1614700dwg19of22PLUMBING.pdf

PDF 3 MB Posted

Attached to
P347 Perimeter Security Improvement, Portsmouth Naval Shipyard, NCTS Cutler, Maine
Solicitation number
N4008523R2539
Issued by

View the file

Other files

File Type Posted
Amendment 0012.pdf PDF
P-347 Price Proposal Form AMD 0012.pdf PDF
1614700Amend0011dwg.pdf PDF
P347 AMENDMENT 0011.pdf PDF
1614700Amend0011spc.pdf PDF
Prospect Harbor Canopy Drawings Calcs Data.pdf PDF
P347 AMENDMENT 0010.pdf PDF
P347 AMENDMENT 0009.pdf PDF
P347 J-A Interior Finishes Redacted.pdf PDF
1614700Amend0008spc.pdf PDF
P347 AMENDMENT 0008.pdf PDF
1614700Amend0008dwg.pdf PDF
P347 AMENDMENT 0007.pdf PDF
P347 AMENDMENT 0006.pdf PDF
09 26 00.pdf PDF
Uline IH-2769-SPFR.PDF PDF
08 14 00.pdf PDF
Uline IH-1119-SPFR.PDF PDF
P347 AMENDMENT 0005.pdf PDF
CS507 - FENCING DETAILS.pdf PDF
P347 AMENDMENT 0004.pdf PDF
1614700dwg08of22CIVIL_SIGNING_UTILITIES.pdf PDF
1614700dwg18of22FIRE.pdf PDF
1614700dwg04of22CIVIL_ALIGNMENT_DEMO.pdf PDF
1614700dwg14of22LANDSCAPING.pdf PDF
1614700dwg21of22ELECTRICAL.pdf PDF
1614700dwg15of22ENVIRONMENTAL.pdf PDF
1614700dwg01of22GENERAL.pdf PDF
1614700dwg10of22CIVIL_EROSION_02.pdf PDF
1614700dwg13of22WETLAND.pdf PDF
1614700dwg12of22CIVIL_EROSION_04.pdf PDF
1614700dwg11of22CIVIL_EROSION_03.pdf PDF
1614700spc1of1.pdf PDF
1614700dwg17of22ARCHITECTURAL_INTERIOR.pdf PDF
1614700dwg05of22CIVIL_SITE.pdf PDF
1614700dwg20of22MECHANICAL.pdf PDF
1614700dwg03of22EXISTING_CONDITION.pdf PDF
1614700dwg02of22HAZMAT_GEOTECH.pdf PDF
1614700dwg09of22CIVIL_EROSION_01.pdf PDF
1614700dwg22of22TELECOM_SECURITY_AUDIO.pdf PDF
1614700dwg07of22CIVIL_GRADING_DRAINAGE_02.pdf PDF
1614700dwg06of22CIVIL_GRADING_DRAINAGE_01.pdf PDF
1614700dwg16of22STRUCTURAL.pdf PDF
P347 AMENDMENT 0003.pdf PDF
P347 AMENDMENT 0002.pdf PDF
P347 AMENDMENT 0001.pdf PDF
Cutler Site Access Requirements-NAVFAC Instructions.docx DOCX document
N4008523R2539 P347 AMENDMENT 01.pdf PDF
Cutler Site Access Requirements-Contractor Instructions.docx DOCX document
SECNAV_5512_1_dtd_May21.pdf PDF
Show 40 more

Latest 50 of 105 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. BASIS OF DESIGN EQUIPMENT NOTED WITHIN THIS SET OF DRAWINGS IS NOT PROPRIETARY. OTHER MANUFACTURER'S MAY BE SUBMITTED FOR REVIEW AND APPROVAL.

2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL ACCESSORIES REQUIRED FOR MANUFACTURER RECOMMENDED OPERATION.

PROVIDE COMPLETE AND FUNCTIONAL SYSTEMS TO OPERATE IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND LOCAL CODES.

3. BEFORE INSTALLATION AND ERECTION OF PIPING, ALL DIMENSIONS AND ROUTING MUST BE VERIFIED IN FIELD.

4. PLUMBING CONTRACTOR MUST COORDINATE LOCATION OF PLUMBING EQUIPMENT, FIXTURES, AND PIPING WITH OTHER TRADES INCLUDING BUT NOT LIMITED TO STRUCTURAL, FIRE PROTECTION, COMMUNICATION, MECHANICAL AND ELECTRICAL, CIVIL, STRUCTURAL, AND OTHER DISCIPLINES.

5. ALL PIPING MUST BE NEW, CLEAN, AND FREE FROM SCALE AND DIRT AT TIME OF INSTALLATION.

6. ALL PIPING TO BE SUPPORTED IN ACCORDANCE WITH SPECIFICATIONS.

7. PROVIDE PIPE HANGERS TO SUPPORT ALL PIPING AND THE CONTENTS OF THE PIPING.

8. FOR PIPE SIZES NOT SHOWN ON FLOOR PLANS, SEE SCHEDULES AND/OR DIAGRAMS.

9. ALL SANITARY WASTE PIPING SHOWN ON PLANS MUST BE CONCEALED BELOW SLAB, UNLESS OTHERWISE NOTED.

10. KEEP ALL UNDERGROUND PIPING CLEAR OF FOOTINGS AND FOUNDATION. PROVIDE PIPE SLEEVES LARGE ENOUGH TO ALLOW FOR REQUIRED LATERAL MOVEMENT OF PIPES

PASSING THROUGH MASONRY OR CONCRETE WALLS.

11. ALL DRAINS THAT REMOVE FLOOR WATER MUST HAVE FINAL SLOPE RECHECKED BY THE CONTRACTOR BEFORE THE SURROUNDING SLAB IS POURED.

12. ALL WALL MOUNTED CLEANOUTS MUST BE 18" AFF (TO BOP), UNLESS OTHERWISE NOTED.

13. ALL EXTERIOR CLEANOUTS SHOWN IN PAVED AREAS MUST BE SET FLUSH IN A 24"X24"X8" THICK CONCRETE PAD.

14. ALL WATER PIPING LOCATED IN EXTERIOR WALLS MUST BE RUN ON INTERIOR SIDE OF WALL INSULATION.

15. ALL DOMESTIC WATER PIPING (COLD, HOT AND RECIRCULATION) MUST BE ROUTED TIGHT TO STRUCTURE, IN CEILING SPACE, UNLESS OTHERWISE NOTED.

16. INSTALL PIPING SO THAT ALL VALVES ARE ACCESSIBLE.

17. PROVIDE A WATER HAMMER ARRESTOR ON THE SUPPLY TO EACH QUICK CLOSING VALVE, UNLESS OTHERWISE NOTED.

18. PROVIDE VACUUM BREAKERS ON ALL WALL HYDRANTS, HOSE BIBBS AND THREADED FAUCET SPOUTS.

19. PLUMBING VENTS LOCATED IN EXTERIOR WALLS MUST BE OFFSET 4'-0" IN CEILING AT ROOF PENETRATION.

20. ALL PIPING SHOWN ON PLANS MUST BE CONCEALED ABOVE CEILING OR IN WALLS UNLESS NOTED OTHERWISE.

21. ALL INTERIOR SANITARY CLEAN-OUTS MUST BE SET FLUSH WITH EITHER FINISHED FLOOR OR FINISHED WALLS.

22. DESIGN AND CONSTRUCTION MUST BE PREFORMED IN ACCORDANCE WITH THE CURRENT GOVERNMENT STANDARDS INCLUDING BUT NOT LIMITED TO: PRODUCTS, INSTALLATION AND TESTING. CONTRACTOR MUST BE FAMILIAR WITH STANDARDS UFGS, UFC, AND ECB REQUIREMENTS.

