPERATURE CONTROL
> 110°F TEMP = PUMP OFF
> 100°F TEMP = PUMP ON
WH-1
ET-1
MV-2
FINISHED FLOOR
DRIP PAN MUST BE
CONSTRUCTED OF
HEAVY GAUGE
GALVANIZED STEEL
0°
F 14 0°
F
MANUAL BALANCING
VALVE (TYP)
THERMOMETER
HOUSEKEEPING
PAD
ROUTE FULL
SIZE DISCHARGE
TO NEAREST
FLOOR DRAIN.
DIELECTRIC HEAT
TRAP UNION
(TYP)
PRESSURE/
TEMPERATURE
RELIEF VALVE
SEE HOT WATER
RECIRC PUMP
PIPING DETAIL
THIS SHEET.
HWRP-1, HWRP-2
HEAT TRAP
27" DROP
CHECK
VALVE (TYP)
VACUUM
BREAKER
ISOLATION
VALVE (TYP)
UNION (TYP)
1"3/4"
1"
1"
1-1/4"
1/2"
3/4"
HEAT PUMP
WATER HEATER
1"
WH-2
ET-2
MV-1
2" CW FROM BLDG
1 1/4" HW TO BLDG
3/4" HWR FROM BLDG
G
VENT TO ATMOSPHERE. TERMINATE
RELIEF VENT 3'-0" ABOVE INTAKE OR
10' AWAY FROM ALL OUTSIDE AIR INTAKES
GAS SHUT-OFF
(FIELD SUPPLIED
OUTSIDE OF
EQUIPMENT CABINET)
6" DIRT
LEG
MINIMUM
UL LISTED GAS TRAIN WITH
REGULATOR AS RECOMMENDED BY
EQUIPMENT MANUFACTURER.
FIELD SUPPLIED
GROUND UNION (TYP)
GAS FIRED
EQUIPMENT
WATER HAMMER ARRESTOR SCHEDULE
PDI SYMBOL
FIXTURE UNIT
RATING
A
1-11
B
12-32 33-60
C
61-113
D E
114-154 155-330
F
SUPPLY RISER
TYPICAL BRANCH LINE
WATER HAMMER
ARRESTOR
PDI SYMBOL
PDI "A"
NOTES:
1. PREFERRED INSTALL WATER HAMMER ARRESTORS AT THE END OF BRANCH LINE
BETWEEN THE LAST TWO FIXTURES SERVED.
2. ONE WATER HAMMER ARRESTOR PER 20' LINE, AND ANOTHER FOR BRANCHES
OVER 20' IN LENGTH.
3. THE SUM OF FIXTURE UNIT RATING OF UNITS OVER 20' IN LENGTH SHALL BE EQUAL
TO OR GREATER THAN THE DEMAND OF THE BRANCHES.
4. ARRESTERS SHALL BE APPROVED FOR INSTALLATION WITH NO ACCESS PANEL
REQUIRED.
PIPE SIZE 3/4" 1" 1" 1" 1" 1"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:4
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-503
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
P
LU
M B
IN
G
D E
T A
IL
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -5 a p u g lie s e
NOT TO SCALE
WATER SERVICE ENTRANCE DETAIL
NOT TO SCALE
HOT WATER RECIRC PUMP PIPING DETAIL
NOT TO SCALE
DOMESTIC HOT WATER PIPING DIAGRAM
NOT TO SCALE
GAS PIPING CONNECTION DETAIL
NOT TO SCALE
WATER HAMMER ARRESTOR DETAIL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881069 358287
MTG HGT
18" AFF
COUNTER
MATERIAL
FIXTURE
PIPE SIZES
W V HW CW
NOTES
3/4"- - -
1/2"1-1/2" 1-1/2" 1/2"
MARK
HB
P-5
1.5 GPM
HOSE BIBB
BREAKROOM SINK SINGLE
COMPARTMENT UNDER MOUNT
(ADAAG COMPLIANT)
PLUMBING FIXTURE SCHEDULE
STAINLESS
STEEL
P-1
P-3
WATER CLOSET
(ADAAG COMPLIANT)
VITREOUS CHINA 1"3" 2" -- 1.28 GPF
RIM @
16-1/2" AFF
P-4
18" AFG- 3/4"- - -WH - -WALL HYDRANT 7
WASHING MACHINE BOX
GENERAL NOTES:
A. ALL FIXTURES NOTED AS "ADAAG COMPLIANT" MUST MEET THE AMERICAN BARRIER ACT FOR BUILDING AND FACILITIES (ABA) STANDARDS FOR CONSTRUCTION, LOCATION, AND
MOUNTING HGTS.
