ATTACHMENT J-1601000-05
UTILITY ASSETS INVENTORY
WASTEWATER AND STORM DRAIN COLLECTION SYSTEMS INVENTORY
FUNDING ACTIVITY: REGION
LOCATION: GAETA
WASTEWATER COLLECTION SYSTEM
Bldg No. Location Equipment Description Technical Specifications Qty
752 Fitness/Rec. Center Buried gravity pipeline 8” diameter 60 lm Fitness/Rec. Center Sewer tank (wet well) 1 cu mt capacity 2 Fitness/Rec. Center Inspection pit 0.05 cu mt capacity 1
752A Underground concrete sewer tank (wet well)
Manhole with cast iron covering 1
Buried pressurized pipeline 3.15" diam., 4 ea. floor clean-outs 100 lm Laundry Drain Pit Submersible pump Mfgr: Idromec, Mod. PV/M 3/A, 1.5
HP, installed in the tank
Laundry Drain Pit Minimum level sensor
Laundry Drain Pit Maximum level sensor 1
Control panel Feeding/controlling pump and sensors 1 Laundry Buried gravity pipeline 8” diameter 20 lm Laundry Sewer tank (wet well) 1 cu mt capacity 1 Laundry Inspection pit 0.05 cu mt capacity 2
757 Trailers/Laundry Underground concrete sewer tank (wet well)
Manhole with cast iron covering 2
Trailers/Laundry Buried pressurized pipeline 3.15" diam. 200 lm Trailers/Laundry Submersible pump 1.5 HP, installed in the tank 2 Trailers/Laundry Minimum level sensor
Trailers/Laundry Maximum level sensor 1 Trailers/Laundry Control panel Feeding/controlling pump and sensors 1
WASTEWATER AND STORM DRAIN COLLECTION SYSTEMS INVENTORY – Cont.
LOCATION: GAETA
SHIP-TO-SHORE WASTEWATER LIFT STATION
Location Equipment Description Manufacturer Model/Type Technical Specification Qty
Wastewater Tank Air blower MAPRO TURBOTRO N
250 m3/h 1
Lift Station Butterfly valve on blower
VALSAR WAFER G/1 DN 125 1
Lift Station Check valve on blower VALSAR AISI 304 DN 65 2 Lift Station Submersible pumps FAGGIOLATI
PUMPS
B210T3A30 50 m3/h 3
Lift Station Ball valve on pump RBR VALVOLE Serie
10WAFER
TYPE
3" 3
Lift Station Check valve on pump FIL-PEMTO D6666AISI
3" 3
Lift Station Control panel for pumps MANIERO
ELETTRONICA
QTDE30/Kw- T
5,5 Kw 1
Lift Station Ultrasonic level meter AUTOMATION
PROGETTI
AP5117 -
NT680E
6 Digital Outputs 1
Lift Station Ultrasonic level probe AUTOMATION
PROGETTI
AP5126 0.25m-5m 1
Lift Station T-Connection 1 Wastewater Tank Electromagnetic flowmeter
DANFOSS MAG1100 -
MAG 5000
DN 8036-90 m3/h 1
Wastewater Tank Printer MJKII
AUTOMATION
MJK 791 2 Timers with hr/24 - hr/yr valves
Wastewater Tank Autom. Feeder for Tank Cathodic Protection
ELME CP2 49V.8A.
D.C.
Feeding 220 V, 50 Hz.Output current 8A
Wastewater Tank Zinc reference electrode SEAGUARD S/D 30 X 400/2
PE/POLIOLEFINA-0,6/1
kV, F1x16mm2
Wastewater Tank Tubular anodes SEAGUARD CPR-8C/CPR-
10FW
1", length 44" 4
Wastewater Tank Exhaust fan on tank DYNAIR BOX-T 9/9 Air flow: 2000 m3/h 1 Wastewater Tank Activated charcoal filters on tank
FCR P-CARB,
PCA-1/12
Size: 610x610x470 mm 12
Wastewater Tank General Control Panel
PWW
VEMER PWW Gen. Disconnect Switch.
LED and Relays
Wastewater Tank Air blower control panel
PWS
VEMER PWS Disconnect switches.
Thermal protection
Pier Alarm Panel Q.AL 1 for lift station
VEMER Q.AL 1 230-400V/24V AC/DC.
Relays R1,R2,RT2
Lift Station Alarm Panel Q.AL 2 for lift station
VEMER Q.AL 2 230-400V/24V AC/DC.
Relays R1,R2,RT2
Next to Bldg 752A
Alarm Panel Q.AL 3 for lift station
VEMER Q.AL 3 230-400V/24V AC/DC.
Relays R1,R2,RT2
WASTEWATER AND STORM DRAIN COLLECTION SYSTEMS INVENTORY – Cont.
GAETA - WASTEWATER SYSTEM LAYOUT
To City Sewer Line
Pressurized Pipeline
Gravity Pipeline
Italian Navy Pipeline
SEWER LINES AND STORM DRAINS SYSTEMS INVENTORY
Funding Activing: REGION
LOCATION: CAPODICHINO –
SEWER LINES AND STORM DRAINS SYSTEMS
Equipment Description Technical Specification (Approx. Quantities and Sizes)
Sewer Trunk Line - 2,000 mt total length
- 300 mm diameter
Inspection Pits - 50 each
- 1 cu mt each
Main Conveyor - 1 each Drain Trunk Line - 3,500 mt total length
- 300 mm diameter Inspection Pits and Grates - 100 each
- 1 cu mt each Internal Grates, Rain Water Collection Bldg 461, East Parking Garage
- 50 mt total length
- 40 cm diameter
LOCATION: LAGO PATRIA SATCOM
SEWER LINE SYSTEMS
Equipment Description Technical Specification (Approx. Quantities and Sizes)
Sewer Gravity Line - 160 mt total length
- 300 mm diameter
Gravity Line Inspection Pits - 4 each
- 1 cu mt each
Lift Station - 1 each Pressurized Line - 50 mt total length Pressurized Line Inspection Pits - 2 each
SEWER LINES AND STORM DRAINS SYSTEMS – Cont.