23. CONTRACTOR MUST PROVIDE ROUGH-IN, INTERCONNECTING PIPING, SUITABLE STOPS, CAST BRASS TRAP, AND FINAL CONNECTION AS REQUIRED FOR ALL EQUIPMENT PROVIDED

BY CONTRACTING OFFICER AND/OR OTHERS.

24. ALL VALVES THAT ARE NOT ADJACENT TO THE FIXTURE OR APPLIANCE MUST BE IDENTIFIED, INDICATING THE FIXTURE OR APPLIANCE SERVED.

25. PROVIDE UL LISTED PENETRATIONS SYSTEM AT FIRE RATTED WALLS/ FLOORS/ PARTITIONS.

26. OFFSET PLUMBING PIPING AS NECESSARY TO CLEAR STRUCTURAL FRAMING.

BOTTOMBTM

REQUEST FOR PROPOSALRFP

ELECTRIC WATER COOLEREWC

URINALUR

WATER CLOSETWC

LAVATORYLAV

HOT WATER RECIRCHWR

P-103

GENERAL NOTESLEGEND AND ABBREVIATIONS

DOMESTIC COLD WATER PIPING - CW

SHEET KEYNOTE DESIGNATION

PIPE TURNING UP

PIPE TURNING DOWN

ISOLATION VALVE

WH WALL HYDRANT DESIGNATION

FD-A FLOOR DRAIN DESIGNATION

AFF ABOVE FINISHED FLOOR

CO CLEANOUT

DN DOWN

ELECT ELECTRICAL

FFE FINISHED FLOOR ELEVATION

HGT HEIGHT

KW KILOWATT

NB NICKEL BRONZE

TYP TYPICAL

GPH GALLONS PER HOUR

CHECK VALVE

DIA DIAMETER

APPROX APPROXIMATE

GPF GALLONS PER FLUSH

GAL GALLONS

°F DEGREES FAHRENHEIT

VOL VOLUME

P-1 PLUMBING FIXTURE DESIGNATION

WH-1 WATER HEATER DESIGNATION

VTR VENT THRU ROOF

FD FLOOR DRAIN

LBS POUNDS

THRU THROUGH

UON UNLESS OTHERWISE NOTED

PIPE WITH ISOLATION VALVE IN RISER

PIPE CONTINUATION

DOMESTIC HOT WATER PIPING - HW

DOMESTIC HOT WATER RECIRC PIPING - HWR

SANITARY WASTE PIPING - W

CO CLEANOUT DESIGNATION

ENLARGED PLAN REFERENCE

AFG ABOVE FINISHED GRADE

BLDG BUILDING

FT FEET

HP HORSE POWER

HZ HERTZ

RPM REVOLUTIONS PER MINUTE

DIRECTION OF SLOPE DOWN

WATER HAMMER ARRESTER WITH PDI SYMBOL'A'

DIRECTION OF FLOW

BOP BOTTOM OF PIPE

TEMP TEMPERATURE

RECIRC RECIRCULATION

MANUAL BALANCING VALVE

∅ PHASE

W WASTE

V VENT

HW HOT WATER

PH PHASE

MAX MAXIMUM

MIN MINIMUM

CW COLD WATER

CONT CONTINUATION

DIMEN DIMENSION

IN INCHES

MTG MOUNTING

BFP-1 BACKFLOW PREVENTER

WCO WALL CLEANOUT

ABV ABOVE

WASTE PIPING ISOMETRIC

WATER PIPING ISOMETRIC

BTUH BRITISH THERMAL UNITS PER HOUR

EQUIP EQUIPMENT

F° DEGREE FAHRENHEIT

GPM GALLONS PER MINUTE

NO NUMBER

RM ROOM

SANITARY VENT PIPING - V

HB HOSE BIBB DESIGNATION

ET-1 EXPANSION TANK DESIGNATION

HWRP-1 HOT WATER RECIRC PUMP DESIGNATION

MV-1 MIXING VALVE DESIGNATION

TP-1 TRAP PRIMER DESIGNATION

PROPANE GAS PIPING - GG

AHU-1 AIR HANDLING UNIT

ABA ARCHITECTURAL BARRIER'S ACT

SD SHOWER DRAIN DESIGNATION

EXISTING TO POINT OF DEMOLITION SYMBOL

NEW TO EXISTING SYMBOL

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:1

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-001

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

P

LU

M B

IN

G

L E

G E

N D

S , N

O T

E S

A N

D A

B B

R E

V

IA

T

IO

N S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -0 a p u g lie s e

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881061 358279

LIMIT OF SAWCUT OF

EXISTING STRUCTURE

DISCONNECT EXISTING

PLUMBING-CAP FOR

SHOWER DRAIN

LIMIT OF SAWCUT OF

EXISTING STRUCTURE

LIMIT OF SAWCUT OF

EXISTING STRUCTURE

2"

4"

4"

2"

2"

4" CO

2" CO

1" DOMESTIC CW SERVICE 3

0' 1' 5' 10' 15'1'

1/4"=1'-0"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:1

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

PD101

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

F

LO

O R

P

LA

N P

LU

M

B

IN

G

V

IS

IT

O

R C

O N

T R

O L

C E

N

TE

R

D E

M O

LI

TI

O N

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P D a p u g lie s e

SCALE: 1/4" = 1'-0"

FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - DEMOLITION GRAPHIC SCALE(S)

DEMOLITION KEYNOTES#

1. DISCONNECT EXISTING FIXTURES FOR NEW TO EXISTING CONNECTION OF

SANITARY AND DOMESTIC WATER.

2. DEMOLISH INSTANTANEOUS WATER HEATER, ASSOCIATED WATER PIPING

AND APPURTENANCES.

3. DEMOLISH 1" DOMESTIC CW SERVICE.

4. SANITARY PIPING NOT IN SAWCUT AREA MAY BE CAPPED ABANDONED IN

PLACE.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881062 358280

R E

F

0' 1' 5' 10' 15'1'

1/4"=1'-0"

MECH/ELEC

VESTIBULE

TOILET

MUD ROOM

COMM

LOCKER ROOM

WAITING

OFFICE

INTERVIEW

OFFICE

SHOWER

ADMIN/COPY

SIPRNET

EXIST

BREAKROOM

MV-1

ET-1BFP-1

WH-1

SD

P-1

P-9

FD-A

PROPOSEDEXISTING

WCO

CO

P-2

P-1

P-4

P-5

4"

4"

2"

2"

VC-AHU-1

VC-AHU-2

LAUNDRY

P-8

TOILET

P-2

2"

JANITOR

P-7

P-3

HALLWAY

HALLWAY

MOTHER'S

DAYROOM

HALLWAY

HOUSEKEEPING PAD

FD-A

HALLWAY

FD-A

3" VTR

4"

WCOWCO

4" VTR4

2"

INVERT = 93.4 FT

wco 4"

WCO

RISER 2

RISER 1

RISER 3

RISER 4

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:2

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-101

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

F

LO

O R

P

LA

N P

LU

M

B

IN

G

V

IS

IT

O

R C

O N

TR

O

L C

E N

T E

R

S A

N

IT

A R

Y

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -1 a p u g lie s e

PLAN

NORTH

GENERAL SHEET NOTES

GRAPHIC SCALE(S)

SHEET KEYNOTES#

SCALE: 1/4" = 1'-0"

FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - SANITARY

A. SANITARY WASTE (W) PIPING MUST BE ROUTED IN WALLS AND BELOW

SLAB, UNLESS OTHERWISE NOTED.