B. PROVIDE ALL FIXTURE ACCESSORIES REQUIRED FOR INSTALLATION OF A COMPLETE, FUNCTIONAL SYSTEM.
C. CONTRACTING OFFICER TO SELECT OR CONFIRM COLOR OF ALL PLUMBING FIXTURES.
D. ROUGH-IN AND CONNECT PIPING TO ALL PLUMBING ITEMS IN ACCORDANCE WITH THE INTERNATIONAL PLUMBING CODE.
E. PROVIDE SELECTION PER BASIS OF DESIGN OR APPROVED EQUAL.
FIXTURE SPECIFIC NOTES:
1. PROVIDE FLOOR MOUNTED, MANUAL FLUSH VALVE TYPE, WATER CLOSET WITH OPEN FRONT SEAT.
2. PROVIDE WALL HUNG LAVATORY WITH CARRIER SUPPORT WITH ADJUSTABLE P-TRAPS AND PERFORATED GRID STRAINER. FAUCETS MUST BE SINGLE LEVER WRISTBLADE, EPA
“WATERSENSE” LABELED WITH AERATOR.
3. PROVIDE TRAP AND SUPPLY PIPE WITH INSULATION GUARD.
4. PROVIDE ANTI-SCALD MIXING VALVE, ADJUSTABLE SHOWER HEAD, ROD AND ACCESORIES.
5. PROVIDE STAINLESS STEEL, UNDER MOUNT, MINIMUM 6" DEEP. PROVIDE ADJUSTABLE P-TRAP WITH DRAIN PIPING TO VERTICAL VENT STACK. PROVIDE WITH 1.5 GPM AERATOR.
PROVIDE GOOSENECK FAUCET. PROVIDE UL LISTED GARBAGE DISPOSAL.
6. PROVIDE FIRE RATED BOX WITH DRAIN KIT, QUARTER TURN SUPPLY VALVES WITH HOSE CONNECTIONS AND INTEGRAL SHOCK ARRESTORS WITH DEEP SEAL TRAP, NICKEL BRONZE
STRAINER AND BARRIER TYPE TRAP SEAL PROTECTION DEVICE (TRAP GUARD); 8" DIAMETER STRAINER.
7. PROVIDE FREEZE PROOF WALL HYDRANTS, WITH AN INTEGRAL VACUUM BREAKER/BACKFLOW PREVENTER HYDRANTS MUST HAVE 3/4 INCH HOSE CONNECTIONS AND LOOSE TEE KEY
HANDLE.
8. PROVIDE ANGLE TYPE COPPER ALLOY HOSE BIBB WITH LOCKSHIELD AND HANDWHEEL, 3/4" EXTERNAL HOSE THREADS. PROVIDE INTEGRAL VACUUM BREAKER.
9. PROVIDE RECESSED WALL BOX WITH FACEPLATE AND SCREWS. UNIT MUST INCLUDE 1/2" LEAD FREE 1/4 TURN VALVE WITH WATER HAMMER ARRESTOR.
