J-1604000 Wastewater Ver 2.1.pdf

PDF 689 KB Posted

Attached to
Base Operations Support (BOS) Services at U. S. Naval Support Activity (NSA) Naples, Italy and Outlying Areas
Solicitation number
N6247022R0008
Issued by

View the file

Other files

File Type Posted
J-0200000-10.c SAAR-N Sample Form for BOSC Amendment 0004.pdf PDF
J-1502000-39.a - HVAC Duct Cleaning Annual Scheduleb Amendment 0004.xlsx XLSX spreadsheet
Attachment F - Section F Deliverables Amendment 0004.pdf PDF
J-0200000 Management and Administration v2.7 Amendment 0004.pdf PDF
J-0200000-10.b. How to Request a Maximo Account Amendment 0004.pptx PPTX presentation
J-1501000-04.b Assets Inventory - DHA Amendment 0004.xlsx XLSX spreadsheet
J-0200000-10.a How to Purchase PKI to Access Maximo Amendment 0004.pptx PPTX presentation
J-1502000 Facility Investment v2.3 - Naples BOSC Amendment 0004.pdf PDF
J-0200000-13 ELINS 05.30.2023 Amendment 0004.xlsx XLSX spreadsheet
N6247022R0008 Amendment 0004.pdf PDF
J-1503030 Integrated Solid Waste Management v2.2 Amendment 0004.pdf PDF
J-3 Section B Supplies or Services and Prices.docx DOCX document
J-9 Pre-Proposal Conference and Site Visit Sign-In Sheets (Amendment 0003).pdf PDF
N6247022R0008 Amendment 0003.pdf PDF
J-1502000 Facility Investment v2.3 revised Amendment 0003.pdf PDF
J-0200000-13 ELINS revised Amendment 0003.xlsx XLSX spreadsheet
J-1 Past Performance Questionnaire (PPQ).doc DOC document
J-10 Pre-Proposal Conference Presentation (Amendment 0003).pdf PDF
J-2 Corporate Experience Project Data Sheet.docx DOCX document
J-1800000 J Environmental v2.1 revised Amendment 0003.pdf PDF
J-1503010 Custodial v2.5 revised Amendment 0003.pdf PDF
N6247022R0008 Amendment 0002.pdf PDF
J-7 Base Access Information Spreadsheet.xlsx XLSX spreadsheet
J-8 Site Visit Map.pdf PDF
N6247022R0008 Amendment 0001.pdf PDF
J-1503010-07.c Custodial Inventory - REGION and Other Commands.xlsx XLSX spreadsheet
J-1501000-04.a Assets Inventory - Region.xlsx XLSX spreadsheet
J-1800000 Environmental v2.1.pdf PDF
J-1606001 Water (Overseas).pdf PDF
J-4 Pre-Award Inquiry Form.xlsx XLSX spreadsheet
J-1503010-14 Non-Recurring Port Call Custodial Services.xlsx XLSX spreadsheet
J-0200000-04.a Hazardous Material Spill Report (Code Orange).pdf PDF
J-1502000-39.a HVAC Duct Cleaning Annual Schedule.xlsx XLSX spreadsheet
J-2 Corporate Experience Project Data Sheet.pdf PDF
J-1502000 Facility Investment v2.3.pdf PDF
J-0200000-04.b ICRA Template USNHNAPINST 6220.1.pdf PDF
J-1700000 Transportation v2.1.pdf PDF
J-1501000-03 Site Maps Naples BOS.pdf PDF
J-1503010-07.b Custodial Inventory - DoDEA.xlsx XLSX spreadsheet
J-0200000-05 SERVICE PROVIDER INFORMATION v1 - 2013-07-07.xlsx XLSX spreadsheet
J-1601000 Utility Management v2.0.pdf PDF
J-6 Antimafia Screening Attachment 2.pdf PDF
Attachment F - Section F Deliverables.pdf PDF
J-1601000-05 Utility Assets Inventory.pdf PDF
J-1502000-38.a Sample As Built Anchor Points (Bldg 402).pdf PDF
J-1502000-04 PM and IMP Services Matrix.xlsx XLSX spreadsheet
J-1503030 Integrated Solid Waste Management v2.2.pdf PDF
J-1503050 Grounds Maint and Landscaping v2.6.pdf PDF
J-0200000-06 ASSET INFORMATION v2 - 2017-04-26.xlsx XLSX spreadsheet
J-3 Section B Supplies or Services and Prices.pdf PDF
Show 40 more

Latest 50 of 72 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION J – 1604000

