S-FD-A-104.09.IFC.09.01.pdf
PDF 187 KB Posted
- Attached to
- LBNF Argon Receiving System
- Solicitation number
- LBNF-357714-JD
About this file
This is an architectural design drawing (S-FD-A-104) showing the plan and elevations for a Purity Check Building, which is part of the LBNF (Long-Baseline Neutrino Facility) project at the Sanford Underground Research Facility. The drawing details a single-story structure containing a Purity Check Room and an Electrical Room, with dimensions and specifications clearly marked.
The building includes specific technical requirements such as an 18"x6" aperture for experiment pipework, wall-mounted racks with plywood backing, and a 5'-0" wide x 3'-0" high operable window. The structure must maintain environmental conditions between 60-80°F using a multi-zone heat pump unit with low ambient kit and electric backup heat. The building is designed for a 30-year lifespan and must meet specific structural requirements including snow loads (ground snow load of 56 PSF), wind loads (115 MPH), and seismic criteria. Construction materials include standing seam metal roof panels, insulated metal sandwich panels for external walls, and vinyl floor tile flooring. The drawing includes detailed general notes, materials notes, structural notes, electrical notes, and mechanical notes for construction guidance.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BRADLEY RYAN
MITZELFELT
R
EG
IS
T
E R
ED
P ROF E S S I ONA L
AR
C H
IT
E
C T
REG . NO.
S
O
U TH D A KO
T
A
15208
DATE:
ELECTRICAL RM
PURITY CHECK RM
3'-0" x 7'-0" x
EQUIPMENT,
REF. ELECTRICAL
CONCRETE EQUIPMENT
PAD, REF. STRUCTURAL,
REF. CIVIL
A-104 2
A-104
PROVIDE 18"X6" APERTURE & SLEEVE
THROUGH FACADE FOR EXPERIMENT
PIPEWORK. PROVIDE WATER AND AIR TIGHT
FLASHINGS / HOOD ON EXTERNAL SIDE &
DEMOUNTABLE PANEL ON INTERNAL SIDE
ZONE FOR FUTURE WALL MOUNTED RACKS.
PROVIDE PLYWOOD FROM 12" ABOVE FLOOR
TO CEILING LEVEL
OWNER FURNISHED DESK / CHAIR
LANDING
STAIR
1 1/2"D HANDRAIL @ 36" AFF.
PROVIDE 12" EXTENSIONS AT TOP
AND BOTTOM OF RUN
1 1/2"D HANDRAIL @ 36" AFF W/
1 1/2"D GUARDRAIL @ 42" AFF.
PROVIDE 12" EXTENSIONS AT
BOTTOM OF RUN
3'-0" x 7'-0"
1' - 4"
2'
1'
0"
4'
4' - 6" 8' - 0"
/2
/2
ARGON FILL STATION CONC PAD
5355'-3"
PURITY CHECK FLOOR
5356'-7"
MINIMUM 8' CLEAR HEIGHT
THROUGHOUT ROOM
ARGON FILL STATION CONC PAD
5355'-3"
PURITY CHECK FLOOR
5356'-7"
CENTER IN WALL A 5'-0" WIDE
x 3'-0" HIGH OPERABLE
WINDOW
11/10/2023
TSP, Inc.
600 Kansas City St.
Rapid City, SD 57701 phone: (605) 343-6102 fax: (605) 343-7159 www.teamtsp.com
Arup USA Inc
77 Water Street, New York NY 10005, T 212 896 3000 www.arup.com
DRAWING NO.
SCALE:
REV.
REVISIONS
DESIGNED
DRAWN
CHECKED
DESCRIPTIONDATEREV.
Fermilab Long-Baseline Neutrino Facility
/1 /2
/9
/2
:0 :3
P
M L T
S P
R e v it L o c a l\ .5
T S
P L
B N
F S w e ie rs a r@ te a m ts p .c o m
.r v t
1015-1-6J S-FD-A-104
SURFACE
LBNF - FSCF - BSI
BRM
ARW/BEJ
ARW/BEJ TSP
ARCHITECTURAL
PURITY CHECK BUILDING PERFORMANCE
DESIGN DRAWINGTSP
TSP
SCALE: 1/4" = 1'-0"
PURITY CHECK BUILDING PLAN
PLAN
NORTH
E
S
W
GENERAL NOTES MATERIALS NOTES: STRUCTURAL NOTES:
1. ELECTRICAL EQUIPMENT, INCLUDING BUILDING ELECTRICAL SERVICE IS
SHOWN ON S-FD-E-501.
2. PROVIDE CONVENIENCE RECEPTACLES AS SHOWN ON S-FD-E-501.
3. PROVIDE LIGHTING AND CONTROLS AS SHOWN ON S-FD-E-401.
1. ROOM ENVIRONMENTAL CONDITIONS TO BE MAINTAINED BETWEEN 60 DEG F AND 80 DEG F, NO HUMIDITY CONTROL REQUIRED.
2. PROVIDE OPERABLE WINDOWS FOR VENTILATION.
3. PROVIDE MULTI-ZONE HEAT PUMP UNIT WITH LOW AMBIENT KIT AND ELECTRIC BACKUP HEAT FOR WINTER OPERATION. EACH ROOM SHALL RECIEVE A DEDICATED INDOOR FAN COIL UNIT. EQUIPMENT SHALL BE CAPABLE OF MAINTAINING INTERIOR CONDITIONS LISTED ABOVE BASED ON ASHRAE CLIMATE DATA FOR LEAD, SD. (BASIS OF DESIGN AMBIENT CONDITIONS: -15°F FOR HEATING, 96.7°F FOR COOLING)
4. ASSUME INTERNAL HEAT GAIN FROM EQUIPMENT OF 2KW (6800 BTU). ASSUME INTERNAL HEAT GAIN TO ELECTRICAL ROOM FROM
TRANSFORMER OF 2.8KW (9,600 BTU).
5. TEMPERATURE CONTROL SHALL BE BY WAY OF LOCALIZED THERMOSTATS AND FACTORY PROVIDED CONTROLLER.
ELECTRICAL NOTES: MECHANICAL NOTES:
SCALE: 1/4" = 1'-0"
PURITY CHECK BUILDING NORTH
ELEVATION
1. FINAL DESIGN TO BE COMPLETED BY DESIGN-BUILD CONTRACTOR WHO
WILL PROVIDE ARCHITECTURE, STRUCTURE, MEP DRAWINGS AND WILL
SUBMIT THESE TO FRA, THE ENGINEER AND THEN A FINAL SET OF
DRAWINGS TO THE LEAD BUILDING DEPARTMENT FOR REVIEW.
2. BUILDING TO BE DESIGNED IN ACCORDANCE WITH THE FOLLOWING
CODES & STANDARDS: 2018 INTERNATIONAL BUILDING CODE (IBC).
3. BUILDING TO SIT ON & BE TIED IN TO THE CONCRETE EQUIPMENT PAD.
4. COORDINATE INCOMING UTILITY POSITIONS AND CONFIGURATION WITH
THE CM/GC.
5. BUILDING IS INTENDED TO BE CONSTRUCTED FOR MINIMUM 30 YEAR
LIFESPAN.
1. ROOF TO BE STANDING SEAM METAL ROOF PANEL SYSTEM.
PROVIDE 2:12 TO 3:12 MONOSLOPE ROOF.
2. EXTERNAL WALLS TO BE CLAD IN INSULATED METAL SANDWICH PANELS.
CLADDING COLOR TO MATCH EXISTING WAREHOUSE. PROVIDE RENDERED
CMU AT BASE.
3. EXTERNAL DOORS TO BE PROVIDED WITH ACCESS CONTROL WITH
SOFTWARE HOUSE ISTAR AS PER SPECIFICATION. COORDINATE
PROGRAMMING OF READERS WITH SDSTA.
4. FLOORING TO BE VINYL FLOOR TILE.
5. INTERNAL WALLS TO BE FINISHED WITH GYPSUM BOARD. WALLS
CONTINUOUS THERMAL INSULATION TO COMPLY WITH REQUIREMENT OF
IECC (VERSION 2009). PAINT TO MATCH INTERIOR OF EXISTING WAREHOUSE.
1. ROOF CONSTRUCTION TO BE PLYWOOD OR OSB SHEATHING SUPPORTED BY COLD-FORMED LIGHT GAUGE STEEL RAFTERS OR WOOD DIMENSION LUMBER OR ENGINEERED WOOD RAFTERS. ALTERNATIVELY, ROOF
STRUCTURE MAY BE STRUCTURAL STEEL FRAMING WITH STEEL ROOF DECK.
THE ROOF SHALL BE DESIGNED TO SUPPORT THE FOLLOWING SNOW LOAD CRITERIA:
GROUND SNOW LOAD Pg = 56 PSF FLAT ROOF SNOW LOAD Pf = 40 PSF SNOW EXPOSURE FACTOR Ce = 1.0
SNOW LOAD IMPORTANCE FACTOR I = 1.0
THERMAL FACTOR Ct = 1.0
PLUS APPLICABLE SLIDING, DRIFTING AND UNBALANCED SNOW LOAD INCREASES
2. EXTERIOR WALLS TO BE STEEL STUD AND/OR CMU BEARING WALL CONSTRUCTION.
3. FLOOR CONSTRUCTION TO BE T&G PLYWOOD OR OSB DECKING SUPPORTED BY COLD-FORMED LIGHT GAUGE
STEEL FLOOR JOISTS OR WOOD DIMENSION LUMBER OR ENGINEERED WOOD JOISTS.
THE FLOOR SHALL BE DESIGNED TO SUPPORT THE FOLLOWING LIVE LOAD CRITERIA:
OFFICE FLOORS - 50 PSF
CORRIDOR AND STAIR LIVE LOAD - 100 PSF
CONCENTRATED LOADS AS SHOWN IN IBC TABLE 1607.1 SHALL BE ADDED TO THE UNIFORM LOADS
SHOWN ABOVE.
4. THE BUILDING SHALL BE DESIGNED TO RESIST LATERAL LOADS DUE TO WIND/SEISMIC BASED ON THE
FOLLOWING CRITERIA:
WIND LOADS: ULTIMATE WIND SPEED = 115 MPH, RISK CATEGORY II (ASCE 7), WIND EXPOSURE = C
SEISMIC LOADS: RISK CATEGORY II (ASCE 7), SITE CLASS C, IMPORTANCE FACTOR = 1.00
SPECTRAL RESPONSE COEFFICIENTS
SS (0.2 SEC)= 0.160g S1 (1.0 SEC)= 0.044g
SEISMIC DESIGN CATEGORY = B (PER CITY OF LEAD)
SCALE: 1/4" = 1'-0"
PURITY CHECK BUILDING WEST
ELEVATION
1/4"=1'-0"
0 4 8
SCALE FEET
1 07/27/18 30% FD SUBMISSION
2 11/16/18 60% FD SUBMISSION
3 02/22/19 90% FD SUBMISSION
4 05/03/19 100% FD SUBMISSION
5 08/21/20 90% DRAFT FD UPDATE
6 10/01/20 90% FD UPDATE
7 11/20/20 100% FD UPDATE
8 05/21/21 ISSUED FOR CONSTRUCTION - BSI HEADFRAME HEATERS
9 03/17/23 ADDENDUM 3
10 11/10/23 ISSUED FOR CONSTRUCTION