B. SANITARY VENT (V) PIPING MUST BE ROUTED IN WALLS AND TIGHT TO

STRUCTURE ABOVE, UNLESS OTHERWISE NOTED.

C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE

SCHEDULE ON SHEET P-601.

D. MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY, SEE

MECHANICAL DRAWINGS.

1. FOR CONTINUATION OF SANITARY PIPE BELOW GRADE, SEE CIVIL UTILITY

PLAN ON SHEET CU101.

2. NON-PERFORATED 4" PVC PASSIVE STACK UP THROUGH ROOF WITH TEE

OPEN TO AGGREGATE BED (PASSIVE RADON MITIGATION). TERMINATE

ABOVE SNOWFALL CLOSURE. SEE RADON PIPING SYSTEM DETAIL ON

SHEET P-501.

3. MATCH EXISTING SANITARY INVERT FOR NEW TO EXISTING CONNECTION.

CONTRACTOR TO FIELD VERIFY.

4. EXISTING 4" VTR. CONTRACTOR TO FIELD VERIFY LOCATION FOR NEW TO

EXISTING CONNECTION.

5. MECHANICAL EQUIPMENT SHOWN FOR CLARITY.

NOTE: FINISHED FLOOR ELEVATION = 95.41 FT.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881063 358281

R E

F

0' 1' 5' 10' 15'1'

1/4"=1'-0"

MECH/ELEC

VESTIBULE

TOILET

MUD ROOM

COMM

LOCKER ROOM

WAITING

OFFICE

INTERVIEW

OFFICE

SHOWER

ADMIN/COPY

SIPRNET

EXIST

BREAKROOM

MV-1

ET-1

BFP-1

WH-1

SD

P-1

P-9

FD-A

PROPOSEDEXISTING

2" CW SERVICE

BUILDING MAIN

ISOLATION VALVE

HB

HWRP-1

3/4"

1 1/4"

2"

VC-AHU-1

VC-AHU-2

3/4"

G

PROPANE GAS LINE ENTRANCE.

SEE CIVIL SITE UTILITY PLAN FOR

LOCATION OF PROPANE GAS TANK.

P-6

P-5

P-4

P-1

P-2

3/4"

WM-1

WH

WH

TOILET

MOTHER'S

P-8

P-3

P-7

P-2

ID/CHECK-IN

HALLWAY

DAYROOM

HALLWAY

HALLWAY

JANITOR

HOUSEKEEPING PAD

FD-A

HALLWAY

FD-A

VC-UH-1

3/4"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:2

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-102

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

F

LO

O R

P

LA

N P

LU

M

B

IN

G

V

IS

IT

O

R C

O N

T R

O L

C E

N

TE

R

D O

M E

S T

IC

W

A

TE

R

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -1 a p u g lie s e

GENERAL SHEET NOTES

GRAPHIC SCALE(S)

SHEET KEYNOTES#

SCALE: 1/4" = 1'-0"

FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - DOMESTIC WATER

PLAN

NORTH

A. DOMESTIC WATER (CW, HW, AND HWR) PIPING MUST BE ROUTED IN

WALLS AND TIGHT TO STRUCTURE ABOVE, UNLESS OTHERWISE

NOTED.

B. PROPANE GAS (G) PIPING MUST BE ROUTED TIGHT TO STRUCTURE

ABOVE, UNLESS OTHERWISE NOTED.

C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE

SCHEDULE ON SHEET P-601.

D. MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY, SEE

MECHANICAL DRAWINGS.

1. PROVIDE TRAP PRIMER SERVING FLOOR DRAIN. SEE AUTOMATIC TRAP

PRIMER DETAIL ON SHEET P-501.

2. ROUTE FULL SIZE DISCHARGE FROM BACKFLOW PREVENTER TO FLOOR

DRAIN WITH 2" AIR GAP. SEE WATER SERVICE DETAIL ON SHEET P-503.

3. FOR CONTINUATION OF DOMESTIC COLD WATER SERVICE PIPE BELOW

GRADE, SEE CIVIL UTILITY PLAN ON SHEET CU101.

4. PROVIDE ISOLATION VALVE, MANUAL BALANCING VALVE AND CHECK

VALVE FOR END OF RUN DOMESTIC HOT WATER RECIRC PIPING LOOP.

SEE MANUAL BALANCING VALVE DETAIL ON SHEET P-501.

5. FOR CONTINUATION OF PROPANE GAS PIPE BELOW GRADE SEE CIVIL

UTILITY PLAN .

6. PROVIDE PROPANE GAS PIPE CONNECTION TO EQUIPMENT. SEE GAS

PIPING CONNECTION DETAIL ON SHEET P-503 AND GAS PIPING DIAGRAM

ON SHEET P-502.

7. MECHANICAL EQUIPMENT SHOWN FOR CLARITY.

8. PROVIDE 12"x12" CEILING ACCESS PANEL FOR ACCESS TO ISOLATION

VALVE FOR WALL HYDRANT.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881064 358282

0' 1' 5' 10' 15'1'

1/4"=1'-0"

STOR/JAN

CORR

WAITING

INSPECTION

OFFICE

RFI/SECURE

ROOM

RESTROOM

MECH/ELEC

ET-2

FD-A

WCO

P-4

3"

MV-2

COMM

WCO

WH-2

3" VTR

4"

4"

INVERT = -7.2'

4"

2"

BREAKROOM

P-7

P-2

P-1

B C D

CO

2"

PIPE TURN DOWN TO INVERT

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:2

:3

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \I n s p e c ti o n S ta ti o n

W

P

C u tl e r_

IS

P

L U

M R

.r v t

P-103

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

F

LO

O R

P

LA

N P

LU

M

B

IN

G

IN

S

P E

C

TI

O N

S

TA

TI

O

N

S A

N

IT

A R

Y

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D C

C O

R E

P -1 a p u g lie s e

PLAN

NORTH

GENERAL SHEET NOTES

GRAPHIC SCALE(S)

SHEET KEYNOTES#

SCALE: 1/4" = 1'-0"

FLOOR PLAN PLUMBING - INSPECTION STATION - SANITARY

A. SANITARY WASTE (W) PIPING MUST BE ROUTED IN WALLS AND BELOW

SLAB, UNLESS OTHERWISE NOTED.

B. SANITARY VENT (V) PIPING MUST BE ROUTED IN WALLS AND TIGHT TO

STRUCTURE ABOVE, UNLESS OTHERWISE NOTED.

C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE

SCHEDULE ON SHEET P-601.

D. MECHANICAL AND ELECTRICAL EQUIPMENT SHOWN FOR REFERENCE

ONLY, SEE MECHANICAL DRAWINGS.

NOTE: FINISHED FLOOR ELEVATION = 0.0 FT. FOR ACTUAL FIRST FLOOR ELEVATION OF THE STRUCTURE REFER TO CIVIL SITE DRAWINGS.

1. FOR CONTINUATION OF SANITARY PIPE BELOW GRADE, SEE CIVIL UTILITY

PLAN ON SHEET CU101.

2. NON-PERFORATED 4" PVC PASSIVE STACKUP THROUGH ROOF WITH TEE

OPEN TO AGGREGATE BED (PASSIVE RADON MITIGATION). TERMINATE

ABOVE SNOWFALL CLOSURE. SEE RADON PIPING SYSTEM DETAIL ON

SHEET P-501.

3. SANITARY INVERT TO BE BELOW THE FROST PENETRATION OF 86 INCHES

(7.2FT).

4. STORM GUTTERS / DOWNSPOUTS SHOWN FOR COORDINATION

PURPOSES. SEE ARCHITECTURAL DRAWINGS AND CIVIL DRAWINGS FOR

ADDITIONAL DETAIL AND FURTHER COORDINATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881065 358283

0' 1' 5' 10' 15'1'

1/4"=1'-0"

STOR/JAN

CORR

BREAKROOM

WAITING

INSPECTION

OFFICE

RFI/SECURE

ROOM

RESTROOM

MECH/ELEC

ET-2

FD-A

WH

HB

HWRP-2

P-4

WH

BUILDING MAIN

ISOLATION VALVE

MV-2

3/4"

IS-AHU-1

PROPANE GAS LINE

ENTRANCE. SEE CIVIL SITE

UTILITY PLAN FOR LOCATION

OF PROPANE GAS TANK.

P-6

3/4"

G

2" CW

SERVICE

WH-2

P-2

P-1

ELECTRICAL

PANELS (REF ONLY)

WM-2

P-7

B C D

BFP-2 IS-UH-1

G

G

3/4"

1 1/2"

3/4"

ELECTRICAL

PANELS (REF ONLY)

7 7

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:2

:4

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \I n s p e c ti o n S ta ti o n

W

P

C u tl e r_

IS

P

L U

M R

.r v t

P-104

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

F

LO

O R

P

LA

N P

LU

M

B

IN

G

IN

S

P E

C T

IO

N

S T

A T

IO

N

D

O M

E S

T

IC

W A

TE

R

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D C

C O

R E

P -1 a p u g lie s e

GENERAL SHEET NOTES

GRAPHIC SCALE(S)

SHEET KEYNOTES#

SCALE: 1/4" = 1'-0"

FLOOR PLAN PLUMBING - INSPECTION STATION - DOMESTIC WATER

PLAN

NORTH

A. DOMESTIC WATER (CW, HW, AND HWR) PIPING MUST BE ROUTED IN

WALLS AND TIGHT TO STRUCTURE ABOVE, UNLESS OTHERWISE

NOTED.

B. PROPANE GAS (G) PIPING MUST BE ROUTED TIGHT TO STRUCTURE

ABOVE, UNLESS OTHERWISE NOTED.

C. FOR PLUMBING FIXTURE DESIGNATIONS, SEE PLUMBING FIXTURE

SCHEDULE ON SHEET P-601.

D. MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY, SEE

MECHANICAL DRAWINGS.

1. PROVIDE TRAP PRIMER SERVING FLOOR DRAIN. SEE AUTOMATIC TRAP

PRIMER DETAIL ON SHEET P-501.

2. ROUTE FULL SIZE DISCHARGE FROM BACKFLOW PREVENTER TO FLOOR

DRAIN WITH 2" AIR GAP. SEE WATER SERVICE DETAIL ON SHEET P-503.

3. FOR CONTINUATION OF DOMESTIC COLD WATER SERVICE PIPE BELOW

GRADE, SEE CIVIL UTILITY PLAN ON SHEET CU101.

4. PROVIDE ISOLATION VALVE, MANUAL BALANCING VALVE AND CHECK

VALVE FOR END OF RUN DOMESTIC HOT WATER RECIRC PIPING LOOP.

SEE BALANCING VALVE DETAIL ON SHEET P-501.

5. FOR CONTINUATION OF PROPANE GAS PIPE BELOW GRADE SEE CIVIL

UTILITY PLAN ON SHEET CU101.

6. PROVIDE PROPANE GAS PIPE CONNECTION TO EQUIPMENT. SEE GAS

PIPING CONNECTION DETAIL AND GAS PIPING DIAGRAM ON SHEET P-503,

AND GAS PIPING DIAGRAM - INSPECTION STATION ON SHEET P-502.

7. STORM GUTTERS / DOWNSPOUTS SHOWN FOR COORDINATION

PURPOSES. SEE ARCHITECTURAL DRAWINGS AND CIVIL DRAWINGS FOR

ADDITIONAL DETAIL AND FURTHER COORDINATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881066 358284

BACK TO HOT WATER RECIRC PUMP

MANUAL BALANCING VALVE

WITH TEST PORTS (1/2" VENTURI VALVE)

ISOLATION VALVE (TYP.)

NOTE:

1. BALANCING VALVE ON END OF RUN LOOP MUST BE SET AT 1.0 GPM EACH.

TO

PLUMBING

FIXTURES

UNION (TYP)

FROM HOT WATER

GENERATION

SYSTEM

CHECK VALVE (TYP.)

3/4"

FINISH GRADE

LENGTH VARIES

W/ DEPTH OF

INVERT BELOW

SURFACE

INVERT

CAST IRON COVER

AND FRAME

8"

2'-0" SQUARE

CONCRETE

PIPE SIZE SAME

AS SERVICE

LINE

UPPER END OF SERVICE LINE

COLD WATER

GATE VALVE (TYP)

FINISH

FLOOR1/2"

SUPPORT VERTICALLY

AS REQUIRED ON

WALL

AUTOMATIC

TRAP PRIMER

NOTE:

1. TRAP PRIMER VALVE MUST BE

INSTALLED A MINIMUM OF 12"

ABOVE THE FLOOD PLANE OF THE

FIXTURE BEING SERVED.

SEE FLOOR DRAIN

DETAIL. (THIS

SHEET)

SEE FLOOR DRAIN

SCHEDULE P-602, FOR

STRAINER & GRATE

TYPE

FINISH FLOOR

4" DEEP SEAL TRAP SEE FLOOR DRAIN

SCHEDULE P-602, FOR

PIPE SIZE

SET RIM OF GRATE

FLUSH WITH

FINISHED FLOOR

SEE FLOOR DRAIN

SCHEDULE P-602, FOR

MODEL NUMBER

SEE

AUTOMATIC

TRAP PRIMER

DETAIL. (THIS

SHEET)

MULTIPLE PIPE RUNS SINGLE PIPE RUN

INSULATION

SADDLE (TYP)

STEEL PIPE

STRAP

BOLT AND

CLAMPING

NUT (TYP.)

LENGTH AS REQUIRED

STEEL CHANNEL

CLEVIS HANGER

(SIZE AS

REQUIRED)

THREADED

ROD

INSULATION SADDLE

SUPPORT FROM

STRUCTURE

THREADED ROD

SUPPORT FROM

STRUCTURE

4" RADON

VENT PIPE

SLAB ON GRADE

4" PASSIVE

RADON STACK

THROUGH ROOF

ROOF

FLASHING ELECTRICAL JUNCTION

BOX (IN CASE OF FAN NEEDED

TO ACTIVATE THE SYSTEM)

FILL

AGGREGATE BED

TEE OPEN TO

AGGREGATE BED

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:3

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-501

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

P

LU

M B

IN

G

D E

T A

IL

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -5 a p u g lie s e

NOT TO SCALE

MANUAL BALANCING VALVE DETAIL

NOT TO SCALE

EXTERIOR TWO-WAY CLEANOUT DETAIL

NOT TO SCALE

AUTOMATIC TRAP PRIMER DETAIL

NOT TO SCALE

FLOOR DRAIN DETAIL

NOT TO SCALE

TYPICAL PIPE SUPPORT DETAIL

NOT TO SCALE

RADON PIPING SYSTEM DETAIL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881067 358285

EXTERIOR

BACKER ROD

WATERPROOF SEALANT

INTERIOR

INSULATION

PIPE

WALL

NOTE:

1. WHERE PIPE IS PENETRATING A FIRE-RATED

PARTITION, PROVIDE UL APPROVED FIRE CAULK.

STAINLESS

STEEL

DRAWBAND

ESCUTCHEON

PLATES WHERE

EXPOSED

PACK WITH

FIBERGLASS AND

SEAL BOTH SIDES

PIPE SLEEVE (SET

AND ANCHOR

DURING WALL

CONSTRUCTION)

PIPE

FINISHED FLOOR

LINK-SEAL PLATE

CAST-IN-PLACE PIPE SLEEVE

AND LINK-SEAL

NOTE:

1. WHERE PIPE IS PENETRATING A FIRE-RATED

PARTITION, PROVIDE UL APPROVED FIRE CAULK.

BACKER ROD

WATERPROOF SEALANT

INSULATION

PIPE

WALL

ESCUTCHEON

PLATES WHERE

EXPOSED

PACK WITH

FIBERGLASS AND

SEAL BOTH SIDES

PIPE SLEEVE (SET

AND ANCHOR

DURING WALL

CONSTRUCTION)

INSULATION

VC-AHU-1

(60 CFH)

3/4" PROPANE GAS MAIN

SERVING BUILDING FROM LP-

GAS TANK

BUILDING

EXTERIOR

WALL

FINISH FLOOR

G

G

SEE GAS PIPING CONNECTION

DETAIL. (SHEET P-503)

G

GRADE

NOTES:

1. EXHAUST VENT MUST TERMINATE ON EXTERIOR OF BUILDING A MINIMUM OF 3 FT. ABOVE INTAKES OR 10 FT AWAY FROM INTAKES.

2. CONTRACTOR MUST COORDINATE INCOMING GAS PRESSURE SERVICE WITH UTILITY PROVIDER AND PROVIDE SECONDARY

REGULATOR AS REQUIRED.

3/4"

3/4"

VC-AHU-2

(60 CFH)

G

EXHAUST TO

ATMOSPHERE. SEE

MECHANICAL FOR

ROUTING AND

TERMINATION.

3/4"

EXHAUST AND INTAKE TO

ATMOSPHERE. SEE

MECHANICAL FOR

ROUTING AND

TERMINATION.

DIELECTRIC COUPLING

3/4"

VC-UH-1

(12 CFH)

IS-AHU-1

(80 CFH)

BUILDING

EXTERIOR

WALL

FINISH FLOOR

G

SEE GAS PIPING CONNECTION

DETAIL. (SHEET P-503)

G

GRADE

NOTES:

1. EXHAUST VENT MUST TERMINATE ON EXTERIOR OF BUILDING A MINIMUM OF 3 FT.

ABOVE INTAKES OR 10 FT AWAY FROM INTAKES.

2. CONTRACTOR MUST COORDINATE INCOMING GAS PRESSURE SERVICE WITH UTILITY

PROVIDER AND PROVIDE SECONDARY REGULATOR AS REQUIRED.

3/4"

EXHAUST TO ATMOSPHERE. SEE

MECHANICAL FOR ROUTING AND

TERMINATION.

G

DIELECTRIC COUPLING

3/4" PROPANE GAS MAIN

SERVING BUILDING FROM LP-

GAS TANK

G

3/4"

IS-UH-1

(12 CFH)

3/4"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:3

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-502

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

P

LU

M B

IN

G

D E

T A

IL

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -5 a p u g lie s e

NOT TO SCALE

TYPICAL PIPE SLEEVE THRU EXTERIOR WALL DETAIL

NOT TO SCALE

TYPICAL PIPE PENETRATION THRU SLAB DETAIL

NOT TO SCALE

TYPICAL PIPE THRU INTERIOR WALL DETAIL

NOT TO SCALE

GAS PIPING DIAGRAM - VISITOR CONTROL CENTER

NOT TO SCALE

GAS PIPING DIAGRAM - INSPECTION STATION

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881068 358286

STRAINER

BFP-1 (VISITOR'S CENTER)

BFP-2 (INSPECTION STATION)

MINIMUM 18"

MAIN BUILDING

ISOLATION VALVE

2"

DISCHARGE TO

FLOOR DRAIN.

TO SITE

DRAIN DN

UNION (TYP)

NOTE:

1. SEE CIVIL DRAWING SITE UTILITY PLAN FOR ADDITIONAL INFORMATION, AND DEPTH OF BURY.

2" TO BUILDING

M

WM-1 (VISITOR'S CENTER)

WM-2 (INSPECTION STATION)

CONCENTRIC

REDUCER (TYP)

* STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE WITHOUT INLINE APPURTENANCES MUST BE

INSTALLED UP / DOWNSTREAM OF FLOW CONTROL BALANCING VALVE PER MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

NOTES:

1. SECURELY FASTEN AQUASTAT TO HOT WATER RECIRC. PIPE.

2. SEE ELECTRICAL DRAWINGS FOR WIRING.

3. PROVIDE AUTOMATIC TIMER KIT/AQUASTAT WITH ABILITY TO CONTROL PUMP AS FOLLOWS:

UNION (TYP.)

PUMP

MOTOR WITH

TIMER

NORMALLY

CLOSED

PUMP SUCTION AND DISCHARGE FLANGE

TAP, FOR PRESSURE GAUGE CONNECTIONS

PRESSURE

GAUGE

NEEDLE

VALVE

MANUAL

BALANCING VALVE

WITH TEST PORTS

CHECK

VALVE

AUTOMATIC TIMER

KIT/AQUASTAT

ISOLATION VALVE

(TYP)

• ADI 24/7 TIME CLOCK

> OCCUPIED MODE = PUMP ON

> UNOCCUPIED MODE = PUMP OFF

• TEMPERATURE CONTROL

> 110°F TEMP = PUMP OFF

> 100°F TEMP = PUMP ON

WH-1

ET-1

MV-2

FINISHED FLOOR

DRIP PAN MUST BE

CONSTRUCTED OF

HEAVY GAUGE

GALVANIZED STEEL

0°

F 14 0°

F

MANUAL BALANCING

VALVE (TYP)

THERMOMETER

HOUSEKEEPING

PAD

ROUTE FULL

SIZE DISCHARGE

TO NEAREST

FLOOR DRAIN.

DIELECTRIC HEAT

TRAP UNION

(TYP)

PRESSURE/

TEMPERATURE

RELIEF VALVE

SEE HOT WATER

RECIRC PUMP

PIPING DETAIL

THIS SHEET.

HWRP-1, HWRP-2

HEAT TRAP

27" DROP

CHECK

VALVE (TYP)

VACUUM

BREAKER

ISOLATION

VALVE (TYP)

UNION (TYP)

1"3/4"

1"

1"

1-1/4"

1/2"

3/4"

HEAT PUMP

WATER HEATER

1"

WH-2

ET-2

MV-1

2" CW FROM BLDG

1 1/4" HW TO BLDG

3/4" HWR FROM BLDG

G

VENT TO ATMOSPHERE. TERMINATE

RELIEF VENT 3'-0" ABOVE INTAKE OR

10' AWAY FROM ALL OUTSIDE AIR INTAKES

GAS SHUT-OFF

(FIELD SUPPLIED

OUTSIDE OF

EQUIPMENT CABINET)

6" DIRT

LEG

MINIMUM

UL LISTED GAS TRAIN WITH

REGULATOR AS RECOMMENDED BY

EQUIPMENT MANUFACTURER.