10. SERVICE SINK MUST BE CONSTRUCTED OF 18 GAUGE, TYPE 304 STAINLESS STEEL WITH A SATIN FINISH. SIZE: 20" W x 20" L SINGLE COMPARTMENT. SINK COMPARTMENT MUST BE
MINIMUM 12" DEEP WITH ROLLED EDGES AND WITH MINIMUM 8" BACK-SPLASH FOR FAUCET WITH 8" CENTERS. SINKS MUST BE FLOOR SUPPORTED ON GALVANIZED OR STAINLESS STEEL LEGS WITH 1" ADJUSTABLE FEET. PROVIDE BACK MOUNTED COMBINATION FAUCET WITH VACUUM BREAKER, AND 3/4" EXTERNAL HOSE THREADS.
11. PROVIDE WALL HUNG URINAL WITH INTEGRAL TRAP AND EXTENDED SHIELDS, ASME A112..19.2M, SIPHON JET, TOP SUPPLY CONNECTION, BACK OUTLET, URINAL FLOOR SUPPORTED
CHAIR CARRIER SUPPORTS WITH HANGERS AND MANUAL FLUSH VALVE.
12. PROVIDE STAINLESS STEEL, UNDER MOUNT, MAXIMUM 6" DEEP. PROVIDE ADJUSTABLE P-TRAP WITH DRAIN PIPING TO VERTICAL VENT STACK. PROVIDE WITH 1.5 GPM AERATOR.
PROVIDE GOOSENECK FAUCET.
6-
SIZE (IN.) FLOW RATE
P-2
WALL HUNG
LAVATORY
(ADAAG COMPLIANT)
RIM @ 34" AFFVITREOUS CHINA 1/2"1-1/2" 1-1/2" 1/2"0.5 GPM 2, 3
SHOWER
(ADAAG COMPLIANT)
- - - 1.5 GPH
1/2"2" 1-1/2" 1/2" 4
STAINLESS
STEEL
42" AFF- 1/2"2" 1-1/2" 1/2"
P-6 ICEMAKER BOX 9-
STAINLESS
STEEL
BOTTOM OF BOX
24" AFF
- 1/2"- - -
- 2" 1-1/2"1.5 GPMSERVICE SINK
STAINLESS
STEEL
10P-7 -
COUNTER 1-1/2"1.5 GPM
STAINLESS
STEEL
12P-8 -
MOTHER'S SINK SINGLE
COMPARTMENT UNDER MOUNT
(ADAAG COMPLIANT)
P-9
WALL HUNG URINAL
(ADAAG COMPLIANT)
RIM @ 17" AFFVITREOUS CHINA 2" 1-1/2"0.125 GPM 11- - 3/4"
1/2"1/2"2"
1/2"1/2"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:4
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-601
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
P
LU
M B
IN
G
S C
H E
D U
LE
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -6 a p u g lie s e
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881070 358288
MARK
ET-1 DIAPHRAGM 6 1.8 60 VERTICAL
DOMESTIC HOT
WATER
TYPE CONFIGURATION LOCATION SERVICE
MIN TANK
VOLUME
(GAL.)
MIN
ACCEPTANCE
VOLUME (GAL.)
AIR
CHARGE
(PSIG)
NOTES:
1. UNITS MUST BE ASME RATED PRECHARGED DIAPHRAGM TYPE PRESSURE VESSEL.
2. TANK MUST BE RATED FOR POTABLE WATER SYSTEM.
3. UNIT MUST HAVE MAXIMUM DESIGN PRESSURE OF 125 PSI WITH A DESIGN TEMPERATURE OF 240°F.
4. APPROX. DIMEN. (DIA. X LENGTH) 16-1/4"Ø X 19-1/8"
MECHANICAL ROOM - 109
VISITOR CONTROL CENTER
NOTESLOCATIONGPM
PRESSURE
DROP
FT HDAMPS
ELECTRICAL DATA
VOLTS/PH/HZ
TYPEMARK
1, 2, 3210.66120/ 1/ 60INLINEHWRP-1
NOTES:
1. PROVIDE AQUASTAT & TIME CLOCK WITH PLUG.
2. PUMP MUST BE BRONZE CONSTRUCTION.
3. PROVIDE PUMP SUITABLE FOR USE IN POTABLE SYSTEMS.
LOCATIONMARK
BFP-1
NOTES
1, 2
SYSTEM
DOMESTIC
WATER
MAXIMUM
PRESSURE
DROP (PSI)
SYSTEM
FLOW
(GPM)
SIZE
2"
MV-1
MARK TYPE
HIGH-LOW
WATER MIXER
MAX PRESSURE
DROP (PSI)
CAPACITY
15 GPM
SET POINT
110°F
LOCATION
1, 2, 3, 4
NOTES
FLOW (GPM)
1 15
MIN. MAX.