WASTEWATER

DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS

TABLE OF CONTENTS

ATTACHMENT

NUMBER ATTACHMENT TITLE

J-1604000-01 DEFINITIONS AND ACRONYMS

J-1604000-02 REFERENCES AND TECHNICAL DOCUMENTS

J-1604000-03 WASTEWATER AND STORM DRAIN COLLECTION SYSTEMS

J-1604000-04 SEWER LINES AND STORM DRAINS SYSTEMS

J-1604000-05 SEPTIC TANKS

J-1604000-06 HISTORICAL SEPTIC TANKS, SEWER LINES AND HOLDING TANK

SEWAGE WASTE TONNAGE DATA

J-1604000-07 HOLDING TANK

ATTACHMENT J-1604000-01

DEFINITIONS AND ACRONYMS

DEFINITION DESCRIPTION

Applicable Regulatory Drivers

The Italian national, regional, and local laws and regulations, including but not limited to the Italian Legislative Decree no.152 of 3 April 2006 (D.Lgs.152/06), as well as, when found not in conflict with them and more protective of the human health and environment, the applicable provisions of the Environmental Final Governing Standards for Italy (I- FGS), and of the additional documents listed in the References and Technical Documents in J-1604000-02, including any amendments to the foregoing.

Equipment, Collateral Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project.

Equipment, Installed Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable.

Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial.

Equipment, Personal Property

Personal property equipment includes all equipment other than collateral equipment.

Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed aster erection or installation without substantial loss of value or damage thereto or to the premises where installed.

Facilities Life Cycle A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.

Facilities Maintenance Management

The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”

Integrated Maintenance Plan

IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to ensure equipment and systems are operational and remain in a constant state of readiness.

Life-Cycle Costs A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.

Repair Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term also applies to replacement of the entire unit or system if beyond economical repair. The intent of repair is to have the equipment at normal working condition.

Replacement Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters. Replacement is performed when the equipment has reached the end of its useful life; when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance.

ATTACHMENT J-1604000-01

DEFINITIONS AND ACRONYMS

DEFINITION DESCRIPTION

Restoration Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.

Sustainment Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.

SCADA A version of telemetry commonly used in wide-area industrial applications, such as electrical power generation and distribution and water distribution, which includes supervisory control of remote stations as well as data acquisition from those stations over a bidirectional communications link.

ACRONYM TITLE

ANSI American National Standards Institute ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers ASME American Society of Mechanical Engineers MACP Manhole Assessment and Certification Program NASSCO National Association of Sewer Service Companies NPDES National Pollutant Discharge Elimination System PACP Pipeline Assessment and Certification Program SCADA Supervisory Control and Data Acquisition SRM Sustainment, Restoration and Modernization UFC Unified Facilities Criteria WEF Water Environmental Federation

ATTACHMENT 1604000-02

REFERENCES AND TECHNICAL DOCUMENTS

The Contractor shall adhere to the applicable portions of the current edition of the following publications and directives in performing the services required under this contract. This list shall not be considered all-inclusive and does not release the Contractor from all obligations that must be fulfilled in the observance and execution of this contract.

When U.S., European and/or Italian directives, instructions and industry standards are applicable to the work to be performed under this contract, the most stringent directives, instructions and industry standards shall govern.

REFERENCE TITLE

EI 11C201 Wastewater Collection and Pumping MIL-HDBK-1005/9 Industrial and Oily Wastewater Control UFC 3-240-02N Wastewater Treatment Systems UFC 3-240-04A Wastewater Collection UFC 3-240-07FA Sanitary and Industrial Wastewater Collection: Gravity Sewers and Appurtenances UFC 3-240-09FA Domestic Wastewater Treatment UFC 4-832-01N Design: Industrial and Oily Wastewater Control

ATTACHMENT J-1604000-03

WASTEWATER AND STORM DRAIN COLLECTION SYSTEMS INVENTORY

FUNDING ACTIVITY: REGION

LOCATION: GAETA

WASTEWATER COLLECTION SYSTEM

Bldg No. Location Equipment Description Technical Specifications Qty

752 Fitness/Rec. Center Buried gravity pipeline 8” diameter 60 lm Fitness/Rec. Center Sewer tank (wet well) 1 cu mt capacity 2 Fitness/Rec. Center Inspection pit 0.05 cu mt capacity 1

752A Underground concrete sewer tank (wet well)

Manhole with cast iron covering 1

Buried pressurized pipeline 3.15" diam., 4 ea. floor clean-outs 100 lm Laundry Drain Pit Submersible pump Mfgr: Idromec, Mod. PV/M 3/A, 1.5

HP, installed in the tank

Laundry Drain Pit Minimum level sensor

Laundry Drain Pit Maximum level sensor 1

Control panel Feeding/controlling pump and sensors 1 Laundry Buried gravity pipeline 8” diameter 20 lm Laundry Sewer tank (wet well) 1 cu mt capacity 1 Laundry Inspection pit 0.05 cu mt capacity 2

757 Trailers/Laundry Underground concrete sewer tank (wet well)

Manhole with cast iron covering 2

Trailers/Laundry Buried pressurized pipeline 3.15" diam. 200 lm Trailers/Laundry Submersible pump 1.5 HP, installed in the tank 2 Trailers/Laundry Minimum level sensor

Trailers/Laundry Maximum level sensor 1 Trailers/Laundry Control panel Feeding/controlling pump and sensors 1

WASTEWATER AND STORM DRAIN COLLECTION SYSTEMS INVENTORY – Cont.

LOCATION: GAETA

SHIP-TO-SHORE WASTEWATER LIFT STATION

Location Equipment Description Manufacturer Model/Type Technical Specification Qty

Wastewater Tank Air blower MAPRO TURBOTRON 250 m3/h 1 Lift Station Butterfly valve on blower

VALSAR WAFER G/1 DN 125 1

Lift Station Check valve on blower VALSAR AISI 304 DN 65 2 Lift Station Submersible pumps FAGGIOLATI

PUMPS

B210T3A30 50 m3/h 3

Lift Station Ball valve on pump RBR VALVOLE Serie 10WAFER

TYPE

3" 3

Lift Station Check valve on pump FIL-PEMTO D6666AISI 316 3" 3 Lift Station Control panel for pumps MANIERO

ELETTRONICA

QTDE30/Kw-T 5,5 Kw 1

Lift Station Ultrasonic level meter AUTOMATION

PROGETTI

AP5117 -

NT680E

6 Digital Outputs 1

Lift Station Ultrasonic level probe AUTOMATION

PROGETTI

AP5126 0.25m-5m 1

Lift Station T-Connection 1 Wastewater Tank Electromagnetic flowmeter

DANFOSS MAG1100 -

MAG 5000

DN 8036-90 m3/h 1

Wastewater Tank Printer MJKII

AUTOMATION

MJK 791 2 Timers with hr/24 -hr/yr valves

Wastewater Tank Autom. Feeder for Tank Cathodic Protection

ELME CP2 49V.8A.

D.C.

Feeding 220 V, 50 Hz.Output current 8A

Wastewater Tank Zinc reference electrode SEAGUARD S/D 30 X 400/2 PE/POLIOLEFINA- 0,6/1 kV, F1x16mm2

Wastewater Tank Tubular anodes SEAGUARD CPR-8C/CPR-

10FW

1", length 44" 4

Wastewater Tank Exhaust fan on tank DYNAIR BOX-T 9/9 Air flow: 2000 m3/h 1 Wastewater Tank Activated charcoal filters on tank

FCR P-CARB, PCA-

1/12 Size: 610x610x470 mm

Wastewater Tank General Control Panel

PWW

VEMER PWW Gen. Disconnect Switch. LED and Relays

Wastewater Tank Air blower control panel

PWS

VEMER PWS Disconnect switches.

Thermal protection

Pier Alarm Panel Q.AL 1 for lift station

VEMER Q.AL 1 230-400V/24V

AC/DC. Relays

R1,R2,RT2

Lift Station Alarm Panel Q.AL 2 for lift station

VEMER Q.AL 2 230-400V/24V

AC/DC. Relays

R1,R2,RT2

Next to Bldg 752A

Alarm Panel Q.AL 3 for lift station

VEMER Q.AL 3 230-400V/24V

AC/DC. Relays

R1,R2,RT2

WASTEWATER AND STORM DRAIN COLLECTION SYSTEMS INVENTORY – Cont.

GAETA - WASTEWATER SYSTEM LAYOUT

To City Sewer Line

Pressurized Pipeline

Gravity Pipeline

Italian Navy Pipeline

ATTACHMENT J-1604000-04

SEWER LINES AND STORM DRAINS SYSTEMS INVENTORY

Funding Activing: REGION

LOCATION: CAPODICHINO –

SEWER LINES AND STORM DRAINS SYSTEMS

Equipment Description Technical Specification and Frequencies of Services (Approx. Quantities and Sizes)

Sewer Trunk Line - 2,000 mt total length

- 300 mm diameter Inspection/Cleaning/Unclogging: Semi-Annually

Inspection Pits - 50 each

- 1 cu mt each Cleaning: Quarterly

Main Conveyor - 1 each Inspection/Cleaning/Unclogging: Quarterly

Drain Trunk Line - 3,500 mt total length

- 300 mm diameter Inspection/Cleaning/Unclogging: Semi-Annually

Inspection Pits and Grates - 100 each

- 1 cu mt each Inspection/Cleaning/Unclogging: Semi-Annually

Internal Grates, Rain Water Collection Bldg 461, East Parking Garage

- 50 mt total length

- 40 cm diameter Inspection/Cleaning/Unclogging: Semi-Annually

LOCATION: LAGO PATRIA SATCOM

SEWER LINE SYSTEMS

Equipment Description Technical Specification and Frequencies of Services (Approx. Quantities and Sizes)

Sewer Gravity Line - 160 mt total length

- 300 mm diameter Inspection/Cleaning/Unclogging: Semi-Annually

Gravity Line Inspection Pits - 4 each

- 1 cu mt each Cleaning: Quarterly

Lift Station - 1 each Inspection/Cleaning/Unclogging: Quarterly

Pressurized Line - 50 mt total length Inspection/Cleaning/Unclogging: Semi-Annually

Pressurized Line Inspection Pits - 2 each

- Inspection: Required in conjunction with the above operations

SEWER LINES AND STORM DRAINS SYSTEMS – Cont.

CAPODICHINO - SEWER SYSTEM LAYOUT

Note: this layout is approximate and may not be showing the entire Capodichino sewer system to be maintained under this contract.

LAGO PATRIA SATCOM - SEWER SYSTEM LAYOUT

SEWER LINES AND STORM DRAINS SYSTEMS – Cont.

CAPODICHINO - STORM DRAIN SYSTEM LAYOUT

Note: this layout is approximate and may not be showing the entire Capodichino storm drain system to be maintained under this contract.

ATTACHMENT J-1604000-05

SEPTIC TANKS INVENTORY

LOCATION: CAPODICHINO

SEPTIC TANKS

Bldg No. Layout Code1

Equipment Description Size

Servicing Frequency Routing

Emptying Complete Empting

402 A Septic Tank 6 m3 As Required (refer to Technical

Specification 1604000, Spec

Item 3.3.3)

Quarterly 401 B1 Inspection Pit 1 m3

B2 Septic Tank 5 m3

LOCATION: CARNEY PARK

SEPTIC TANKS

Bldg No. Layout Code1

Equipment Description Size

Routing Emptying

Complete Empting

526/540 A1 Septic Tank 10 m3 As Required (refer to Technical

Specification 1604000, Spec

Item 3.3.3)

Quarterly A2 Septic Tank 10 m3

A3 Septic Tank 10 m3 525 B Septic Tank 9 m3 524 C Septic Tank 9 m3 522 D Septic Tank 9 m3 528 E Septic Tank 12 m3 500 F Septic Tank 9 m3 514 G Septic Tank 12 m3 551 H Septic Tank 12 m3

522/554 J Septic Tank 10 m3

Note 1: Refer to the below attached Capodichino and Carney Park maps for approximate locations

SEPTIC TANKS INVENTORY – Cont.

CAPODICHINO - SEPTIC TANKS AND INSPECTION PIT

SEPTIC TANKS INVENTORY – Cont.

CARNEY PARK - SEPTIC TANKS AND HOLDING TANK

ATTACHMENT J-1604000-06

HISTORICAL SEPTIC TANKS, SEWER LINES SEWAGE WASTE TONNAGE DATA

LOCATION CER CODE TYPE OF WASTE Annual Quantity (Liter)

FY2020 FY2021

Capodichino 200304 Septic Tank Sludge /

Fanghi delle Fosse Settiche

131,080 129,000 Carney Park 1,002,060 1,142,120

Gaeta 19,080 19,060

Carney Park 161002 Aqueous Liquid Wastes / Soluzioni Acquose di Scarto 129,560 109,180

ATTACHMENT J-1604000-07

HOLDING TANK INVENTORY

Funding Activity: REGION

CARNEY PARK - Holding Tank1

Bldg No. Equipment Description Size Frequencies of Services

528 Swimming Pool Holding Tank

16 m3 From mid-April to Pool Opening Day (Memorial Day): 2 times a week From Opening Day to 2nd week in September: every 2 weeks

Note 1: Refer to attached Carney Park map (J-1604000-05) for holding tank location.

ATTACHMENT NUMBER

File details come from the government source that posted it. Updated .