FIELD SUPPLIED

GROUND UNION (TYP)

GAS FIRED

EQUIPMENT

WATER HAMMER ARRESTOR SCHEDULE

PDI SYMBOL

FIXTURE UNIT

RATING

A

1-11

B

12-32 33-60

C

61-113

D E

114-154 155-330

F

SUPPLY RISER

TYPICAL BRANCH LINE

WATER HAMMER

ARRESTOR

PDI SYMBOL

PDI "A"

NOTES:

1. PREFERRED INSTALL WATER HAMMER ARRESTORS AT THE END OF BRANCH LINE

BETWEEN THE LAST TWO FIXTURES SERVED.

2. ONE WATER HAMMER ARRESTOR PER 20' LINE, AND ANOTHER FOR BRANCHES

OVER 20' IN LENGTH.

3. THE SUM OF FIXTURE UNIT RATING OF UNITS OVER 20' IN LENGTH SHALL BE EQUAL

TO OR GREATER THAN THE DEMAND OF THE BRANCHES.

4. ARRESTERS SHALL BE APPROVED FOR INSTALLATION WITH NO ACCESS PANEL

REQUIRED.

PIPE SIZE 3/4" 1" 1" 1" 1" 1"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:4

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-503

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

P

LU

M B

IN

G

D E

T A

IL

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -5 a p u g lie s e

NOT TO SCALE

WATER SERVICE ENTRANCE DETAIL

NOT TO SCALE

HOT WATER RECIRC PUMP PIPING DETAIL

NOT TO SCALE

DOMESTIC HOT WATER PIPING DIAGRAM

NOT TO SCALE

GAS PIPING CONNECTION DETAIL

NOT TO SCALE

WATER HAMMER ARRESTOR DETAIL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881069 358287

MTG HGT

18" AFF

COUNTER

MATERIAL

FIXTURE

PIPE SIZES

W V HW CW

NOTES

3/4"- - -

1/2"1-1/2" 1-1/2" 1/2"

MARK

HB

P-5

1.5 GPM

HOSE BIBB

BREAKROOM SINK SINGLE

COMPARTMENT UNDER MOUNT

(ADAAG COMPLIANT)

PLUMBING FIXTURE SCHEDULE

STAINLESS

STEEL

P-1

P-3

WATER CLOSET

(ADAAG COMPLIANT)

VITREOUS CHINA 1"3" 2" -- 1.28 GPF

RIM @

16-1/2" AFF

P-4

18" AFG- 3/4"- - -WH - -WALL HYDRANT 7

WASHING MACHINE BOX

GENERAL NOTES:

A. ALL FIXTURES NOTED AS "ADAAG COMPLIANT" MUST MEET THE AMERICAN BARRIER ACT FOR BUILDING AND FACILITIES (ABA) STANDARDS FOR CONSTRUCTION, LOCATION, AND

MOUNTING HGTS.

B. PROVIDE ALL FIXTURE ACCESSORIES REQUIRED FOR INSTALLATION OF A COMPLETE, FUNCTIONAL SYSTEM.

C. CONTRACTING OFFICER TO SELECT OR CONFIRM COLOR OF ALL PLUMBING FIXTURES.

D. ROUGH-IN AND CONNECT PIPING TO ALL PLUMBING ITEMS IN ACCORDANCE WITH THE INTERNATIONAL PLUMBING CODE.

E. PROVIDE SELECTION PER BASIS OF DESIGN OR APPROVED EQUAL.

FIXTURE SPECIFIC NOTES:

1. PROVIDE FLOOR MOUNTED, MANUAL FLUSH VALVE TYPE, WATER CLOSET WITH OPEN FRONT SEAT.

2. PROVIDE WALL HUNG LAVATORY WITH CARRIER SUPPORT WITH ADJUSTABLE P-TRAPS AND PERFORATED GRID STRAINER. FAUCETS MUST BE SINGLE LEVER WRISTBLADE, EPA

“WATERSENSE” LABELED WITH AERATOR.

3. PROVIDE TRAP AND SUPPLY PIPE WITH INSULATION GUARD.

4. PROVIDE ANTI-SCALD MIXING VALVE, ADJUSTABLE SHOWER HEAD, ROD AND ACCESORIES.

5. PROVIDE STAINLESS STEEL, UNDER MOUNT, MINIMUM 6" DEEP. PROVIDE ADJUSTABLE P-TRAP WITH DRAIN PIPING TO VERTICAL VENT STACK. PROVIDE WITH 1.5 GPM AERATOR.

PROVIDE GOOSENECK FAUCET. PROVIDE UL LISTED GARBAGE DISPOSAL.

6. PROVIDE FIRE RATED BOX WITH DRAIN KIT, QUARTER TURN SUPPLY VALVES WITH HOSE CONNECTIONS AND INTEGRAL SHOCK ARRESTORS WITH DEEP SEAL TRAP, NICKEL BRONZE

STRAINER AND BARRIER TYPE TRAP SEAL PROTECTION DEVICE (TRAP GUARD); 8" DIAMETER STRAINER.

7. PROVIDE FREEZE PROOF WALL HYDRANTS, WITH AN INTEGRAL VACUUM BREAKER/BACKFLOW PREVENTER HYDRANTS MUST HAVE 3/4 INCH HOSE CONNECTIONS AND LOOSE TEE KEY

HANDLE.

8. PROVIDE ANGLE TYPE COPPER ALLOY HOSE BIBB WITH LOCKSHIELD AND HANDWHEEL, 3/4" EXTERNAL HOSE THREADS. PROVIDE INTEGRAL VACUUM BREAKER.

9. PROVIDE RECESSED WALL BOX WITH FACEPLATE AND SCREWS. UNIT MUST INCLUDE 1/2" LEAD FREE 1/4 TURN VALVE WITH WATER HAMMER ARRESTOR.

10. SERVICE SINK MUST BE CONSTRUCTED OF 18 GAUGE, TYPE 304 STAINLESS STEEL WITH A SATIN FINISH. SIZE: 20" W x 20" L SINGLE COMPARTMENT. SINK COMPARTMENT MUST BE

MINIMUM 12" DEEP WITH ROLLED EDGES AND WITH MINIMUM 8" BACK-SPLASH FOR FAUCET WITH 8" CENTERS. SINKS MUST BE FLOOR SUPPORTED ON GALVANIZED OR STAINLESS STEEL LEGS WITH 1" ADJUSTABLE FEET. PROVIDE BACK MOUNTED COMBINATION FAUCET WITH VACUUM BREAKER, AND 3/4" EXTERNAL HOSE THREADS.

11. PROVIDE WALL HUNG URINAL WITH INTEGRAL TRAP AND EXTENDED SHIELDS, ASME A112..19.2M, SIPHON JET, TOP SUPPLY CONNECTION, BACK OUTLET, URINAL FLOOR SUPPORTED

CHAIR CARRIER SUPPORTS WITH HANGERS AND MANUAL FLUSH VALVE.

12. PROVIDE STAINLESS STEEL, UNDER MOUNT, MAXIMUM 6" DEEP. PROVIDE ADJUSTABLE P-TRAP WITH DRAIN PIPING TO VERTICAL VENT STACK. PROVIDE WITH 1.5 GPM AERATOR.

PROVIDE GOOSENECK FAUCET.

6-

SIZE (IN.) FLOW RATE

P-2

WALL HUNG

LAVATORY

(ADAAG COMPLIANT)

RIM @ 34" AFFVITREOUS CHINA 1/2"1-1/2" 1-1/2" 1/2"0.5 GPM 2, 3

SHOWER

(ADAAG COMPLIANT)

- - - 1.5 GPH

1/2"2" 1-1/2" 1/2" 4

STAINLESS

STEEL

42" AFF- 1/2"2" 1-1/2" 1/2"

P-6 ICEMAKER BOX 9-

STAINLESS

STEEL

BOTTOM OF BOX

24" AFF

- 1/2"- - -

- 2" 1-1/2"1.5 GPMSERVICE SINK

STAINLESS

STEEL

10P-7 -

COUNTER 1-1/2"1.5 GPM

STAINLESS

STEEL

12P-8 -

MOTHER'S SINK SINGLE

COMPARTMENT UNDER MOUNT

(ADAAG COMPLIANT)

P-9

WALL HUNG URINAL

(ADAAG COMPLIANT)

RIM @ 17" AFFVITREOUS CHINA 2" 1-1/2"0.125 GPM 11- - 3/4"

1/2"1/2"2"

1/2"1/2"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:4

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-601

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

P

LU

M B

IN

G

S C

H E

D U

LE

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -6 a p u g lie s e

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881070 358288

MARK

ET-1 DIAPHRAGM 6 1.8 60 VERTICAL

DOMESTIC HOT

WATER

TYPE CONFIGURATION LOCATION SERVICE

MIN TANK

VOLUME

(GAL.)

MIN

ACCEPTANCE

VOLUME (GAL.)

AIR

CHARGE

(PSIG)

NOTES:

1. UNITS MUST BE ASME RATED PRECHARGED DIAPHRAGM TYPE PRESSURE VESSEL.

2. TANK MUST BE RATED FOR POTABLE WATER SYSTEM.

3. UNIT MUST HAVE MAXIMUM DESIGN PRESSURE OF 125 PSI WITH A DESIGN TEMPERATURE OF 240°F.

4. APPROX. DIMEN. (DIA. X LENGTH) 16-1/4"Ø X 19-1/8"

MECHANICAL ROOM - 109

VISITOR CONTROL CENTER

NOTESLOCATIONGPM

PRESSURE

DROP

FT HDAMPS

ELECTRICAL DATA

VOLTS/PH/HZ

TYPEMARK

1, 2, 3210.66120/ 1/ 60INLINEHWRP-1

NOTES:

1. PROVIDE AQUASTAT & TIME CLOCK WITH PLUG.

2. PUMP MUST BE BRONZE CONSTRUCTION.

3. PROVIDE PUMP SUITABLE FOR USE IN POTABLE SYSTEMS.

LOCATIONMARK

BFP-1

NOTES

1, 2

SYSTEM

DOMESTIC

WATER

MAXIMUM

PRESSURE

DROP (PSI)

SYSTEM

FLOW

(GPM)

SIZE

2"

MV-1

MARK TYPE

HIGH-LOW

WATER MIXER

MAX PRESSURE

DROP (PSI)

CAPACITY

15 GPM

SET POINT

110°F

LOCATION

1, 2, 3, 4

NOTES

FLOW (GPM)

1 15

MIN. MAX.

INLET

1"

CW HW

1-1/2"

TEMPID

OUTLET

PIPE CONNECTION SIZE

NOTES:

1. PROVIDE LEAD FREE TYPE WITH BRONZE FINISH.

2. PROVIDE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP, INLET CHECK STOPS, OUTLET BALL VALVE, INLET THERMOMETERS AND MANIFOLD PIPING.

3. PROVIDE LOCKING TEMPERATURE REGULATOR WITH PROTECTION AGAINST HOT OR COLD WATER SUPPLY LINE FAILURE AND THERMOSTAT FAILURE.

4. PROVIDE FACTORY ASSEMBLED AND TESTED MIXING VALVE. INSTALL IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

NOTES:

1. PROVIDE REDUCED PRESSURE TYPE BACKFLOW PREVENTER WITH AIR GAP DRAIN. ASSEMBLY MUST

INCLUDE STRAINER, SHUTOFF VALVES, RELIEF VALVE AND AIR GAP FITTING.

2. UNIT MUST COMPLY TO "LEAD FREE" REQUIREMENTS.

LOCATIONMARK NOTES

PIPE

SIZE

NOTE:

1. PROVIDE ROUND NB STRAINER, SET RIM FLUSH WITH FINISH FLOOR. PROVIDE WITH TRAP

PRIMER.

EXPANSION TANK SCHEDULE

HOT WATER RECIRCULATING PUMP SCHEDULE

BACKFLOW PREVENTER SCHEDULE

THERMOSTATIC MIXING VALVE SCHEDULE

FLOOR DRAIN SCHEDULE

FD-A 1MECHANICAL ROOM 4"

TYPE

REDUCED PRESSURE ZONE

ASSEMBLY

1"

MECHANICAL ROOM - 109

VISITOR CONTROL CENTER

MV-2

HIGH-LOW

WATER MIXER

11 GPM 110°F 1, 2, 3, 41 18 3/4" 3/4"10

1, 2, 3, 4

NOTES

ET-2 DIAPHRAGM 4 1.0 VERTICAL

DOMESTIC HOT

WATER

MECHANICAL ROOM - 110

INSPECTION STATION 1, 2, 3, 4

MECHANICAL ROOM - 110

INSPECTION STATION

210.66120/ 1/ 60INLINEHWRP-2 1, 2, 3

3/4"

BFP-2 1, 2

DOMESTIC

WATER

10402"

REDUCED PRESSURE ZONE

ASSEMBLY

MECHANICAL ROOM - 109

VISITOR CONTROL CENTER

MECHANICAL ROOM - 110

INSPECTON STATION

MECHANICAL ROOM - 109

VISTITOR CONTROL CENTER

MECHANICAL ROOM - 110

INSPECTION STATION

SD -SHOWER 2"

METER SCHEDULE

NOTE:

1. WATER METER: ADVANCED WATER METER, NON-RESETTABLE WITH REMOTE READ-OUT. (TURBINE TYPE)

MARK SYSTEM NOTES

WM-1

44 GPM @10 PSI

MAX PD

1DOMESTIC WATER

REQUIRED @

BUILDING

TYPE

ELECTRONIC PULSE

OUTPUT

LOCATION

MECHANICAL ROOM - 109

VISITOR CONTROL CENTER

WM-2

40 GPM @10 PSI

MAX PD

1DOMESTIC WATER

ELECTRONIC PULSE

OUTPUT

MECHANICAL ROOM - 110

INSPECTION STATION

SIZE

2"

2"

NOTES

LOCATION

VOLTS/ PH/ HZ

208/1/60

ELECTRICAL DATA

WATER HEATER SCHEDULE

MARK

WH-1

MECHANICAL ROOM - 109

VISITOR CONTROL

CENTER

AMP

13.7

NOTE:

1. WATER HEATERS MUST MEET OR EXCEED THE REQUIREMENTS OF ASHRAE 90.1-2013 STANDARD FOR ENERGY EFFICIENCY.

TYPE

HEAT PUMP

RECOVERY

25 GPH

TEMPERATURE

RISE ºF

100ºF

TEMPERATURE

DELIVERY

SETPOINT ºF

140ºF

CAPACITY

(GAL)