INLET
1"
CW HW
1-1/2"
TEMPID
OUTLET
PIPE CONNECTION SIZE
NOTES:
1. PROVIDE LEAD FREE TYPE WITH BRONZE FINISH.
2. PROVIDE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP, INLET CHECK STOPS, OUTLET BALL VALVE, INLET THERMOMETERS AND MANIFOLD PIPING.
3. PROVIDE LOCKING TEMPERATURE REGULATOR WITH PROTECTION AGAINST HOT OR COLD WATER SUPPLY LINE FAILURE AND THERMOSTAT FAILURE.
4. PROVIDE FACTORY ASSEMBLED AND TESTED MIXING VALVE. INSTALL IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
NOTES:
1. PROVIDE REDUCED PRESSURE TYPE BACKFLOW PREVENTER WITH AIR GAP DRAIN. ASSEMBLY MUST
INCLUDE STRAINER, SHUTOFF VALVES, RELIEF VALVE AND AIR GAP FITTING.
2. UNIT MUST COMPLY TO "LEAD FREE" REQUIREMENTS.
LOCATIONMARK NOTES
PIPE
SIZE
NOTE:
1. PROVIDE ROUND NB STRAINER, SET RIM FLUSH WITH FINISH FLOOR. PROVIDE WITH TRAP
PRIMER.
EXPANSION TANK SCHEDULE
HOT WATER RECIRCULATING PUMP SCHEDULE
BACKFLOW PREVENTER SCHEDULE
THERMOSTATIC MIXING VALVE SCHEDULE
FLOOR DRAIN SCHEDULE
FD-A 1MECHANICAL ROOM 4"
TYPE
REDUCED PRESSURE ZONE
ASSEMBLY
1"
MECHANICAL ROOM - 109
VISITOR CONTROL CENTER
MV-2
HIGH-LOW
WATER MIXER
11 GPM 110°F 1, 2, 3, 41 18 3/4" 3/4"10
1, 2, 3, 4
NOTES
ET-2 DIAPHRAGM 4 1.0 VERTICAL
DOMESTIC HOT
WATER
MECHANICAL ROOM - 110
INSPECTION STATION 1, 2, 3, 4
MECHANICAL ROOM - 110
INSPECTION STATION
210.66120/ 1/ 60INLINEHWRP-2 1, 2, 3
3/4"
BFP-2 1, 2
DOMESTIC
WATER
10402"
REDUCED PRESSURE ZONE
ASSEMBLY
MECHANICAL ROOM - 109
VISITOR CONTROL CENTER
MECHANICAL ROOM - 110
INSPECTON STATION
MECHANICAL ROOM - 109
VISTITOR CONTROL CENTER
MECHANICAL ROOM - 110
INSPECTION STATION
SD -SHOWER 2"
METER SCHEDULE
NOTE:
1. WATER METER: ADVANCED WATER METER, NON-RESETTABLE WITH REMOTE READ-OUT. (TURBINE TYPE)
MARK SYSTEM NOTES
WM-1
44 GPM @10 PSI
MAX PD
1DOMESTIC WATER
REQUIRED @
BUILDING
TYPE
ELECTRONIC PULSE
OUTPUT
LOCATION
MECHANICAL ROOM - 109
VISITOR CONTROL CENTER
WM-2
40 GPM @10 PSI
MAX PD
1DOMESTIC WATER
ELECTRONIC PULSE
OUTPUT
MECHANICAL ROOM - 110
INSPECTION STATION
SIZE
2"
2"
NOTES
LOCATION
VOLTS/ PH/ HZ
208/1/60
ELECTRICAL DATA
WATER HEATER SCHEDULE
MARK
WH-1
MECHANICAL ROOM - 109
VISITOR CONTROL
CENTER
AMP
13.7
NOTE:
