Section 07 21 16
BlaNKEt insulation
Part 1 – GENERAL
1.01 Related Documents
A.
Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.02
SUMMARY
A.
Section Includes:
1.
Thermal batt insulation between bottom chords of trusses.
B.
Related Requirements:
Section 05 40 00 – Cold Formed Metal Framing.
2.
Section 07 27 19 – Plastic Sheet Air Barriers.
1.03
REFERENCES
Definitions:
Or approved equal = Products similar to those listed immediately above and equivalent in quality, function, durability, and longevity (as determined by the Contracting Officer).
Reference Standards:
ASTM International / NFPA International / Underwriters Laboratories (UL) Incorporated: Standard Test Method for Surface Burning Characteristics of Building Materials (ASTM E‑84‑04 / NFPA 255 / UL 723).
ASTM International:
a.
Standard Specification for Mineral‑Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing (ASTM C‑665‑01).
b.
Standard Specification for Glass Cullet Recovered from Waste for Use in Manufacture of Glass Fiber (ASTM D‑5359‑98 (Reapproved 2004)).
c.
Standard Test Methods for Water Vapor Transmission of Materials (ASTM E‑96‑00).
1.04
SUBMITTALS
A.
General: Submit the following per the General Requirements.
Informational Submittals:
Manufacturer's Instructions: Submit the Batt Insulation Manufacturer's installation instructions.
Sustainable Design Submittals:
Recycled Content: For materials and assemblies proposed under this Section that have recycled content, document the following.
1) The percentage of post‑consumer and pre‑consumer recycled content of the respective material or assembly (by weight).
PART 2 – PRODUCTS
2.01
MANUFACTURERS
Attic Ventilation Baffles:
ADO Products, Rogers MN (Website: www.adoproducts.com, Voice: 866.240.4933).
Insulation Solutions, Incorporated, Meyer Industries, LLC, East Peoria IL (Website: www.insulationsolutions.com, Voice: 866.698.6562).
3.
Rettew Solar Development Company, Greenville SC (Website: www.ventshield.com, Voice: 864.242.4733).
4.
Or approved equal.
Thermal Batt Insulation:
Insulation Group of CertainTeed Corporation, Compagnie de Saint‑Gobain, Valley Forge PA (Website: www.certainteed.com, Voice: 800.233.8990).
Guardian Building Products, Incorporated, Albion MI (Website: www.guardianfiberglass.com, Voice: 800.748.0437).
Building Insulation Division of The Johns Manville Company (JM), Berkshire Hathaway Incorporated, Denver CO (Website: www.specjm.com, Voice: 800.654.3103)
Knauf Insulation, Shelbyville IN (Website: www.knauffiberglass.com, Voice: 800.825.4434).
5.
Owens Corning, Toledo OH (Website: www.owenscorning.com, Voice: 800.438.7465).
6.
2.02 MAnufactured Units
Thermal Batt Insulation: A light‑density glass fiber insulation with a foil/scrim/kraft (FSK) fire‑resistant vapor retarder facing per ASTM C‑665, Type III, Class A, Category 1, providing a flame spread index of 25 or less per ASTM E‑84 / NFPA 255 / UL 723 and a perm rating of 0.5 perm or less per ASTM E‑96.
Minimum R‑value shall be as indicated on the Drawings.
Recycled Content: Utilize glass fiber with a minimum recycled content (from cullet) of 20 percent per ASTM D‑5359.
Acceptable Products:
Thermal FSK‑25 Faced Batts by CertainTeed.
Flame Spread 25 Insulation by Guardian.
FSK‑25 Faced Batts by JM.
d.
FSK‑Foil by Knauf.
e.
Flame Spread 25 Fiberglas Insulation by Owens Corning.
f.
B.
Tapes: Pressure‑sensitive and compatible with facing.
PART 3 – EXECUTION
3.01
PREPARATION
A.
Verify that adjacent materials are dry and ready to receive insulation.
B.
Verify that mechanical and electrical services have been installed and tested.
3.02
INSTALLATION
Insulation:
Extend insulation full thickness as shown over entire area to be insulated. Cut and fit tightly around obstructions, and fill voids with insulation.
Install so that facing with integral vapor retarder membrane is on the warm side of insulation. Seal the following with tape in accordance with the Batt Insulation Manufacturer's instructions:
Butt ends of insulation joints.
Lapped side flanges of insulation joints.
Cuts, punctures, and tears in the facing.
Friction‑fit faced insulation batts between trusses.
Staple flanges to face or side of wood truss between 8‑ and 12‑inches on center.
Penetrations: Carefully cut insulation to fit around outlets, junction boxes, penetrations, and the like.
END OF sEctioN 07 21 16
07 21 16-4
BLANKET INSULATION