About this file

Part 11 FP

View the file

Other files

File Type Posted
UAS_SATCOM_RELAY_PADS_AND_FACILITY_11005.docx DOCX document
AMENDMENT_0011_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
AMENDMENT_0010_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
AMENDMENT_009_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
AMENDMENT_008_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
AMENDMENT_007_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
1118648_SPC_03-09-2015.pdf PDF
1118648_DWG_03-09-2015.pdf PDF
AMENDMENT_006_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
1118648_Amendment_2_Continuation_Sheet_2015-03-06.doc DOC document
AMENDMENT_005_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
AMENDMENT_004_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
PPI_015__Response_Attachments.pdf PDF
AMENDMENT_003_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
AMENDMENT_002_N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
N62470-09-R9034_Part10-FP.pdf PDF
N62470-09-R9034_Part03-CIV.pdf PDF
N62470-09-R9034_Part02-LS.pdf PDF
N62470-09-R9034_Part05-GEO.pdf PDF
11005R_SPECS_Final-EBS_04.13.12_Vol_1.pdf PDF
11005_SPECS_Final-EBS_04.13.12_Vol_2.pdf PDF
N62470-09-R9034_Part08-AR.pdf PDF
N62470-09-R9034_Part04-CIV_(CONT).pdf PDF
N62470-09-R9034_Part09-IN.pdf PDF
N62470-09-R9034_Part06-LAND.pdf PDF
N62470-09-R9034_Part13-ME.pdf PDF
AMENDMENT_0001N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
N62470-09-R9034_Part14-EL.pdf PDF
N62470-09-R9034_Part07-ST.pdf PDF
N62470-09-R9034_Part12-PL.pdf PDF
N62470-09-R9034_Part01-GEN.pdf PDF
N62470-09-R9034_Part08-AR.pdf PDF
N62470-09-R9034_Part03-CIV-revised.pdf PDF
Contract_Risk_Assessment_and_QA_Responsibility_Spreadsheet-.pdf PDF
N62470-09-R9034_Part01-GEN.pdf PDF
N33191-15-R-0802_SATCOM_Relay_Pads.pdf PDF
N62470-09-R9034_Part04-CIV.pdf PDF
N62470-09-R9034_Part14-EL 1 .pdf PDF
11005R_SPECS_Final-EBS_04.13.12_Vol_1.pdf PDF
11005_SPECS_Final-EBS_04.13.12_Vol_2.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MNT

WP

MASS NOTIFICATION SYSTEM RADIO TRANSCEIVER. MOUNT 1.8m ABOVE

FINISHED GRADE.

LOCATION WHEN DUCT DETECTORS ARE NO IN A READILY VISIBLE LOCATION

AOM

ADDRESSABLE INTERFACE DEVICE FOR MONITORING OF WATER FLOW SWITCH

ADDRESSABLE INTERFACE DEVICE - CONTROL MODULE. WHEN SHOWN, SUBSCRIPT INDICATES DEVICE

OR EQUIPMENT BEING CONTROLLED.

DUCT MOUNTED SMOKE DETECTOR.

SUBSCRIPTS INDICATE THE FOLLOWING:

SUPPLY DUCT

RETURN DUCT

-S -R

ADDRESABLE INTERFACE DEVICE - MONITOR MODULE.

FIRE ALARM SYSTEM

FIRE ALARM CONTROL PANEL. FLUSH MOUNT AT 1.5m ABOVE

FIRE ALARM RADIO TRANSMITTER PANEL. FLUSH MOUNT AT 1.5m ABOVE

CONNECTION TO SPRINKLER SYSTEM FLOW SWITCH.

MANUAL PULL STATION. WALL MOUNT AT 1.2m ABOVE FINISHED FLOOR TO CENTER.

CEILING MOUNTED SMOKE DETECTOR.

CONNECTION TO SPRINKLER SYSTEM TAMPER SWITCH.

FINISHED FLOOR TO BOTTOM.

FINISHED FLOOR TO BOTTOM.

ADDRESSABLE INTERFACE DEVICE FOR MONITORING OF VALVE TAMPER SWITCH

COMBINATION VOICE EVACUATION-EMERGENCY NOTIFICATION SPEAKER/STROBE.

SUBSCRIPT INDICATES CANDELLA RATING. MOUNT AT 2.3m ABOVE FINISHED FLOOR TO CENTER.

SUBSCRIPT INDICATES CANDELLA RATING. MOUNT AT 2.3m ABOVE FINISHED FLOOR TO CENTER.

WEATHER PROOF COMBINATION VOICE EVACUATION-EMERGENCY NOTIFICATION SPEAKER/STROBE.

MASS NOTIFICATION SYSTEM

REMOTE INDICATING LIGHT SERVING DUCT MOUNTED SMOKE DETECTOR. LOCATE IN A CONSPICUOUS

IMPIANTO ALLARME INCENDIO

STAZIONE MANUALE. MONTARE A PARETE CON MEZZERIA A 1.2m DAL PAVIMENTO FINITO.

RILEVATORE DI FUMO MONTATO A SOFFITTO.

COLLEGAMENTO ALL'INTERRUTTORE ANTI-MANOMISSIONE DELL'IMPIANTO SPRINKLER.

COLLEGAMENTO AL FLUSSOSTATO DELL'IMPIANTO SPRINKLER.

COMBINAZIONE ALTOPARLANTE PER AVVISO A VOCE DI EVACUAZIONE- EMERGENZA/LUCE

STROBOSCOPICA. LA SCRITTA INDICA LA POTENZA NOMINALE IN CANDELE. MONTARE DAL MEZZERIA 2.3m

DAL PAVIMENTO FINITO.

RESISTENTE ALLE INTEMPERIE. LA SCRITTA INDICA LA POTENZA NOMINALE IN CANDELE. MONTARE DAL MEZZERIA 2.3m DAL PAVIMENTO FINITO.

COMBINAZIONE ALTOPARLANTE PER AVVISO A VOCE DI EVACUAZIONEI-EMERGENZA/LUCE STROBOSCOPICA, PAVIMENTO FINITO ALL'INTRADOSSO.

TRASMETTITORE ALLARME INCENDIO. MONTARE A FILO A 1.5 m DAL

QUADRO ALLARME INCENDIO. MONTARE A FILO A 1.5 m DAL PAVIMENTO

FINITO ALL'INTRADOSSO.

CHE IL DISPOSITIVO O L'APPARECCHIATURA SONO CONTROLLATI.

DISPOSITIVO INTERFACCIA INDIRIZZABILE - MODULO DI CONTROLLO. QUANDO MOSTRATO, SUBSCRIPT INDICA

RIVELATORE DI FUMO MONTATO A CANALE

CONDOTTO DI MANDATA

CONDOTTO DI RIPRESA

LE SIGLE INDICANO QUANTO SEGUE:

S R

DISPOSITIVO CON INTERFACCIA INDIRIZZABILE PER CONTROLLO VALVOLA ANTIMANOMISSIONE

DISPOSITIVO INTERFACCIA CON INDIRIZZABILE PER CONTROLLO FLUSSOSTATO

DISPOSITIVO CON INTERFACCIA INDIRIZZABILE - MODULO DI CONTROLLO

IMPIANTO DI NOTIFICA GLOBALE

RICETRASMITTENTE DELL'IMPIANTO DI NOTIFICA GLOBALE. MONTARE AD 1,8m DAL

PIANO DI CAMPAGNA.

LUCE DI SEGNALAZIONE A DISTANZA ASSERVITA AL RIVELATORE DI FUMO MONTATO NEL CANALE.

INSTALLARE BENE IN VISTA QUANDO I RIVELATORI NEI CANALI NON SONO FACILMENTE VISIBILI.

FACP

FATP

P

AIM

AIM

AIM

FS

TS

ASD ULTRASENSITIVE ASPIRATING TYPE SMOKE DETECTOR. SUBSCRIPT IDENTIFIES A PARTICULAR

ASPIRATING SMOKE DETECTOR.

RIVELATORE DI FUMO TIPO ASPIRANTE ULTRA SENSIBILE. LA SCRITTA IDENTIFICA UN RIVELATORE DI

FUMO ASPIRANTE PARTICOLARE.

75 EMERGENCY NOTIFICATION STROBE. SUBSCRIPT INDICATES CANDELLA RATING. MOUNT AT 2.3m ABOVE FINISHED

FLOOR TO CENTER.

LAMPADA STROBOSCOPICA PER NOTIFICA EMERGENZA. IL NUMERO INDICA LA POTENZA IN CANDELE. MONTARE DAL MEZZERIA 2.3m DAL PAVIMENTO FINITO.

AOM ADDRESSABLE INTERFACE DEVICE - CONTROL MODULE TO SIGNAL DDC SYSTEM TO CLOSE SOMKE EXHAUST

SYSTEM MAKE UP AIR DAMPERS.

RIVELATORE DI FUMO TIPO ASPIRANTE ULTRA SENSIBILE. LA SCRITTA IDENTIFICA UN RIVELATORE DI FUMO

ASPIRANTE PARTICOLARE.

SD

AOM ADDRESSABLE INTERFACE DEVICE - CONTROL MODULE TO SHUT DOWN COMPUTER ROOM AIR CONDITIONING UNIT DISPOSITIVO CON INTERFACCIA INDIRIZZABILE - MODULO DI CONTROLLO PER ARRESTO CONDIZIONATORE NELLA

COMPUTER ROOM.

CRAC

AOM ADDRESSABLE INTERFACE DEVICE - CONTROL MODULE TO SHUT DOWN AIR HANDLING UNIT

DISPOSITIVO CON INTERFACCIA INDIRIZZABILE - MODULO DI CONTROLLO PER ARRESTO UNITA'

TRATTAMENTO ARIA.

AHU

ADDRESSABLE INTERFACE DEVICE FOR MONITORING OF ASPIRATING SMOKE DETECTOR, DETECTION THRESHOLD 1 DISPOSITIVO CON INTERFACCIA INDIRIZZABILE PER CONTROLLO RIVELATORE DI FUMO ASPIRANTE RIVELAZIONE SOGLIA 1AIM

ASD-1

ADDRESSABLE INTERFACE DEVICE FOR MONITORING OF ASPIRATING SMOKE DETECTOR, DETECTION THRESHOLD 2 DISPOSITIVO CON INTERFACCIA INDIRIZZABILE PER CONTROLLO RIVELATORE DI FUMO ASPIRANTE RIVELAZIONE SOGLIA 2AIM

ASD-2

ADDRESSABLE INTERFACE DEVICE FOR MONITORING OF ASPIRATING SMOKE DETECTOR, DETECTION THRESHOLD 3

AIM

ASD-3

ADDRESSABLE INTERFACE DEVICE FOR MONITORING OF COMPUTER ROOM AIR CONDITIONING UNIT SMOKE DETECTOR DISPOSITIVO CON INTERFACCIA INDIRIZZABILE PER CONTROLLO RIVELATORE DI FUMO DEL CONDIZIONATORE DELLA COMPUTER ROOM.AIM

CRAC

SD

VOICE EVACUATION/MASS NOTIFICATION SPEAKER. FLUSH MOUNT IN CEILING UNLESS OTHERWISE NOTED.

ALTOPARLANTE AVVISO EVACUAZIONE/NOTIFICA GLOBALE. MONTATO A FILO SOFFITTO SALVO DIVERSAMENTE INDICATO.

EX

EXTERIOR WEATHERPROOF WALL MONTED VOICE EVACUATION/MASS NOTIFICATION SPEAKER, MOUNT AT 3m

ABOVE FINISHED GRADE UNLESS OTHERWISE INDICATED.

ALTOPARLANTE AVVISO EVACUAZIONE/NOTIFICA GLOBALE STAGNO, MONTATO SU PARETE ESTERNA A

3.00M DAL PIANO CAMPAGNA SALVO DIVERSAMENTE INDICATO.

ASD-A

DISPOSITIVO CON INTERFACCIA INDIRIZZABILE PER CONTROLLO RIVELATORE DI FUMO ASPIRANTE RIVELAZIONE SOGLIA 3

AD L

EK

N

LL

E F

S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

U

AS

S

AT

C O

M R

EL

AY

P

AD

S

AN

D F

AC

IL

IT

Y

1118648

N

AV

AL

A

IR

S

TA

TI

O N

II

SI

G O

N

EL

LA

, S

IC

IL

Y, IT

AL

Y

SATISFACTORY TO

1 2

PM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

E

ER

IN

G

C O

M M

AN

D

A

TL

AN

TI

C

LA

N T

C

AP

IT

AL

IM

PR

O

VE

M

EN

TS

N

O R

FO

LK

, V

IR

G

IN

IA

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DRAWFORM REVISION: 10 MARCH 2009

SE QUESTO DISEGNO E' PIU' PICCOLO DI 841 X 594mm

E' UN DISEGNO A DIMENSIONI RIDOTTE

IF THIS DRAWING IS LESS THAN 841 X 594mm

IT IS A REDUCED SIZE DRAWING

NOTE / N62470-11-D-1008 NOTE:

INC.ROGERS, LOVELOCK FRITZ,&

LICENSE # AA C000564 # EB 0000629

esignrchitectureA ngineeringE nteriorI D

4750 New Broad Street Orlando, FL www.rlfae.com

1 : 1

FI

RE

A

LA

RM

LE

GE

ND

FG001

CA

DRS SAE KLM

LE

GE

ND

A

AN

TI

NC

EN

DI

O

14024781

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

LL LL LL

L LL LL LL

PP PP

PP

FA

CP

PP

PP

PP

PP

FA

RP

ELEC

OFFICE

IT-2 OPS

CONFERENCE

CORR

TLT F

IT-1 RACK

ROOM

COMM EXT

STORAGE /

SHOP

HVAC

BOILER

TLT M

VEST

15 15

A B C D E F

JAN

AIM AIM

FS TS

S

AHU

AOM

AIM

AOM

CRAC

SD

CRAC

AIM

AOM

CRAC

SD

CRAC

AIM

AOM

CRAC

SD

CRAC

SECURE

ROOM

CORR

SD

AOM

EX

MNT

EX

EX

EX

EX

EX

G.C m m m m

ASD-E

ASD-F

ASD

ASD

AS

D

AS

D

7 (TYPICAL)

ASD-A

ASD-B

ADS-C

ASD-D

ASD-5

ASD-E

m m

210 mm

210 mm m m

ASD ASD

ASDASD AS

D

AS

D

7(TYPICAL)

3 3

C

FA101 A4

FA101

A3

AIM

ASD-1

AIM

ASD-2

AIM

ASD-3

ASD-A

ASD-B ASD-D

ADS-C

ASD-E

ASD-F

AIM

ASD-1

AIM

ASD-2

AIM

ASD-1

AIM

ASD-2

AIM

ASD-3

AIM

ASD-2

AIM

ASD-3

AIM

ASD-1

AIM

ASD-2

AIM

ASD-3

AIM

ASD-1

AIM

ASD-2

AIM

ASD-3

ASD

ASD

ASD

ASD

AS

D

AS

D

4 6

AD L

EK

N

LL

E F

S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

U

AS

S

AT

C O

M R

EL

AY

P

AD

S

AN

D F

AC

IL

IT

Y

1118648

N

AV

AL

A

IR

S

TA

TI

O N

II

SI

G O

N

EL

LA

, S

IC

IL

Y, IT

AL

Y

SATISFACTORY TO

1 2

PM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

E

ER

IN

G

C O

M M

AN

D

A

TL

AN

TI

C

LA

N T

C

AP

IT

AL

IM

PR

O

VE

M

EN

TS

N

O R

FO

LK

, V

IR

G

IN

IA

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DRAWFORM REVISION: 10 MARCH 2009

SE QUESTO DISEGNO E' PIU' PICCOLO DI 841 X 594mm

E' UN DISEGNO A DIMENSIONI RIDOTTE

IF THIS DRAWING IS LESS THAN 841 X 594mm

IT IS A REDUCED SIZE DRAWING

NOTE / N62470-11-D-1008 NOTE:

INC.ROGERS, LOVELOCK FRITZ,&

LICENSE # AA C000564 # EB 0000629

esignrchitectureA ngineeringE nteriorI D

4750 New Broad Street Orlando, FL www.rlfae.com

As indicated

FI

RE

A

LA

RM

P

LA

N

FA101

CA

DRS SAE KLM

PI

AN

TA

A

NT

IN

CE

ND

IO

14024782

N

TRUE

NORTH

1:100 GRAPHIC SCALE (MILLIMETERS)

50000 1000 3000 10000

KEY PLAN

A

1 : 100B1 FIRE ALARM PLAN - MAIN BUILDING

NOTE:

NOTE DI RIFERIMENTO:

NOTES:

KEY NOTES:

1. ANTENNA IMPIANTO ALLARME INCENDIO.

VEDEREPARTICOLARE C1/FA601.

2. MONTARE TUTTI GLI ALTOPARLANTI IN QUESTA STANZA CON

LA PARTE INFERIORE A 4.60m AFF.

3. TUBI CPVC 21mm I.D. PAVIMENTO. VEDERE D3/FA102 PER

VISTA IN PIANTA E PERCORSO.

4. TUBI CPVC 21mm I.D. PERCORSO DEI TUBI SOTTO IL

PAVIMENTO. PER IL PROSEGUIMENTO VEDERE B3/FA102.

5. TUBO CPVC 21mm I.D. AL CANALE DI MANDATA ARIA

TRATTATA. PER IL PROSEGUIMENTO VEDERE D3/FA102.

6. TUBI CPVC 21mm I.D. PER IL PROSEGUIMENTO VEDERE

D3/FA102.

7. MODULO CON INTERFACCIA INDIRIZZABILE.

8. TUBI CPVC 21mm I.D. PAVIMENTO. VEDERE B3/FA102 PER

VISTA IN PIANTA E PERCORSO.

9. PREVEDERE TARGHETTA CON L’INDICAZIONE DEI NUMERI DI

RACK MONITORATI IN CIASCUNA AREA. I NUMERI ESATTI DEI

RACK SARANNO QUELLI FISSATI DALL’UFFICIALE

CONTRAENTE.

1 FIRE ALARM SYSTEM ANTENNA. SEE DETAIL C1/FA601.

2 MOUNT ALL SPEAKERS IN THIS ROOM AT 4.6m AFF TO

BOTTOM OF SPEAKER.

3 21mm I.D. CPVC PIPES. SEE D3/FA102 FOR PLAN VIEW

AND ROUTING.

4 21mm I.D. CPVC PIPES. ROUTE PIPES BELOW FLOOR, SEE B3/FA102 FOR CONTINUATION.

5 21mm I.D. CPVC PIPE. ROUTE PIPE TO SMOKE EXHAUST

MAKEUP AIR INTAKE DUCT IN ROOM 112, SEE D3/FA102

FOR CONTINUATION.

6 21mm I.D. CPVC PIPES. SEE D3/FA102 FOR

CONTINUATION.

7 ADDRESSABLE INTERFACE MODULE.

8 21mm I.D. CPVC PIPES. SEE B3/FA102 FOR PLAN VIEW

AND ROUTING.

9 PROVIDE LABEL INDICATING WHICH RACK NUMBERS

EACH ZONE IS DETECTING. EXACT RACK NUMBERS

SHALL BE AS DIRECTED BY THE CONTRACTING OFFICER.

1 : 20A4

ASPIRATING SMOKE DETECTORS -

SOUTH ELEVATION

1 : 20A3

ASPIRATING SMOKE DETECTORS -

EAST ELEVATION

1 : 20A1 ROOM 115 - PARTIAL ENLARGED PLAN

ROOM 115 - PIANTA INGRANDITA PARZIALE

RIVELATORI DI FUMO ASPIRANTI

PROSPETTO EST

RIVELATORI DI FUMO ASPIRANTI

PROSPETTO SUD

PIANTA ALLARME INCENDIO - EDIFICIO PRINCIPALE

1:20 GRAPHIC SCALE (MILLIMETERS)

1000250 500 1500 20000

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

A B C D E F

ELEC

IT-1 RACK

ROOM

COMM EXT

HVAC

BOILER

SECURE

ROOM

CORR

IT-2 OPS

FA101

A1

(TYPICAL FOR 20)

(TIPICO PER 20)

12 (TYPICAL FOR 20)

(TIPICO PER 20)

G.C

A B C D E F

ELEC

IT-2 OPS

IT-1 RACK

ROOM

COMM EXT

HVAC

BOILER

SECURE

ROOM

CORR

(TYPICAL)

G.C

(TYPICO)

AD L

EK

N

LL

E F

S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

U

AS

S

AT

C O

M R

EL

AY

P

AD

S

AN

D F

AC

IL

IT

Y

1118648

N

AV

AL

A

IR

S

TA

TI

O N

II

SI

G O

N

EL

LA

, S

IC

IL

Y, IT

AL

Y

SATISFACTORY TO

1 2

PM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

E

ER

IN

G

C O

M M

AN

D

A

TL

AN

TI

C

LA

N T

C

AP

IT

AL

IM

PR

O

VE

M

EN

TS

N

O R

FO

LK

, V

IR

G

IN

IA

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DRAWFORM REVISION: 10 MARCH 2009

SE QUESTO DISEGNO E' PIU' PICCOLO DI 841 X 594mm

E' UN DISEGNO A DIMENSIONI RIDOTTE

IF THIS DRAWING IS LESS THAN 841 X 594mm

IT IS A REDUCED SIZE DRAWING

NOTE / N62470-11-D-1008 NOTE:

INC.ROGERS, LOVELOCK FRITZ,&

LICENSE # AA C000564 # EB 0000629

esignrchitectureA ngineeringE nteriorI D

4750 New Broad Street Orlando, FL www.rlfae.com

1 : 100

AS

PI

RA

TI

NG

S

MO

KE

D

ET

EC

TO

R

LA

YO

UT

FA102

CA

DRS SAE KLM

DI

SP

OS

IZ

IO

NE

R

IV

EL

AT

OR

I D

I F

UM

O

AS

PI

RA

NT

I

14024783

1 : 100D3

PARTIAL PLAN - ASPIRATING SMOKE DETECTOR CEILING

PLAN LAYOUT

N

TRUE

NORTH

1:100 GRAPHIC SCALE (MILLIMETERS)

50000 1000 3000 10000

KEY PLAN

A

1 AIR SAMPLING HOLES (TYPICAL)

2 21mm I.D. CPVC PIPE BELOW RASED FLOOR.

3 21mm I.D. CPVC PIPE ABOVE RACKS AT CEILING LEVEL. ROUTE TO

ASPIRATING SMOKE DETECTOR ASD-B. SEE A3/FA101 FOR CONTINUATION.

4 21mm I.D. CPVC PIPE ABOVE RACKS AT CEILING LEVEL. ROUTE TO

ASPIRATING SMOKE DETECTOR ASD-F. SEE A4/FA101 FOR CONTINUATION.

5 SMOKE EXHAUST MAKEUP AIR INTAKE DUCT LOCATION.

6 TRANSITION FITTING

7 TO ASPIRATING SMOKE DETECTOR ASD-A. SEE A3/FA101 FOR

CONTINUATION.

8 21mm I.D. CPVC PIPE FOR SMOKE EXHAUST MAKEUP AIR INTAKE DUCT.

ROUTE PIPE TO ASPIRATING SMOKE DETECTOR ASD-A. SEE A3/FA101 FOR

CONTINUATION.

9 21mm I.D. CPVC PIPE ABOVE RACKS AT CEILING LEVEL. ROUTE TO

ASPIRATING SMOKE DETECTOR ASD-C. SEE A3/FA101 FOR CONTINUATION.

10 21mm I.D. CPVC PIPE ABOVE RACKS AT CEILING LEVEL. ROUTE TO

ASPIRATING SMOKE DETECTOR ASD-D. SEE A3/FA101 FOR CONTINUATION.

11 21mm I.D. CPVC PIPE ABOVE RACKS AT CEILING LEVEL. ROUTE TO

ASPIRATING SMOKE DETECTOR ASD-E. SEE A4/FA101 FOR CONTINUATION.

12 FLXIBLE 15mm I.D. CAPILLARY TUBE TO CONNECT TO GOVERNMENT

FURNISHED, GOVERNMENT INSTALLED EQUIPMENT RACK. CAPILLARY

TUBE SHALL EXTEND FROM RIGID CPVC PIPE TO FINISHED FLOOR AND

SHALL BE PROVIDED WITH A MINIATURE SAMPLING POINT ON THE END OF

THE TUBE. FINAL CONNECTIONS TO RACKS SHALL BE MADE BY THE

GOVERNMENT.

NOTES:

KEY NOTES:

SHEET NOTES:

A. AIR SAMPLING HOLE SIZE SHALL BE AS RECOMMENDED BY THE

MANUFACTURER.

B. POSITION SAMPLING HOLES 20° TO 45° AWAY FROM AIR FLOW PATH.

C. FINAL PIPING ROUTING AND HOLE POSITION AND SIZE SHALL BE AS

RECOMMENDED BY THE MANUFACTURER.

D. SUPPORT UNDER FLOOR SAMPLING PIPING HIGH ON FLOOR STANCHIONS.

E. SUPPORT SAMPLING PIPE EVERY 1.2m.

1 : 100B3

PARTIAL PLAN - ASPIRATING SMOKE DETECTOR UNDER

FLOOR PLAN LAYOUT

NOTE:

NOTE DI RIFERIMENTO:

1. FORI CAMPIONATURA ARIA (TIPICO).

2. TUBO CPVC 21 mm D.I. AL DISOTTO DEL PAVIMENTO SOPRAELEVATO.

3. TUBO CPVC 21 mm D.I. AL DISOPRA DEGLI SCAFFALI A LIVELLO

SOFFITTO. INDIRIZZARE AL RIVELATORE DI FUMO AD ASPIRAZIONE

ASD-B. PER IL PROSEGUIMENTO VEDERE A3/FA101.

4. TUBO CPVC 21 mm D.I. AL DISOPRA DEGLI SCAFFALI A LIVELLO

SOFFITTO. INDIRIZZARE AL RIVELATORE DI FUMO AD ASPIRAZIONE

ASD-F. PER IL PROSEGUIMENTO VEDERE A4/FA101.

5. UBICAZIONE DEL CANALE DI PRESA ARIA ESTERNA PER L'ESTRAZIONE

DEI FUMI.

6. RACCORDO DI TRANSIZIONE.

7. AL RIVELATORE DI FUMO AD ASPIRAZIONE ASD-A. PER IL

PROSEGUIMENTO VEDERE A3/ FA101.

8. TUBO CPVC 21 mm D.I. PER IL CANALE DI PRESA ARIA ESTERNA PER

L'ESTRAZIONE DEI FUMI. PORTARE IL TUBO FINO AL RIVELATORE DI

FUMO AD ASPIRAZIONE ASD-A. PER IL PROSEGUIMENTO VEDERE

A3/FA101.

9. TUBO CPVC 21 mm D.I. AL DISOPRA DEGLI SCAFFALI A LIVELLO

SOFFITTO. INDIRIZZARE AL RIVELATORE DI FUMO AD ASPIRAZIONE

ASD-C. PER IL PROSEGUIMENTO VEDERE A3/FA101.

10. TUBO CPVC 21 mm D.I. AL DISOPRA DEGLI SCAFFALI A LIVELLO

SOFFITTO. INDIRIZZARE AL RIVELATORE DI FUMO AD ASPIRAZIONE

ASD-D. PER IL PROSEGUIMENTO VEDERE A3/FA101.XXXXX

11. TUBO CPVC 21 mm D.I. AL DISOPRA DEGLI SCAFFALI A LIVELLO

SOFFITTO. INDIRIZZARE AL RIVELATORE DI FUMO AD ASPIRAZIONE

ASD-E. PER IL PROSEGUIMENTO VEDERE A4/FA101.

12. TUBO CAPILLARE FLESSIBILE 15 mm I.D. DA COLLEGARE AGLI SCAFFALI

CON GLI APPARATI, FORNITI DAL GOVERNO, INSTALLATI DAL

GOVERNO. ESTENDERE IL TUBO CAPILLARE DAL TUBO CPVC 21 mm

D.I. FINO AL PAVIMENTO FINITO E PREVEDERE UN PUNTO DI

CAMPIONATURA ALLA FINE DEL TUBO. IL COLLEGAMENTO FINALE AGLI

ARMADI SARÀ COMPLETATO DAL GOVERNO.

PIANTA PARZIALE - PIANTA DISPOSIZIONE RIVELATORI DI

FUMO ASPIRANTI A SOFFITTO

PIANTA PARZIALE - PIANTA DISPOSIZIONE RIVELATORI DI

FUMO ASPIRANTI SOTTO PAVIMENTO

NOTE:

NOTE DEL FOGLIO:

A. IL FORO PER LA CAMPIONATURA DELL'ARIA SARA' COMERACCOMANDATO DAL

FABBRICANTE.

B. POSIZIONARE I FORI PER LA CAMPIONATURA DA 20° A 45°RISPETTO AL

PERCORSO DEL FLUSSO DELL'ARIA.

C. IL PERCORSO FINALE DELLE TUBAZIONI, LA POSIZIONE E LA DIMENSIONE DEL

FORO SARANNO COME RACCOMANDATO DAL FABBRICANTE.

D. SOSTENERE LA TUBAZIONE DI CAMPIONATURA SOTTO PAVIMENTO SU SUPPORTI

A PAVIMENTO.

E. SOSTENERE LA TUBAZIONE DI CAMPIONATURA OGNI 1.20m

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

MNT

CIRCUITO TIPICO DISPOSITIVO DI NOTIFICA

CIRCUITO DI SEGNALAZIONE

TIPICO

PIANO TERRA

FSTS

ST#

FARP

FACP

TYPICAL NOTIFICATION APPLIANCE CIRCUIT

TYPICAL SIGNALING

LINE CIRCUIT

GROUND FLOOR

EH2-19

P

AOM AIM AIM AIM

ULTRA SENSITIVE SMOKE

DETECTION SYSTEM ASPIRATING

SMOKE DETECTOR (ASD)

ASD-3

AIM

ASD-3

AIM

ASD-3

AIM

2 34

EH2-17 EH2-18

25 25

AOM

CRAC AIM

SD

CRAC

26 VFD

22 23

AD L

EK

N

LL

E F

S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

U

AS

S

AT

C O

M R

EL

AY

P

AD

S

AN

D F

AC

IL

IT

Y

1118648

N

AV

AL

A

IR

S

TA

TI

O N

II

SI

G O

N

EL

LA

, S

IC

IL

Y, IT

AL

Y

SATISFACTORY TO

1 2

PM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

E

ER

IN

G

C O

M M

AN

D

A

TL

AN

TI

C

LA

N T

C

AP

IT

AL

IM

PR

O

VE

M

EN

TS

N

O R

FO

LK

, V

IR

G

IN

IA

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DRAWFORM REVISION: 10 MARCH 2009

SE QUESTO DISEGNO E' PIU' PICCOLO DI 841 X 594mm

E' UN DISEGNO A DIMENSIONI RIDOTTE

IF THIS DRAWING IS LESS THAN 841 X 594mm

IT IS A REDUCED SIZE DRAWING

NOTE / N62470-11-D-1008 NOTE:

INC.ROGERS, LOVELOCK FRITZ,&

LICENSE # AA C000564 # EB 0000629

esignrchitectureA ngineeringE nteriorI D

4750 New Broad Street Orlando, FL www.rlfae.com

As indicated

FI

RE

A

LA

RM

R

IS

ER

D

IA

GR

AM

FA601

CA

DRS SAE KLM

SC

HE

MA

M

ON

TA

NT

I A

NT

IN

CE

ND

IO

14024784NOT TO SCALEB2

TYPICAL ADDRESSABLE CLASS A FIRE ALARM DEVICE

CONNECTION DIAGRAM

SCHEMA DI COLLEGAMENTO DISPOSITIVI D'ALLARME INCENDIO

ANDIRIZZABILI TIPICI DI CLASSE A

NOT TO SCALED2 ANTENNA MOUNTING DETAIL

PARTICOLARE MONTAGGIO ANTENNA

NOTES:

SHEET NOTES:

A. INSTALL ALL FIRE ALARM SYSTEM WIRING IN

20mm, MINIMUM CONDUIT.

KEY NOTES:

1 TYPICAL MOTOR CONTROLLER SERVING HVAC SYSTEM

FAN.

2 CONTROL MODULE FOR FAN SHUT-DOWN. LOCATE WITHIN

90mm OF MOTOR STARTER.

3 CONNECT TO ADDITIONAL DEVICES, SEE FIRE PROTECTION

FLOOR PLANS, SEE FX SERIES DRAWINGS FOR QUANTITY.

4 LOCATE MONITOR MODULE WITHIN 900mm OF THE FLOW

OR TAMPER SWITCH WHICH IT SERVES.

5 INITIATING LINE CIRCUIT CONNECTING MONITOR MODULE

TO INITIATING DEVICE.

6 FIRE ALARM RADIO ANTENNA. SEE SHEET FA101 FOR

LOCATION.

7 20mm CONDUIT MINIMUM WITH FIRE ALARM ANTENNA

CABLING.

8 MASS NOTIFICATION MONITOR MODULE. MOUNT WITHIN

900mm OF MASS NOTIFICATION TRANSCEIVER.

9 FIRE ALARM CONTROL PANEL.

10 FIRE ALARM RADIO TRANSMITTER.

11 MASS NOTIFICATION SYSTEM TRANSCEIVER.

12 MASS NOTIFICATION DRY CONTACT SIGNAL TO MONITOR

MODULE FOR ACTIVATION OF EMERGENCY NOTIFICATION

STROBES.

13 AUDIO INPUT FROM MASS NOTIFICATION TRANSCEIVER.

AUDIO INPUT SHALL OVERRIDE ANY PRE-RECORDED

DIGITAL MESSAGE OR ANY LIVE LOCAL MESSAGE WHEN

MASS NOTIFICATION SYSTEM IS ACTIVATED.

14 FIRE ALARM SYSTEM ANTENNA.

15 LIGHTNING ARRESTOR MOUNTED ON ANTENNA BASE.

16 FIRE ALARM SYSTEM ANTENNA CABLE.

17 20mm SINGLE CONDUCTOR WATERHEAD.

18 20mm RIGID PVC CONDUIT DOWN TO MAIN BUILDING.

19 20mm RIGID STEEL CONDUIT DOWN TO RADIO

TRANSMITTER/RECEIVER.

20 BARE COPPER GROUND TO MAIN ELECTRICAL SERVICE

GROUND.

21 STEEL SUPPORT CHANNEL FASTENED TO WALL.

22 EXTERIOR WALL.

23 TWO HOLE CONDUIT STRAP.

24 PROVIDE WATERPROOF SEAL FOR CONDUIT OPENINGS.

25 LOCATE MONITOR MODULE WITHIN 900mm OF ASPIRATING

SMOKE DETECTOR.

26 TYPICAL COMPUTER ROOM AIR CONDITIONING UNIT.

27 LOCATE MONITOR MODULE WITHIN 900mm OF COMPUTER

ROOM AIR CONDITIONING UNIT.

A. INSTALLARE TUTTI CAVI DELL'IMPIANTO DI ALLARME

INCENDIO IN TUBI DA 20mm MINIMO.

NOTE:

NOTE DEL FOGLIO:

1. AVVIATORE MOTORE TIPICO A SERVIZIO VENTILATORE

DELL'IMPIANTO HAVAC

2. MODULO DI CONTROLLO PER ARRESTO VENTILATORE.

POSIZIONARE ENTRO 900mm DALL'AVIATORE MOTORE.

3. COLLEGARE A DISPOSITIVI AGGIUNTIVI. PER LA QUANTITA' VEDI

PIANTE PROTEZIONE INCENDIO, DISEGNI SERIE FX.

4. POSIZIONARE IL MODULO DI CONTROLLO ENTRO 900mm DAL

FLUSSOSTATO O DALL'INTERRUTTORE ANTIMANOMISSIONE CHE

ESSO ALIMENTA.

5. CIRCUITO DI INIZIALLIZZAZIONE COLLEGANTE IL MODULO DI

CONTROLLO AL DISPOSITIVO DI INIZIALIZZAZIONE.

6. ANTENNA RADIO ALLARME INCENDIO.

7. TUBO 20mm MINIMO CON CAVI ANTENNA ALLARME INCENDIO.

8. MODULO CONTROLLO NOTIFICA GLOBALE. MONTARE ENTRO

900mm DA RICETRASMETTITORE DI NOTIFICA GLOBALE

9. QUADRO DI CONTROLLO ALLARME INCENDIO.

10. RADIO TRASMITTENTE ALLARME INCENDIO.

11. RICETRASMETTITORE IMPIANTO NOTIFICA GLOBALE.

12. SEGNALE CONTATTO PULITO PER MODULO DI CONTROLLO

NOTIFICA GLOBALE PER ATTIVAZIONE LAMPADE

STROBOSCOPICHE DI EMERGENZA.

13. SEGNALE AUDIO DAL RICETRASMETTITORE NOTIFICA GLOBALE.

IL SEGNALE AUDIO SI SOVRAPPORRA' A QUALSIASI MESSAGGIO

DIGITALE PREREGISTRATO O A QUALSIASI MESSAGGIO LOCALE

QUANDO L'IMPIANTO DI NOTIFICA GLOBALE E' ATTIVATO.

14. ANTENNA IMPIANTO ALLARME INCENDIO.

15. SCARICATORE MONTATO SULLA BASE DELL'ANTENNA.

16. CAVO PER ANTENNA IMPIANTO ALLARME INCENDIO.

17. TERMINALE STAGNO DI CONDUTTORE SIGOLO DA 20mm.

18. TUBO RIGIDO IN PVC DA 20mm DISCENDENTE FINO ALL'IMPIANTO

DI TERRA DELL'EDIFICIO.

19. TUBO IN ACCIAIO RIGIDO DA 20mm DISCENDENTE FINO AL

TRASMETTITORE/RICEVITORE RADIO.

20. TERRA IN RAME NUDO ALL'IMPIANTO DI TERRA PRINCIPALE.

21. PROFILATO DI SUPPORTO IN ACCIAIO ANCORATO A PARETE.

22. PARETE ESTERNA.

23. STAFFA PER TUBO CON DUE FORI.

24. PREVEDERE SIGILLANTE STAGNO PER LE APERTURE DEL TUBO.

25. POSIZIONARE IL MODULO DI CONTROLLO ENTRO 900mm DAL

RIVELATORE DI FUMO ASPIRANTE.

26. CONDIZIONARE TIPICO PER COMPUTER ROOM.

27. POSIZIONARE IL MODULO DI CONTROLLO ENTRO 900mm DAL

CONDIZIONATORE DEL COMPUTER ROOM.

NOTE DI REFERIMENTO:

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

TRANSMIT TROUBLE SIGNAL

DISPLAY TROUBLE

OVERRIDE PRE-RECORDED

ACTIVATE STROBES UNTIL

FIRE ALARM SYSTEM SEQUENCE OF OPERATION

DEL FUOCO DELLA BASE

TRASMETTERE IL SEGNALE DI GUASTO AI VIGILI

VISUALIZZARE LA CONDIZIONE DI GUASTO AL FACP

SUPERVISIONE PER I

VIGILI DEL FUOCO DELLA BASE

TRASMISSIONE SEGNALE DI

SEQUENZA DI FUNZIONAMENTO IMPIANTO DI ALLARME INCENDIO

DELL'INFORMAZIONE

DEL FACP

CONDIZIONE DI

SUPERVISIONE SUL DISPLAY

TRASMISSIONE SEGNALE

DEL FUOCO DELLA BASE

DI ALLARME AI VIGILI

REGISTRAZIONE SU CPU

SUL DISPLAY DEL FACP

INDICAZIONE DI ALLARME

IMPIANTO

NOTIFICA

GLOBALE

AZIONE INIZIALE

D'AREAPER IMPIANTOA CANALE

SPRINKLER

FLUSSOSTATOSTAZIONE

MANUALE FUMO

RIVELATORE

ACQUA

VALVOLA

ANTIMANOMISSIONE

RIVELATORE

DI FUMO

MESSAGGIO

IN VIVA VOCE

UNITA' TRATTAMENTO ARIA

ASSOCIATO

ARRESTO

INZIO LUCI STROBOSCOPICHE FINO A

RESETTAGGIO MANUALE IMPIANTO

DIGITALE PREREGISTRATO

SCORRE UN MESSAGGIO VOCALE

ATTIVARE L'ALLARME ANTINCENDIO CON LUCI

LAMPEGGIANTI E A VOCE CON ALTOPARLANTI

PER L'EVACUAZIONE

DEL CONDUTTORE

INTERRUZIONEGUASTO A TERRA

TO BASE FIRE DEPARTMENT

CONDITION AT FACP

DIGITIZED VOICE MESSAGE

AIR HANDLING UNIT

SYSTEM IS MANUALLY RESET

ASSOCIATED

SHUT DOWN

FIRE DEPARTMENT

SIGNAL TO THE BASE

X

X

X

X

X

CONDITION @ FACP

DISPLAY SUPERVISION

TRANSMIT SUPERVISORY

DEPARTMENT

ON CPU

RECORD INFORMATION

TO THE BASE FIRE

DISPLAY ALARM

INDICATION AT FACP

TRANSMIT ALARM SIGNAL

AND VOICE EVACUATION SPEAKERS

ACTIVATE FIRE ALARM STROBE LIGHTS

INITIATION ACTION

X X X

X

X

X

X

X

X

X

X X

X

X

X

X X

X

X

X

VALVE TAMPER

DUCT

SMOKE

DETECTOR

MANUAL PULL

STATION

WATER FLOW

SWITCH

SWITCH

SPRINKLER

DETECTOR

AREA

SMOKE

SYSTEM

NOTIFICATION

MASS

X

X

MESSAGE

LIVE

VOICE

GROUND FAULT

BREAK

CONDUCTOR

RIVELATORE DI

FUMO ASPIRANTE

SOGLIA 1

ASPIRATING

SMOKE

DETECTION

TRESHOLD 1

RIVELATORE DI

FUMO ASPIRANTE

SOGLIA 2

ASPIRATING

SMOKE

DETECTION

TRESHOLD 2

ASPIRATING

SMOKE

DETECTION

TRESHOLD 3

X

X

X

X

X X

X X

ACTIVATE SMOKE EXHAUST SYSTEM

ATTIVAZIONE IMPIANTO

ESPULSIONE FUMO

X

SIGNAL BUILDING OCCUPANTS OF THRESHOLD

CONDITION BY LOCAL ALARM INTEGRAL WITH ASD XX

RILEVATORE DI FUMO

DELL’UNITA’ DI

CONDIZIONAMENTO

NELLA COMPUTER

ROOM

COMPUTER ROOM

UNIT A/C SMOKE

DETECTOR

X

X

X

X

X

X

X

X X

SIGNAL DDC SYSTEM TO CLOSE MAKE UP AIR SMOKE

DAMPERS AND INITIATE RECIRCULATION MODE

SEGNALE AL DDC DI CHIUDERE AMMORTIZZATORI

FUMO ARIA TRATTATA E ATTIVA RICIRCOLO

SHUT DOWN COMPUTER ROOM AIR

CONDITIONING UNIT

ARRESTO CONDIZIONATORE

COMPUTER ROOM

XX

SEGNALE AD OCCUPANTI CONDIZIONE SOGLIA

CON ALLARME LOCALE INTEGRATO CON ASD

RIVELATORE DI

FUMO ASPIRANTE

SOGLIA 3

X

CONDIZIONE DI

ANOMALIA DEL

RILEVATORE DI

FUMO AD

ASPIRAZIONE

ASPIRATING SMOKE

DETECTOR TROUBLE

CONDITION

AD L

EK

N

LL

E F

S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

U

AS

S

AT

C O

M R

EL

AY

P

AD

S

AN

D F

AC

IL

IT

Y

1118648

N

AV

AL

A

IR

S

TA

TI

O N

II

SI

G O

N

EL

LA

, S

IC

IL

Y, IT

AL

Y

SATISFACTORY TO

1 2

PM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

E

ER

IN

G

C O

M M

AN

D

A

TL

AN

TI

C

LA

N T

C

AP

IT

AL

IM

PR

O

VE

M

EN

TS

N

O R

FO

LK

, V

IR

G

IN

IA

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DRAWFORM REVISION: 10 MARCH 2009

SE QUESTO DISEGNO E' PIU' PICCOLO DI 841 X 594mm

E' UN DISEGNO A DIMENSIONI RIDOTTE

IF THIS DRAWING IS LESS THAN 841 X 594mm

IT IS A REDUCED SIZE DRAWING

NOTE / N62470-11-D-1008 NOTE:

INC.ROGERS, LOVELOCK FRITZ,&

LICENSE # AA C000564 # EB 0000629

esignrchitectureA ngineeringE nteriorI D

4750 New Broad Street Orlando, FL www.rlfae.com

NTS

FI

RE

A

LA

RM

S

EQ

UE

NC

E

OF

O

PE

RA

TI

ON

M

AT

RI

X

FA701

CA

DRS SAE KLM

MA

TR

IC

E

SE

QU

EN

ZA

O

PE

RA

TI

VA

A

NT

IN

CE

ND

IO

14024785

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

SPARE

SPARE

DUCT SMOKE DETECTOR

MASS NOTIFICATION SYSTEM (SUPERVISORY)

FIRE ALARM TRANSMITTER

ZONE SCHEDULE

SCHEDA ZONE TRASMETTITORI DI

ALLARME INCENDIO

RISERVA

RISERVA

INTERRUTTORE ANTIMANOMISSIONE (DI SUPERVISIONE)

RIVELATORE DI FUMO D'AREA

FLUSSOSTATO

ZONA

STAZIONE MANUALE

DESCRIZIONE

IMPIANTO DI NOTIFICA GLOBALE (DI SUPERVISIONE)

RIVELATORE DI FUMO DEL CONDOTTO

CONDIZIONE DI GUASTO

TAMPER SWITCH (SUPERVISORY)

TROUBLE CONDITION

AREA SMOKE DETECTOR

WATER FLOW SWITCH

ZONE

MANUAL PULL STATION

DESCRIPTION

ASPIRATING SMOKE DETECTOR THRESHOLD 3

RIVELATORE FI FUMO ASPIRANTE SOGLIA 3

AD L

EK

N

LL

E F

S

R P

O

IS EN

L

GI

O N A

E E

N R

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

U

AS

S

AT

C O

M R

EL

AY

P

AD

S

AN

D F

AC

IL

IT

Y

1118648

N

AV

AL

A

IR

S

TA

TI

O N

II

SI

G O

N

EL

LA

, S

IC

IL

Y, IT

AL

Y

SATISFACTORY TO

1 2

PM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

E

ER

IN

G

C O

M M

AN

D

A

TL

AN

TI

C

LA

N T

C

AP

IT

AL

IM

PR

O

VE

M

EN

TS

N

O R

FO

LK

, V

IR

G

IN

IA

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DRAWFORM REVISION: 10 MARCH 2009

SE QUESTO DISEGNO E' PIU' PICCOLO DI 841 X 594mm

E' UN DISEGNO A DIMENSIONI RIDOTTE

IF THIS DRAWING IS LESS THAN 841 X 594mm

IT IS A REDUCED SIZE DRAWING

NOTE / N62470-11-D-1008 NOTE:

INC.ROGERS, LOVELOCK FRITZ,&

LICENSE # AA C000564 # EB 0000629

esignrchitectureA ngineeringE nteriorI D

4750 New Broad Street Orlando, FL www.rlfae.com

NTS

FI

RE

A

LA

RM

S

CH

ED

UL

ES

FA702

CA

DRS SAE KLM

PA

RT

IC

OL

AR

I A

LL

AR

ME

IN

CE

ND

IO

14024786

NTSC1 FIRE ALARM TRANSMITTER ZONE SCHEDULE

TABELLA ZONE TRASMETTITORI DI ALLARME INCENDIO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

FG001 - FIRE ALARM LEGEND.pdf
FA101 - FIRE ALARM PLAN
FA102 - ASPIRATING SMOKE DETECTOR LAYOUT
FA601 - FIRE ALARM RISER DIAGRAM
FA701 - FIRE ALARM SEQUENCE OF OPERATION MATRIX
FA702 - FIRE ALARM SCHEDULES
2012-04-20T11:31:55-0400
Kendall Mason
2012-04-20T11:32:50-0400
Kendall Mason
2012-04-20T11:32:51-0400
Kendall Mason
2012-04-20T11:32:51-0400
Kendall Mason
2012-04-20T11:32:51-0400
Kendall Mason
2012-04-20T11:32:51-0400
Kendall Mason
2012-05-08T12:29:45-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:30:10-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:30:07-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:30:04-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:30:01-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:29:59-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:30:45-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:31:05-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:31:02-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:31:00-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:30:57-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.
2012-05-08T12:30:55-0400
Robert J. Tabet, P.E.
I, Robert J. Tabet, P.E., am signing this document to confirm that it has been reviewed.

2012-05-11T06:54:37-0400

2012-05-11T06:55:00-0400

2012-05-11T06:55:01-0400

2012-05-11T06:55:02-0400

2012-05-11T06:55:03-0400

2012-05-11T06:55:08-0400

File details come from the government source that posted it. Updated .