1. WATER HEATERS MUST MEET OR EXCEED THE REQUIREMENTS OF ASHRAE 90.1-2013 STANDARD FOR ENERGY EFFICIENCY.
TYPE
HEAT PUMP
RECOVERY
25 GPH
TEMPERATURE
RISE ºF
100ºF
TEMPERATURE
DELIVERY
SETPOINT ºF
140ºF
CAPACITY
(GAL)
208/1/60WH-2
MECHANICAL ROOM - 110
INSPECTION STATION
HEAT PUMP 13.2 GPH 100ºF 140ºF 40 113.7
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:5
P M
U P ro je c ts
\2
\2 -0
C u tl e r, M E
P e ri m e te r S e c u ri ty
\0
S U
B M
IT
T
A L S
\0
F in a l S ig n e d
M a r
\R e v it \V is it o rs
C e n te r\
W
P
C u tl e r_
V C
P
L U
M R
.r v t
P-602
P -3
P
E R
IM
E
TE
R
S E
C U
R
IT
Y
P
LU
M B
IN
G
S C
H E
D U
LE
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N
TS
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T
LE
R , M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -6 a p u g lie s e
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
12881071 358289
P-1
P-4 P-2
P-5
SD
P-9
P-1
FD-A
WCO
CO
4"
4"
2"
2"
P-3
2"
2"
2"
2"
4"
P-2
P-7
P-8
2"
FD-A
FD-A
3" VTR
4"
WCO
WCO
4" VTR
2"
4"
4"
WCO
2"
RISER 1
RISER 2
RISER 3
RISER 4
2"
EXISTING
WCO
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:5
P
M U
P ro je ct s\
\2
-0
C u tle r, M E
P e ri m et e r S ec u ri ty
\0
S
U B
M
IT
T A
L S
\0
F in a l S ig ne d
M a r
\R e vi t\
V is ito rs
C e n te r\
W
_P
C u tle r_ V
C
P
LU
M
R
.r vt
P-901
P -3
P
E R
IM
E
T E
R S
E C
U R
IT
Y
P L
U M
B
IN
G
IS
O M
E
TR
IC
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N T
S
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T L
E R
M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -9 a p u g li e s e
NOT TO SCALE
VISITOR CONTROL CENTER - SANITARY ISOMETRICS
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881072 358290
P-1 P-4
P-2
P-9 P-1
FD-A
HB
BFP-1
WM-1
MV-1
TRAP PRIMER
P-6
P-5
WH
WH
2"
3/4"
1 1/4"
3/4"
3/4"
3/4"
1"
1 1/2" 1"
PROVIDE ISOLATION VALVE, BALANCING VALVE
AND CHECK VALVE FOR END OF RUN DOMESTIC
HOT WATER RECIRC PIPING LOOP. SEE MANUAL
BALANCING VALVE DETAIL ON SHEET P-501.
SEE DOMESTIC HOT WATER
PIPING DIAGRAM DETAIL ON
SHEET P-503.
2" DOMESTIC COLD WATER
SERVICE, SEE CIVIL UTILTIY FOR
CONTINUATION AND WATER
SERVICE ENTRANCE DETAIL ON
SHEET P-503.
