S-FD-S-701.08.IFC.08.01.pdf
PDF 166 KB Posted
- Attached to
- LBNF Argon Receiving System
- Solicitation number
- LBNF-357714-JD
About this file
This file is an engineering drawing showing typical structural details for the Long-Baseline Neutrino Facility (LBNF) project at Fermilab, dated November 10, 2023. The drawing contains three detailed sections: typical housekeeping pads, typical control/construction joint details, and typical wall/footing reinforcement specifications.
The drawing provides specific construction requirements including #4 reinforcement bars at 12" on center, vapor retarder and drainage course specifications, and detailed joint construction methods. It includes precise measurements for dowel bars, corner bars, and concrete pad specifications. The drawing is stamped by registered professional engineer Alex R. Weiers of South Dakota and was prepared by TSP, Inc. in Rapid City, SD in collaboration with Arup USA Inc. The drawing has gone through multiple revisions from 30% design submission in July 2018 to the final "Issued for Construction" version in November 2023.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11332
ALEX R.
WEIERS
R E
G
IS
TE
RED PROFESSIONAL ENG
IN
E ER
REG. NO.
S
O
U TH D A KO
T
A
DATE:
DOWEL BAR SAME SIZE
& SPACING AS LONG
BAR x 2'-6" LONG
CORNER BAR SAME
SIZE & SPACING AS
LONG BAR x 4'-0"
LONG
#4 @ 12" OC EW
REF PLANS
TOOLED EDGE
CLEAN TOP OF CIPC FLOOR OF ALL
DELETERIOUS MATERIALS PRIOR TO
CASTING HOUSEKEEPING SLAB
NOTE:
COORDINATE EXACT SIZE AND LOCATION OF
HOUSEKEEPING PADS WITH MECHANICAL/ELECTRICAL
DRAWINGS & CONTRACT(S)/EQUIPMENT SUPPLIER(S)
[0 .1 m
4"
M
IN
(T
YP
#4 @ 12" OC DOWELED INTO
CONCRETE SLAB PERIMETER
W/ HILTI HIT-HY 200 SYSTEM
(4" MIN EMBED)
CONTINUOUS FORMED CONTROL JOINT (KCJ)
w/ SEALANT @ EXPOSED TO VIEW AREAS AND
JOINT FILLER (REF SPEC 033000) @ COVERED
AREAS PER FLOOR COVER MFR
SAWED CONTROL JOINT (CJ) w/ SEALANT
@ EXPOSED TO VIEW AREAS AND JOINT
FILLER (REF SPEC 033000) @ COVERED
AREAS PER FLOOR COVER MFR
VAPOR RETARDER
DRAINAGE COURSE
KCJ
CJ
D /4
D /4
VAPOR RETARDER
DRAINAGE COURSE
D D
2D
CONTINUE SLAB REINF THRU
(REF PLAN FOR REINF)
SLAB REINF
(REF PLAN FOR REINF)
[0 .0 m
2"
C
LR
[0 .0 m
2"
C
LR
11/10/2023
TSP, Inc.
600 Kansas City St.
Rapid City, SD 57701 phone: (605) 343-6102 fax: (605) 343-7159 www.teamtsp.com
Arup USA Inc 77 Water Street, New York NY 10005, T 212 896 3000 www.arup.com
DRAWING NO.
SCALE:
REV.
REVISIONS
DESIGNED
DRAWN
CHECKED
DESCRIPTIONDATEREV.
Fermilab Long-Baseline Neutrino Facility
/1 /2
/9
/2
4:
:4
P
M L:
T
S P
R ev it Lo ca l\0
9.
T
S P
L B
N F
S
_w ei er sa r@ te am ts p.
co m .r vt
915-1-6J S-FD-S-701
SURFACE
LBNF - FSCF - BSI
TMH
ARW
ARW TSP
STRUCTURAL
TYPICAL DETAILS
TSP
TSP
SCALE: 3/4" = 1'-0"
3TYPICAL WALL/FTG REINF
SCALE: 3/4" = 1'-0"
1TYP HOUSEKEEPING PADS
SCALE: 3/4" = 1'-0"
TYP CONTROL
/CONSTRUCTION JOINT
AS NOTED
1 07/27/18 30% FD SUBMISSION
2 11/16/18 60% FD SUBMISSION
3 02/22/19 90% FD SUBMISSION
4 05/03/19 100% FD SUBMISSION
5 08/21/20 90% DRAFT FD UPDATE
6 10/01/20 90% FD UPDATE
7 11/20/20 100% FD UPDATE
8 05/21/21 ISSUED FOR CONSTRUCTION - BSI HEADFRAME HEATERS
9 11/10/23 ISSUED FOR CONSTRUCTION
File details come from the government source that posted it. Updated .