CAPODICHINO - SEWER SYSTEM LAYOUT
Note: this layout is approximate and may not be showing the entire Capodichino sewer system to be maintained under this contract.
LAGO PATRIA SATCOM - SEWER SYSTEM LAYOUT
SEWER LINES AND STORM DRAINS SYSTEMS – Cont.
CAPODICHINO - STORM DRAIN SYSTEM LAYOUT
Note: this layout is approximate and may not be showing the entire Capodichino storm drain system to be maintained under this contract.
SEPTIC TANKS INVENTORY
Bldg No. Layout Code1
Equipment Description Size
402 A Septic Tank 6 m3 401 B1 Inspection Pit 1 m3
B2 Septic Tank 5 m3
Bldg No. Layout Code1
Equipment Description Size
526/540 A1 Septic Tank 10 m3 A2 Septic Tank 10 m3 A3 Septic Tank 10 m3
525 B Septic Tank 9 m3 524 C Septic Tank 9 m3 522 D Septic Tank 9 m3 528 E Septic Tank 12 m3 500 F Septic Tank 9 m3 514 G Septic Tank 12 m3 551 H Septic Tank 12 m3
522/554 J Septic Tank 10 m3
Note 1: Refer to the below attached Capodichino and Carney Park maps for approximate locations
CAPODICHINO - SEPTIC TANKS AND INSPECTION PIT
CARNEY PARK - SEPTIC TANKS AND HOLDING TANK
WATER TREATMENT PLANT AND DISTRIBUTION SYSTEM DESCRIPTION AND INVENTORY
FUNDING ACTIVITY: Region LOCATION: Gaeta - Old Mill Inn
Bldg No. Equipment Description Manufacturer/Model Technical Specification Qty
707 (Rec Field)
Pressure Reducing Valve Pressure reducing Valve assembly
ZURN WILKINS 600XL/610XL 2 inch 1
Filters Filter Housings HARMSCO HUR 1X170FL 1 cartridge 6 Filter Cartridge HARMSCO HC/170‐50 2 Filter Cartridge HARMSCO HC/170‐5 2 Filter Cartridge HARMSCO HC/170‐LT2 2 Pressure Measurement Differential Pressure Transmitter
SITRANS P250 1
Magnetic Flow Meters Flow Sensor MAG 5100 W 2 inch 2 Transmitter MAG 6000 2 inch 2 UV Reactors Vessels SITA UV40 IT 2 Lamps HO LP Type 028124 40 mJ/cmq each 12 Dosing Station Chemical Tank EMEC CNT PD 120 Polyethylene V=120 lt 1 Mixer EMEC MIXVN8‐MON EMEC Dosing Station
CNT 120
Metering Pumps EMEC AMS MF 1506 2 Suction Lance EMEC LASP4V 1 Motorized Valve Electric Quarter-Turn Actuator
HASELHOFER EQ40 2 inch 1
Butterfly Valve SIRCA S301 2 inch 1 Tanks Finished Water ROTOTEC P7500 Polyethylene V=7800 lt 1 Float Switch MINIMATIC/C WRAS 3 Pumping System Distribution GRUNDFOS Hydro Multi‐E 2
CRNE3‐10
Tank Recirculation LOWARA 1SV04F003M 1 Monitoring Station Digital Controller HACH SC200 3 Turbidimeter HACH 1720E SC Nephelometric 2 Chlorine Analyzer HACH 9184 SC Amperometric 1 pH and Temperature Analyzer
DPD1R1.99 Built‐In NTC300 Temperature Sensor
Remote Unit Controller LACROIX SOFREL S550 1
UPS
Uninterruptible Power Supply
NILOX UPS SERVER 1400 1
ATTACHMENT J-1606000-03
WATER TREATMENT PLANT AND DISTRIBUTION SYSTEM DESCRIPTION AND INVENTORY
FUNDING ACTIVITY: Region LOCATION: Gaeta - Fleet Landing
Bldg No. Equipment Description Type Technical
Specification Qty
752/ 752A
Hot/Cold Water Supply/ Return Piping Galvanized 3/4" 40 lm Valve System Ball Valve 1/2" 19 ea.
3/4" 3 ea.
1 1/4" 4 ea.
WATER TREATMENT PLANT AND DISTRIBUTION SYSTEM DESCRIPTION
Acqua Latina feeds the Gaeta Old Mill Inn compound, by the municipality aqueduct. Old Mill Inn water treatment plant/repotabilization system has been installed in May 2016. Average Daily Demand (ADD) drinking water consumption estimated between 2.5 and 3 cubic meters per day.
UV sensors monitor the disinfection process continuously by measuring the UV-C intensity inside the UV chamber. System is equipped with electronic board modem GSM/GPRS complete with antenna and serial port for remote data report and cable connection to PC and it allows to set point alarm and transmits data via SMS.
The modem GSM/GPRS is SIM card type (Sim card and phone operator contract will be provided by U.S. Navy).
The monitoring system is equipment with controller and alarm relaying "SMS" Auto dialer.
Manufacturer’s recommended preventative maintenance, regularly scheduled calibration and any necessary repairs to be performed by manufacturer’s factory-trained service personnel. Use of manufacturer’s service parts and reagents is required. Third-party parts and reagents are not approved for use.