P-2
P-7
P-8
1"
1 1/2"
1"1"
P-3
1"
WH-A
WH-A
1 1/2"
TRAP PRIMER
3/4"3/4"
FD-A
FD-A
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:3
:0
P
M U
P ro je ct s\
\2
-0
C u tle r, M E
P e ri m et e r S ec u ri ty
\0
S
U B
M
IT
T A
L S
\0
F in a l S ig ne d
M a r
\R e vi t\
V is ito rs
C e n te r\
W
_P
C u tle r_ V
C
P
LU
M
R
.r vt
P-902
P -3
P
E R
IM
E
T E
R S
E C
U R
IT
Y
P L
U M
B
IN
G
IS
O M
E
TR
IC
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N T
S
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T L
E R
M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D I
C O
R E
P -9 a p u g li e s e
NOT TO SCALE
VISITOR CONTROL CENTER - DOMESTIC WATER ISOMETRICS 1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881073 358291
FD-A
WCO
P-4
P-2
P-1
WCO
CO
3" VTR
2"2"
4"
4"
4"
4"
2"
2"
4"
4" SAN, SEE CIVIL UTILITY
FOR CONTINUATION
P-7
4"
FD-A
P-4
P-2
P-1
2" DOMESTIC COLD WATER
ENTRANCE, SEE CIVIL UTILITY
FOR CONTINUATION
WH
BFP-2
SEE DOMESTIC HOT
WATER PIPING DIAGRAM
DETAIL ON SHEET P-503.
PROVIDE ISOLATION VALVE,
BALANCING VALVE AND CHECK
VALVE FOR END OF RUN
DOMESTIC HOT WATER RECIRC
PIPING LOOP. SEE MANUAL
BALANCING VALVE DETAIL ON
SHEET P-501.
ISOLATION VALVE
TRAP PRIMER
WH
P-7
WH-A
P-6
HB
1 1/2"
3/4"
3/4"
2"
3/4"
1"
1"
3/4"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
F
IL
E N
A M
E
L A
Y O
U T
N A
M E
P
L O
T T
E D
U
S E
R
03/09/2023
/8
/2
:2
:5
P
M U
P ro je ct s\
\2
-0
C u tle r, M E
P e ri m et e r S e cu ri ty
\0
S
U B
M
IT
T A
L S
\0
F in al
S ig n ed
M a r
\R e vi t\ In sp e ct io n S ta tio n
W _0
2_ P
7C u tle r_
IS
P L
U M
R
.r vt
P-903
P -3
P
E R
IM
E
T E
R S
E C
U R
IT
Y
P L
U M
B
IN
G
IS
O M
E
TR
IC
S
JDARGT ARP
02/08/23
Approved by Jeffrey Hoyt, PWD ME, via Email
IM
P
R O
V E
M E
N T
S
CRH/LAF
1614700
N40085-19-D-9008 T008
C U
T L
E R
M
A
IN
E
EJA
ALG
DSN
M
ID
L A
N T
D C
C O
R E
P -9 a p u g li e s e
NOT TO SCALE
INSPECTION STATON - SANITARY ISOMETRICS
NOT TO SCALE
INSPECTION STATION - DOMESTIC WATER ISOMETRICS2
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
12881074 358292
| 279 - P-001 - PLUMBING LEGENDS, NOTES AND ABBREVIATIONS |
| 280 - PD101 - FLOOR PLAN PLUMBING- VISITOR CONTROL CENTER - DEMOLITION |
| 281 - P-101 - FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - SANITARY |
| 282 - P-102 - FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - DOMESTIC WATER |
| 283 - P-103 - FLOOR PLAN PLUMBING - INSPECTION STATION - SANITARY |
| 284 - P-104 - FLOOR PLAN PLUMBING - INSPECTION STATION - DOMESTIC WATER |
| 285 - P-501 - PLUMBING DETAILS |
| 286 - P-502 - PLUMBING DETAILS |
| 287 - P-503 - PLUMBING DETAILS |
| 288 - P-601 - PLUMBING SCHEDULES |
| 289 - P-602 - PLUMBING SCHEDULES |
| 290 - P-901 - PLUMBING ISOMETRICS |
| 291 - P-902 - PLUMBING ISOMETRICS |
| 292 - P-903 - PLUMBING ISOMETRICS |
| 2023-03-16T21:45:09-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:41-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:43-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:44-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:46-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:47-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:48-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:50-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:51-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:52-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:54-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:55-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:57-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:45:58-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:16-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:37-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:38-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:40-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:41-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:43-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:44-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:45-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:47-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:48-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:50-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:51-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-03-16T21:46:52-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |