Solicitation #FA6656-09-R-0005 Construct Addition/Fire Suppression B104 Questions with Answers/Clarifications as of 28 August 2009:
Correction
24. The finish schedule on sheet A-11 is showing CT2/P1 for the wall finishes in Rooms 105 and 110. The interior elevations for these two rooms on sheet A-08 is showing full height ceramic tile (CT2/CT3). Please clarify your intent.
Response: Follow scheme shown in the interior elevations for these two rooms as detailed on Sheet A-08 and use full height ceramic tile with accent ceramic tile (CT2/CT3) as per Air Force material board color selection.