208/1/60WH-2

MECHANICAL ROOM - 110

INSPECTION STATION

HEAT PUMP 13.2 GPH 100ºF 140ºF 40 113.7

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:5

P M

U P ro je c ts

\2

\2 -0

C u tl e r, M E

P e ri m e te r S e c u ri ty

\0

S U

B M

IT

T

A L S

\0

F in a l S ig n e d

M a r

\R e v it \V is it o rs

C e n te r\

W

P

C u tl e r_

V C

P

L U

M R

.r v t

P-602

P -3

P

E R

IM

E

TE

R

S E

C U

R

IT

Y

P

LU

M B

IN

G

S C

H E

D U

LE

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N

TS

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T

LE

R , M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -6 a p u g lie s e

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

12881071 358289

P-1

P-4 P-2

P-5

SD

P-9

P-1

FD-A

WCO

CO

4"

4"

2"

2"

P-3

2"

2"

2"

2"

4"

P-2

P-7

P-8

2"

FD-A

FD-A

3" VTR

4"

WCO

WCO

4" VTR

2"

4"

4"

WCO

2"

RISER 1

RISER 2

RISER 3

RISER 4

2"

EXISTING

WCO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

M

ID

-A

T

LA

N

TI

C N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:5

P

M U

P ro je ct s\

\2

-0

C u tle r, M E

P e ri m et e r S ec u ri ty

\0

S

U B

M

IT

T A

L S

\0

F in a l S ig ne d

M a r

\R e vi t\

V is ito rs

C e n te r\

W

_P

C u tle r_ V

C

P

LU

M

R

.r vt

P-901

P -3

P

E R

IM

E

T E

R S

E C

U R

IT

Y

P L

U M

B

IN

G

IS

O M

E

TR

IC

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N T

S

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T L

E R

M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -9 a p u g li e s e

NOT TO SCALE

VISITOR CONTROL CENTER - SANITARY ISOMETRICS

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881072 358290

P-1 P-4

P-2

P-9 P-1

FD-A

HB

BFP-1

WM-1

MV-1

TRAP PRIMER

P-6

P-5

WH

WH

2"

3/4"

1 1/4"

3/4"

3/4"

3/4"

1"

1 1/2" 1"

PROVIDE ISOLATION VALVE, BALANCING VALVE

AND CHECK VALVE FOR END OF RUN DOMESTIC

HOT WATER RECIRC PIPING LOOP. SEE MANUAL

BALANCING VALVE DETAIL ON SHEET P-501.

SEE DOMESTIC HOT WATER

PIPING DIAGRAM DETAIL ON

SHEET P-503.

2" DOMESTIC COLD WATER

SERVICE, SEE CIVIL UTILTIY FOR

CONTINUATION AND WATER

SERVICE ENTRANCE DETAIL ON

SHEET P-503.

P-2

P-7

P-8

1"

1 1/2"

1"1"

P-3

1"

WH-A

WH-A

1 1/2"

TRAP PRIMER

3/4"3/4"

FD-A

FD-A

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

M

ID

-A

T

LA

N

TI

C N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:3

:0

P

M U

P ro je ct s\

\2

-0

C u tle r, M E

P e ri m et e r S ec u ri ty

\0

S

U B

M

IT

T A

L S

\0

F in a l S ig ne d

M a r

\R e vi t\

V is ito rs

C e n te r\

W

_P

C u tle r_ V

C

P

LU

M

R

.r vt

P-902

P -3

P

E R

IM

E

T E

R S

E C

U R

IT

Y

P L

U M

B

IN

G

IS

O M

E

TR

IC

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N T

S

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T L

E R

M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D I

C O

R E

P -9 a p u g li e s e

NOT TO SCALE

VISITOR CONTROL CENTER - DOMESTIC WATER ISOMETRICS 1

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881073 358291

FD-A

WCO

P-4

P-2

P-1

WCO

CO

3" VTR

2"2"

4"

4"

4"

4"

2"

2"

4"

4" SAN, SEE CIVIL UTILITY

FOR CONTINUATION

P-7

4"

FD-A

P-4

P-2

P-1

2" DOMESTIC COLD WATER

ENTRANCE, SEE CIVIL UTILITY

FOR CONTINUATION

WH

BFP-2

SEE DOMESTIC HOT

WATER PIPING DIAGRAM

DETAIL ON SHEET P-503.

PROVIDE ISOLATION VALVE,

BALANCING VALVE AND CHECK

VALVE FOR END OF RUN

DOMESTIC HOT WATER RECIRC

PIPING LOOP. SEE MANUAL

BALANCING VALVE DETAIL ON

SHEET P-501.

ISOLATION VALVE

TRAP PRIMER

WH

P-7

WH-A

P-6

HB

1 1/2"

3/4"

3/4"

2"

3/4"

1"

1"

3/4"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

M

ID

-A

T

LA

N

TI

C N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

A

AS NOTED

F

IL

E N

A M

E

L A

Y O

U T

N A

M E

P

L O

T T

E D

U

S E

R

03/09/2023

/8

/2

:2

:5

P

M U

P ro je ct s\

\2

-0

C u tle r, M E

P e ri m et e r S e cu ri ty

\0

S

U B

M

IT

T A

L S

\0

F in al

S ig n ed

M a r

\R e vi t\ In sp e ct io n S ta tio n

W _0

2_ P

7C u tle r_

IS

P L

U M

R

.r vt

P-903

P -3

P

E R

IM

E

T E

R S

E C

U R

IT

Y

P L

U M

B

IN

G

IS

O M

E

TR

IC

S

JDARGT ARP

02/08/23

Approved by Jeffrey Hoyt, PWD ME, via Email

IM

P

R O

V E

M E

N T

S

CRH/LAF

1614700

N40085-19-D-9008 T008

C U

T L

E R

M

A

IN

E

EJA

ALG

DSN

M

ID

L A

N T

D C

C O

R E

P -9 a p u g li e s e

NOT TO SCALE

INSPECTION STATON - SANITARY ISOMETRICS

NOT TO SCALE

INSPECTION STATION - DOMESTIC WATER ISOMETRICS2

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

12881074 358292

279 - P-001 - PLUMBING LEGENDS, NOTES AND ABBREVIATIONS
280 - PD101 - FLOOR PLAN PLUMBING- VISITOR CONTROL CENTER - DEMOLITION
281 - P-101 - FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - SANITARY
282 - P-102 - FLOOR PLAN PLUMBING - VISITOR CONTROL CENTER - DOMESTIC WATER
283 - P-103 - FLOOR PLAN PLUMBING - INSPECTION STATION - SANITARY
284 - P-104 - FLOOR PLAN PLUMBING - INSPECTION STATION - DOMESTIC WATER
285 - P-501 - PLUMBING DETAILS
286 - P-502 - PLUMBING DETAILS
287 - P-503 - PLUMBING DETAILS
288 - P-601 - PLUMBING SCHEDULES
289 - P-602 - PLUMBING SCHEDULES
290 - P-901 - PLUMBING ISOMETRICS
291 - P-902 - PLUMBING ISOMETRICS
292 - P-903 - PLUMBING ISOMETRICS
2023-03-16T21:45:09-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:41-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:43-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:44-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:46-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:47-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:48-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:50-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:51-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:52-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:54-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:55-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:57-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:45:58-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:16-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:37-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:38-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:40-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:41-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:43-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:44-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:45-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:47-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:48-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:50-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:51-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:52-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2023-03-16T21:46:54-0400
Norfolk, VA
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.

File details come from the government source that posted it. Updated .