P347 AMENDMENT 0004.pdf
PDF 234 KB Posted
- Solicitation number
- N4008523R2539
View the file
Other files
Show 40 more
Latest 50 of 105 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Amendment to provide answ ers to PPIs 4-8.
Pre-proposal Inquiry Due Day: 19 May 2023 by COB Proposal Due Date via Electronic Submission: 30 May 2023 @ 2:00pm EDT
1. CONTRACT ID CODE PAGE OF PAGES
J 1 3
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 03-May-2023
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N4008523R2539
X 9B. DATED (SEE ITEM 11)
05-Apr-2023
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
03-May-2023
CODE
NAVFACSYSCOM MID-ATLANTIC
ACQUISITION CORE
9324 VIRGINIA AVENUE
NORFOLK VA 23511-3095
N40085 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
N4008523R2539
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)
The following have been added by full text:
PRE-PROPOSAL INQUIRY (4-8)
PRE‐PROPOSAL INQUIRY ATTACHMENT 2023 05 03
Solicitation Number: N40085‐23‐R‐2539
Contractor Name:
Contractor POC:
Instructions: DO NOT submit in PDF format. DO submit as a word document
Contractor
PPI#
Section of
RFP
or Page Number
Paragraph Reference
Drawing Number
Question RESPONSE
4 AM0001
and
AM0002
With the Site Visit scheduled for 15 May 2023, and the PPI cutoff the following day on 16 May, we request that the PPI due date be extended from 16 May to 23 May to allow time to gather information and prepare any new PPIs resulting from the Site Visit.
PPI cutoff shall be extended to 19 May 2023 by close of business.
5 N/A N/A S‐104 & S‐311
Details A1, A4, C1, & C2 indicate 8" CMU for the exterior walls of the Inspection Station. The Building Roof Framing Plan ‐ Inspection Station on S‐104 has Key Notes 3 & 6 that inidicate the interior and exterior faces of the building and the CMU wall, and appear to indicate that the exterior wall is 7" thick. PLease clarify the thickness of the exterior wall for the Inspection Station.
Exterior wall thickness is 1’‐4” at exterior precast panels near base of wall. Exterior veneer changes above panels and thus wall thickness changes between foundation and roof framing plans, refer to arch dwgs for exterior veneer above panels. CMU interior face (keynote 6 on S‐104, is the interior face of the cmu, within the building) is consistent between fndn and framing plans. On roof framing plan, the exterior face of wall (veneer), keynote 3, is not dimensioned to as the exterior face is siding at the roof level with no single definitive exterior plane. Refer to arch drawings for full height wall construction.
6 Section 13 35 11 Page
2.4.2 A1/A‐
Spec section 13 35 11 item 2.4.2.c indicates that any doors required for the Prefabricated Steel Guard Booth are indicated on the plans.
Section 13 35 11, 2.4.c and 2.4.2.b should be omitted from Spec. The door should be part of the Sentry booth. 13 35 11, 2.4.a REVISE TO
N4008523R2539
(End of Summary of Changes)
Detail A1 on A‐704 does not indicate any doors for the Guard Booth. Please clarify.
READ: Commercial Grade Steel Swing Door 36 inches by 84 inches with 12 inch by 12 inch (305 mm by 305 mm) lite with steel single bore lever handle lockset with keyed entry. Use Hardware Group 7.0 as specified in 08 71 00. Coordinate door prep with manufacturer and door hardware in Group 7.0.
7 Plan Set 1614700dw g22of22TEL
ECOM_SEC
URITY_AUDI
O
TS‐101 The Drawings indicate to install a 6 strand SMFOC and 240V power feeder to each of the Mid‐range Radar Detection systems in multiple locations. Are the ductbanks to these locations existing, or is the installation of the ductbanks part of the contract? If so, please provide drawings of the required ductbanks configurations and locations.
New ductbanks are required and shall be direct buried conduit below grade from the nearest power station at the bottom of the antenna tower. Power and data runs shall be coordinated with the NCTAMSLANT site representative.
8 Plan Set 1614700dw g21of22ELE
CTRICAL
EP‐701 Please clarify the requirements of the Service Disconnect. Is the 400/400 intended to indicate a400 amp rated switch with 400 amp fuses, or an Enclosed Circuit Breaker with 400 amp frame and 400 amp trip setting?
The 400/400 is the disconnect size with the fuse size